RESTRICTED EARTH FAULT RELAY
type JRD 011
ELECTRONICS]
JVS ELECTRONICS PVT. LTD.
SO 9001 - 2000 COMPANY
Corporate Office:
#331,9th Cross,4th Phase,Peenya Industrial Area,Bangalore:560058
Tel: 080-28361208,28360223, Fax: 080-28361335.
E-mail : info@vensonelectric.comRESTRICTED EARTH FAULT RELAY
FEATURES
Software based design
Very sensitive and wide setting range
Insensitive to currents at harmonic frequencies
Negligible burden
Trip indication with LED
Trip test facility
Dust proof enclosure
Compact size
APPLICATION
Restricted earth fault protection of transformers, generators & motors
Differential protection of bus bars, motors and generators
DESCRIPTION
Type JRD 011 & JRD 013 are basically a current operated, software based, differential relays
which works on the high impedance principle. An external series stabilizing resistor is used
with this relay to make it a voltage operated relay. The voltage setting of the relay is adjusted
to be higher than that developed by the current transformers under maximum external fault
conditions.
JRD 011 is a single pole relay where as JRD 013 is a triple pole relay.
The power required by the electronic circuitry is drawn from the auxiliary DC supply.
The sensing current is converted to voltage by an internal resistor and this voltage is
amplified and fed to a harmonic filtering network which is tuned to the fundamental frequency.
The output of the filter is fed to a voltage comparator. When the sensing current signal at the
fundamental frequency exceeds the set value, the comparator gates a train of pulses to the
processor. The program residing in the CPU (Central Processing Unit) performs the function
of control and also gives output signals for relay and LED(Light Emitting Diode) driver circuits.
The operation of the relay is indicated by the glowing of a ‘Red’ LED, which has to be reset
manually by means of a ‘RESET’ push button provided on the front of the relay.
A\Trip Test’ push button is also provided in the relay to enable testing of the trip and alarm
circuits. This push button is accessible only after the front poly-carbonate cover is removed.
This ensures that unauthorised testing of the trip and alarm circuits is prevented. When this
push button is pressed, the output element of the relay is energised and its contacts close to
energise trip and alarm circuits.RESTRICTED EARTH FAULT RELAY
SPECIFICATIONS
Rated Current 1AorsA
Setting Range 2.5% to 80% of rated current in steps of 2.5%
(common setting for all the tree poles in case
of JRD 013 relay )
Drop-off to pick-up ratio More than 85%
Burden on CT 1A-0.2 VA(max) at rated current at all settings
5A-0.5 VA(max) at rated current at all settings|
Impedance 1A-— 200 milli ohms at all settings
5A-— 20 milli ohms at all settings
Calibration accuracy + 5 as per IEC 60255
External series stabilizing resistor 0 to 100 ohms (adjustable), 100 watts for 5A relay
and 0 to 600 ohms (adjustable), 100 watts for 1A
relay
Thermal rating 2 times the rated current continuously
20 times the rated current for 3 seconds
Auxiliary supply 20 to 60 VDC or 75 to 150 V DC/AC or
175 to 300 V DC (185 to 250 V AC)
Rejection ratio of 3rd harmonic to 25:1 — the relay will not operate at third harmonic’
fundamental frequency currents upto 25 times the setting
Operating time 40 milli seconds at 2 times current setting
Time accuracy +5as per lEC 60255 with minimum of + 50 milli]
seconds.
Burden on aux.supply 6 watts (max.)
Operation indicator LEDs (Light Emitting Diodes ) are provided for
Indication of Relay Trip (Red)( separate indications
are available in case of three pole relay and
‘Aux.Supply Healthy’ (Green)
Contacts 2 pairs, self reset, ‘Make’ type (common contacts
for all the three poles in case if three pole relay,
type JRD 013)RESTRICTED EARTH FAULT RELAY
Contact rating (AC - DC)
a) Make & Carry
1250 VA with current maxima of 5A and voltage maxima of 660 V AC
1000 watts with current maxima of 5A and voltage maxima of 250 V DC
b) Break
2500 VA with current maxima 10 A and voltage maxima of 660V AC
200 watts (resistive) 100 watts (inductive) with current maxima of 10A and voltage
maxima of 250 V DC
Insulation
a) 2KV RMS, 50 Hz. for 1 minute / 2.5 KV RMS, 50 Hz.. For 1 sec. between all
terminals and case as per IEC 60255
b) 1 KV RMS, 50Hz. for1 minute between open contacts as per IEC 60255
Impulse withstand 5 KV peak, 1 / 50 micro seconds as per IEC 60255
High frequency disturbance 4 MHz.,1KV across input circuits and 2.5 KV
between Independent circuits as per IEC 60255
Impulse withstand 5 KV peak, 1/50 micro second, as per IEC 60255
High frequency disturbance 1 MHz.1 KV across input circuits and 1 MHz.2/5 KV)
between independent circuits, as per IEC 60255
Operating temperature - 10 deg. C to +55 deg. C
Case 144 sq.mm case, suitable for flush mounting;
panel cutout dimension is 138 x 138 mm.
Weight 2000gms. ( approx.)
INFORMATION REQUIRED WITH ORDER
1) Rated Current 1AorsA
2) Auxiliary Supply 20 to 60 V DC or 75 to 150 V DC / AC or
175 to 300 V DC (185 to 250 V AC)