BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance = 150 ft

# of Poles = 10
poles
kVAresidential = 41.22 kVA

System Voltage =240 V


Voltage Drop = 5 %

VDC = System Voltage x Voltage Drop = 240 x 0.05 = 12 V


kVANORTH=

41.222 + (0.16 x 10) =

kVA SpanNORTH =

42.82 kVA

No. of Bundles:

128.69 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (42.822 x1000)/240
= 178.425 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (128.686 42.822)x150
= 450.771 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 178.425 x 450.771) / (12 x 1)
=

160858 CM

167806

CM

Based on Table For Circular Mill:


Use:

AWG Copper Conductor, 2-Wires


7 Strands Hard Drawn Copper Conductor
167806 CMILS

No. 000

(For 3 ft. Spacing Between Two 167806 CM Wires:)


Based on Table
Ra = 0.382 /mile
Xa =
Xd =

0.518

/mile

0.2794 log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.651 /mile
Reactance and Resistance Ratio (X t/Ra):
Ratio= Xt Ra
= 0.651307678568674 0.382
= 1.705
Based on Table : AC DROP FACTOR @ 85% = 1.85

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 178.425 x 450.771) (167806 x 1)
=
11.503 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.503 x 1.85
=
21.281 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (21.281 240) x 100
= 8.867 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


# of Poles = 10 poles
kVAresidential = 56.80 kVA

Pole Distance = 150 ft


System Voltage = 240 V
Voltage Drop = 5 %
VDC = System Voltage x Voltage Drop = 240 x 0.05 = 12 V
kVASOUTH = 56.796 + (0.16 x 10) = 58.40 kVA

No. of Bundles:

kVA SpanSOUTH = 129.25 kVA


Total Current Computation:
ISOUTH = (kVASOUTH) (System Voltage)
= (58.396 x1000)/240
= 243.317 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (129.252 58.396)x150
= 332.006 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 243.317 x 332.006) / (12 x 1)
= 161565 CM 167806 CM
Based on Table For Circular Mill:
Use:

No.
167806

000
7

167806

AWG Copper Conductor, 2-Wires


Strands Hard Drawn Copper Conductor
CMILS

(For 3 ft. Spacing Between Two 167806 CM Wires:)


Based on Table
Ra = 0.382 /mile
Xa =

0.518

Xd =

0.2794

/mile
log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6513 /mile
Reactance and Resistance Ratio (X t/Ra):
Ratio= Xt Ra

Based on Table :

= 0.651307678568674 0.382
=
1.705
AC DROP FACTOR @ 85% =

1.85

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 243.317 x 332.006) (167806 x 1)
=
11.554 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.554 x 1.85
=
21.375 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (21.375 240) x 100
=
8.906 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

52.60 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

52.6 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

54.20 kVA

=
No. of Bundles:

189.18 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (54.2 x1000)/240
= 225.833 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (189.178 54.2)x150
= 523.555 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 225.833 x 523.555) / (12 x 1)
=

236472 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

400

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 225.833 x 523.555) (250000 x 1)
=
11.351 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.351 x 3.1
=
35.188 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (35.188 240) x 100
=
14.662 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

65.41

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

65.408 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

67.01 kVA

=
No. of Bundles:

188.81 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (67.008 x1000)/240
= 279.200 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (188.81 67.008)x150
= 422.658 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 279.200 x 422.658) / (12 x 1)
=

236012 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

400

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 279.200 x 422.658) (250000 x 1)
=
11.329 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.329 x 3.1
=
35.120 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (35.120 240) x 100
=
14.633 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

78.00 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

77.996 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

79.60 kVA

=
No. of Bundles:

287.64 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (79.596 x1000)/240
= 331.650 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (287.642 79.596)x150
= 542.066 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 331.650 x 542.066) / (12 x 1)
=

359552 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 331.650 x 542.066) (400000 x 1)
=
10.787 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.787 x 3.1
=
33.440 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (33.440 240) x 100
=
13.933 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

63.90

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

63.9 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

65.50 kVA

=
No. of Bundles:

288.16 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (65.5 x1000)/240
= 272.917 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (288.164 65.5)x150
=
659.918 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 272.917 x 659.918) / (12 x 1)
=

360206 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 272.917 x 659.918) (400000 x 1)
=
10.806 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.806 x 3.1
=
33.499 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (33.499 240) x 100
=
13.958 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

57.75 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

57.746 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

59.35 kVA

=
No. of Bundles:

256.93 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (59.346 x1000)/240
= 247.275 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (256.926 59.346)x150
= 649.393 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 247.275 x 649.393) / (12 x 1)
=

321157 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 247.275 x 649.393) (400000 x 1)
=
9.635 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.635 x 3.1
=
29.869 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (29.869 240) x 100
=
12.445 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

59.15

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

59.152 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

60.75 kVA

=
No. of Bundles:

256.89 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (60.752 x1000)/240
=
253.133 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (256.892 60.752)x150
= 634.280 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 253.133 x 634.280) / (12 x 1)
=

321114 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 253.133 x 634.280) (400000 x 1)
=
9.633 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.633 x 3.1
=
29.862 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (29.862 240) x 100
=
12.443 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =
System Voltage =
Voltage Drop =

150 ft
240 V
5 %

VDC = System Voltage x Voltage Drop


kVANORTH

79.164 + (0.16 x 10) =

kVA SpanNORTH =

# of Poles =
kVAresidential =

10
poles
79.16 kVA

240 x 0.05

80.76 kVA

No. of Bundles:

280.44 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (80.764 x1000)/240
= 336.517 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (280.438 80.764)x150
= 520.847 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 336.517 x 520.847) / (12 x 1)
400000 CM
= 350548 CM
Based on Table For Circular Mill:
Use:

No.

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS
400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (Xt/Ra):
Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 336.517 x 520.847) (400000 x 1)
=
10.516 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.516 x 3.1
= 32.600 V

12 V
1

Voltage Regulation Computation:


%VR = (Vac Drop System Voltage) x 100
= (32.600 240) x 100
=
13.583 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =
System Voltage =
Voltage Drop =

150 ft
240 V
5 %

# of Poles =
kVAresidential =

VDC = System Voltage x Voltage Drop


kVASOUTH =

64.978 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

66.58 kVA

10
64.98

poles
kVA

No. of Bundles:

279.69 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (66.578 x1000)/240
= 277.408 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (279.694 66.578)x150
= 630.150 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 277.408 x 630.150) / (12 x 1)
=
349617 CM
400000 CM
Based on Table For Circular Mill:
Use:

No.

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS
400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 277.408 x 630.150) (400000 x 1)
=
10.489 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.489 x 3.1
=
32.516 V

12 V
1

Voltage Regulation Computation:


%VR = (Vac Drop System Voltage) x 100
= (32.516 240) x 100
=
13.548 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

poles

53.96 kVA

240 x 0.05

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

53.958 + (0.16 x 10) =

kVA SpanNORTH =

55.56 kVA

No. of Bundles:

254.52 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (55.558 x1000)/240
= 231.492 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (254.518 55.558)x150
= 687.168 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 231.492 x 687.168) / (12 x 1)
=

318148 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

300

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.609 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
= 2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 231.492 x 687.168) (400000 x 1)
=
9.544 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.544 x 2.6
=
24.814 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (24.814 240) x 100
=
10.339 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

64.04

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

64.044 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

65.64 kVA

=
No. of Bundles:

255.19 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (65.644 x1000)/240
=
273.517 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (255.192 65.644)x150
=
583.127 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 273.517 x 583.127) / (12 x 1)
=

318990 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

300

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6093 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
=
2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 273.517 x 583.127) (400000 x 1)
=
9.570 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.570 x 2.6
=
24.882 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (24.882 240) x 100
=
10.368 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

50.67 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

50.672 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

52.27 kVA

=
No. of Bundles:

192.12 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (52.272 x1000)/240
= 217.800 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (192.12 52.272)x150
= 551.309 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 217.800 x 551.309) / (12 x 1)
=

240150 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + X d =
0.62 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
= 2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 217.800 x 551.309) (250000 x 1)
=
11.527 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.527 x 2.28
=
26.282 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (26.282 240) x 100
=
10.951 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

46.42

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

46.418 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

48.02 kVA

=
No. of Bundles:

191.17 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (48.018 x1000)/240
= 200.075 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (191.174 48.018)x150
=
597.195 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 200.075 x 597.195) / (12 x 1)
=

238968 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6203 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
=
2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 200.075 x 597.195) (250000 x 1)
=
11.470 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.470 x 2.28
=
26.152 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (26.152 240) x 100
=
10.897 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

240 x 0.05

poles

71.65 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

71.648 + (0.16 x 10) =

kVA SpanNORTH =

73.25 kVA

No. of Bundles:

262.86 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (73.248 x1000)/240
= 305.200 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (262.858 73.248)x150
= 538.290 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 305.200 x 538.290) / (12 x 1)
=

328572 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 305.200 x 538.290) (400000 x 1)
=
9.857 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.857 x 3.1
=
30.557 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.557 240) x 100
=
12.732 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

75.02

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

75.018 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

76.62 kVA

=
No. of Bundles:

263.43 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (76.618 x1000)/240
= 319.242 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (263.426 76.618)x150
=
515.726 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 319.242 x 515.726) / (12 x 1)
=

329283 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 319.242 x 515.726) (400000 x 1)
=
9.878 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.878 x 3.1
=
30.622 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.622 240) x 100
=
12.759 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

78.07 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

78.068 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

79.67 kVA

=
No. of Bundles:

294.48 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (79.668 x1000)/240
= 331.950 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (294.484 79.668)x150
= 554.459 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 331.950 x 554.459) / (12 x 1)
=

368105 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 331.950 x 554.459) (400000 x 1)
=
11.043 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.043 x 3.1
=
34.233 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (34.233 240) x 100
=
14.264 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

67.05

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

67.048 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

68.65 kVA

=
No. of Bundles:

294.48 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (68.648 x1000)/240
= 286.033 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (294.484 68.648)x150
= 643.465 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 286.033 x 643.465) / (12 x 1)
=

368104 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 286.033 x 643.465) (400000 x 1)
=
11.043 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.043 x 3.1
=
34.233 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (34.233 240) x 100
=
14.264 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

10

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

240 x 0.05

poles

48.13 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

48.132 + (0.16 x 10) =

kVA SpanNORTH =

49.73 kVA

No. of Bundles:

179.28 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (49.732 x1000)/240
= 207.217 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (179.276 49.732)x150
= 540.726 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 207.217 x 540.726) / (12 x 1)
=

224095 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + X d =
0.62 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
= 2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 207.217 x 540.726) (250000 x 1)
=
10.757 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.757 x 2.28
=
24.526 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (24.526 240) x 100
=
10.219 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

45.00

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

44.996 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

46.60 kVA

=
No. of Bundles:

179.28 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (46.596 x1000)/240
= 194.150 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (179.276 46.596)x150
=
577.118 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 194.150 x 577.118) / (12 x 1)
=

224095 CM

250000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6203 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
=
2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 194.150 x 577.118) (250000 x 1)
=
10.757 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.757 x 2.28
=
24.526 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (24.526 240) x 100
=
10.219 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

11

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

44.68 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

44.676 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

46.28 kVA

=
No. of Bundles:

191.89 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (46.276 x1000)/240
= 192.817 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (191.888 46.276)x150
= 621.990 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 192.817 x 621.990) / (12 x 1)
=

239860 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

400

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 192.817 x 621.990) (250000 x 1)
=
11.513 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.513 x 3.1
=
35.690 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (35.690 240) x 100
=
14.871 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

54.91

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

54.912 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

56.51 kVA

=
No. of Bundles:

191.93 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (56.512 x1000)/240
= 235.467 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (191.932 56.512)x150
= 509.446 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 235.467 x 509.446) / (12 x 1)
=

239915 CM

250000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

400

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 235.467 x 509.446) (250000 x 1)
=
11.516 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.516 x 3.1
=
35.700 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (35.700 240) x 100
=
14.875 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

12

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

240 x 0.05

poles

77.11 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

77.114 + (0.16 x 10) =

kVA SpanNORTH =

78.71 kVA

No. of Bundles:

294.14 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (78.714 x1000)/240
= 327.975 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (294.142 78.714)x150
= 560.527 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 327.975 x 560.527) / (12 x 1)
=

367678 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 327.975 x 560.527) (400000 x 1)
=
11.030 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.030 x 3.1
=
34.193 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (34.193 240) x 100
=
14.247 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

70.82

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

70.82 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

72.42 kVA

=
No. of Bundles:

293.34 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (72.42 x1000)/240
= 301.750 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (293.336 72.42)x150
= 607.572 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 301.750 x 607.572) / (12 x 1)
=

366670 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 301.750 x 607.572) (400000 x 1)
=
11.000 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.000 x 3.1
=
34.100 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (34.100 240) x 100
=
14.208 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

13

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

65.47 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

65.468 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

67.07 kVA

=
No. of Bundles:

270.21 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (67.068 x1000)/240
= 279.450 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (270.208 67.068)x150
= 604.330 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 279.450 x 604.330) / (12 x 1)
=

337760 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 279.450 x 604.330) (400000 x 1)
=
10.133 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.133 x 3.1
=
31.412 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (31.412 240) x 100
=
13.088 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

65.16

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

65.16 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

66.76 kVA

=
No. of Bundles:

270.71 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (66.76 x1000)/240
= 278.167 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (270.712 66.76)x150
= 608.250 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 278.167 x 608.250) / (12 x 1)
=

338390 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 278.167 x 608.250) (400000 x 1)
=
10.152 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.152 x 3.1
=
31.471 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (31.471 240) x 100
=
13.113 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

14

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

240 x 0.05

poles

48.61 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

48.614 + (0.16 x 10) =

kVA SpanNORTH =

50.21 kVA

No. of Bundles:

163.92 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (50.214 x1000)/240
= 209.225 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (163.918 50.214)x150
= 489.658 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 209.225 x 489.658) / (12 x 1)
=

204897 CM

211600

CM

Based on Table For Circular Mill:


Use:

AWG Copper Conductor, 2-Wires


211600
19
Strands Hard Drawn Copper Conductor
211600 CMILS

No.

0000

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.303 /mile
Xa =

0.496

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.629 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.629307678568674 0.303
= 2.0769
AC DROP FACTOR @ 85% =

2.03

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 209.225 x 489.658) (211600 x 1)
=
11.620 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.620 x 2.03
=
23.589 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (23.589 240) x 100
=
9.829 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

50.68

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

50.684 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

52.28 kVA

=
No. of Bundles:

163.03 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (52.284 x1000)/240
= 217.850 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (163.028 52.284)x150
=
467.719 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 217.850 x 467.719) / (12 x 1)
=

203785 CM

211600

CM

Based on Table For Circular Mill:


Use:

No.
211600

0000
19

211600

AWG Copper Conductor, 2-Wires


Strands Hard Drawn Copper Conductor
CMILS

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.303 /mile
Xa =

0.496

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6293 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.629307678568674 0.303
=
2.0769
AC DROP FACTOR @ 85% =

2.03

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 217.850 x 467.719) (211600 x 1)
=
11.557 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.557 x 2.03
=
23.461 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (23.461 240) x 100
=
9.775 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

15

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

240 x 0.05

poles

68.15 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

68.152 + (0.16 x 10) =

kVA SpanNORTH =

69.75 kVA

No. of Bundles:

214.62 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (69.752 x1000)/240
= 290.633 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (214.624 69.752)x150
= 461.544 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 290.633 x 461.544) / (12 x 1)
=

268280 CM

300000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.609 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
= 2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 290.633 x 461.544) (300000 x 1)
=
10.731 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.731 x 2.6
=
27.901 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (27.901 240) x 100
=
11.625 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

56.81

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

56.812 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

58.41 kVA

=
No. of Bundles:

214.28 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (58.412 x1000)/240
= 243.383 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (214.284 58.412)x150
= 550.274 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 243.383 x 550.274) / (12 x 1)
=

267855 CM

300000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6093 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
=
2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 243.383 x 550.274) (300000 x 1)
=
10.714 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.714 x 2.6
=
27.856 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (27.856 240) x 100
=
11.607 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

16

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

63.72 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

63.724 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

65.32 kVA

=
No. of Bundles:

209.51 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (65.324 x1000)/240
= 272.183 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (209.512 65.324)x150
= 481.091 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 272.183 x 481.091) / (12 x 1)
=

261890 CM

300000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.609 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
= 2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 272.183 x 481.091) (300000 x 1)
=
10.476 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.476 x 2.6
=
27.238 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (27.238 240) x 100
=
11.349 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

55.70

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

55.696 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

57.30 kVA

=
No. of Bundles:

209.18 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (57.296 x1000)/240
= 238.733 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (209.18 57.296)x150
= 547.630 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 238.733 x 547.630) / (12 x 1)
=

261475 CM

300000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6093 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
=
2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 238.733 x 547.630) (300000 x 1)
=
10.459 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.459 x 2.6
=
27.193 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (27.193 240) x 100
=
11.330 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

17

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

48.78 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

48.784 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

50.38 kVA

=
No. of Bundles:

236.36 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (50.384 x1000)/240
= 209.933 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (236.356 50.384)x150
= 703.664 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 209.933 x 703.664) / (12 x 1)
=

295445 CM

300000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.609 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
= 2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 209.933 x 703.664) (300000 x 1)
=
11.818 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.818 x 2.6
=
30.727 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.727 240) x 100
=
12.803 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

49.88

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

49.876 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

51.48 kVA

=
No. of Bundles:

235.70 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (51.476 x1000)/240
= 214.483 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (235.7 51.476)x150
= 686.825 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 214.483 x 686.825) / (12 x 1)
=

294625 CM

300000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6093 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
=
2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 214.483 x 686.825) (300000 x 1)
=
11.785 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.785 x 2.6
=
30.641 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.641 240) x 100
=
12.767 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

18

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

46.56 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

46.564 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

48.16 kVA

=
No. of Bundles:

195.52 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (48.164 x1000)/240
= 200.683 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (195.52 48.164)x150
= 608.920 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 200.683 x 608.920) / (12 x 1)
= 244400 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + X d =
0.62 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
= 2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 200.683 x 608.920) (250000 x 1)
=
11.731 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.731 x 2.28
=
26.747 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (26.747 240) x 100
=
11.145 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

48.00

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

48 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

49.60 kVA

=
No. of Bundles:

195.91 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (49.6 x1000)/240
= 206.667 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (195.908 49.6)x150
= 592.464 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 206.667 x 592.464) / (12 x 1)
=

244886 CM

250000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6203 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
=
2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 206.667 x 592.464) (250000 x 1)
=
11.755 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.755 x 2.28
=
26.801 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (26.801 240) x 100
=
11.167 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

19

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

poles

59.63 kVA

240 x 0.05

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

59.634 + (0.16 x 10) =

kVA SpanNORTH =

61.23 kVA

No. of Bundles:

253.14 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (61.234 x1000)/240
= 255.142 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (253.144 61.234)x150
= 620.106 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 255.142 x 620.106) / (12 x 1)
=

316430 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 255.142 x 620.106) (400000 x 1)
=
9.493 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.493 x 3.1
=
29.428 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (29.428 240) x 100
=
12.262 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

59.48

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

59.484 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

61.08 kVA

=
No. of Bundles:

253.20 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (61.084 x1000)/240
= 254.517 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (253.196 61.084)x150
=
621.757 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 254.517 x 621.757) / (12 x 1)
=

316495 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 254.517 x 621.757) (400000 x 1)
=
9.495 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.495 x 3.1
=
29.435 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (29.435 240) x 100
=
12.265 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

20

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

33.28 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

33.278 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

34.88 kVA

=
No. of Bundles:

100.80 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (34.878 x1000)/240
= 145.325 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (100.796 34.878)x150
= 433.494 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 145.325 x 433.494) / (12 x 1)
=

125995 CM

133077

CM

Based on Table For Circular Mill:


Use:

No.
133077

AWG Copper Conductor, 2-Wires


7
Strands Hard Drawn Copper Conductor
133077 CMILS
00

(For 3 ft. Spacing Between Two 133077 CM Wires:)


Based on Table
Ra =
0.48 /mile
Xa =

0.532

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.665 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.665307678568674 0.48
= 1.3861
AC DROP FACTOR @ 85% =

1.61

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 145.325 x 433.494) (133077 x 1)
=
11.361 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.361 x 1.61
=
18.291 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (18.291 240) x 100
=
7.621 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

39.48

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

39.482 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

41.08 kVA

=
No. of Bundles:

100.63 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (41.082 x1000)/240
=
171.175 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (100.628 41.082)x150
=
367.416 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 171.175 x 367.416) / (12 x 1)
=

125785 CM

133077

CM

Based on Table For Circular Mill:


Use:

No.
133077

00
7

133077

AWG Copper Conductor, 2-Wires


Strands Hard Drawn Copper Conductor
CMILS

(For 3 ft. Spacing Between Two 133077 CM Wires:)


Based on Table
Ra =
0.48
/mile
Xa =

0.532

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6653 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.665307678568674 0.48
=
1.3861
AC DROP FACTOR @ 85% =

1.61

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 171.175 x 367.416) (133077 x 1)
=
11.342 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.342 x 1.61
=
18.261 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (18.261 240) x 100
=
7.609 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

21

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

46.97 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

46.97 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

48.57 kVA

=
No. of Bundles:

144.08 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (48.57 x1000)/240
= 202.375 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (144.08 48.57)x150
= 444.966 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 202.375 x 444.966) / (12 x 1)
=

180100 CM

211600

CM

Based on Table For Circular Mill:


Use:

AWG Copper Conductor, 2-Wires


167806
7
Strands Hard Drawn Copper Conductor
211600 CMILS

No.

000

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.382 /mile
Xa =
Xd =

0.518

/mile

0.2794 log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.651 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.651307678568674 0.382
= 1.705
AC DROP FACTOR @ 85% =

1.85

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 202.375 x 444.966) (211600 x 1)
=
10.214 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.214 x 1.85
=
18.896 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (18.896 240) x 100
=
7.873 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

48.61

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

48.614 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

50.21 kVA

=
No. of Bundles:

144.84 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (50.214 x1000)/240
= 209.225 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (144.84 50.214)x150
= 432.668 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 209.225 x 432.668) / (12 x 1)
=

181050 CM

211600

CM

Based on Table For Circular Mill:


Use:

No.
167806

000
7

211600

AWG Copper Conductor, 2-Wires


Strands Hard Drawn Copper Conductor
CMILS

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.382 /mile
Xa =

0.518

Xd =

0.2794

/mile
log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6513 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.651307678568674 0.382
=
1.705
AC DROP FACTOR @ 85% =

1.85

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 209.225 x 432.668) (211600 x 1)
=
10.267 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.267 x 1.85
=
18.994 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (18.994 240) x 100
=
7.914 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

22

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

61.08 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

61.08 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

62.68 kVA

=
No. of Bundles:

236.48 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (62.68 x1000)/240
= 261.167 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (236.482 62.68)x150
= 565.927 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 261.167 x 565.927) / (12 x 1)
=

295603 CM

300000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.609 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
= 2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 261.167 x 565.927) (300000 x 1)
=
11.824 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.824 x 2.6
= 30.742 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.742 240) x 100
=
12.809 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

61.61

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

61.608 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

63.21 kVA

=
No. of Bundles:

237.09 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (63.208 x1000)/240
= 263.367 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (237.094 63.208)x150
= 562.652 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 263.367 x 562.652) / (12 x 1)
=

296368 CM

300000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6093 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
=
2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 263.367 x 562.652) (300000 x 1)
=
11.855 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.855 x 2.6
=
30.823 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.823 240) x 100
=
12.843 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

23

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

poles

76.67 kVA

240 x 0.05

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

76.672 + (0.16 x 10) =

kVA SpanNORTH =

78.27 kVA

No. of Bundles:

290.05 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (78.272 x1000)/240
= 326.133 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (290.05 78.272)x150
= 555.850 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 326.133 x 555.850) / (12 x 1)
=

362562 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 326.133 x 555.850) (400000 x 1)
=
10.877 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.877 x 3.1
=
33.719 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (33.719 240) x 100
=
14.050 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

69.17

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

69.172 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

70.77 kVA

=
No. of Bundles:

289.66 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (70.772 x1000)/240
= 294.883 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (289.662 70.772)x150
=
613.933 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 294.883 x 613.933) / (12 x 1)
=

362077 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 294.883 x 613.933) (400000 x 1)
=
10.862 V
Vac Drop = Vdc Actual x AC Drop Factor
= 10.862 x 3.1
=
33.672 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (33.672 240) x 100
=
14.030 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

24

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

44.37 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

44.374 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

45.97 kVA

=
No. of Bundles:

137.36 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (45.974 x1000)/240
= 191.558 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (137.356 45.974)x150
= 448.153 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 191.558 x 448.153) / (12 x 1)
=

171695 CM

211600

CM

Based on Table For Circular Mill:


Use:

AWG Copper Conductor, 2-Wires


211600
19
Strands Hard Drawn Copper Conductor
211600 CMILS

No.

0000

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.303 /mile
Xa =

0.496

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.629 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.629307678568674 0.303
= 2.0769
AC DROP FACTOR @ 85% =

2.03

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 191.558 x 448.153) (211600 x 1)
=
9.737 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.737 x 2.03
=
19.766 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (19.766 240) x 100
=
8.236 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

49.65

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

49.654 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

51.25 kVA

=
No. of Bundles:

137.11 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (51.254 x1000)/240
=
213.558 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (137.114 51.254)x150
= 401.278 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 213.558 x 401.278) / (12 x 1)
=

171392 CM

211600

CM

Based on Table For Circular Mill:


Use:

No.
211600

0000
19

211600

AWG Copper Conductor, 2-Wires


Strands Hard Drawn Copper Conductor
CMILS

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.303 /mile
Xa =

0.496

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6293 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.629307678568674 0.303
=
2.0769
AC DROP FACTOR @ 85% =

2.03

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 213.558 x 401.278) (211600 x 1)
=
9.720 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.720 x 2.03
=
19.732 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (19.732 240) x 100
=
8.222 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

25

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

240 x 0.05

poles

60.11 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

60.11 + (0.16 x 10) =

kVA SpanNORTH =

61.71 kVA

No. of Bundles:

241.85 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (61.71 x1000)/240
= 257.125 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (241.846 61.71)x150
= 587.861 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 257.125 x 587.861) / (12 x 1)
=

302308 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 257.125 x 587.861) (400000 x 1)
=
9.069 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.069 x 3.1
=
28.114 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (28.114 240) x 100
=
11.714 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

59.89

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

59.89 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

61.49 kVA

=
No. of Bundles:

241.64 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (61.49 x1000)/240
= 256.208 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (241.638 61.49)x150
= 589.457 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 256.208 x 589.457) / (12 x 1)
=

302047 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 256.208 x 589.457) (400000 x 1)
=
9.061 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.061 x 3.1
=
28.089 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (28.089 240) x 100
=
11.704 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

26

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

10

240 x 0.05

poles

66.33 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

# of Poles =
kVAresidential =

66.334 + (0.16 x 10) =

kVA SpanNORTH =

67.93 kVA

No. of Bundles:

254.51 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (67.934 x1000)/240
= 283.058 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (254.506 67.934)x150
= 561.956 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 283.058 x 561.956) / (12 x 1)
=

318132 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 283.058 x 561.956) (400000 x 1)
=
9.544 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.544 x 3.1
=
29.586 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (29.586 240) x 100
=
12.328 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

78.88

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

78.88 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

80.48 kVA

=
No. of Bundles:

255.07 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (80.48 x1000)/240
=
335.333 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (255.07 80.48)x150
= 475.404 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 335.333 x 475.404) / (12 x 1)
=

318837 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 335.333 x 475.404) (400000 x 1)
=
9.565 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.565 x 3.1
=
29.652 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (29.652 240) x 100
=
12.355 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

27

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

55.79 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

55.793 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

57.39 kVA

=
No. of Bundles:

137.82 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (57.393 x1000)/240
= 239.138 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (137.821 57.393)x150
= 360.203 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 239.138 x 360.203) / (12 x 1)
=

172276 CM

211600

CM

Based on Table For Circular Mill:


Use:

AWG Copper Conductor, 2-Wires


211600
19
Strands Hard Drawn Copper Conductor
211600 CMILS

No.

0000

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.303 /mile
Xa =

0.496

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.629 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.629307678568674 0.303
= 2.0769
AC DROP FACTOR @ 85% =

2.03

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 239.138 x 360.203) (211600 x 1)
=
9.770 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.770 x 2.03
=
19.833 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (19.833 240) x 100
=
8.264 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

40.58

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

40.579 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

42.18 kVA

=
No. of Bundles:

137.39 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (42.179 x1000)/240
=
175.746 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (137.393 42.179)x150
= 488.607 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 175.746 x 488.607) / (12 x 1)
=

171741 CM

211600

CM

Based on Table For Circular Mill:


Use:

No.
211600

0000
19

211600

AWG Copper Conductor, 2-Wires


Strands Hard Drawn Copper Conductor
CMILS

(For 3 ft. Spacing Between Two 211600 CM Wires:)


Based on Table
Ra = 0.303 /mile
Xa =

0.496

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6293 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.629307678568674 0.303
=
2.0769
AC DROP FACTOR @ 85% =

2.03

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 175.746 x 488.607) (211600 x 1)
=
9.740 V
Vac Drop = Vdc Actual x AC Drop Factor
= 9.740 x 2.03
=
19.772 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (19.772 240) x 100
=
8.238 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

28

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

73.90 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

73.902 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

75.50 kVA

=
No. of Bundles:

294.63 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (75.502 x1000)/240
= 314.592 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (294.628 75.502)x150
= 585.338 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 314.592 x 585.338) / (12 x 1)
=

368285 CM

400000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.591 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 314.592 x 585.338) (400000 x 1)
=
11.049 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.049 x 3.1
=
34.252 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (34.252 240) x 100
=
14.272 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

71.22

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

71.218 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

72.82 kVA

=
No. of Bundles:

295.18 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (72.818 x1000)/240
= 303.408 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (295.176 72.818)x150
= 608.042 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 303.408 x 608.042) / (12 x 1)
=

368970 CM

400000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


400000
19
Strands Hard Drawn Copper Conductor
400000 CMILS

No.

400

(For 3 ft. Spacing Between Two 400000 CM Wires:)


Based on Table
Ra = 0.162 /mile
Xa =

0.458

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.5913 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.591307678568674 0.162
=
3.65
AC DROP FACTOR @ 85% =

3.1

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 303.408 x 608.042) (400000 x 1)
=
11.069 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.069 x 3.1
=
34.314 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (34.314 240) x 100
=
14.298 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

29

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

49.03 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

49.03 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

50.63 kVA

=
No. of Bundles:

233.92 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (50.63 x1000)/240
= 210.958 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (233.924 50.63)x150
= 693.040 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 210.958 x 693.040) / (12 x 1)
=

292405 CM

300000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + Xd = 0.609 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
= 2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 210.958 x 693.040) (300000 x 1)
=
11.696 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.696 x 2.6
=
30.410 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.410 240) x 100
=
12.671 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

47.30

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

47.302 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

48.90 kVA

=
No. of Bundles:

234.70 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (48.902 x1000)/240
= 203.758 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (234.696 48.902)x150
=
719.897 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 203.758 x 719.897) / (12 x 1)
=

293370 CM

300000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


300000
19
Strands Hard Drawn Copper Conductor
300000 CMILS

No.

300

(For 3 ft. Spacing Between Two 300000 CM Wires:)


Based on Table
Ra = 0.215 /mile
Xa =

0.476

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6093 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.609307678568674 0.215
=
2.834
AC DROP FACTOR @ 85% =

2.6

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 203.758 x 719.897) (300000 x 1)
=
11.735 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.735 x 2.6
=
30.511 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (30.511 240) x 100
=
12.713 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

BLOCK No.

Prepared by: JR Ejorcadas

30

North Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

poles

52.85 kVA

5 %

VDC = System Voltage x Voltage Drop


kVANORTH

10

52.854 + (0.16 x 10) =

kVA SpanNORTH =

240 x 0.05

54.45 kVA

=
No. of Bundles:

194.86 kVA

Total Current Computation:


INORTH = (kVANORTH) (System Voltage)
= (54.454 x1000)/240
= 226.892 A
Total Distance Computation:
dNORTH = (kVA-SpanNORTH kVANORTH) x (Pole Distance)
= (194.864 54.454)x150
= 536.776 ft
Circular Mill Computation:
CM = (24 x INORTH x dNORTH ) / (VDC x B)
= (24 x 226.892 x 536.776) / (12 x 1)
=

243580 CM

250000

CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

Xd =

0.2794 log GMR /mile

/mile

= 0.2794 log (3 x 3) /mile


= 0.133 /mile
Xt = Xa + X d =
0.62 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
= 2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x INORTH x dNORTH) (CM x B)
= (24 x 226.892 x 536.776) (250000 x 1)
=
11.692 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.692 x 2.28
=
26.658 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (26.658 240) x 100
=
11.108 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

South Side Computations:


Pole Distance =

150 ft

System Voltage =

240 V

Voltage Drop =

# of Poles =
kVAresidential =

10

poles

43.19

kVA

5 %

VDC = System Voltage x Voltage Drop


kVASOUTH =

43.194 + (0.16 x 10) =

kVA SpanSOUTH =

240 x 0.05

44.79 kVA

=
No. of Bundles:

193.98 kVA

Total Current Computation:


ISOUTH = (kVASOUTH) (System Voltage)
= (44.794 x1000)/240
= 186.642 A
Total Distance Computation:
dSOUTH = (kVA-SpanSOUTH kVASOUTH) x (Pole Distance)
= (193.976 44.794)x150
= 649.560 ft
Circular Mill Computation:
CM = (24 x ISOUTH x dSOUTH ) / (VDC x B)
= (24 x 186.642 x 649.560) / (12 x 1)
=

242470 CM

250000 CM

Based on Table For Circular Mill:


Use:

MCM Copper Conductor, 2-Wires


250000
19
Strands Hard Drawn Copper Conductor
250000 CMILS

No.

250

(For 3 ft. Spacing Between Two 250000 CM Wires:)


Based on Table
Ra = 0.257 /mile
Xa =

0.487

/mile

Xd =

0.2794

log GMR /mile

= 0.2794 log (3 x 3) /mile


= 0.1333 /mile
Xt = Xa + Xd = 0.6203 /mile
Reactance and Resistance Ratio (X t/Ra):

12 V
1

Ratio= Xt Ra

Based on Table :

= 0.620307678568674 0.257
=
2.4136
AC DROP FACTOR @ 85% =

2.28

AC Voltage Drop Calculation:


Vdc Actual = (24 x ISOUTH x dSOUTH) (CM x B)
= (24 x 186.642 x 649.560) (250000 x 1)
=
11.639 V
Vac Drop = Vdc Actual x AC Drop Factor
= 11.639 x 2.28
=
26.537 V
Voltage Regulation Computation:
%VR = (Vac Drop System Voltage) x 100
= (26.537 240) x 100
=
11.057 %
Note: The addditional 0.16 kVA per pole is the Street light Load per Pole

Per Block Transformers Sizing Calculation


Block No:

1 Transformer = kVANORTH + kVASOUTH


= 42.822 + 58.396
= 101.22 kVA
At 80% Transformer Loading:
1 Transformer =

126.52

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.92kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
126.5225
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 19.05

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =

= 19.92 kV (125%)

Vp x 125%

Use:

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

1 Transformer = kVANORTH + kVASOUTH


= 54.2 + 67.008
=
121.21 kVA
At 80% Transformer Loading:
1 Transformer =

151.51

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.92kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
151.51
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 22.82

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =

= 19.92 kV (125%)

Vp x 125%

Use:

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

1 Transformer = kVANORTH + kVASOUTH


= 79.596 + 65.5
= 145.10 kVA
At 80% Transformer Loading:
1 Transformer =

181.37

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.92kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
kVA x 1000
Primary Voltage
181.37
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 27.31

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =

= 19.92 kV (125%)

Vp x 125%

Use:

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

1 Transformer = kVANORTH + kVASOUTH


= 59.346 + 60.752
= 120.10 kVA
At 80% Transformer Loading:
1 Transformer =

150.12

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.92kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =

kVA x 1000
Primary Voltage

x 300%

Where: Vp =19.92 kV

150.1225
19.92

Fuse Rating =
Use:

x 300%

= 22.61

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =

= 19.92 kV (125%)

Vp x 125%

Use:

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

1 Transformer = kVANORTH + kVASOUTH


= 80.764 + 66.578
= 147.34 kVA
At 80% Transformer Loading:
1 Transformer =

184.18

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
kVA x 1000
Primary Voltage
184.1775
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 27.74

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

1 Transformer = kVANORTH + kVASOUTH


= 55.558 + 65.644
= 121.20 kVA
At 80% Transformer Loading:
1 Transformer =

151.50

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.92kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
151.5025
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 22.82

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =
Use:

Vp x 125%

= 19.92 kV (125%)

27 kV, Lightning Arrester, Expulsion Type

24.9 kV

Per Block Transformers Sizing Calculation


Block No:

1 Transformer = kVANORTH + kVASOUTH


= 52.272 + 48.018
= 100.29 kVA
At 80% Transformer Loading:
1 Transformer =

125.36

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
125.3625
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 18.88

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

1 Transformer = kVANORTH + kVASOUTH


= 73.248 + 76.618
= 149.87 kVA
At 80% Transformer Loading:
1 Transformer =

187.33

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
187.3325
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 28.21

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =

= 19.92 kV (125%)

Vp x 125%

Use:

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

1 Transformer = kVANORTH + kVASOUTH


= 79.668 + 68.648
= 148.32 kVA
At 80% Transformer Loading:
1 Transformer =

185.40

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
kVA x 1000
Primary Voltage
185.395
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 27.92

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

10

1 Transformer = kVANORTH + kVASOUTH


= 46.596 + 49.732
=
kVA
96.33
At 80% Transformer Loading:
1 Transformer =

120.41

kVA

For Transformer Specification:


Use:

125 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =

kVA x 1000
Primary Voltage

x 300%

Where: Vp =19.92 kV

120.41
19.92

Fuse Rating =
Use:

x 300%

= 18.13

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =

= 19.92 kV (125%)

Vp x 125%

Use:

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

11

1 Transformer = kVANORTH + kVASOUTH


= 46.276 + 56.512
= 102.79 kVA
At 80% Transformer Loading:
1 Transformer =

128.49

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
128.485
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 19.35

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

12

1 Transformer = kVANORTH + kVASOUTH


= 78.714 + 72.42
=
151.13
kVA
At 80% Transformer Loading:
1 Transformer =

188.92

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
188.9175
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 28.45

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =
Use:

Vp x 125%

= 19.92 kV (125%)

27 kV, Lightning Arrester, Expulsion Type

24.9 kV

Per Block Transformers Sizing Calculation


Block No:

13

1 Transformer = kVANORTH + kVASOUTH


= 67.068 + 66.76
133.83 kVA
=
At 80% Transformer Loading:
1 Transformer =

167.29

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
kVA x 1000
Primary Voltage
167.285
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 25.19

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

14

1 Transformer = kVANORTH + kVASOUTH


= 50.214 + 52.284
= 102.50 kVA
At 80% Transformer Loading:
1 Transformer =

128.12

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
128.1225
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 19.30

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =

= 19.92 kV (125%)

Vp x 125%

Use:

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

15

1 Transformer = kVANORTH + kVASOUTH


= 69.752 + 58.412
=
128.16 kVA
At 80% Transformer Loading:
1 Transformer =

160.21

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
160.205
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 24.13

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

16

1 Transformer = kVANORTH + kVASOUTH


= 65.324 + 57.296
= 122.62 kVA
At 80% Transformer Loading:
1 Transformer =

153.28

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =

kVA x 1000
Primary Voltage

x 300%

Where: Vp =19.92 kV

153.275
19.92

Fuse Rating =
Use:

x 300%

= 23.08

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

17

1 Transformer = kVANORTH + kVASOUTH


= 50.384 + 51.476
= 101.86 kVA
At 80% Transformer Loading:
1 Transformer =

127.33

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
127.325
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 19.18

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

18

1 Transformer = kVANORTH + kVASOUTH


= 48.164 + 49.6
=
97.76
kVA
At 80% Transformer Loading:
1 Transformer =

122.21

kVA

For Transformer Specification:


Use: 125 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
122.205
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 18.40

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =
Use:

Vp x 125%

= 19.92 kV (125%)

27 kV, Lightning Arrester, Expulsion Type

24.9 kV

Per Block Transformers Sizing Calculation


Block No:

19

1 Transformer = kVANORTH + kVASOUTH


= 61.234 + 61.084
= 122.32 kVA
At 80% Transformer Loading:
1 Transformer =

152.90

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
152.8975
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 23.03

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

20

1 Transformer = kVANORTH + kVASOUTH


= 34.878 + 41.082
=
kVA
75.96
At 80% Transformer Loading:
1 Transformer =

94.95

kVA

For Transformer Specification:


Use: 100 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
94.95
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 14.30

15 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

21

1 Transformer = kVANORTH + kVASOUTH


= 48.57 + 50.214
=
kVA
98.78
At 80% Transformer Loading:
1 Transformer =

123.48

kVA

For Transformer Specification:


Use: 125 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
kVA x 1000
Primary Voltage
123.48
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 18.60

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

22

1 Transformer = kVANORTH + kVASOUTH


= 62.68 + 63.208
= 125.89 kVA
At 80% Transformer Loading:
1 Transformer =

157.36

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =

kVA x 1000
Primary Voltage

x 300%

Where: Vp =19.92 kV

157.36
19.92

Fuse Rating =
Use:

x 300%

= 23.70

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

23

1 Transformer = kVANORTH + kVASOUTH


= 78.272 + 70.772
= 149.04 kVA
At 80% Transformer Loading:
1 Transformer =

186.31

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming
For Fuse Rating:
kVA x 1000
Primary Voltage
186.305
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 28.06

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

24

1 Transformer = kVANORTH + kVASOUTH


= 45.974 + 51.254
=
97.23
kVA
At 80% Transformer Loading:
1 Transformer =

121.54

kVA

For Transformer Specification:


Use: 125 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
121.535
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 18.30

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =
Use:

Vp x 125%

= 19.92 kV (125%)

27 kV, Lightning Arrester, Expulsion Type

24.9 kV

Per Block Transformers Sizing Calculation


Block No:

25

1 Transformer = kVANORTH + kVASOUTH


= 61.71 + 61.49
= 123.20 kVA
At 80% Transformer Loading:
1 Transformer =

154.00

kVA

For Transformer Specification:


Use:

167 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz


Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
154
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 23.19

25 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

26

1 Transformer = kVANORTH + kVASOUTH


= 67.934 + 80.48
= 148.41 kVA
At 80% Transformer Loading:
1 Transformer =

185.52

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
185.5175
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 27.94

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

27

1 Transformer = kVANORTH + kVASOUTH


= 57.393 + 42.179
=
kVA
99.57
At 80% Transformer Loading:
1 Transformer =

124.47

kVA

For Transformer Specification:


Use: 125 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
124.465
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 18.74

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

28

1 Transformer = kVANORTH + kVASOUTH


= 75.502 + 72.818
= 148.32 kVA
At 80% Transformer Loading:
1 Transformer =

185.40

kVA

For Transformer Specification:


Use: 200 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =

kVA x 1000
Primary Voltage

x 300%

Where: Vp =19.92 kV

185.4
19.92

Fuse Rating =
Use:

x 300%

= 27.92

30 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Per Block Transformers Sizing Calculation


Block No:

29

1 Transformer = kVANORTH + kVASOUTH


= 50.63 + 48.902
=
kVA
99.53
For 80% Transformer Loading:
1 Transformer =

124.42

kVA

For Transformer Specification:


Use: 125 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


kVA x 1000
Primary Voltage
124.415
19.92

Fuse Rating =
Fuse Rating =
Use:

x 300%
x 300%

Where: Vp =19.92 kV
= 18.74

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


Vp x 125%

L.A =
Use:

= 19.92 kV (125%)

24.9 kV

27 kV, Lightning Arrester, Expulsion Type

Block No:

30

1 Transformer = kVANORTH + kVASOUTH


= 54.454 + 44.794
=
kVA
99.25

1 Transformer =

124.06

kVA

For Transformer Specification:


Use: 125 kVA Distribution Transformer, 19.91kV/240V, 1ph, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
1H+G MECO Incoming

For Fuse Rating:


Fuse Rating =
Fuse Rating =
Use:

kVA x 1000
Primary Voltage
124.06
19.92

x 300%
x 300%

Where: Vp =19.92 kV
= 18.68

20 Amps., 19.92kV Fuse Cut-out (Open Type)

For Lightning Arrester:


L.A =
Use:

Vp x 125%

= 19.92 kV (125%)

27 kV, Lightning Arrester, Expulsion Type

24.9 kV

Calculations for 3 Transformers:


Facility Name:
S

SM Department Store - Silang

= 33.06 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

33.06 0.8

41.33 kVA

For Transformer Specification:


Use: 45 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
59.65
= (33.06 x 1000 x 1.25)4003
=
59.65 A
Use:
3-No. 8 AWG + 8 AWG (G) Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (33.06 (34.5 x 3)) x 300%
=
1.66 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Cleanway Technology Corp.


425 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

425 0.8

= 531.25 kVA

For Transformer Specification:


Use: 750 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
766.82
= (425 x 1000 x 1.25) 4003
= 766.82
A
Use: 3-No. 500 MCM + 1/0 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (425 (34.5 x 3)) x 300%
= 21.34 A
Use:
25 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:

Facility Name:
S

Hypermarket

= 47.22 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

47.22 0.8

59.03 kVA

For Transformer Specification:


Use: 75 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
85.2
= (47.22 x 1000 x 1.25) 4003
=
85.20 A
Use: 3-No. 8 AWG + 8AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (47.22 (34.5 x 3)) x 300%
=
2.37 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Waltermart
47.2 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

47.22 0.8

59.03 kVA

For Transformer Specification:


Use: 75 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
85.2
= (47.22 x 1000 x 1.25) 4003
=
85.20 A
Use: 3-No. 8 AWG + 8AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (47.22 (34.5 x 3)) x 300%
=
2.37 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

FEU Silang-Cavite
47.2 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

47.22 0.8

59.03 kVA

For Transformer Specification:


Use: 75 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
85.2
= (47.22 x 1000 x 1.25) 4003
=
85.20 A
Use: 3-No. 8 AWG + 8AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (47.22 (34.5 x 3)) x 300%
=
2.37 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Cavite State University


47.2 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

47.22 0.8

59.03 kVA

For Transformer Specification:


Use: 75 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
85.2
= (47.22 x 1000 x 1.25) 4003
=
85.20 A
Use: 3-No. 8 AWG + 8AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (47.22 (34.5 x 3)) x 300%
=
2.37 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

Silang Municipal Hall

= 47.22 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

47.22 0.8

59.03 kVA

For Transformer Specification:


Use: 75 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
85.2
= (47.22 x 1000 x 1.25) 4003
=
85.20 A
Use: 3-No. 8 AWG + 8AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (47.22 (34.5 x 3)) x 300%
=
2.37 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Facility Name:
S

Philippine Oasis Hotel & Resort


283.3 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

283.33 0.8

= 354.16 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (Pad Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
511.2
= (283.33 x 1000 x 1.25) 4003
=
511.20 A
Use: 3-No. 250 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (283.33 (34.5 x 3)) x 300%
= 14.22 A

Use:

15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

The Hills Condotel


188.9 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

188.89 0.8

236.11 kVA

For Transformer Specification:


Use: 300 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
340.81
= (188.89 x 1000 x 1.25) 4003
=
340.81 A
Use: 3-No. 2/0 AWG + 4 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (188.89 (34.5 x 3)) x 300%
= 9.48 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Facility Name:
S

Renz Villa Hotel


188.9 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

188.89 0.8

236.11 kVA

For Transformer Specification:


Use: 300 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
340.81
= (188.89 x 1000 x 1.25) 4003
=
340.81 A
Use: 3-No. 2/0 AWG + 4 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (188.89 (34.5 x 3)) x 300%

=
Use:

9.48 A
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

D-Zone Backpackers Inn


94.44 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 94.44 0.8

118.05 kVA

For Transformer Specification:


Use: 150 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
170.4
= (94.44 x 1000 x 1.25) 4003
=
170.40 A
Use: 3-No. 4 AWG + 8 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (94.44 (34.5 x 3)) x 300%
=
4.74 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Estrella Hospital
283.3 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 283.33 0.8

354.16 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
511.2
= (283.33 x 1000 x 1.25) 4003
=
511.20 A
Use: 3-No. 250 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (283.33 (34.5 x 3)) x 300%
= 14.22 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:

Facility Name:
S

Silang General Hospital

= 283.33 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 283.33 0.8

354.16 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
511.2
= (283.33 x 1000 x 1.25) 4003
=
511.20 A
Use: 3-No. 250 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (283.33 (34.5 x 3)) x 300%
= 14.22 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Velasco Hospital

= 283.33 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 283.33 0.8

354.16 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
511.2
= (283.33 x 1000 x 1.25) 4003
=
511.20 A
Use: 3-No. 250 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (283.33 (34.5 x 3)) x 300%
= 14.22 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

La Freva Hotel
236.1 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 236.11 0.8

295.14 kVA

For Transformer Specification:


Use: 300 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
426.01
= (236.11 x 1000 x 1.25) 4003
=
426.01 A
Use: 3-No. 4/0 AWG + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (236.11 (34.5 x 3)) x 300%
=
11.85 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Green Papaya Hotel


236.1 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 236.11 0.8

295.14 kVA

For Transformer Specification:


Use: 300 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
426.01
= (236.11 x 1000 x 1.25) 4003
=
426.01 A
Use: 3-No. 4/0 AWG + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (236.11 (34.5 x 3)) x 300%
=
11.85 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

The Theodore Hotel


236.1 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 236.11 0.8

295.14 kVA

For Transformer Specification:


Use: 300 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
426.01
= (236.11 x 1000 x 1.25) 4003
=
426.01 A
Use: 3-No. 4/0 AWG + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (236.11 (34.5 x 3)) x 300%
=
11.85 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Facility Name:
S

Microtel Inn and Suites Eagle-Ridges


94.4 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 94.44 0.8

118.05 kVA

For Transformer Specification:


Use: 150 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
170.4
= (94.44 x 1000 x 1.25) 4003
=
170.40 A
Use: 3-No. 4 AWG + 8 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (94.44 (34.5 x 3)) x 300%
=
4.74 A

Use:

15 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

Tagaytay Heaven Hotel


236.1 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 236.11 0.8

295.14 kVA

For Transformer Specification:


Use: 300 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
426.01
= (236.11 x 1000 x 1.25) 4003
=
426.01 A
Use: 3-No. 4/0 AWG + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (236.11 (34.5 x 3)) x 300%
=
11.85 A
Use:
15 Amps., 19.92kV Fuse Cut-out (Open Type)

Facility Name:
S

TRI-R ALLIED INDUSTRIAL INC


425 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 425 0.8

531.25 kVA

For Transformer Specification:


Use: 750 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
766.82
= (425 x 1000 x 1.25) 4003
=
766.82 A
Use: 3-No. 500 MCM + 1/0 AWG (G) Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (425 (34.5 x 3)) x 300%

=
Use:

21.34 A
25 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

Sustamina Dressing Plant

= 377.8 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 377.78 0.8

472.23 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
681.62
= (377.78 x 1000 x 1.25) 4003
= 681.62 A
Use: 3-No. 400 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (377.78 (34.5 x 3)) x 300%
= 18.97 A
Use:
20 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Eurotiles

= 330.6 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 330.56 0.8

413.20 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
596.42
= (330.56 x 1000 x 1.25) 4003
= 596.42 A
Use: 3-No. 300 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (330.56 (34.5 x 3)) x 300%
= 16.60 A
Use:
20 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:

Facility Name:
S

Cavite Techno Industrial Supply

= 377.8 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 377.78 0.8

472.23 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
1185.42
= (377.78 x 1000 x 1.25) 4003
= 681.62 A
Use: 2 SETS OF 3-No. 300 MCM + 2/0 AWG (G) Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (377.78 (34.5 x 3)) x 300%
= 18.97 A
Use:
20 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

NAV Trading Corporation

= 377.8 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 377.78 0.8

472.23 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
681.62
= (377.78 x 1000 x 1.25) 4003
= 681.62 A
Use: 3-No. 400 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (377.78 (34.5 x 3)) x 300%
= 18.97 A
Use:
20 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

RS-Unitech Manufacturing & Trading


425 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 425 0.8

531.25 kVA

For Transformer Specification:


Use: 750 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
766.82
= (425 x 1000 x 1.25) 4003
= 766.82 A
Use: 3-No. 500 MCM + 1/0 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (425 (34.5 x 3)) x 300%
= 21.34 A
Use:
25 Amps., 19.92kV Fuse Cut-out (Open Type)
Facility Name:
S

Cleanway Technology Corp.


425 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 425 0.8

531.25 kVA

For Transformer Specification:


Use: 750 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
766.82
= (425 x 1000 x 1.25) 4003
= 766.82 A
Use: 3-No. 500 MCM + 1/0 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (425 (34.5 x 3)) x 300%
= 21.34 A
Use:
25 Amps., 19.92kV Fuse Cut-out (Open Type)

Calculations for 3 Transformers:


Facility Name:
S

Cavite Techno Industry

= 377.8 kVA

At 80% Transformer Loading:


3 Transformer = S 80%

= 377.8 0.8

472.25 kVA

For Transformer Specification:


Use: 500 kVA, 3, 34.5kV/400,Y230V, 60Hz
Oil - Immersed Self Cooled Transformer (pole Mounted)
3H+G MECO Incoming
Secondary Wire Size:
I = (S x 1000 x 1.25) (System Voltage x 3)
681.65
= (377.8 x 1000 x 1.25) 4003
= 681.65 A
Use: 3-No. 400 MCM + 2 AWG (G)
Copper Conductor, 3H+G
Lightning Arrester:
L.A. = Vp x 125%
= 34.5kV x 1.25
= 43.13 A
Use:
48 kV Lightning Arrester (Expulsion Type)
Fuse Rating:
Fuse = (S (Vp x3)) x 300%
= (377.8 (34.5 x 3)) x 300%
= 18.97 A
Use:
20 Amps., 19.92kV Fuse Cut-out (Open Type)

SUMMARY OF LOADS
BLOCK NO.

RESIDENTIAL

COMMERCIAL

INDUSTRIAL

TOTAL kVA

68.16

66.116

134.28

102.32

184.16

286.48

116.77

75.55

192.32

91.77

28.33

425

545.10

109.57

37.774

377.78

525.12

92.87

28.33

377.78

498.98

48.34

240.84

289.18

116.81

221.95

338.76

115.26

269.17

384.43

10

63.27

33.06

96.33

11

69.73

127.5

197.23

12

89.75

108.606

198.35

13

100.77

80.28

181.05

14

74.17

28.33

377.78

480.28

15

95.10

33.06

377.78

505.94

16

89.56

33.06

425

547.62

17

68.80

269.17

337.97

18

64.70

269.17

333.87

19

93.99

264.44

358.43

20

47.63

28.33

75.96

21

70.45

75.55

146.00

22

97.56

28.33

125.89

23

120.71

28.33

149.04

24

68.90

311.66

380.56

25

104.31

18.89

425

548.20

26

115.36

316.386

431.74

27

71.24

311.664

382.90

28

129.44

302.21

431.65

29

94.81

38.45

330.56

463.82

30

70.92

75.55

146.47

TOTAL kVA

2663.02

3934.25

3116.68

9713.95

FEEDER LOAD BALANCING

BLOCK
1

PHASE
AB

BC

101.22

121.21

3
4

145.10
120.10

147.34

6
7

121.20
100.29

149.87

148.32

10

96.33

Sum

417.934

Total

CA

418.416

414.614

3290.964

Total Load kVA = 9713.95

BLOCK

33.06

11

165.27

12

47.22

13

425

14

377.78

15

377.78

16

188.89

17

188.89

18

236.11

19

2040

PHASE
AB

CA

102.79
151.13
133.83
102.50
128.16
122.62
101.86
97.76
122.32

20

75.96

Sum

383.106

Total

BC

377.062

378.766

3216.704

BLOCK

94.44

21

47.22

22

47.22

23

377.78

24

377.78

25

425

26

236.11

27

236.11

28

236.11

29

2077.77

PHASE
AB

CA

98.78

3
47.22

125.89
149.04
97.23

283.33
123.20

425
148.41

99.57

283.33
99.53

99.25

Sum

394.83

283.33
283.33

148.32

30
Total

BC

364.29
47.22

397.41

396.99

3206.28

2017.05

134.28

197.23

146.00

286.48

198.35

125.89

192.32

181.05

149.04

545.10

480.28

380.56

525.12

505.94

548.20

498.98

547.62

431.74

289.18

337.97

382.90

338.76

333.87

431.65

384.43

358.43

463.82

96.33

75.96

146.47

3290.96

3216.70

3206.28

DESIGN OF PRIMARY DISTRIBUTION SYSTEM FEEDER 1


Computation of Distance:
Division

# of Poles

Po-Po

SS - AB

29

150

4350 ft

A-C

18

150

2700 ft

A-D

31

150

4650 ft

B-E

44

150

6600 ft

B-F

11

150

1650 ft

F-G

22

150

3300 ft

F-H

10

150

1500 ft

Total =

Distance

24750

Allowable Voltage Drop per 1000ft:


Allowable VD = (1725 x 1000) 24750
=

69.70 V

Voltage Drop per Division:


Vdc

Division

Distance

VD

SS - AB

4350

69.70

303.20 V

A-C

2700

69.70

188.19 V

A-D

4650

69.70

324.11 V

B-E

6600

69.70

460.02 V

B-F

1650

69.70

115.01 V

F-G

3300

69.70

230.01 V

F-H

1500

69.70

104.55 V

Total =

1725 V

FEEDER 1: SUMMARY OF VALUES


Reference

TCL (kVA)

CM

DcVd

Vac

SS - AB

512.06

8.57

16510

54.19

40.1

45.99

A-C

262.87

4.40

16510

27.82

13

23.6103

A-D

737.41

12.34

16510

83.41

62

70.7884

B-E

935.50

15.66

16510

150.24

111

127.506

B-F

338.76

5.67

16510

13.60

10

11.542

F-G

384.43

6.43

16510

30.85

23

26.1818

F-H

96.33

1.61

16510

3.51

2.598

2.97887

3267.35

54.68

363.62

261.27

308.60

TOTAL

SS - AB
Total kVA =

512.06 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (512.058) (34.5kV x 3)
=

8.57 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 4350 x 8.57) 303.20
=

2951 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 4350 x 8.57) 16510
=

54.19 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 54.19 x 0.98
=

45.99 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 4350 x 8.57 x (cos31.79 + 0.108893846588041sin31.79)] 5280
=

40.1 V

A-C
Total kVA =

262.87 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (262.868) (34.5kV x 3)
=

4.40 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 2700 x 4.40) 188.19
=

1515 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 2700 x 4.40) 16510
=

27.82 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 27.82 x 0.98
=

23.61 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 2700 x 4.40 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

12.78 V

A-D
Total kVA =

737.41 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (737.414) (34.5kV x 3)
=

12.34 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 4650 x 12.34) 324.11
=

4249 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 4650 x 12.34) 16510
=

83.41 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 83.41 x 0.98
=

70.79 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 4650 x 12.34 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

61.72 V

B-E
Total kVA =

935.50 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (935.504) (34.5kV x 3)
=

15.66 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 6600 x 15.66) 460.02
=

5392 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 6600 x 15.66) 16510
=

150.24 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 150.24 x 0.98
=

127.5 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 6600 x 15.66 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

111.2 V

B-F
Total kVA =

338.76 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (338.756) (34.5kV x 3)
=

5.67 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 1650 x 5.67) 115.01
=

1952 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 1650 x 5.67) 16510
=

13.60 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 13.60 x 0.98
=

11.54 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 1650 x 5.67 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

10.06 V

F-G
Total kVA =

384.43 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (384.426) (34.5kV x 3)
=

6.43 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 3300 x 6.43) 230.01
=

2214 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 3300 x 6.43) 16510
=

30.85 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 30.85 x 0.98
=

26.18 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 3300 x 6.43 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

22.82 V

F-H
Total kVA =

96.33 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (96.328) (34.5kV x 3)
=

1.61 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 1500 x 1.61) 104.55
=

554 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 1500 x 1.61) 16510
=

3.51 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 3.51 x 0.98
=

2.979 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 1500 x 1.61 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

2.598 V

DESIGN OF PRIMARY DISTRIBUTION SYSTEM FEEDER 2


Computation of Distance:
Division

# of Poles

Po-Po

Distance

SS - A'

150

1050

ft

A'-C'

19

150

2850

ft

B'-E'

18

150

2700

ft

D'-H'

14

150

2100

ft

F'-G'

150

1050

ft

A'-L'

43

150

6450

ft

J'-K'

150

450

ft

I'-Q'

17

150

2550

ft

M'-P'

12

150

1800

ft

N'-O'

11

150

1650

ft

Total =

22650

Allowable Voltage Drop per 1000ft:


Allowable VD = (1725 x 1000) 22650
=

76.16 V

Voltage Drop per Division:


Vdc

Division

Distance

VD

SS - A'

1050

76.16

79.97 V

A'-C'

2850

76.16

217.06 V

B'-E'

2700

76.16

205.63 V

D'-H'

2100

76.16

159.94 V

F'-G'

1050

76.16

79.97 V

A'-L'

6450

76.16

491.23 V

J'-K'

450

76.16

34.27 V

I'-Q'

2550

76.16

194.21 V

M'-P'

1800

76.16

137.09 V

N'-O'

1650

76.16

125.66 V

Total =

1725 V

FEEDER 2: SUMMARY OF VALUES


Reference TCL (kVA)

CM

DcVd

Vac

SS - A'

94.44

#REF!

16510

#REF!

#REF!

#REF!

A'-C'

480.28

#REF!

16510

#REF!

#REF!

#REF!

B'-E'

505.96

#REF!

16510

#REF!

#REF!

#REF!

SS - A'
Total kVA =

94.44 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (94.44) (34.5kV x 3)
=

1.58 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 1050 x 1.58) 79.97
=

498 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 1050 x 1.58) 16510
=

2.41 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 2.41 x 0.98
=

2.045 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 1050 x 1.58 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

1.785 V

A' - C'
Total kVA =

480.28 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (480.278) (34.5kV x 3)
=

8.04 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 2850 x 8.04) 217.06
=

2534 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 2850 x 8.04) 16510
=

12.27 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 12.27 x 0.98
=

10.413 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 2850 x 8.04 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

24.648 V

B' - E'
Total kVA =

505.96 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (505.964) (34.5kV x 3)
=

8.47 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 2700 x 8.47) 205.63
=

2669 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 2700 x 8.47) 16510
=

33.24 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 33.24 x 0.98
=

28.21 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 2700 x 8.47 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

24.60 V

D' - H'
Total kVA =

337.97 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (337.97) (34.5kV x 3)
=

5.66 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 2100 x 5.66) 159.94
=

1784 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 2100 x 5.66) 16510
=

17.28 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 17.28 x 0.98
=

14.67 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 2100 x 5.66 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

12.79 V

F' - G'
Total kVA =

547.62 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (547.62) (34.5kV x 3)
=

9.16 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 1050 x 9.16) 79.97
=

2886 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 1050 x 9.16) 16510
=

13.98 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 13.98 x 0.98
=

11.86 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 1050 x 9.16 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

10.35 V

A' - L'
Total kVA =

434.97 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (434.97) (34.5kV x 3)
=

7.28 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 6450 x 7.28) 491.23
=

2294 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 6450 x 7.28) 16510
=

68.26 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 68.26 x 0.98
=

57.93 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 6450 x 7.28 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

50.51 V

J' - K'
Total kVA =

47.22 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (47.22) (34.5kV x 3)
=

0.79 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 450 x 0.79) 34.27
=

249 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 450 x 0.79) 16510
=

0.52 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 0.52 x 0.98
=

0.441 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 450 x 0.79 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

0.382 V

I' - Q'
Total kVA =

333.87 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (333.874) (34.5kV x 3)
=

5.59 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 2550 x 5.59) 194.21
=

1762 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 2550 x 5.59) 16510
=

20.72 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 20.72 x 0.98
=

17.58 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 2550 x 5.59 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

15.33 V

M' - P'
Total kVA =

75.96 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (75.96) (34.5kV x 3)
=

1.27 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 1800 x 1.27) 137.09
=

400 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 1800 x 1.27) 16510
=

3.32 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 3.32 x 0.98
=

2.818 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 1800 x 1.27 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

2.459 V

N' - O'
Total kVA =

122.32 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (122.318) (34.5kV x 3)
=

2.05 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 1650 x 2.05) 125.66
=

646 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 1650 x 2.05) 16510
=

4.92 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 4.92 x 0.98
=

4.176 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 1650 x 2.05 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

3.638 V

DESIGN OF PRIMARY DISTRIBUTION SYSTEM FEEDER 1


Computation of Distance:
Division

# of Poles

Po-Po

Distance

SS - D''

15

150

2250

ft

A''-B''

31

150

4650

ft

A''-C''

37

150

5550

ft

D''-F''

23

150

3450

ft

E''-G''

150

300

ft

D''-H''

47

150

7050

ft

Total =

23250

Allowable Voltage Drop per 1000ft:


Allowable VD = (1725 x 1000) 23250
=

74.19 V

Voltage Drop per Division:


Vdc

Division

Distance

VD

SS - D'

2250

74.19

166.93 V

A''-B''

4650

74.19

344.98 V

A''-C''

5550

74.19

411.75 V

D''-F''

3450

74.19

255.96 V

E''-G''

300

74.19

22.26 V

D''-H''

7050

74.19

523.04 V

Total =

1725 V

FEEDER 1: SUMMARY OF VALUES


Reference TCL (kVA)

CM

DcVd

Vac

SS - D'

#REF!

#REF!

16510

#REF!

#REF!

#REF!

A''-B''

#REF!

#REF!

16510

#REF!

#REF!

#REF!

A''-C''

#REF!

#REF!

16510

#REF!

#REF!

#REF!

D''-F''

#REF!

#REF!

16510

#REF!

#REF!

#REF!

E''-G''

#REF!

#REF!

16510

#REF!

#REF!

#REF!

D''-H''

#REF!

#REF!

16510

#REF!

#REF!

#REF!

#REF!

29.38

525.96

433.59

355.28

TOTAL

SS - D"
Total kVA =

146.00 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (146.004) (34.5kV x 3)
=

2.44 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 2250 x 2.44) 166.93
=

789 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 2250 x 2.44) 16510
=

7.98 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 7.98 x 0.98
=

6.772 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 2250 x 2.44 x (cos31.79 + 0.108893846588041sin31.79)] 5280
=

5.905 V

A" - B"
Total kVA =

274.93 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (274.932) (34.5kV x 3)
=

4.60 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 4650 x 4.60) 344.98
=

1488 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 4650 x 4.60) 16510
=

15.05 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 15.05 x 0.98
=

12.77 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 4650 x 4.60 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

23.01 V

A" - C"
Total kVA =

928.76 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (928.758) (34.5kV x 3)
=

15.54 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 5550 x 15.54) 411.75
=

5027 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (24 x 5550 x 15.54) 16510
=

125.37 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table :

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 125.37 x 0.98
=

106.4 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 5550 x 15.54 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

92.77 V

D" - F"
Total kVA =

715.07 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (715.074) (34.5kV x 3)
=

11.97 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 3450 x 11.97) 255.96
=

3872 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 3450 x 11.97) 16510
=

60.03 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 60.03 x 0.98
=

50.95 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 3450 x 11.97 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

44.42 V

E" - G"
Total kVA =

99.57 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (99.572) (34.5kV x 3)
=

1.67 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 300 x 1.67) 22.26
=

540 CM

16510

CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

16510

CMILS @ 3ft. Spacing Between Conductor

Actual Voltage Drop:


VDc Actual = (24 x D x I) CM)
= (O824 x 300 x 1.67) 16510
=

0.73 V

(For 3 ft. Spacing Between Three 16510 CM Wires:)


Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= 0.866 x 0.73 x 0.98
=

0.62 V

Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 300 x 1.67 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

0.539 V

D" - H"
Total kVA =

384.43 kVA

Total Current Computation:


INORTH = (Total kVA) (System Voltage x 3)
= (384.426) (34.5kV x 3)
=

6.43 A

Circular Mill Computation:


CM = (24 x D x I) Vdc
= (24 x 7050 x 6.43)
= #DIV/0! CM

#DIV/0! CM

Based on Table For Circular Mill:


Use:

No.
16510

AWG Copper Conductor, 2-Wires

Strand Hard Drawn Copper Conductor

#DIV/0! CMILS @ 3ft. Spacing Between Conductor


Actual Voltage Drop:
VDc Actual = (24 x D x I) CM)
= #DIV/0!
= #DIV/0! V
#DIV/0!
Based on Table
Ra =

3.79

/mile

Xa =

0.665

/mile

Xd = 0.2794 log GMR /mile


= 0.2794 log (3 x 3) /mile
=

0.133

/mile

Xt = Xa + Xd =

0.4127

/mile

Reactance and Resistance Ratio (Xt/Ra):


Ratio= Xt Ra
= 0.412707678568674 3.79
=
Based on Table:

0.109
AC DROP FACTOR @ 85% =

0.98

Vac SS - A = 0.866 x Vdc actual x AC Drop Factor


= #DIV/0!
= #DIV/0! V
Approximate Method:
e = [3 x D x I x (Racos +Xtsin)] 5280
= [3 x 7050 x 6.43 x (3.79cos31.79 + 0.108893846588041sin31.79)] 5280
=

48.76 V

SUMMARY OF VALUES FOR FEEDER 1


Reference TCL, kVA

I, Amp

CM

ACSR

PP - A
A-B
A - A'
A' - C'
A" - C"
TOTAL

#REF!
#REF!
#REF!
#REF!
#REF!
26.38

#REF!
#REF!
#REF!
#REF!
#REF!

16510
16510
16510
16510
16510

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

AWG
8
8
8
8
8

DCvd

e, V

Vac

#REF!
#REF!
#REF!
#REF!
#REF!
525.96

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

VOLTAGE REGULATION FOR FEEDER 1


%VR=(Vac/Vp)x100=

#REF!

#REF!

%VR=(Ve/Vp)x100=

#REF!

#REF!

SUMMARY OF VALUES FOR FEEDER 2


Reference TCL, kVA

I, Amp

CM

ACSR

AWG

DCvd

e, V

Vac

PP - A
A - A'
A -B
B - B'
B - B"
B-C
C - C'
C - C"
TOTAL

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
29.98

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

16510
16510
16510
16510
16510
16510
16510
16510

8
8
8
8
8
8
8
8

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
295.43

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

VOLTAGE REGULATION FOR FEEDER 1


%VR=(Vac/Vp)x100=

#REF!

#REF!

%VR=(Ve/Vp)x100=

#REF!

#REF!

SUMMARY OF VALUES FOR FEEDER 3


Reference TCL, kVA

I, Amp

CM

ACSR

AWG

DCvd

e, V

Vac

PP - A
A - A'
A -B
B - B'
B - B"
B-C
C - C'
TOTAL

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
28.9

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

16510
16510
16510
16510
16510
16510
16510

8
8
8
8
8
8
8

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
295.43

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!

VOLTAGE REGULATION FOR FEEDER 1


%VR=(Vac/Vp)x100=

#REF!

#REF!

%VR=(Ve/Vp)x100=

#REF!

#REF!

PEC2009Edition,Table2.50.3.17
GroundingElectrodeConductorforAlternatingCurrentSystem
SizeofLargestUngrounded
EquivalentforUngrounded
ServiceEntranceConductoror
SizeofGrounding
EquivalentAreaforParallelConductors
ElectrodeConductor
(mm)
(mm)
AWG/MCM
COPPER
COPPER
COPPER
30orSmaller
8
2AWGorSmaller
38or50
14
1AWGor1/0AWG
60or80
22
2/0or3/0AWG
30
Over3/0AWGto400MCM
Over80through200
Over400MCMto600MCM
50
Over200through325
Over600MCMto1000MCM
Over325through500
60
Over500
80

Equivalentfor
grounded
AWG/MCM
COPPER
8AWG
6AWG
4AWG
2AWG
1/0AWG
2/0AWG

SUMMARY OF LOADS
BLOCK NO.

RESIDENTIAL

COMMERCIAL

INDUSTRIAL

TOTAL kVA

TOTAL kVA

FEEDER LOAD BALANCING

BLOCK

PHASE
AB

BC

CA

BLOCK

PHASE
AB

BC

CA

BLOCK

11

21

12

22

13

23

14

24

15

25

16

26

17

27

18

28

19

29

10

20

30

Sum

Sum

Sum

Total

Total

Total

Total Load kVA =

PHASE
AB

BC

CA

You might also like