Logic Diagram

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

PLN ENJINIRING

DOUBLE IGNITION

Program diagram
B18

B25

B02

B07

Q1

I1
IGNITE
B05

B49

B26

B56

IGNITE MODE
B06

Q2
B39
B27

B63

B38

I3

PILOT 1 ON
B08

B34

I2

B21

Q3

TIMER FAIL

AUTO/MANUAL

PILOT 2 ON
B09

B44

B53

B48

B03

IGNITION FAIL
B10

I4

Q4

B54

B24
RESET

B51

B04

DIRECT
B11

I5
B55

B17

Q5

B50

B15
LAMP TEST

B52

B00

FFG
B12

Q6

I6
B64
T/C 1 ON

B16

B59

B60

B46
Q7

B01

I7
T/C 2 ON

SIREN

B57
B62

B61

I8

SOLENOID AIR
B47
Q8
SOLANOID GAS

B58

Q9

I9
B65
IA

IB

QA

B66
O1
XT1
%MW20..X0 - X2

IC

O2
XT1

ID

O3
XT1

IE

O4
XT1

IF

IG

J1
XT1

J2
XT1

J3
XT1

J4
XT1

PLN ENJINIRING

DOUBLE IGNITION

Physical inputs
Input

No

I1

Symbol

Function

Lock

Parameters

Comment

B02

Discrete input

---

No parameters

IGNITE

I2

B05

Discrete input

---

No parameters

IGNITE MODE

I3

B06

Discrete input

---

No parameters

AUTO/MANUAL

I4

B03

Discrete input

---

No parameters

RESET

I5

B04

Discrete input

---

No parameters

LAMP TEST

I6

B00

Discrete input

---

No parameters

T/C 1 ON

I7

B01

Discrete input

---

No parameters

T/C 2 ON

Physical outputs
Output

No

Symbol

Function

Comment

Q1

B07

Discrete output PILOT 1 ON

Q2

B08

Discrete output PILOT 2 ON

Q3

B09

Discrete output IGNITION FAIL

Q4

B10

Discrete output DIRECT

Q5

B11

Discrete output FFG

Q6

B12

Discrete output SIREN

Q7

B46

Discrete output SOLENOID AIR

Q8

B47

Discrete output SOLANOID GAS

Configurable functions
No

Symbol

Function

Lock

Latching

Parameters
On time : 0H 3M 0S
Off time : 0H 0M 1S

B34

Timer

No

No

B44

Cyclic timing

No

No

On time : 0H 0M 5S
Off time : 0H 0M 10S
Function L - Continuous flashing

B50

Cyclic timing

No

No

On time : 2 x 0,1 s
Off time : 100 x 0,1 s
Function L - Continuous flashing

B53

Timer

No

No

On time : 0H 3M 0S
Off time : 0H 0M 1S

Comment
TIMER FAIL

PLN ENJINIRING

No

Symbol

DOUBLE IGNITION

Function

Lock

Latching

B59

Timer

No

No

Parameters
On time : 0H 0M 0S
Off time : 0H 0M 15S

B62

Timer

No

No

On time : 0H 0M 15S
Off time : 0H 0M 0S

B66

Output integer

---

---

No parameters

Comment

%MW20..X0 - X2

You might also like