Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

BAY NAME

CRANE CAPACITY
VOLTAGE

AB
100/30T
690 V

DETAILS OF MOTORS
MH
AH1
AH2
CT1
CT2
LT
OTHERS ( LIGHTING+ BRAKES ETC.)

KW
160.8
143

A
QTY.
192.2
2
170.9
1

19.7

23.5

47.1

49.1
30

58.7
35.9

4
1

234.8
35.9

LENGTH OF BAY (METERS)


LENGTH OF DSL (METERS)
NO. OF CRANES

TOTAL (A)
384.4
170.9

111
93
2

METERS
METERS
NOS.

IMAX1

(MH+LT+OTHERS)

655.1

IMAX2

(MH+LT+OTHERS)

655.1

ITOTAL

IMAX1 + IMAX2
D.F.

1310.1
0.7

DIVERSITY FACTOR

917
0.5

A
A/mm2

1834

mm2

2400

mm2

ITOTAL (D.F.)
CURRENT DENSITY OF STEEL
AREA REQUIRED FOR DSL

SELECTED DSL SIZE

AREA

100 x 100 x 12

NOTE : HENCE DSL SIZE SELECTED IS OK


VOLTAGE DROP
RESTDSL
RDSL
XDSL
WHERE
F

RESISTIVITY OF STEEL
RESISTANCE OF ANGLE/
METER

0.000000118
4.91667E-005

REACTANCE OF DSL/
METER = 2 x x F x L

XDSL

FREQUANCY
DISTANCE BETWEEN
ANGLES
EQUIVALENT RADIUS OF
ANGLE = SQ.ROOT OF
(AREA OF DSL/)
PERMIABILITY FACTOR
INDUCTANCE OF DSL
0.5(9.2LOG(D/RAD)+ )
2xxFxL

9.38403E-007
0.0002947525

ZDSL

(RDSL X 0.8 + XDSL X 0.6)

0.0002161848

VDSL / MTR

VOLTAGE DROP PER METER


IN DSL

0.3433992759

VDSL

VOLTAGE DROP IN DSL

16.0

% Voltage drop

% 690 V

2.3

D
RAD
MUE ()
L

50

Hz

500

mm

27.6
7.2

V/MTRS

BAY NAME
CRANE CAPACITY
VOLTAGE

BC
150/50/10T
690 V

DETAILS OF MOTORS
MH
AH1
AH2
CT1
CT2
LT

KW
250
223.4
80.4
33.1
13.4
67

A
298.8
267.0
96.1
39.6
16.0
80.1

QTY.
2
1
1
2
1
4

TOTAL (A)
597.7
267.0
96.1
79.1
16.0
320.4

OTHERS ( LIGHTING+ BRAKES ETC.)

30

35.9

35.9

LENGTH OF BAY (METERS)


LENGTH OF DSL (METERS)
NO. OF CRANES

123
105
2

MTRS
MTRS
NOS.

IMAX1

(MH+LT+OTHERS)

953.9

IMAX2

(MH+LT+OTHERS)

953.9

ITOTAL

IMAX1 + IMAX2
D.F.

1907.8
0.7

DIVERSITY FACTOR

1335
0.5

A
A/mm2

AREA

2671

mm2

125 x 125 x 12

3000

mm2

ITOTAL (D.F.)
CURRENT DENSITY OF STEEL
AREA REQUIRED FOR DSL

SELECTED DSL SIZE

NOTE : HENCE DSL SIZE SELECTED IS OK


VOLTAGE DROP
RESTDSL
RDSL
XDSL
WHERE
F
D

RESISTIVITY OF STEEL
RESISTANCE OF ANGLE/
METER

0.000000118
3.9333E-005

REACTANCE OF DSL/ METER =


2xxFxL

XDSL

FREQUANCY
DISTANCE BETWEEN ANGLES
EQUIVALENT RADIUS OF
ANGLE = SQ.ROOT OF (AREA
OF DSL/)
PERMIABILITY FACTOR
INDUCTANCE OF DSL
0.5(9.2LOG(D/RAD)+ )
2xxFxL

9.1611E-007
0.000287751

ZDSL

(RDSL X 0.8 + XDSL X 0.6)

0.000204117

VDSL / MTR

VOLTAGE DROP PER METER IN


DSL

0.472146501

VDSL

VOLTAGE DROP IN DSL

24.8

% Voltage drop

% 690 V

3.6

RAD
MUE ()
L

50
500

Hz
mm

30.9
7.2

V/MTRS

BAY NAME
CRANE CAPACITY
VOLTAGE

DE & FG
250/60/20T
690 V

DETAILS OF MOTORS
MH
AH1
AH2
CT1
CT2
LT

KW
425
230.2
98.3
55.4
26.8
67

A
508.0
275.2
117.5
66.2
32.0
80.1

QTY.
2
1
1
2
1
8

TOTAL (A)
1016.1
275.2
117.5
132.4
32.0
640.7

OTHERS ( LIGHTING+ BRAKES ETC.)

40

47.8

47.8

LENGTH OF BAY (METERS)


LENGTH OF DSL (METERS)
NO. OF CRANES

135
117
2

MTRS
MTRS
NOS.

IMAX1

(MH+LT+OTHERS)

1704.6

IMAX2

(MH+LT+OTHERS)

1704.6

ITOTAL

IMAX1 + IMAX2
D.F.

3409.2
0.7

DIVERSITY FACTOR

2386
0.5

A
A/mm2

4773

mm2

6583

mm2

ITOTAL (D.F.)
CURRENT DENSITY OF STEEL
AREA REQUIRED FOR DSL

SELECTED DSL SIZE

AREA

IRS52(RAIL)

NOTE : HENCE DSL SIZE SELECTED IS OK


VOLTAGE DROP
RESTDSL

RESISTIVITY OF STEEL

0.000000118

RDSL

RESISTANCE OF ANGLE/ METER

0.000017925

XDSL

REACTANCE OF DSL/ METER =


2xxFxL

WHERE
F
D

XDSL

FREQUANCY
DISTANCE BETWEEN ANGLES
EQUIVALENT RADIUS OF
ANGLE = SQ.ROOT OF (AREA
OF DSL/)
PERMIABILITY FACTOR
INDUCTANCE OF DSL
0.5(9.2LOG(D/RAD)+ )
2xxFxL

8.3761E-007
0.000263095

ZDSL

(RDSL X 0.8 + XDSL X 0.6)

0.000172197

RAD
MUE ()
L

VDSL / MTR

VDSL

VOLTAGE DROP PER METER IN


DSL
Total no. of Power Feeder 2
nos.
VOLTAGE DROP IN DSL

50
500

Hz
mm

45.8
7.2

0.711767508

13.9

V/MTRS

% Voltage drop

% 690 V

2.0