Professional Documents
Culture Documents
HMI Server Status Primary ActiveCant Reach Partner Secondary Loading
HMI Server Status Primary ActiveCant Reach Partner Secondary Loading
RockwellAutomation
62020HMIserverstatus:Primary"Active,Can'tReachPartner",Secondary"Loading..."
AccessLevel:TechConnect
DateCreated:06/04/200906:00PM
LastUpdated:03/30/201503:55PM
Problem
FactoryTalkViewSERedundantPrimaryHMIServer,Propertiespageshowsthefollowingstatus
"Active,Can'tReachPartner"
TheRedundantSecondaryHMIServerstatusis
"Loading...".
Environment
TheWindowsEventViewerLogfilesontheSecondaryHMIservershowsanerrorsimilartothefollowing:
RockwellHMIFramework"ThedescriptionforEventID(0)inSource(RockwellHMIFramework)cannotbefound.Thelocalcomputer
maynothavethenecessaryregistryinformationormessageDLLfilestodisplaymessagesfromaremotecomputer.Youmaybeableto
usethe/AUXSOURCE=flagtoretrievethisdescription;seeHelpandSupportfordetails.Thefollowinginformationispartofthe
event:FailedtocompletetheTagDBSyncaction(41000).."
ForViewSEv6.0andearlier:CheckingthesizeoftheSecondaryHMIServer'sProject.DBfile(intheTagssubfolder)showsittobe201Kinsize.
AttemptingtorestoretheProject/DatabasetotheSecondaryHMIServergivesthefollowingerror
"HMIServerisrunningpleaseshutdowntheHMIServerbeforerestoring"
Answer
ThePrimaryandSecondaryHMIServerProjectswerenotproperlysynchronizedortheProjectDatabaseiscorrupt.
UseoneofthefollowingmethodstocopytheHMIProjectfromthePrimarytotheSecondary:
1. UsetheReplicatebuttonontheHMIServer'sRedundancytab.
2. CopytheProjectfromthePrimarytotheSecondary
UsetheHMIBackup/RestoreUtilitytobackupthePrimaryProject/Database
OnPrimaryServer,gototheRedundancytab,andturnoff(uncheck)Redundancy
OnSecondaryServer,restoretheProject/DatabasefromtheBackupfile
Aftertherestorecheckthefilesizesforthe.DBfileinthesecondaryproject'sTAGfolder
ThisshouldbethesamesizeastheoneonthePrimary.Iftheyarenotthesame,trytorestorethefilesfromaDOScommandpromptinsteadofusingtheBackup
/Restoreutility
NOTEIftheHMIBackup/RestoreUtilityfromTechnote30310isusedandthesizeofthe.DBfilestillshows201K,theneithermanuallymakeacopyofthe
Primary'sHMIserverprojectoruseWinZiptobackitup
OnPrimaryServer,gototheRedundancytab,andturnon(check)Redundancy
AfterrestoringtheProject/DatabasetoSecondary'sHMIServer,iftheproblempersists,thenreboottheSecondaryHMIServer.
Comments(0)
Thisanswerhasnocomments
PostaComment
ProductTreeforThisAnswer(expand/collapse)
ThispageisbestviewedinInternetExplorer10,Firefox31,Chrome37,Safari6ornewer.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/62020/related/1