Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

4

2
REV
DESCRIPTION
ISSUED ENGINEERING DRAWING
A
ADDED VALVE INDICATOR OPEN/CLOSE TO LOOP
B
C
ADDED NEW ALARMS TO PIPING KIT

1
DWN
MAL
JJW
KFB

ECN#
N/A
540
3633

APVD

DATE
14AUG03
04APR06
30MAR15

RAW WATER
OUTLET FLOW

ENGINE
HEAT
EXCHANGER

RAW WATER
INLET FLOW

PRESSURE SENSOR (HEAT EXCHANGER OUTLET)

PRESSURE SENSOR
(COOLING LOOP)

0-60 PSI PRESSURE GAUGE

PRESSURE REGULATOR (QTY 2)

PIPING KIT TO CHARGE AIR


COOLER OR HEAT EXCHANGER

SHUT-OFF
VALVE (QTY 4)

WYE STRAINER (QTY 2)

PRESSURE GAUGE
SHUT-OFF VALVE
BYPASS LINE
INDICATING PLATE (QTY 2)

UNION (QTY 2)

105 F TEMPERATURE SWITCH

B
2

PUMP DISCHARGE
CONNECTION

FRONT OF ENGINE
2

SOLENOID VALVE (NOT USED WITH VERTICAL TURBINE FIRE PUMPS)


AUTOMATIC LINE INDICATING PLATE (QTY 2)

COOLING LOOP
(BY CLARKE)

ENGINE COOLING WATER


PIPED TO DRAIN

NOTES:

PIPING ARRANGEMENT PER NFPA-20.

PIPING BY OTHER.

THIS DRAWING AND THE


INFORMATION HEREON ARE OUR
PROPERTY AND MAY BE USED BY
OTHERS ONLY AS AUTHORIZED BY
US. UNPUBLISHED--ALL RIGHTS
RESERVED UNDER THE
COPYRIGHT LAWS
MACHINE TOLERANCE
inch
DECIMAL mm
1.5
X.
X.X
0.06
0.8
0.03
X.XX
0.3
0.01
0.025
X.XXX
X.XXXX
0.001
ANGULAR: 0.5
FABRICATION TOLERANCE
inch
DECIMAL mm
3
X.
X.X
0.12
1.5
0.06
X.XX
ANGULAR: 1.0

DISCHARGE PIPING FROM HEAT EXCHANGER OUTLET IS AT A MINIMUN


ONE PIPE SIZE LARGER THAN THE INLET PIPING TO THE HEAT EXCHANGERS
COOLING LOOP WATER - DIRECTION OF FLOW

YES

NO

CONTROLLED
DRAWING
DRWN
DATE

MALAUER

Fire Protection Products, Inc.


NAME

NFPA-20 COOLING LOOP


PIPING DETAIL

3/30/2015

ENGR

KRWAULIGMAN
MATERIAL
PART NO.

UNITS

SCALE

SIMILAR TO

N/A

NTS

REV

C130977

ASSEMBLY

C
PAGE

MM [INCH]

OF