Air-Conditioner: Service Manual
Air-Conditioner: Service Manual
DAS-SM-00-003
SUPPLEMENT
SERVICE MANUAL
AIR-CONDITIONER
SPLIT WALL TYPE
RAS-07YKH-E/RAS-07YAH-E
RAS-10YKH-E / RAS-10YAH-E
RAS-13YKH-E / RAS-13YAH-E
RAS-07YKH-ES/RAS-07YAH-ES
RAS-10YKH-ES / RAS-10YAH-ES
RAS-13YKH-ES / RAS-13YAH-ES
CONTENTS
1. SPECIFICATIONS .................................................................................... 3
2. CONSTRUCTION VIEWS ....................................................................... 7
3. WIRING DIAGRAM ................................................................................ 10
4. SPECIFICATIONS OF ELECTRICAL PARTS ..................................... 12
5. REFRIGERANT CYCLE DIAGRAM ..................................................... 15
6. CONTROL BLOCK DIAGRAM ............................................................. 21
7. OPERATION DESCRIPTIONS ................................................................ 22
8. INSTALLATION PROCEDURE .............................................................. 30
9. TROUBLESHOOTING CHART .............................................................. 44
10. PART REPLACEMENT .......................................................................... 60
11. EXPLODED VIEWS AND PARTS LIST .............................................. 65
1. SPECIFICATIONS
RAS-10YKH-E / RAS-10YAH-E, RAS-13YKH-E / RAS-13YAH-E
MODEL
ITEM
Capacity
kW 1
Power source
Power consumption
Power factor
Running current
Indoor/Outdoor
Starting current
Moisture removal
Noise
(SPL at 1 meter)
Refrigerant
Indoor (H/M/L)
Outdoor (220240V)
Name of refrigerant
Rated volume
Refrigerant control
Interconnection pipe
Outdoor unit
Outer diameter
RAS-10YKH-E/10YAH-E
Cooling
Heating
220V240V
220V240V
2,652,70
3,003,10
Phase
Single
V
220240
Hz
50
kW
0,981,02
0,890,91
1,261,30
1,191,27
%
9590
9588
9892
9593
V
220V240V
220V240V
220V240V
220V240V
A
0,11/4,58 - 0,11/4,61 0,11/4,17 - 0,11/4,22 0,15/5,70 - 0,15/5,75 0,15/5,54 - 0,15/5,44
A
19
14
25
25
lit/h
1,2
2,0
dB (A)
41 / 36 / 29
41 / 36 / 29
44 / 39 / 34
44 / 39 / 34
dB (A)
4749
4749
49 / 51
49 / 51
R-22
kg
0,74
0,88
Capillary tube
mm
9,52
12,7
Flare connection
mm
6,35
Flare connection
m 2
10
15
16
RAS-10YKH-E
Height
Width
Depth
mm
mm
mm
kg
High fan
Medium fan
Low fan
m/h
m/h
m/h
W
Net weight
Evaporator type
Indoor fan type
Air flow rate
Fan motor output
Air filter
Height
Width
Depth
Net weight
Condenser type
Outdoor fan type
Air flow rate (220240V)
Fan motor output
Compressor
RAS-13YKH-E
265
790
189
8
Finned tube
Cross flow fan
600
500
400
650
560
510
20
Polypropylene net filter (Washable)
OUTDOOR UNIT
Dimensions
mm
INDOOR UNIT
Dimensions
RAS-13YKH-E/13YAH-E
Cooling
Heating
220V240V
220V240V
3,453,50
4,004,10
RAS-10YAH-E
530
770
200
31
mm
mm
mm
kg
RAS-13YAH-E
538
780
300
42
Finned tube
Propeller
m/h
W
Model
Output
Safety device
Auto louver
Usable outdoor temperature range
15001700
18
PH120T1-4C
750
2143
16901730
28
PH170T2-4L2
1100
-521
Capacity
kW 1
Power source
Power consumption
Power factor
Running current
Indoor/Outdoor
Starting current
Moisture removal
Noise
(SPL at 1 meter)
Refrigerant
Indoor (H/M/L)
Outdoor (220240V)
Name of refrigerant
Rated volume
Refrigerant control
Interconnection pipe
Outdoor unit
Outer diameter
RAS-10YKH-ES/10YAH-ES
RAS-13YKH-ES/13YAH-ES
Cooling
Heating
Cooling
Heating
220V240V
2,652,70
3,003,10
3,453,50
4,004,10
Single
220240
50
0,981,02
0,890,91
1,261,30
1,191,27
9590
9588
9894
9793
220V240V
Phase
V
Hz
kW
%
V
0,11/4,44 - 0,11/4,46 0,11/4,15 - 0,11/4,10 0,15/5,70 - 0,15/5,61 0,15/5,43 - 0,15/5,54
A
A
19
14
25
25
lit/h
1,2
2,0
dB (A)
41 / 36 / 29
41 / 36 / 29
44 / 39 / 34
44 / 39 / 34
dB (A)
4749
4749
49 / 51
49 / 51
R-410A
kg
0,69
0,80
Capillary tube
mm
9,52
Flare connection
mm
6,35
Flare connection
m 2
10
15
m
mm
16
INDOOR UNIT
Dimensions
RAS-10YKH-ES
Height
Width
Depth
mm
mm
mm
kg
High fan
Medium fan
Low fan
m/h
m/h
m/h
W
Net weight
Evaporator type
Indoor fan type
Air flow rate
Fan motor output
Air filter
Height
Width
Depth
Net weight
Condenser type
Outdoor fan type
Air flow rate (220240V)
Fan motor output
Compressor
RAS-13YKH-ES
265
790
189
8
Finned tube
Cross flow fan
600
500
400
650
560
510
20
Polypropylene net filter (Washable)
OUTDOOR UNIT
Dimensions
RAS-13YAH-E
530
770
200
31
mm
mm
mm
kg
RAS-13YAH-ES
538
780
300
42
Finned tube
Propeller
m/h
W
Model
Output
Safety device
Auto louver
Usable outdoor temperature range
15001700
18
PA118X1T-4FZ
750
2143
16901730
28
PA160X2T-4FM
1100
-521
Note : 1
Capacity is based on the following temperature conditions.
CONDITION
COOLING
HEATING
(DB)
27 C
20 C
(WB)
19 C
12 C
(DB)
35 C
7 C
(WB)
24 C
6 C
TEMPERATURE
Notes : 2
CHARGELESS
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
Air inlet
Heat exchanger
Air filter
790
47
Air outlet
10
50
265
189
790
232
326
Front panel
232
Back body
10
50
Hanger
321
Hanger
Connecting pipe (0,39m)
(Flare 9,52)
(Flare 12,7 for 13YKH-E only)
65,5
659
65,5
Hanger
For stud bolt
(8~10)
For stud bolt
(6)
20
2,5
Minimum
distance
to wall
120 or more
Minimum
distance
to wall
20
46
20
Hanger
120 or more
Hanger
40,5
40,5
3,5
37
265
178,5
17
450
326
66 or more
Minimum
distance
to ceiling
Hanger
Installation
plate outline
Center line
76
47
319
269
60,5
126
790
Detail Drawing
600
A
216
230
216
25
11x14 Hole
85
Gas side (flare 9,52)
25 Drain hole
R10
230
36
50
600
111
36
30
6 Hole
8-6 Holes
(For fixing the outdoor unit)
Handle
11
Fan guard
111
200
12
420
11
TOSHIBA
Electric
parts cover
525
530
Z
62
268
54
89
Service
port
250
59
89
268
770
59
770
View
600
Inlet port
600 or more
Inlet port
100 or more
230
45 or more
Outlet
port
Center
port
RAS-13YAH-E, RAS-13YAH-ES
A
A
120
Detail Drawing
Gas side
(Flare 12,7 for 13YAH-E,
Flare 9,52 for 13YAH-ES)
600
50
36
325
301
23
325
52,5
R10
6 hole
11x14 hole
8-6 hole(for fixing outdoor unit)
25 Drain outlet
Fan guard
420
538
Z
27
100
130
54 61
600
780
300
(8,5)
90
59
Service
port
325 (pitch)
342
(8,5)
View
Installation dimension
600
100 or more
600 or more
325
Air inlet
100 or more
Air outlet
07
07
07
07
RAS-13YKH-E / RAS-13YAH-E
RAS-13YKH-ES / RAS-13YAH-ES
LOUVER MOTOR
BLU
BLU
BLU
BLU
BLU
BLU
PNK
BLK
WHI
BLU
PNK
YEL
ORN
RED
BRW
ORN
ORN
THERMAL
FUSE
77C x 2
1 2
CN04 1 2
BLK P04
GRN&YEL
1 2 3 4 5 6 7 8 9 CN13
R22
SG01
DSA
6 5 4 3 2 1
CN07 6 5 4 3 2 1
VARISTOR
F01
R21 C15
L01
DC 12V
DC 5V
RY01
CR03 IC 03
WHI RY03
RY04
C58
CR01
1
1 2 3 CN11
1 2 3
Detail A
RAS-13YAH-ES
RAS-13YAH-E
Same as
figure.
BLK
Detail B
RAS-13YAH-ES
Same as
figure.
RAS-13YAH-E
OVER LOAD
RELAY
BLK
THERMOSTAT
FOR
COMPRESSOR
GRN&YEL
BLU
RED
WHI
BLK
1
3
3
1 CN10
1
1 2 CN01
1 2
THERMO
SENSOR
(TA)
HEAT
EXCHANGER
SENSOR
(TC)
AC FAN MOTOR
INDOOR
OUTDOOR
OUTDOOR
TERMINAL
BLOCK
BLK
RED
BLUBLU
BLK
A
SOLENOID
COIL
CAPACITOR
RED
WHI
RED
COMPRESSOR
BLK
COMPRESSOR
CAPACITOR
B
5
5
MCC-798
1 2 CN03
1 2
1 2 3 4 5 6
1 2 3 4 5 6
CR02
INDOOR
TERMINAL
BLOCK
POWER
SUPPLY
CIRCUIT
BLK
BLK
BLK 4
T02
C.T
DB01
C02
BLK
BLK
RY02
R01
PNK
WHI
220V-240V
50Hz
BLK
BLU
YEL
BLK
BRW
POWER L
TERMINAL N
BLOCK
C01
6,3A
250V
BRW
PNK
WHI
11
FAN
MOTOR
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN&YEL : GREEN &
YELLOW
PARTS NAME
MODELS
TYPE
SPECIFICATIONS
Output (Rated) 750W, 2poles, 1phase, 220240V, 50Hz
RAS-10YAH-E
PH120T1-4C
C-R
C-S
4,53
8,73
PH170T2-4L2
C-R
C-S
2,22
3,04
Compressor
Output (Rated) 750W, 2poles, 1phase, 220240V, 50Hz
RAS-10YAH-ES
PA118X1T-4FZ
C-R
C-S
3,17
5,18
PA160X2T-4FM
C-R
C-S
2,26
3,53
Fan motor
(for outdoor)
5
6
Running
capacitor
(for fan motor)
Running
capacitor
(for compressor)
Overload relay
Thermostat
(for compressor)
Solenoid coil
(for 4-way valve)
Red-Black
White-Black
370
370
UE6-21SJ5P
AF-230-28P
RAS-10YAH-E
RAS-10YAH-ES
SK-50FMP1,5U1
AC 500V, 1,5mF
RAS-13YAH-E
RAS-13YAH-ES
SK-50FMP1,5U2
AC 500V, 1,5mF
RAS-10YAH-E
RAS-10YAH-ES
SK-40CMP25U1
AC 400V, 25mF
RAS-13YAH-E
RAS-13YAH-ES
SK-40CMP35U1
AC 400V, 35mF
Red-Black
White-Black
198
160
RAS-10YAH-E
JMRA99269-9200
RAS-13YAH-E
JMRA99257-9200
RAS-10YAH-E
CS-7
RAS-10YAH-E
RAS-13YAH-E
LB60012
AC 200 / 240V
VHV-01A1501A1
AC 200 / 240V
RAS-10YAH-ES
RAS-13YAH-ES
13
Indoor unit
Evaporator
Cooling
0,39m
(Connecting pipe)
9,52
0,49m
(Connecting pipe)
6,35
Heating
Cross flow fan
O.D.:9,52mm
O.D.:6,35mm
P
Packed valve
(9,52)
Packed valve
(6,35)
Heating
Cooling
4-way valve
Capillary tube
1,5x500
Dryer
Accumulator
Condenser
Cooling
Heating
50Hz
Standard
Heating
Cooling
High temperature *1
Refrigerant
R-22 0,74kg
Propeller fan
Outdoor unit
Mark(
Ambient temp.
conditions DB/WB (C)
Standard
pressure P
(kg/cmG)
Fan speed
(indoor)
Indoor
Outdoor
15,0
40,0
High
21/ -
7/6
1923
52,059,0
Low
27/ -
21/15
Low temperature
12,5
35,0
High
21/ -
-10/-10
Standard
6,0
12,0
High
27/19
35/24
High temperature
6,5
15,0
High
32/23
43/26
Low temperature
4,0
2,0
Low
21/15
21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating overload, the high temperature limit control operation is included.
15
RAS-13YKH-E / RAS-13YAH-E
Indoor unit
Heat exchanger
Cooling
0,49m
(Connecting pipe)
12,7
0,39m
(Connecting pipe)
6,35
Heating
Cross flow fan
O.D.:12,7mm
O.D.:6,35mm
P
Packed valve
(12,7)
Gas container connection (Reinstall etc.)
Packed valve
(6,35)
Heating
Cooling
4-way valve
Capillary tube
0,6x1500
Capillary tube
1,7x400
Accumulator
Capillary tube
1,2x400
Condenser
Cooling
Heating
50Hz
Standard
Heating
Cooling
High temperature *1
Refrigerant
R-22 0,88kg
Propeller fan
Outdoor unit
Mark(
Ambient temp.
conditions DB/WB (C)
Standard
pressure P
(kg/cmG)
Fan speed
(indoor)
Indoor
Outdoor
15,0
43,0
High
21/ -
7/6
1923
52,059,0
Low
27/ -
21/15
Low temperature
12,5
35,0
High
21/ -
-10/-10
Standard
5,0
10,0
High
27/19
35/24
High temperature
6,0
14,0
High
32/23
43/26
Low temperature
4,0
2,0
Low
21/15
21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating overload, the high temperature limit control operation is included.
16
RAS-07YKH-E / RAS-07YAH-E
Indoor unit
Evaporator
Cooling
0,39m
(Connecting pipe)
9,52
0,49m
(Connecting pipe)
6,35
Heating
Cross flow fan
O.D.:9,52mm
O.D.:6,35mm
P
Packed valve
(9,52)
Packed valve
(6,35)
Heating
Cooling
4-way valve
Capillary tube
1,5x1400
Dryer
Accumulator
Condenser
Cooling
Heating
50Hz
Standard
Heating
Cooling
High temperature *1
Refrigerant
R-22 0,63kg
Propeller fan
Outdoor unit
Mark(
Ambient temp.
conditions DB/WB (C)
Standard
pressure P
(kg/cmG)
Fan speed
(indoor)
Indoor
Outdoor
15,0
40,0
High
21/ -
7/6
1923
52,059,0
Low
27/ -
21/15
Low temperature
12,5
35,0
High
21/ -
-10/-10
Standard
6,0
12,0
High
27/19
35/24
High temperature
6,5
15,0
High
32/23
43/26
Low temperature
4,0
2,0
Low
21/15
21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating overload, the high temperature limit control operation is included.
17
RAS-10YKH-ES / RAS-10YAH-ES
Indoor unit
Evaporator
Cooling
0,39m
(Connecting pipe)
9,52
O.D.:9,52mm
0,49m
(Connecting pipe)
6,35
Heating
Cross flow fan
O.D.:6,35mm
P
Packed valve
(9,52)
Packed valve
(6,35)
Heating
Cooling
4-way valve
Muffler
Muffler
Dryer
Accumulator
Capillary tube
1,2x400
Capillary tube
0,8x400
Condenser
Cooling
Heating
50Hz
Standard
Heating
Cooling
High temperature *1
Refrigerant
R-410A 0,69kg
Propeller fan
Outdoor unit
Mark(
Ambient temp.
conditions DB/WB (C)
Standard
pressure P
(MPaG)
Fan speed
(indoor)
Indoor
Outdoor
2,5
43,0
High
20/ -
7/6
3,13,6
51,058,0
Low
27/ -
21/15
Low temperature
2,2
36,0
High
20/ -
-10/-10
Standard
0,9
10,0
High
27/19
35/24
High temperature
1,1
16,0
High
32/23
43/26
Low temperature
0,6
2,0
Low
21/15
21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating overload, the high temperature limit control operation is included.
18
RAS-13YKH-ES / RAS-13YAH-ES
Indoor unit
Heat exchanger
Cooling
0,49m
(Connecting pipe)
9,52
(Note)
Maximum pipe length is 15m
Maximum pipe head is 6m
0,39m
(Connecting pipe)
6,35
O.D.:9,52mm
O.D.:6,35mm
P
Packed valve
(9,52)
Gas container connection (Reinstall etc.)
Packed valve
(6,35)
Heating
Cooling
4-way valve
Muffler
Dryer
Capillary tube
1,2x1200
Capillary tube
1,5x500
Condenser
Cooling
Heating
50Hz
Standard
Heating
Cooling
High temperature *1
Refrigerant
R-410A 0,80kg
Propeller fan
Outdoor unit
Mark(
Ambient temp.
conditions DB/WB (C)
Standard
pressure P
(MPaG)
Fan speed
(indoor)
Indoor
Outdoor
2,7
43,0
High
20/ -
7/6
3,23,6
52,057,0
Low
27/ -
21/15
Low temperature
2,0
30,0
High
20/ -
-10/-10
Standard
0,9
11,0
High
27/19
35/24
High temperature
1,0
14,0
High
32/23
43/26
Low temperature
0,6
2,0
Low
21/15
21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating overload, the high temperature limit control operation is included.
19
RAS-07YKH-ES / RAS-07YAH-ES
Indoor unit
Evaporator
Cooling
0,39m
(Connecting pipe)
9,52
0,49m
(Connecting pipe)
6,35
Heating
Cross flow fan
O.D.:9,52mm
O.D.:6,35mm
P
Packed valve
(9,52)
Packed valve
(6,35)
Heating
Cooling
4-way valve
Capillary tube
1,2x900
Dryer
Accumulator
Condenser
Cooling
Heating
50Hz
Standard
Heating
Cooling
High temperature *1
Refrigerant
R-410A 0,73kg
Propeller fan
Outdoor unit
Standard
pressure P
(kg/cmG)
2,5
Mark(
Fan speed
(indoor)
High
Ambient temp.
conditions DB/WB (C)
Indoor
Outdoor
20/ -
7/6
3,1-3,6
51,058,0
Low
27/ -
21/15
Low temperature
2,2
36,0
High
20/ -
-10/-10
Standard
0,9
10,0
High
27/19
35/24
High temperature
1,1
16,0
High
32/23
43/26
Low temperature
0,6
2,0
Low
21/15
21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating overload, the high temperature limit control operation is included.
20
C. P. U
Operation
Display
Functions
Louver Control
Current Sensor
(Compressor Current)
Timer
Display
Remote Control
Initializing Circuit
Clock Frequency
Oscillator Circuit
Processing
(Temperature Processing)
PRE-DEF.
Sign Display
Indoor
Fan Motor
Operation (START/STOP)
Timer
21
Power Supply
Circuit
Compressor
ON/OFF Signal
Outdoor Fan
ON/OFF Signal
4-Way Valve
ON/OFF Signal
Louver
ON/OFF Signal
Louver
Motor
Noise Filter
ON TIMER Setting
OFF TIMER Setting
Relay
RY01
Relay
RY03
Relay
RY04
Relay
RY02
AC 220/230/240V ~
50Hz
Compressor
4-Way Valve
Infrared
Rays
7. OPERATION DESCRIPTIONS
ON
ON OFF
OFF
Set
0
temp.
28
HIGH
27
MED
26
ON
+1
ON
OFF
Compressor
(RY01)
Common relay
(RY02)
4-way valve
(RY04)
Outdoor fan
(RY03)
OPERATION
display
LOW(+)
25
Set
temp.
LOW
24
Fig. 7-2-1
LOW
(2) Relays RY01 and RY02 are turned on to energize the outdoor unit, and a cool operation is
carried out.
1) When the FAN is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-2.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constant
in volume as listed in Table 7-1-1.
LOW
400 (430)*
510
MED
500 (490)*
560
HIGH
600 (550)*
FAN
(Room temp. Set temp.)
Indication of
FAN SPEED
650
Set
temp.
AUTO
Manual
HIGH
+4
MED
+3
According
LOW(+) to the set
position
LOW
+2
+1
LOW
(continuous)
0
RY01
OFF
Fig. 7-2-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter simply
by pushing the START/STOP button.
22
ON:6min.
OFF:4min.
ON OFF
OFF
OFF
ON ON
ON
1
ON
ON
Compressor
(RY01)
Common relay
(RY02)
4-way valve
(RY04)
Outdoor fan
(RY03)
OPERATION
display
+2
ON:5min.
OFF:5min.
ON:6min.
OFF:4min.
+3
ON:5min.
OFF:5min.
ON
+1
OFF
Fig. 7-4-1
OFF
Compressor
(RY01)
Common relay
(RY02)
4-way valve
(RY04)
Outdoor fan
(RY03)
OPERATION
display
Set
0
temp.
Fig. 7-3-1
The microprocessor turns the compressor on
and off at regular intervals (4 to 6 minutes on
and/or off). During the compressor off, the
indoor fan will operate in the super low
position.
The indoor fan will operate in the AUTO
position.
(2) The pattern of operation depending on the
relation between room temperature and set
temperature is shown below:
(2) Relays RY01 and RY02 are turned on to energize the outdoor unit, and a heat operation is
carried out. The indoor fan motor operates as
shown in Fig. 7-4-2, when the FAN is set to
AUTO.
The motor operates with a constant air volume
as listed in Table 7-1-1, when the FAN is set to
LOW, MED, or HIGH.
RY01 OFF
Set
temp.
Room temp.
Set temp.+1
Set temp.
Compressor
ON
ON
ON
AUTO
Manual
0
LOW
-2
According
LOW(+) to the set
position
MED(-)
-3
-4
MED
ON
Fig. 7-4-2
Outdoor fan
OFF
Indoor fan
FAN
-1
(Room temp. Set temp.)
L.
*S.L.
OFF
L.
S.L.
*Super Low
OFF
L.
S.L.
L.
Fig. 7-3-2
23
7-6-1. Cooling
(1) In the ECONO. mode, the set temp. by the
remote control is changed automatically as
shown in Fig. 7-6-1.
(2) Fan speed LOW
(C)
Input
current
13,5A/
10A I4
Set temp.
is changed
+2
12,5,A/
9A
I3
Set temp.
is changed
Compressor
Outdoor fan
+1
Set temp.
0H
1H
2H
TIME
Fig. 7-7-1
ECONO. button
is pushed
Fig. 7-6-1
7-6-2. Heating
(1) In the ECONO. mode, the set temp. by the
remote control is changed automatically as
shown in Fig. 7-6-2.
(2) Fan speed LOW
ECONO. button
is pushed
0H
1H
2H
Set temp.
TIME
Compressor
10A/
8A I2
9A/
7.5A I1
ON
Fig. 7-7-2
-2
Set temp.
is changed
(C)
Fig. 7-6-2
25
OFF
ON
-1
Set temp.
is changed
Outdoor fan
The microprocessor detects the indoor heat exchanger temperature so as to prevent exceeding the
condensate pressure.
Control is performed as shown in Fig. 7-8-1.
Heat exchanger
temperature
(C)
60
Compressor,
Outdoor fan
*1
Heat exchanger
temperature
53
OFF
(C)
30
52
25
ON
20
<
Fig. 7-8-1
Fig. 7-10-1
RAS-13YKH-E, RAS-13YKH-ES
The microprocessor detects the indoor heat exchanger temperature so as to prevent freezing up the
indoor heat exchanger.
Control is performed as shown in Fig. 7-9-1 and 7-92.
Heat exchanger
temperature
(C)
35
Indoor fan speed
32
According to the
set position
<
(C)
7
20
ON
Less than 5C continues
for 5 minutes
OFF
Fig. 7-10-2
(2) As soon as the defrost operation starts, the
indoor fan stops.
Fig. 7-9-1
RAS-13YKH-E, RAS-13YKH-ES
Heat exchanger
temperature
(C)
6
2
Fig. 7-9-2
26
Max 6 minutes
Defrost
Heating
minutes
40
Defrost
minutes
40
Heating
minutes
40
Defrost
Heating
minutes
40
Defrost
Heating
10 minutes
1 cycle
Fig. 7-11-2
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operation time is 10 minutes.
(C)
D
19
10
Cumulative
compressor
operation time
C
40
90
(min.)
DEFROST LAMP :
During defrost operation, the PRE-DEF. lamp is
on and the indoor and outdoor fans are off.
The compressor start protection timer is
interlocked with the PRE-DEF. lamp. So the
PRE-DEF. lamp is off (the fans stop) for about 3
minutes after the START/STOP button is turned
on. When the compressor is turned on, the
PRE-DEF. lamp comes on. After the heat
exchanger is preheated to about 30C or
higher, the PRE-DEF. lamp goes off, and the
indoor fan starts.
27
MOTION
0
3S
Stand-by
TEMPORARY
If the system is not required to run at this time, push the TEMPORARY
button once more or use the remote control and the unit will stop.
OPERATION
Push the TEMPORARY button
continuously more than three
seconds.
0
3S
Operating
The green light is lit.
TEMPORARY
If the system is not required to stop at this time, use the remote control
and to restart.
28
OPERATION
Push the TEMPORARY button
continuously more than three
seconds.
0
3S
TEMPORARY
Stand-by
MOTION
0
3S
Operating
The orange light is lit.
TEMPORARY
If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the green light is lighting.
29
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be more than polychloroprene sheathed flexible cord
(design H05 RN-F), or cord designation 245 IEC 57.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY.
This appliance must be connected to the mains by means of a circuit breaker or a switch with a contact separation
of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance
completely from the mains.
DANGER
` FOR ELECTRICAL WORKS THE WIRING AND CABLES MUST BE PERFORMED IN COMPLIANCE WITH
NATIONAL WIRING STANDARD OR REGULATION.
IF INCORRECT AND INCOMPLETE WIRING IS CARRIED OUT, IT WILL CAUSE AN ELECTRICAL FIRE OR
ELECTRICAL SHOCK.
` USE THE SPECIFIED CABLE (1,5 to 2,0mm) AND CONNECT TIGHTLY FOR INDOOR/OUTDOOR
CONNECTION. CONNECT TIGHTLY AND CLAMP THE CABLE SO THAT EXTERNAL FORCE WILL BE
ACTED ON THE TERMINAL.
` WIRE ROUTING MUST BE PROPERLY ARRANGED SO THAT CONTROL BOARD COVER IS FIXED
PROPERLY.
` DO NOT DAMAGE OR SCRATCH THE CONDUCTIVE CORE AND INNER INSULATOR OF THE CABLES.
` DO NOT DEFORM OR SMASH ON THE SURFACE OF THE CABLES. DO NOT PRESS OR FIX THE CORD
AND CABLES FIRMLY WITH STAPLES, etc.
` DO NOT USE THE EXTENSION CABLE FOR POWER SUPPLY CORD OR INTER-CONNECTING CABLE.
NEVER EXECUTE THE CONNECTION OF WIRING WITH OTHER METHOD THAN THE APPROVED ONE.
OTHERWISE, OVERHEAT, SMOKE OR FIRE MAY BE GENERATED BY CONTACT ERROR.
` TURN OFF MAIN POWER SUPPLY AND BREAKER BEFORE ATTEMPTING ANY ELECTRICAL WORK.
MAKE SURE ALL POWER SWITCHES AND BREAKER TURN OFF. FAILURE TO DO SO MAY CAUSE
ELECTRIC SHOCK.
` CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY
WRONG WAY, ELECTRIC PARTS MAY BE DAMAGED.
` GROUNDING WIRE WORKS MUST BE CONSTRUCTED IN COMPLIANCE WITH INSTALLATION MANUAL.
` DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
` TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD. PLACE THE UNIT WELL
AWAY (MORE THAN 2M.) FROM HEAT SOURCE SUCH AS RADIATORS, HEAT REGISTORS. FURNACE,
STOVES, etc.
` IF A REFRIGERATION GAS LEAKS DURING INSTALLATION, BE SURE TO PERFORM VENTLATION.
IF THE REFRIGERANT GAS COMES INTO CONTACT WITH FIRE, A POISONOUS GAS MAY OCCUR.
WHEN INSTALLING AN AIR CONDITIONER, DO NOT ALLOW AIR OR MOISTURE TO REMAIN IN THE
REFRIGERATION CYCLE. OTHERWISE, PRESSURE IN THE REFRIGERATION CYCLE MAY BECOME
ABNORMALLY HIGH SO THAT A RUPTURE OR PERSONAL INJURY MAY BE CAUSED.
` BE SURE TO USE THE CORD-CLAMPS AND THE ELECTRIC PARTS COVER TO THE SPECIFIED
POSITION WITH ATTACHED TO THE PRODUCT. MOUNT THE ELECTRIC PARTS COVER FOR CABLES OF
CONNECTING SECTION FIRMLY WITH THE SCREWS.
30
WARNING
Never modify this unit by removing any of the safety guards or by-passing any of the safety interlock
switches.
Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply cord.
And make sure the equipment to be earthed.
Appliance shall be installed in accordance with national wiring requlations.
If you detect any damage, do not install the unit. Contact your Toshiba dealer immediately.
CAUTION
Exposure of unit to water or other moisture before installation will result in an electrical short.
Do not store in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb users neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read the installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
31
66 mm or more
Clip anchor
Hook
120
mm
or m
Front cabinet
ore
Wall
Hook
1 Installation
plate
Front panel
120
or mmm
ore
Hook
4 Mounting screw
Air
Shield pipe
the
fron
t ca
bin
et)
(At
tac
h to
5 Deodorizing
filter
Pan head
wood screw
9
the
fron
t ca
bin
et)
6 Purifying
filter
2 Wireless
remote
control
Right
re
r mo
mo
m
B
Rear
Rear left
Bottom
Extension
drain hose
(Option:
RB-821SW)
600
mm
or m
ore
re
r mo
mo
Am
3
Batteries
8 Remote
control
holder
100
mm
or m
ore
RAS-10YA-ES
RAS-10YAH-ES
RAS-13YA-ES
RAS-13YAH-ES
400 *
45*
600
100
32
Left
Cover
A
B
filte
600 mm or more
(At
tac
h to
8-3. Installation
8-3-1. Optional Parts
Part
code
Parts name
Qty
Refrigerant piping
A
Each
one
Bottom plate
7 Drain nipple
Each
one
Fig. 8-3-2
600mm
Air inlet
52,5mm
301mm
120mm
7 Drain nipple
Air outlet
600mm
Air inlet
30mm
111mm
230mm
7 Drain nipple
Air outlet
33
Name of parts
Q'ty
Part
No.
Name of parts
Q'ty
Installation plate x 1
Mounting screw 4x 25 x 6
Batteries x 2
Drain nipple* x 1
Deodorizing filter x 1
Name of parts
Q'ty
Part
No.
Purifying filter x 1
Others
Name
Installation manual
Owners manual
34
CAUTION
<Remote control>
A place where there are no obstacles such as a
curtain that may block the signal from the remote
control.
Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment.
(This is necessary to prevent image disturbances
or noise interference.)
The location of the remote control should be
determined as shown below.
Fig. 8-4-2
(1) After determining the pipe hole position with the
mounting plate (80 mm ), drill the pipe hole
(65 mm) at a slight downward slant to the
outdoor side.
NOTE :
When drilling the wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe hole
brim ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper
pattern on the back.
(Top view)
45
*7m
5m
Indoor unit
66mm or more
5m
65,5mm
120mm
or more
65,5mm
75
7m
40,5
mm
m
65
80mm
Reception Remote
control
range
Reception
range
*:Axial distance
Remote
control
Pipe
hole
Pipe hole
Thread
Indoor unit
Fig. 8-4-1
Weight
4 Mounting
screw
Fig. 8-4-3
35
1
Installation
plate
CAUTION
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
In case of block, brick, concrete or similar type
walls, make holes in the wall.
Insert clip anchors for appropriate T mounting
screws.
NOTE :
Install the installation plate using 4 to 6 pieces of
mounting screw securing four corners with screws.
CAUTION
When installing the installation plate with mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
(Keep horizontal direction)
CAUTION
Anchor bolt
Projection
15mm
or less
5mm dia, hole
Clip anchor
4 Mounting screw 4 x 25
NOTE :
Perform wiring works so as to allow a generous
wiring capacity.
Fig. 8-4-4
MODEL
Power source
Maximum running current
Plug socket & fuse rating
Wiring
RAS-07YKH-E, RAS-10YKH-E
RAS-13YKH-E
RAS-07YKH-ES, RAS-10YKH-ES
RAS-13YKH-ES
50Hz *220240V ~ Single-phase
7,5A (4,0A For RAS-07YKH-E, ES only)
12A
16A
16A
1mm2 or more
1,3mm2 or more
* No adjustment is necessary.
36
WARNING
To plug the cable in the plug receptacle, take the
following precaution.
THIS APPLIANCE MUST BE EARTHED.
Slitted portion
IMPORTANT
THE WIRES IN THIS MAINS LEAD ARE COLORED
IN ACCORDANCE WITH THE FOLLOWING CODE:
L : Brown
N : Blue
: Green and Yellow
-LIVE
-NEUTRAL
-EARTH
L
N
Fig. 8-4-5
As the colors of the flexible cord of this appliance
may not correspond with the colored markings, to
identify terminals in your plug, as follows:
Connect BROWN colored core to plug terminal
marked letter L.
Connect BLUE colored core to plug terminal marked
letter N.
Connect GREEN AND YELLOW colored core to plug
terminal marked Earth Symbol
.
Cord clamp
Terminal block
Power supply
cord
Terminal cover
Screw
L
N
4
4
Screw
1 2
1 2 3
Vertical air flow louver.
Earth line
Screw
Fig. 8-4-6
Fig. 8-4-7
L
N
(1) Open the screw caps and remove the two screws
securing the front cabinet.
(2) Close the screw caps as behind.
(3) Open the vertical airflow louver horizontally by
hand.
(4) Slightly open the lower part of the front cabinet
then pull the upper part of the front cabinet
toward you to remove it from the rear plate.
10mm
Earth line
40mm
NOTE :
Use standard wire only.
Wire type: More than H05-RN-F
37
Fig. 8-4-8
Push
Push
CAUTION
Push
Fig. 8-4-11
Terminal block
Cord
Terminal
clamp
cover
Screw
1 2
Earth
line
about 15cm
Screw
Screw
Connecting cable
Fig. 8-4-12
Fig. 8-4-9
Earth line
4
3
2
1
10mm
40mm
Slit
(front panel)
Slit
(rear panel)
Fig. 8-4-13
38
196mm
96mm
(1)
Hook here
1 Installation
plate
43mm
(2)
Push
Hook
80
Fig. 8-4-15
Fig. 8-4-14
NOTE :
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to auxiliary pipes
and wrap the facing tape around them.
CAUTION
Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the
auxiliary pipes (two) only with facing tape.
Push
Fig. 8-4-16
Indoor unit
Auxiliary
pipes
Push
Connecting
cable
Installation
plate
39
8-4-6. Drainage
KInstallation place
NOTE :
Hole should be made at a slight downward slant to
the outdoor side.
50 mm
or more
Fig. 8-4-17
(2) Put water in the drain pan and make sure that the
water is drained outdoors.
(3) When connecting extension drain hose, insulate
the connecting part of extension drain hose with
U shield pipe.
5 Shield pipe
CAUTION
Fig. 8-4-18
CAUTION
Arrange the drain pipe for proper drainage from
the unit.
Improper drainage can result in damage to
property.
This air conditioner has the structure designed to
drain water collected from dew, which forms on the
back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
Strong
wind
Wall
Drain guide
Fig. 8-5-1
Space for pipes
Fig. 8-4-19
40
CAUTION
Installation in the following places may result in
trouble. Do not install the unit in such places.
A place full of machine oil.
A saline place such as coast.
A place full of sulfide gas.
A place where high-frequency waves are likely
to be generated as from radio equipment,
welders, and medical equipment.
<Flaring>
(1) Cut the pipe with a pipe cutter.
Obliquity
90
Roughness
Warp
Fig. 8-5-2
(2) Insert a flare nut into the pipe, and flare the pipe.
A (mm) R22
A (mm) R410A
Outer
dia.
Imperial
Rigid
Imperial
Rigid
6,35mm
1,0 ~ 1,5
0,5 ~ 1,0
1,5 ~ 2,0
1,0 ~ 1,5
9,52mm
1,0 ~ 1,5
0,5 ~ 1,0
1,5 ~ 2,0
1,0 ~ 1,5
12,7mm
1,5 ~ 2,0
0,5 ~ 1,1
Die
Pipe
Fig. 8-5-3
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers.
Then tighten the nut with a spanner and torque
wrench as shown in the figure.
CAUTION
Do not apply excess torque. Otherwise, the
nut may crack depending on the installation
conditions.
Outer dia.
Tightening touque
Nm (kgfm)
6,35mm
16 ~ 18 (1,6 ~ 1,8)
9,52mm
30 ~ 42 (3,0 ~ 4,2)
12,7mm
50 ~ 62 (5,0 ~ 6,2)
Externally
threaded
side
Internally
threaded
side
Use a torque wrench
to tighten.
Use a wrench
to secure.
Fig. 8-5-4
41
Flare nut
INFORMATION
7/16 UNF
20 threads per inch
1/2 UNF
20 threads per inch
Hi
Charge
hose (B)
Gas
(9,52)
Service port
Lo
Outdoor unit
Indoor unit
Port
size
Manifold valve
High pressure
side handle
VP
Packed
valve
B
Liquid
(6,35)
Fig. 8-5-5
AIR PURGE
Evacuate the air in the connecting pipes and in
the indoor unit using vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the manual of vacuum pump.
<Use of vacuum pump>
(1) Connect the charge hose (A) from the manifold
valve to the charge inlet of the gas side packed
valve.
(2) Connect the charge hose (B) to the port of
vacuum pump.
(3) Open fully the low pressure side handle of the
manifold valve.
(4) Operate the vacuum pump.
(5) Close the low pressure side handle of manifold
valve after vacuumizing and stop the vacuum
pump.
CAUTION
KEEP IMPORTANT 4 POINTS FOR
INSTALLATION (PIPING WORK)
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
<Packed Valve Handling Precautions>
Open the valve stem all the way out; so not try
to open it beyond the stopper.
Securely tighten the valve stem cap with the
wrench or like.
Valve stem cap tightening torque is as follows;
Gas pipes side (12,7) : 49 ~ 62 Nm (5,0 ~ 6,2 kgfm)
Stopper
Wrench
Valve body
5m
Service port
Valve stem
Service port cap
42
8-6. Others
Electric parts
cover
Service port
Valve stem cap connection
Fig. 8-6-1
Check the flare nut connections, valve stem cap
connections and service cap connections for gas
leak with a leak detector or soap water.
Terminal block
70mm
Terminal
Earth line
10mm
screw
Screw
10mm
60mm
A
B
4
3
2
1
Flare nut
connections
(Outdoor unit)
Connecting
cable
Cord clamp
Fig. 8-5-7
CAUTION
TEMPORARY
button
TEMPORARY
Fig. 8-6-2
INFORMATION
The product was shipped with Auto Restart
function in the off position. Turn it on as required.
9. TROUBLESHOOTING CHART
TROUBLESHOOTING PROCEDURES :
Following details of What to be pre-checked first, make sure of the basic items.
When there is no trouble corresponding to above, check in detail the faulty parts following How to judge
faulty parts by symptoms later.
2
3
Description
The OPERATION lamp blinks, indicating that power is turned on.
If this happens, push the START/STOP button once to cause the lamp to stop
blinking. A power outage also causes the lamp to blink.
Fan speed is automatically controlled in the dry mode.
In the dry mode, the compressor goes on and off at regular intervals,
independent of the thermo. control.
The PRE-DEF. lamp comes on during defrost operation and when the indoor
heat exchanger temperature is low when the heating operation is started.
At this time, the indoor fan is stopped to prevent cold air from drifting into the
room.
When the indoor heat exchanger temperature is high, the outdoor fan may
be stopped by the high-temperature limit control operation.
When the compressor current is large, the outdoor fan may be stopped by
the current limit control operation.
Compressor does not work while the compressor restart delay (3-min.) timer
is active. The same is true after power is turned on, as the time is still active.
After selection of the cooling and heating operation, the operation mode is
selected again when the compressor off mode continues for 15min.
according to the room temperature.
When the room temperature is within setting temperature 1C the fan only
mode is selected.
44
Description
Compressor trouble
No reaction on remote
control operation
Check
Primary judgement
OK.
45
[ METHOD ]
1 Push the [CHK] button with a thin tip of pencil or
FAN
2 Push
AUTO
AUTO
COOL
DRY
HEAT
FAN ONLY
LOW
MED.
HIGH
3 Operating
TEMP.
2
3
START/STOP
to
SET
key of TEMP.
>
<>
6
AUTO
OFF
RSV
<--
<>
<--->
<
ECONO.
TIMER
ON
<>
FAN
-->
MODE ACL CHK
CNL
WH-E1BE
To clear the memory, need to use another service check remote control.
(service part No. 43T69058).
46
Table 9-2-3
Block level
Check
code
Block
Indoor
P.C. board
Cable
connectio
n/Therm
al fuse
Refrigera
nt system
Diagnosis function
Check
code
Air
Conditioner
status
Condition
Thermo. sensor
short/break.
Continued
operation
Indicated when
detected abnormal
Heat exchanger
sensor
short/break.
Continued
operation
Indicated when
detected abnormal
All off
Abnormality of
other indoor unit
P.C. board.
All off
Indicated when
detected abnormal
1) Wrong wiring or
disconnection of
connective
cable.
All off
Indicated when
detected abnormal
Symptom
All off
Indicated when
detected abnormal
Compressor break
down.
All off
Indicated when
detected abnormal
1. Check compressor.
2. If it is OK, check P.C.
board.
47
Operation
Check Items
Main cause
Countermeasure
Symptom
NO
NO
YES
NO
YES
(No problem)
Remote control
is defective.
YES
YES
Wrong wiring of
AC cord or connecting
cable is defective.
Replace the
remote control.
NO
Does the thermal
fuse blow?
(Under PF. Terminal)
Replace the
thermal fuse set.
Check connection.
NO
NO
NO
P.C. board
is defective.
YES
Is the voltage
NO Refer to the paragraph
Pre-check, or defective circuit
across C02 measured
before power PC board block.
DC310V~340V?
YES
Shut off the power
Is the secondary
voltage of SW trans- NO supply once, and turn
it on again after disformer (T01) measured
connecting the motor
DC35V, DC12V,
connector CN10 .
and DC7V ?
YES
Is the secondary
voltage of SW
NO
transformer measured
DC35V, DC12V,
and DC7V?
SW transformer
(T01) or Tr (Q01)
for power supply
is defective.
YES
Motor is defective.
sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of dam* Be
age of the motor.
48
9-3-2. Power can not be Turned on after Replacing Indoor P.C. Board
<Checking Procedure>
Connect the AC
Power supply
NO
Is it wired as shown
in Figure below?
NO
YES
YES
To the paragraph of
No Power turns on.
Black
White
Blue
Bind Band
Brown
Indoor
terminal
block
RY01
N L
Power
terminal
block
P.C. board
Double
winding
RY02
T02
RY02
T02
RAS-13YKH-E, RAS-13YKH-ES
Black
White
Blue
Brown
Indoor
terminal
block
RY01
N L
Power
terminal
block
P.C. board
49
NO
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
NO
YES
Is AC 220240V
supplied between terminal block
1 - 2 ?
NO
YES
Is cable connection
between indoor and outdoor
units correct?
NO
YES
Check items as following procedure
in 9-3-4, 9-3-5, 9-3-6.
50
Replace the
P.C. board.
NO
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
NO
YES
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220240V?
NO
NO
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220240V?
NO
YES
Are all the cords for compressor normal?
NO
YES
Is the compressor motor winding normal?
(Check the winding resistor.)
NO
Compressor is defective.
YES
Is the capacitor for compressor normal?
NO
Capacitor is defective.
YES
Is the overload relay normal?
NO
YES
Does the compressor start?
NO
Compressor is defective.
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
NO
YES
Compressor is defective
51
Replace the
P.C. board.
NO
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
NO
YES
Is the voltage across the indoor terminal
( 2 - 4 ) AC 220240V?
NO
NO
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 4 ) AC 220240V?
NO
NO
YES
Are all the cords for outdoor
fan motor normal?
YES
Is the outdoor fan motor winding normal?
(Check the winding resistance)
NO
YES
Is the capacitor for compressor normal?
NO
YES
Outdoor fan motor is defective.
52
Replace the
P.C. board.
9-3-6. Only 4-Way Valve does not Operate (During Heating Operation)
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
NO
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
NO
YES
Is the voltage across the terminal
( 2 - 3 ) 220-240 V?
NO
NO
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 3 ) 220-240 V?
NO
YES
Is the wiring of solenoid coil
for 4-way valve normal?
NO
YES
4-way valve is defective.
53
Replace the
P.C. board.
NO
YES
Start the operation
with low fan setting
in cool operation.
NO
YES
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
NO
YES
YES
NO
NO
Repair the
bearing of
the fan.
YES
Turn on the power supply.
NO
Operation
stops
YES
Replace the P.C. board.
NO
Replace the
fan motor
YES
Normal
54
9-4. How to Check the Remote Control (Including the Indoor P.C. Board)
There is no beep from
the indoor unit.
The operation lamp of
the air conditioner main
unit does not light.
NO
YES
Is there direct
sunlight on the
receptor of the
air conditioner?
NO
YES
Is there any
thyristor
fluorescent light
near by?
NO
NO
YES
Is operation
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
air conditioner?
YES
Battery life
NO
Does the
transmission
indicator light?
Is operation
possible when setting
the temporary switch of the
air conditioner main unit to
TEST RUN or
TEMPORARY AUTO?
NO
YES
NO
YES
Is there any
beep and
operation?
YES
NO
YES
Remote control
is failure.
Avoid direct
sunlight.
Replace
P.C. board.
Replace the
batteries
Normal
55
Replace remote
control.
56
Procedure
Causes
1. Application of shock voltage.
Overload by short-circuit of the parts.
Voltage check
Voltage check
2. Cool operation
3. Air volume [AUTO]
1. Heat operation
1. Operation [Cooling]
2. Airflow [High fan]
3. Continuous operation
57
Top View
Bottom View
58
Table 9-4-2 Approximate value of the sensor (thermistor) resistance (TA, TC)
(= k)
Temperature
Sensor
Themo. Sensor
0C
10C
20C
25C
30C
35,8
20,7
12,6
10,0
7,92
TEMP.
START/STOP
SET
AUTO
FAN
ECONO.
[CHK] button
TIMER
ON
OFF
RSV
CNL
WC-E1BE
[CNL] button
Fig. 9-4-1
59
Part name
Front panel
Procedure
Remarks
3 2
2 3
4) Check the gap between the front panel and the main
unit.
If cooling or drying operation is performed without
pressing the center of the air outlet, the surface of the
front panel may be covered with frost and have a dew
drop.
Drain guide
Upper nail
Screw
Electrical
part cover
Drain-pan
assembly
TC-sensor
When assembling dress the connecting
cable in loop and put it into the drain-pan.
60
No.
Part name
Horizontal grille
Procedure
1) Perform the process R.
Heat exchanger
Remarks
Louver motor
Horizontal grille
Screw
Hooks
Pipe holder
Shaft
bearing
6~7m
Shaft bearing
Screw
Cross
flow fan
Rear plate
Fan motor
61
Ribs
10-2. Microcomputer
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES, RAS-13YKH-E, RAS-13YKH-ES
No.
Part name
Common
procedure
Procedure
Remarks
1) Turn the power supply off to stop the operation of airconditioner, and disconnect the power cord from the AC
supply.
62
Part name
Common
procedure
Procedure
Remarks
Remove
7-ST1T
4 10
1-ST1T
4 10
Capacitor for
compressor
Capacitor for
fan motor
Same as above.
Overload
relay
Q above.
63
RAS-13YAH-E, RAS-13YAH-ES
No.
Part name
Common
procedure
Procedure
Remarks
2-ST1T
4 10
Capacitor for
compressor
Capacitor for
fan motor
1-ST2T
f4 8
Overload
relay
1-ST2T
f4 8
1-ST2T
f4 10
OL-Holder
Thermostat
bimetal
Compressor
Thermo
holder
64
405
404
402
401
406
413
403
412
402
Location
No.
401
402
403
404
405
Part
No.
Description
Location
No.
Part
No.
Description
406
406
406
407
65
24
23
16
25
17, 26
12, 15
19
14 2
8, 9
13
10, 11
20
21
22
18
7 : CAPILLARY TUBE
27 : DRYER
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
43T19001
43T20001
43005037
43T43001
43062194
43T00320
43T47014
43T46017
43T47021
43T46016
43T47020
43T46003
43T21001
43T47001
Description
Location
Part
No.
No.
15
16
17
18
19
20
21
22
23
24
25
26
27
43T49030
43T19005
43T49001
43T79001
43T19002
43T63001
43054403
43T41400
43055483
43T55001
43060049
43T97001
43T45003
Guard, Fan
Fan, Propeller
Cabinet, Front
Condenser (10YAH-E)
Cover, E-Parts
Cabinet, Back
Tube, Capillary
Valve, Packed 9,52
Bonnet
Valve, Packed 6,35
Bonnet
4-Way-Valve, VH7100D
Motor, Fan, UE6-21SJ5P
Nut, Flange
67
Description
Solenoid coil
Handle
Rubber, Cushion
Nipple, Drain
Stopper, Guard
Holder, OL-Relay
Relay, Over Load
Compressor, PH120T1-4C
Capacitor, 25F 400V
Capacitor, 1,5F 500V
Base,Terminal , 5P
Nut, Flat-washer
Dryer
RAS-10YAH-ES
23
22
17
24
18
15 2
9, 11
14
10, 12
21
19
7 : CAPILLARY TUBE
8 : CAPILLARY TUBE
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
43T19001
43T20001
43005037
43T43011
43062194
43T00320
43T47024
43T47007
43T46011
43T46010
43T47021
43T47020
43T46012
Description
Location
Part
No.
No.
14
15
16
17
18
19
20
21
22
23
24
25
26
43T21001
43T47001
43T46013
43T19005
43T49001
43T79001
43T19002
43T41406
43055483
43T55001
43060049
43T46005
43T45004
Guard, Fan
Fan, Propeller
Cabinet, Front
Condenser
Cover, E-Parts
Cabinet, Back
Tube, Capillary, 0,8DIA
Tube, Capillary, 1,2DIA
Valve, Packed 9,52
Valve, Packed 6,35
Bonnet
Bonnet
4-Way-Valve, VHV-0104
68
Description
Motor, Fan, UE6-21SJ5P
Nut, Flange
Coil, 4-Way, VHV-01AI501A
Handle
Rubber, Cushion
Nipple, Drain
Stopper, Guard
Compressor, PA118X1T-4FZ
Capacitor, 25F 400V
Capacitor, 1,5F 500V
Base,Terminal , 5P
Valve, Checked
Dryer
RAS-13YAH-E
13
5
33
34
29
30
14
28
35
7
8
25
10
20
11
21, 36
17,18
6
4
9
12
3
23
24
19
15,16
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
43005144
43005143
43042446
43T19007
43T19005
43T19002
43T62007
43020302
43021984
43T47001
43T46005
43T63004
43T96001
43043609
43T46016
43T47020
43T46019
43T47018
43T47029
Description
Location
Part
No.
No.
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
43T47007
43T47014
43041764
43T97001
43T49008
43045085
43054398
43T79004
43043610
43055496
43T55009
43T50002
43T63005
43146482
43T49030
43060049
43T47017
Cabinet, Front
Cabinet-Side
Base
Guard, Fan
Handle
Stopper, Guard
Cover, E-Parts
Fan, Propeller
Motor, Fan, AF-230-28P
Nut, Flange
Valve, Check
Holder, Wire, Lead
Bushing
Condenser
Valve, Packed 6,35
Bonnet
Valve, Packed 12,7
Bonnet
ASM, Packed Valve Cap
12,7, 6,35
69
26
22
27
Location
No.
31, 32
Description
RAS-13YAH-ES
13
5
29
30
26
2
27
14
28
7
8
1
24
10
20
17
18
4
9
12
3
22
23
15
16
25
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
43005144
43005143
43042446
43T19007
43T19005
43T19002
43T62007
43020302
43021984
43T47001
43T46005
43T63004
43T96001
43T43012
43T46016
Description
Location
Part
No.
No.
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
43T47021
43T46011
43T47020
43T47007
43T47008
43041700
43T97001
43T49008
43T45004
43T79004
43055496
43T55009
43060049
43T46012
43T46013
Cabinet, Front
Cabinet-Side
Base
Guard, Fan
Handle
Stopper, Guard
Cover, E-Parts
Fan, Propeller
Motor, Fan, AF-230-28P
Nut, Flange
Valve, Check
Holder, Wire, Lead
Bushing
Condenser
Valve, Packed 6,35
70
11
19
21
Description
Bonnet
Valve, Packed 9,52
Bonnet
Tube, Capillary, 1,2DIA
Tube, Capillary, 1,5DIA
Compressor, PA160x2T-4FZ
Nut, Flat-Washer
Cushion, Rubber
Dryer
Nipple, Drain
Capacitor, 35F 400V
Capacitor, 1,5F 500V
Base,Terminal, 5P
4Way-Valve, VHV-0104
Coil, 4Way, VHV-01AI501A
RAS-07YAH-E
24
23
16
25
17
12, 15
19
14 2
8, 9
13
10, 11
20
21
22
18
7 : CAPILLARY TUBE
1
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
43T19001
43T20001
43005037
43T43001
43T62007
43T00032
43T47307
43T46303
43T47021
43T46306
43T47020
43T46003
43021928
43T47001
Description
Location
Part
No.
No.
15
16
17
18
19
20
21
22
23
24
25
43T49030
43T19005
43T49001
43T79001
43T19002
43T63001
43T54302
43T41304
43055483
43T55009
43060049
Guard, Fan
Fan, Propeller
Cabinet, Front
Condenser
Cover, E-Parts
Cabinet, Back
Tube, Capillary
Valve, Packed 9.52
Bonnet , 3/8 IN
Valve, Packed 6.35
Bonnet , 1/4 IN
4-Way-Valve, VH7100D
Motor, Fan, HFNut, Flange
71
Description
Solenoid coil
Handle
Rubber, Cushion
Nipple, Drain
Stopper, Guard
OL-Relay
Relay, Over Load
Compressor, PH80T1-4C
Capacitor, 25MF 400V
Capacitor, PLASTIC-FILM
Terminal Block , 5P
RAS-07YAH-ES
22
21
16
23
17
12,15
19
14 2
8, 9
13
10,11
20
18
7 : CAPILLARY TUBE
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
43T19001
43T20001
43005037
43T43011
43T62007
43T00032
43T47306
43T46302
43T47021
43T46305
43T47020
43T46012
43021928
Description
Location
Part
No.
No.
14
15
16
17
18
19
20
21
22
23
43T47001
43T46013
43T19005
43T49001
43T79001
43T19002
43T41309
43055470
43T55009
43060049
Guard, Fan
Fan, Propeller
Cabinet, Front
Condenser
Cover, E-Parts
Cabinet, Back
Tube, Capillary
Vale,Packed 9.52
BONNET,3/8IN
Valve, Packed 6,35
Bonnet,1/4IN
Valve,4Way,VHV-0104
Fan-Motor
72
Description
Nut,Flange
Coil,4Way,VHV-01AI501A1
Handle
Rubber,Cushion
Drain -Nipple
Guard - Stopper
Compressor,PA79X1T-4FZ
Capacitor,15MFD,400V
Capacitor,Plastic-Film
Terminal Block,5P