Sizing Example

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

Document no.

: Page: 1 of 2 Rev: 0
Date: 12/8/2015

FLA (A)

Breaker Size In
(A)

Final DB

26

32

100A Sub-Board at Switch


LVSB
Room

Sub-Board

80

100

CU Lv 1

FCU

26

32

S/N

Equipment

Cable from

Final 32A DB at Renovated


SB
Office

CU

Cable To

KW

Design Curent,
Method of Containment
Ib (A)

Derating Factors
Ca

Cg

Ci

Effective Current Carrying Capacity


Required of Conductor Iz (A)

32

Cable Trunking

0.8

40

100

Cable Tay

100

26

Flexible conduit

0.8

40

Tabulated Current
Carrying Capacity It (A)

Number of
Effective Current Carrying
Cables per Phase Cable Size
Capacity of conductor Iz xN (A)
(N)

50

40

4x1Cx10mm2 PVC+1C10 mm2


CPC

127

100

4x1Cx25mm2 PVC+1C25 mm2


CPC

41

41

4x1Cx6mm2 PVC+1C6 mm2


CPC

Voltage Drop
(mV/A/m )

Length (m)

Actual Voltage Drop Actual Voltage


Remarks
(mV/A/m )
Drop (%)

3.8

30

3.6

1%

<4%

1.7

10

1.7

0.40%

<4%

7.3

80