Design calculation sheet

Project no:

LY06070

Date:

Sheet no.:

of

Chilled Water Secondary Pumps

Subject:

S.A.

Checked by:

Office Building

Computed by:

Approved by:

Pump Capacity (AHU & FCU flow summation)

Flow Rate

43.0

l/s

681.5

gpm

Pump Head
A- Pipe Losses
Dia

Length

Eq.leng

Flow

Fr. losses

Losses

in

ft

ft

GPM

L/s

ft/100ft

ft

8
6

22.0
14.4

72.18
47.24

83.01
54.33

534
485

33.70
30.60

0.50
1.40

0.42
0.76

5
4

21.6
14.4

70.87
47.24

81.50
54.33

377
216

23.80
13.60

2.25
2.70

1.83
1.47

3
2.5
Sub-Total-1

7.2
7.2

23.62
23.62

27.17
27.17

108
54

6.80
3.40

2.70
1.80

0.73
0.49

5.70 ft

B- Accessories Losses

AHU-fresh

AHU-Food

Secon.P
ump

Item

Dia

Qty.

in.

Equ. L

Flow

Fr. losses

ft.

gpm

ft/100ft

Losses
ft

Gate Valve

10

534

0.5

0.09

Globe valve

220

534

0.5

1.1

Isolating valve

534

0.5

0.045

Gate Valve

2.5

2.8

73

3.5

0.098

2-way control valve

2.5

69

73

3.5

2.415

Balancing valve

2.5

69

73

3.5

2.415

Strainer

2.5

28

73

3.5

0.98

Gate Valve

2.5

2.8

58.6

2.75

0.077

2-way control valve

2.5

69

58.6

2.75

1.8975

Balancing valve

2.5

69

58.6

2.75

1.8975

Strainer

2.5

28

58.6

2.75

0.77

Coil

8.5

Coil

8.5

28.79 ft

Sub-Total-2

Sum

34.48

ft

Friction Losses

10.51

Static head

2.0

sub total=

12.5

Total with 10% safety=

13.8