Overhead Electric Distribution Standards

TRANSFORMERS
1)

This section shows different configurations of one, two, and three-phase transformers for the 4kV,
13.2kV, and 26.4kV primary systems used by JEA.

2)

On one, two, and three-phase vertical structures, the cutout/arrester bracket shall always be mounted
behind the bottom phase even if the lowest phase is not present. The top transformer bolt will always
be 54 inches below the top bolt of the cutout/arrester bracket.

3)

For horizontal construction, the cutout/arrester bracket shall always be mounted 43 inches below the
crossarm mounting bolt. For step-down application, the second crossarm shall always be 54 inches
below the top transformer bolt.

4)

Jumper pin locations are listed in a table within this section and must be used to support primary
jumpers. Call for the sub-structures as indicated in the table.

5)

Caution shall be observed if installing a streetlight with the 8 rise bracket on poles with 100kVA or
larger transformers. No other equipment shall be mounted on the same pole with a transformer.
Standard clearances will be strictly observed when mounting streetlights and taking primary taps from
the same pole.

6)

Transformers installed on structures utilizing aerial cable should be treated as if it was bare primary.
No special plates are required.

7)

Transformers are NOT to be installed on corner poles with the following exceptions:
Definition: Any structure, single or multiple-phase, where the primary creates a 90 degree angle or
thereabouts.
Rules and allowable exceptions:
i)

No three-phase corner poles and/or three-phase tap poles will have transformers installed
on them.

ii)

On a 90 degree single-phase 45 pole with primary mounted in the A-phase position, the
cutout/arrester bracket for a transformer may be installed in the B-phase holes and still
have 54 of clearance to the transformer.

iii) On a single-phase tap pole, the lateral fuse cutout can be installed with the transformer
cutout, provided they are mounted on opposite sides of the pole.
iv) On three-phase tangent poles, A and B-phase may be tapped with a single-phase
transformer on C-phase.
v) No more than three cutouts shall be installed on a pole.
8)

Hot-line clamps are not part of the transformer plates and must be plated separately.

9)

Plate options are listed on each page in the upper left-hand corner of each construction standard.

10)

For proper energizing and de-energizing procedures when working with closed-delta transformer
banks, refer to Standards Bulletin SB-29. This bulletin also addresses the application and installation
of a temporary grounding switch for nuisance banks.

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 1

Approved By: KKR

Overhead Electric Distribution Standards


11)

Transformer Secondary Downlead Sizes*:


Transformer Size
10-15kVA
25-50kVA*
75kVA and larger

12)

Conductor Size
2/0 Copper
4/0 Copper*
500KCM Copper

Insulation Type
RHW or USE
RHW or USE
RHW or USE

Secondary Downleads shall not be utilized for single-phase 25 & 50 kVA transformer
installations (all primary voltages). Plates for 25 & 50 kVA single-phase transformers include
the CNNTS007 multi-tap connectors.

Three NEW options have been added to the transformer plates. For single-phase transformer
plates, options have been added to provide 240/480V transformers. For three-phase transformer
plates, options have been added to supply 120/208V or 277/480V transformers. See the following
examples:
DGA*50/480 = 26.4kV, 1, 50kVA transformer, 240/480V
DGC*50/208 = 26.4kV, 3 bank, 3-50kVA transformers, 120/208V
RGC*75/480 = 4kV, 3 bank, 3-75kVA transformers, 277/480V

NOTE: Only plates DGC*25/208, DGC*50/208, and DGC*75/208, supply transformers that have already
had their secondary internal taps changed to provide 208V. All other 208 transformer options must
have their internal taps changed in the field or prior to issue by the storeroom.

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 2

Approved By: KKR

Overhead Electric Distribution Standards


JUMPER PIN LOCATION TABLE

* Indicates hole must be field drilled

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 3

Approved By: KKR

Overhead Electric Distribution Standards


TRANSFORMER WIRING DIAGRAM

SINGLE-PHASE CONNECTION
120/240 VOLT, 1-PHASE, 3-WIRE SERVICE

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 4

Approved By: KKR

Overhead Electric Distribution Standards


TRANSFORMER WIRING DIAGRAM

OPEN-WYE, OPEN-DELTA CONNECTION


120/240 VOLT, 3-PHASE, 4-WIRE SERVICE
Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 5

Approved By: KKR

Overhead Electric Distribution Standards


TRANSFORMER WIRING DIAGRAM

UNGROUNDED WYE-DELTA CONNECTION


120/240 VOLT, 3-PHASE, 4-WIRE SERVICE

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 6

Approved By: KKR

Overhead Electric Distribution Standards


TRANSFORMER WIRING DIAGRAM

GROUNDED WYE, GROUNDED WYE CONNECTION


120/208 VOLT, 3-PHASE, 4-WIRE SERVICE

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 7

Approved By: KKR

Overhead Electric Distribution Standards


TRANSFORMER WIRING DIAGRAM

GROUNDED WYE, GROUNDED WYE CONNECTION


277/480 VOLT, 3-PHASE, 4-WIRE SERVICE

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 8

Approved By: KKR

Overhead Electric Distribution Standards


TRANSFORMER WIRING DIAGRAM

FOR REFERENCE ONLY


UNGROUNDED WYE-DELTA CONNECTION
240/480 VOLT, 3-PHASE, 4-WIRE SERVICE

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 9

Approved By: KKR

Overhead Electric Distribution Standards

RGA
SINGLE-PHASE TRANSFORMER 4kV
OPTIONS: 10, 15, 25, 50, 75, 100, 167, 50/480
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
*5
6
7
8
9
10
11
12
13
14
15

ARR LI 001
BOL MS 020
BOL MS 035
BKT AC 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA CA ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

1
2
2
1
22
1
20
2
1
1
1
2
4
4
4

DESCRIPTION

ARRESTER, LIGHTNING, 3KV, POLYMER MOV (DIST.)


BOLT, MACHINE, SQUARE HEAD, 5/8X14
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BRACKET, ARRESTER AND CUTOUT, POLE MOUNTED
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT
CONNECTOR, TRANSFORMER SECONDARY SET SCREW TYPE WITH INHIBITOR STUD,
** 16
CNNTS007
3
RANGE: 10 500, 6 HOLES
* NOT ISSUED WITH 25 & 50 KVA TRANSFORMERS
** ONLY ISSUED WITH 25 & 50 KVA TRANSFORMERS

MULTI-TAP INSTALLATION

1. Tie one secondary neutral to the mainline neutral and then continue that secondary neutral to the multi-tap
connector.
2. Tie the remaining secondary neutrals directly to the multi-tap connector.
3. Take one continuous piece of #4 solid copper and run it from the multi-tap connector to the tank grounds
then to the pole ground.

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 10

Approved By: KKR

Overhead Electric Distribution Standards

RGA
SINGLE-PHASE TRANSFORMER 4kV

MOUNT CUTOUTS IN THE


SAME DIRECTION OR
PLANE AS THE PRIMARY
CONDUCTOR.

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 11

Approved By: KKR

Overhead Electric Distribution Standards

RGB
TWO-PHASE TRANSFORMER BANK 4kV
OPTIONS: 10-10, 15-10, 15-15, 25-10, 25-15, 25-25, 50-10, 50-15, 50-25, 50-50, 75-25, 75-50, 75-75,
100-50, 100-75, 100-100, 167-75, 167-100, 167-167
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

ARR LI 001
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 002
BKT TM 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA CA ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

2
4
2
2
1
2
45
2
42
4
2
2
2
4
10
2
4

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 3KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 12

Approved By: KKR

Overhead Electric Distribution Standards

RGB
TWO-PHASE TRANSFORMER BANK 4kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 13

Approved By: KKR

Overhead Electric Distribution Standards

RGC
THREE-PHASE TRANSFORMER BANK 4kV
OPTIONS: 75-75, 100-75, 100-100, 167-100, 167-167,
25/208, 50/208, 75/208, 100/208, 167/208,
50/480, 75/480, 100/480, 167/480
NOTE: 25-167kVA TRANSFORMERS MUST HAVE THEIR INTERNAL SECONDARY TAPS CHANGED
IN THE FIELD OR PRIOR TO ISSUE IN ORDER TO PROVIDE 208 VOLTAGE.
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

ARR LI 001
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 002
BKT TM 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA CA ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

3
6
2
4
1
3
32
3
60
6
3
3
3
6
14
4
6

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 3KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 14

Approved By: KKR

Overhead Electric Distribution Standards

RGC
THREE-PHASE TRANSFORMER BANK 4kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 15

Approved By: KKR

Overhead Electric Distribution Standards

WGA
SINGLE-PHASE TRANSFORMER 13.2kV
OPTIONS: 10, 15, 25, 50, 75, 100, 167, 50/480
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
*5
6
7
8
9
10
11
12
13
14
15

ARR LI 002
BOL MS 020
BOL MS 035
BKT AC 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA CD ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

1
2
2
1
22
1
20
2
1
1
1
2
4
4
4

DESCRIPTION

ARRESTER, LIGHTNING, 10KV, POLYMER MOV (DIST.)


BOLT, MACHINE, SQUARE HEAD, 5/8X14
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BRACKET, ARRESTER AND CUTOUT, POLE MOUNTED
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT
CONNECTOR, TRANSFORMER SECONDARY SET SCREW TYPE WITH INHIBITOR STUD,
** 16
CNNTS007
3
RANGE: 10 500, 6 HOLES
* NOT ISSUED WITH 25 & 50 KVA TRANSFORMERS
** ONLY ISSUED WITH 25 & 50 KVA TRANSFORMERS

MULTI-TAP INSTALLATION

1. Tie one secondary neutral to the mainline neutral and then continue that secondary neutral to the multi-tap
connector.
2. Tie the remaining secondary neutrals directly to the multi-tap connector.
3. Take one continuous piece of #4 solid copper and run it from the multi-tap connector to the tank grounds
then to the pole ground.
Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 16

Approved By: KKR

Overhead Electric Distribution Standards

WGA
SINGLE-PHASE TRANSFORMER 13.2kV

MOUNT CUTOUTS IN THE


SAME DIRECTION OR
PLANE AS THE PRIMARY
CONDUCTOR.

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 17

Approved By: KKR

Overhead Electric Distribution Standards

WGB
TWO-PHASE TRANSFORMER BANK 13.2kV
OPTIONS: 10-10, 15-10, 15-15, 25-10, 25-15, 25-25, 50-10, 50-15, 50-25, 50-50, 75-25, 75-50, 75-75,
100-50, 100-75, 100-100, 167-100, 167-167
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

ARR LI 002
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 002
BKT TM 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA CD ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

2
4
2
2
1
2
45
2
42
4
2
2
2
4
10
2
4

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 10KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 18

Approved By: KKR

Overhead Electric Distribution Standards

WGB
TWO-PHASE TRANSFORMER BANK 13.2kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 19

Approved By: KKR

Overhead Electric Distribution Standards

WGC
THREE-PHASE TRANSFORMER BANK 13.2kV
OPTIONS: 75-75, 100-75, 100-100, 167-100, 167-167,
25/208, 50/208, 75/208, 100/208, 167/208,
50/480, 75/480, 100/480, 167/480
NOTE: 25-167kVA TRANSFORMERS MUST HAVE THEIR SECONDARY INTERNAL TAPS CHANGED
IN THE FIELD TO PROVIDE 208 VOLTAGE.
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

ARR LI 002
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 002
BKT TM 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA CD ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

3
6
2
4
1
3
32
3
60
6
3
3
3
6
14
4
6

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 10KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 20

Approved By: KKR

Overhead Electric Distribution Standards

WGC
THREE-PHASE TRANSFORMER BANK 13.2kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 21

Approved By: KKR

Overhead Electric Distribution Standards

DGA
SINGLE-PHASE TRANSFORMER 26.4kV
OPTIONS: 10, 15, 25, 50, 75, 100, 167, 25/480, 50/480, 75/480
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
*5
6
7
8
9
10
11
12
13
14
15

ARR LI 003
BOL MS 020
BOL MS 035
BKT AC 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA ** ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

1
2
2
1
22
1
20
2
1
1
1
2
4
4
4

DESCRIPTION

ARRESTER, LIGHTNING, 21KV, POLYMER MOV (DIST.)


BOLT, MACHINE, SQUARE HEAD, 5/8X14
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BRACKET, ARRESTER AND CUTOUT, POLE MOUNTED
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT
CONNECTOR, TRANSFORMER SECONDARY SET SCREW TYPE WITH INHIBITOR STUD,
** 16
CNNTS007
3
RANGE: 10 500, 6 HOLES
* NOT ISSUED WITH 25 & 50 KVA TRANSFORMERS
** ONLY ISSUED WITH 25 & 50 KVA TRANSFORMERS

MULTI-TAP INSTALLATION

4. Tie one secondary neutral to the mainline neutral and then continue that secondary neutral to the multi-tap
connector.
5. Tie the remaining secondary neutrals directly to the multi-tap connector.
6. Take one continuous piece of #4 solid copper and run it from the multi-tap connector to the tank grounds
then to the pole ground.

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 22

Approved By: KKR

Overhead Electric Distribution Standards

DGA
SINGLE-PHASE TRANSFORMER 26.4kV

MOUNT CUTOUTS IN THE


SAME DIRECTION OR
PLANE AS THE PRIMARY
CONDUCTOR.

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 23

Approved By: KKR

Overhead Electric Distribution Standards

DGB
TWO-PHASE TRANSFORMER BANK 26.4kV
OPTIONS: 10-10, 15-10, 15-15, 25-10, 25-15, 25-25, 50-10, 50-15, 50-25, 50-50, 75-10, 75-15, 75-25,
75-50, 75-75, 100-10, 100-15, 100-25, 100-50, 100-75, 100-100, 167-10, 167-15, 167-25,
167-50, 167-75, 167-100, 167-167
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

ARR LI 003
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 002
BKT TM 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA ** ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

2
4
2
2
1
2
45
2
42
4
2
2
2
4
10
2
4

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 21KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 24

Approved By: KKR

Overhead Electric Distribution Standards

DGB
TWO-PHASE TRANSFORMER BANK 26.4kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 25

Approved By: KKR

Overhead Electric Distribution Standards

DGC
THREE-PHASE TRANSFORMER BANK 26.4kV
OPTIONS: 75-75, 100-75, 100-100, 167-100, 167-167,
25/208, 50/208, 75/208, 100/208, 167/208,
50/480, 75/480, 100/480, 167/480
NOTE: 100kVA AND 167kVA TRANSFORMERS MUST HAVE THEIR INTERNAL SECONDARY TAPS
CHANGED IN THE FIELD TO PROVIDE 208 VOLTAGE.
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

ARR LI 003
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 002
BKT TM 001
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT 004
FUS OH ***
TRA ** ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

3
6
2
4
1
3
32
3
60
6
3
3
3
6
14
4
6

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 21KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 26

Approved By: KKR

Overhead Electric Distribution Standards

DGC
THREE-PHASE TRANSFORMER BANK 26.4kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 27

Approved By: KKR

Overhead Electric Distribution Standards

DGRA
SINGLE-PHASE STEP-DOWN TRANSFORMER 26.4kV TO 4kV
OPTIONS: 50, 75, 100, 167, 250
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

ARR LI 001
ARR LI 003
BOL MS 020
BOL MS 035
BKT AC 002
CAI RH ***
CLA TG 001
COB CO 028
CNN VG 003
CUT OT X01
CUT OT 004
FUS OH ***
TRA SB ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

1
1
2
2
1
22
1
20
2
1
1
2
1
2
4
4
4

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 3KV, POLYMER MOV (DIST.)
ARRESTER, LIGHTNING, 21KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X14
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
GENERAL CODE FOR COPPER RHW CABLE
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 125KV BIL, 100 AMP, 27KV
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 28

Approved By: KKR

Overhead Electric Distribution Standards

DGRA
SINGLE-PHASE STEP-DOWN TRANSFORMER 26.4kV TO 4kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 29

Approved By: KKR

Overhead Electric Distribution Standards

DGRB
TWO-PHASE STEP-DOWN TRANSFORMER BANK 26.4kV TO 4kV
OPTIONS: 50, 75, 100, 167, 250
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

ARR LI 001
ARR LI 003
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 003
BKT AC 002
BKT TM 001
CLA TG 001
COB CO 028
CNN VG 003
CUT OT X01
CUT OT 004
FUS OH ***
TRA SB ***
WAS RD 004
WAS RD 005
WAS SP 002

2
2
4
2
2
8
1
2
2
40
4
2
2
4
2
4
6
2

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 3KV, POLYMER MOV (DIST.)
ARRESTER, LIGHTNING, 21KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER OR CUTOUT, CROSSARM MOUNTING
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 125KV BIL, 100 AMP, 27KV
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 30

Approved By: KKR

Overhead Electric Distribution Standards

DGRB
TWO-PHASE STEP-DOWN TRANSFORMER BANK 26.4kV TO 4kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 31

Approved By: KKR

Overhead Electric Distribution Standards

DGRC
THREE-PHASE STEP-DOWN TRANSFORMER BANK 26.4kV TO 4kV
OPTIONS: 50, 75, 100, 167, 250
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

ARR LI 001
ARR LI 003
BOL MS 015
BOL MS 035
BOL MS 036
BKT AC 003
BKT AC 002
BKT TM 001
CLA TG 001
COB CO 028
CNN VG 003
CUT OT X01
CUT OT 004
FUS OH ***
TRA SB ***
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002

3
3
6
2
4
6
1
3
2
60
6
3
3
6
3
6
14
4
6

Revised: July 1, 2004

DESCRIPTION
ARRESTER, LIGHTNING, 3KV, POLYMER MOV (DIST.)
ARRESTER, LIGHTNING, 21KV, POLYMER MOV (DIST.)
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X12
BOLT, MACHINE, SQUARE HEAD, 3/4X14
BRACKET, ARRESTER OR CUTOUT, CROSSARM MOUNTING
BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
BRACKET, TRANSFORMER MOUNTING
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CUTOUT, FUSED, 125KV BIL, 100 AMP, 27KV
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
GENERAL CODE FOR FUSE-LINK
GENERAL CODE FOR TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised By: TAC

TRANSFORMERS
TR - 32

Approved By: KKR

Overhead Electric Distribution Standards

DGRC
THREE-PHASE STEP-DOWN TRANSFORMER BANK 26.4kV TO 4kV

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 33

Approved By: KKR

Overhead Electric Distribution Standards

LG2
CONSTANT CURRENT TRANSFORMER FOR U.G. STREETLIGHT CIRCUIT
OPTIONS: NONE
BOLT PLATE: NONE
NO.

ITEM ID

QTY

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57

ANC ST 001
ARR LI ***
BKT AC 003
BKT TM 001
BKT TM 003
BOL DA 020
BOL MS 015
BOL MS 037
BOL MS 038
BOX SE 001
CAI CL 004
CLA TG 001
CNN CP 020
CNN CP 021
CNN VG 003
CNN WC 003
COB CO 028
COD ST 003
COD ST 006
COI BW 003
COI BW 005
COI BW 021
COI BW 022
CUT OT 004
CXA ST 001
FUS UG 009
INS VP 001
MET HU 002
STL PC 001
STL PC 004
STP ST 001
STP ST 005
STU LI 003
TRA SL 001
WAS RD 004
WAS RD 005
WAS SF 003
WAS SP 002
WEA HE 001
-------------------

24
1
4
1
2
3
2
3
1
1
60
1
2
2
2
2
20
20
20
10
10
25
25
3
3
1
3
1
1
1
6
6
3
1
2
23
4
4
1
1
1
20FT
1
3
1
8FT
8
8
1
2
12FT
4FT
1
1
2
6
8FT

Revised: July 1, 2004

DESCRIPTION
ANCHOR, STUD BOLT, 1/4X3/4 IN.
GENERAL CODE FOR ARRESTER
BRACKET, ARRESTER AND CUTOUT, CROSSARM MOUNT
BRACKET, TRANSFORMER MOUNTING
BRACKET, TRANSFORMER ADAPTER PLATE
BOLT, DOUBLE ARMING, 3/4X24
BOLT, MACHINE, SQUARE HEAD, 5/8X2
BOLT, MACHINE, SQUARE HEAD, 3/4X16
BOLT, MACHINE, SQUARE HEAD, 3/4X18
BOX, CONCRETE SECONDARY SERVICE, 17X28
CABLE, PRIMARY, 5kV, 8CU
CLAMP, TRANSFORMER TANK GROUND, #6 SOL. - #1 STR.
CONNECTOR, COMPRESSION, CU, 1/0
CONNECTOR, COMPRESSION, CU, #2 STR.
CONNECTOR, VISE TYPE, 6-2 SOL. - 10-2 SOL.
CONNECTOR, TERMINAL, 12-10 AWG
CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
CONDUIT, STEEL, 1 IN.
CONDUIT, STEEL, 2 IN.
WIRE, THWN, 12 SOL. BLACK
WIRE, THWN, 12 SOL., WHITE
WIRE, THWN, 6 STR., BLACK
WIRE, THWN, 6 STR., WHITE
CUTOUT, FUSED, 150KV BIL, 100 AMP, 27KV
CROSSARM, STEEL, 5 X 5 X 10
FUSE, UNDERGROUND, 15A, NON-15
INSULATOR, VERTICAL POST, 34.5kV
HUB, CONDUIT, 1 IN., INTERCHANGEABLE
PHOTOELECTRIC CONTROL, ELECTRONIC, 105-130V
PHOTOELECTRIC CONTROL BRACKET
STRAP, CONDUIT, STEEL, 1 IN.
STRAP, CONDUIT, STEEL, 2 IN.
STUD, LINE POST
6.6 AMP REGULATED OUTPUT TRANSFORMER
WASHER, ROUND, 1-3/4 IN. DIA., FOR 5/8 IN. BOLT
WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT
WEATHERHEAD, 2 IN.
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
1 INCH EMT
FS BOX
1 INCH SEALTITE STRAIGHT CONNECTOR
1 INCH SEALTITE 45 DEGREE CONNECTOR
3/8 IN. THREADED ROD
3/8 IN. NUTS
3/8 IN. WASHERS
1 INCH EMT COUPLING
1 INCH EMT CONNECTORS
CONDUCTOR, COPPER, #4 SOFT DRAWN
CONDUCTOR, COPPER, #6 SOFT DRAWN
SINGLE GANG METER CAN
4-POLE TEST BLOCK
C.T. TERMINAL CONNECTORS
1 IN. PIPE STRAPS
KINDORF OR UNISTRUT CHANNEL

Revised By: TAC

TRANSFORMERS
TR - 34

Approved By: KKR

Overhead Electric Distribution Standards

LG2
CONSTANT CURRENT TRANSFORMER FOR U.G. STREETLIGHT CIRCUIT

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 35

Approved By: KKR

Overhead Electric Distribution Standards

LG2
CONSTANT CURRENT TRANSFORMER FOR U.G. STREETLIGHT CIRCUIT

Revised: July 1, 2004

Revised By: TAC

TRANSFORMERS
TR - 36

Approved By: KKR