Sizing exercise: Internet caf, 8 INVENEO low energy computers for 12h /day:

cos app.
phi Power

Qty. Power
8

33 W
W
W
W
W

1
1
1
1
1
sum

264.0
0.0
0.0
0.0
0.0
264.0

hours Energy
VA
VA
VA
VA
VA

12

sum:

Inverter efficiancy
Inverter runtime
Inverter standby

consumer energy demand

3168.0
0.0
0.0
0.0
0.0
3168.0

device
VAh
VAh
VAh
VAh
VAh
VAh

90.0 %
12.0 h
5.0 W

consumer energy demand = sum of


energy of all consumers divided by
inverter efficiency plus inverter standby
3580 VAh consumption x inverter runtime

Battery Voltage
Battery discharge (consumer energy demand)
Depth of Discharge (DoD)

24.0 V
149.2 Ah
30 %

Battery Capacity

497 Ah

Performance Ratio (PR)

total PV energy demand


Peak Sun hours

total PV Power

Inveneo PC

(consumer energy demand / Battery Voltage)

(Battery Discharge / DoD)

65.0 %

5508 VAh (consumer energy demand / PR)


4.7 h

1172 Wp

Solar Charge Controller

40.6 A

minimum Inverter Power

330.0 VA

(PV current + 20%)

(sum of apparent power consumers+25%)


If CFL then double the total CFL power due to harmonic stress. Consider startup power of motors
Battery 12V 250Ah, 2 in series, 2 times parallel

2500 US$

PV module 185Wp, 6 parallel, 6 x185W = 1110Wp

2800US$

Charge controller PHOCOS 24V 40A

200 US$

Inverter 24V, 240Vac, 500VA

400 US$

Wiring, string connection box, fuses

100 US$

Mountings roof

200 US$

8 x INVENEO PC

5600 US$
Total

11800 US$