4106 Specification

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 3

4106

( Grounded resistance tester 4106)

Features

2 pole /
3poles and /
4 poles
method of
grounding
resistance

measurement.
Measurement of soil resistivity.
Can remove the residual resistance test line RK setting function.
Has over limit and incorrectness warning function about testing condition

Specifications:
Product characteristics
Basic measuring function
2 pole /3poles and /4 poles method of grounding resistance measurement.
Measurement of soil resistivity ().
Automatic interference voltage connected measuring.
Grounding resistance measurement using square wave excitation test,4 kinds of testing frequency
(94Hz,105Hz,111Hz,128Hz ), can be manually selected, so as to avoid the interference source for
ground measurement. Testing of the open-circuit voltage : the maximum50V, square wave; short-circuit
current <20mA.
l

It can remove the residual resistance test line RK setting function.

It has over limit and incorrectness warning function about testing condition

Instrument panel calibration technology, to ensure that the expected accuracy and performance.

Convenient operation data recording function, the query log data, the internal memory can store

100(Group) measurement data.


Basic index
Grounding resistance RE (test )
range

Measuring range

Resolution

Precision

20

0.1019.99

0.01

2%+5

200

20.0199.9

0.1

www.ttbvision.com

2000

2001999

3%+5

20K

2.00K19.99K

0.01K

Measurement of soil resistivity ()


range

Measuring range

Resolution

Precision

20m

0m19.99m

0.01m

Depend on RG

200m

20.0m199.9m

0.1m

2000m

200m1999m

1m

20Km

2.00Km

0.01Km

2aRG
Note: electrodes a
:0 ~ 30 m

19.99Km
200Km

20.0Km

0.1Km

199.9Km
2000Km

200Km

1Km

3768Km
Characteristic
l

Working temperature and humidity: 0to 40 C ( no condensation10 C, 85%RH ).

Storage temperature and humidity: -20 C to 60 C, 90%RH.

Working altitude: 2000m. ( indoor ).

Electrical safety grade: CAT 600V pollution degree 2.

High voltage: between the electrical circuit and the outside box AC3250V (50/60Hz ) / 5seconds.

Display and backlight

Segment LCD dual display:80 52mm


White LED backlight, can set the backlight time 0 60minutes
l

Power supply

8x1.5V AA alkaline batteries.


Automatic shutdown operation : can be set to automatically shutdown time 0 60minutes.
l

Dimensions and weight

175( L ) x 110( W ) x 70( D ) mm, about 680g


l

Annex

Test lead 6m ( black )


Test lead 6m ( green )
Test lead 15m ( red)
Test lead 30m ( blue )
Test grounding rod4
Alkaline batteries(LR6) x 8
Instruction manual
Portable bag
Meet the standard
l

IEC/EN 61557-15

IEC/EN61010-1

www.ttbvision.com

IEC/EN 61010-2-031

IEC/EN61326

www.ttbvision.com