For 50 Hertz operation of the following breakers
equipped with Ground Trip element, the instantaneous
pickup settings should not exceed the following maximums to avoid ground error signals possible due to
sensor saturation.

Long-Time
Pickup 0.8C to 1.1C

0.9

4000

50 60 70 80 90

3000

40

2000

30

1000
900
800
700

20

600

6 7 8 9 10

500

400

3000

0.8

5000
4000

300

200

6000

.5 .6 .7 .8 .9 1

100

10000
9000
8000
7000

Breaker
Type

1.1

AK, AKR-50
AKT, AKRT-50

1000
900
800
700

Sensor Tap
Setting
(Amperes)

Max. Pickup
Setting
(Amperes)

1200
1600
1600
2000

14,000
18,000
16,000
20,000

10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700

600

600

500

500

400

400

300

300

200

200

Long-Time
Delay Bands

Maximum Total
Clearing Time

50
3

40

40
30

20

10
9
8
7

10
9
8
7

MULTIPLES OF INSTANTANEOUS UNIT PICK UP SETTING


1

GES-6194

6 7 8 9 10

20

30

40

50 60 70 80 90100

1
.9
.8
.7
.6

.9
.8
.7
.6

.5

.5

.4

.4

.3

.3

.2

.2

Low Voltage Power


Circuit Breaker
Total Clearing Time

Molded Case and


Insulated Case
Circuit Breaker
Total Clearing Time

.1
.09
.08
.07
.06

.1
.09
.08
.07
.06

.05

.05

.04

.04

.03

.03

Application
Determines
End of Curve

.02

.02

.01

.01
100
90
80
70

60

50

40

50 60

30

40

20

30

10
9
8

20

6 7 8 9 10

.5 .6 .7 .8 .9 1

MULTIPLES OF CURRENT SETTING, C


GE Consumer & Industrial Electrical Distribution
X = Current Sensor Taps (Amperes)
AKR-30 100, 150, 225, 300 or 300, 400, 600, 800
AKR-50 300, 400, 600, 800 or 600, 800, 1200, 1600
AKRT-50 800, 1200, 1600, 2000
AKR-75 1200, 1600, 2000, 3200
AKR-100 1600, 2000, 3000, 4000
Power Break and Molded Case Circuit Breakers
150, 200, 300, 400, 500, 600, 800, 1000, 1200,
1600, 2000, 2500, 3000 and 4000 Amperes
Voltage Ratings: 600 Vac
01.87 1M

Low-Voltage Power Circuit Breakers


Insulated Case and Molded Case
Circuit Breakers with MicroVersaTrip
Solid-State Overcurrent Trip Device
Type AKR
Long-time-delay and Instantaneous
Time-Current Curves
Curves apply at 50/60 Hertz
and from -20C to 70C Programmer Ambient.
For 50 Hz operation see note above.

GES-6194

20

Minimum
Total
Clearing
Time

50

GES-6194

Programmer Set Points:

Long-Time Current Setting:


50, 60, 70, 80, 85, 95 and 100%
multiples of current sensor tap setting or rating (X).
Long-Time Pickup: 0.8, 0.9, 1.0, 1.1 multiples of the
current setting, C.
Instantaneous: 1.5, 2.0, 2.5, 3.0, 4.0, 6.0, 8.0, & 10.0X
for 150A through 3000A ratings and 1.5, 2.0, 2.5, 3.0, 4.0,
5.0, 7.0, & 9.0X for 4000A rating multiples of current
setting (X).