K ça 0.65 ; K kr 0.8
; cos = 0.8 ; Pn 200 kw ;
n = 20 ; Pn max 20 kw ;
K ça 0.2 ; K kr 0.28
; cos = 0.6 ; Pn 400 kw ;
n = 40 ; Pn max 40 kw ;
K ça 0.55 ; K kr 0.75
; cos = 0.9 ; Pn 1000 kw ;
n = 20 ; Pn max 100 kw ; Pn1=600KW,n1=4
1
S = 2000 ( m2) ; P0 = 15(w/m2) ; K kr 1 ;
Ps-2 Pn1 20 kw ; Pn 2 14 kw ; Pn 3 10 kw ;
Pn 4 7 kw ; Pn 5 4.5kw ;cos =0.75; =0.85.
Ps-3 Pn1
1.1 kw ; Pn 2 1.4 kw ; Pn 3 2.1 kw ;
Pn 4 28 kw ; Pn 5 40 kw ;cos =0.8; =0.9
Ps-4 Pn1
20 kw ; Pn 2 14 kw ; Pn 3 10 kw ;
Pn 4 7 kw ; Pn 5 4.5kw ;cos =0.75; =0.85.
Nr I kateve n = 20 nr I apartamenteve m = 3
2
GRUPI i I
K ça 0.65 ; K kr 0.8
; cos = 0.8 ; Pn 200 kw ;
n = 20 ; Pn max 20 kw ;
P
Pll K kr * Pn 0.8 * 200 = 160 kw ; S ll ll cos 160 /0.8 =200 ; kWAR
Qll ( S ll ) 2 ( Pll ) 2 = (200)2 – (160)2 = 120 kWAR ;
GRUPI i II
GRUPI i III
GRUPI i IV
K ça 0.55 ; K kr 0.75
; cos = 0.9 ; Pn 1000 kw ;
n = 20 ; Pn max 100 kw ; Pn1=600kw,n1=4
GRUPI i V
K ça 0.4 ; K kr 0.5
; cos = 0.35 ; VR% = 25% ;
S nA 50 kw ; S nB 100 kw ; S nC 150 kw ;
S nAB 150 kw ; S nBC 100 kw ; S nAC 50 kw ;
3
Pnc 0 S nC * VR * cos 150* 25 *0.35 = 26.25 kw ;
P nA PnAB * p ( ab) a Pnac * p ( ac)a Pna 0
S nAB * cos * p ( ab)a S nAC * cos * p( ac)a Pna 0
150*0.35*(-0.285)+100*0.35*1.285+17.5 = 47.5125 kw ;
P nC PnAC * p (ac)c Pnbc * p (bc )c Pn 0
S nAC * cos * p (ac)c S nBC * cos * p (bc)c Pn 0
50*0.35*1.285+100*0.35*0.285+26.25=38.7625kw
Pnek 3 * PnB 3*71.225=213.675kw
Pll K kr * Pnek 0.5*213.675=106.8375kw|;
Pll
S ll 106.8375/0.35 =305.25 kWAR ;
cos
Qll S ll2 Pll2 = (305.25)-(106.8375)=285.942kw
GRUPI i VI
S = 2000 ( m2) ; P0 = 15(w/m2) ; K kr 1 ;
Pn P0 * S = 15* 2000 =30kw ;
Pll K kr * Pn 1*30 =30kw ; S ll Pll 30kWAR ; Q ll 0 kwar ;
P
i 1
lli Pll1 Pll 2 Pll 3 Pll 4 Pll 5 Pll 6 =160+112+275+750+310.53+30=1637.53kw ;
6
Q
i 1
lli Qll1 Qll 2 Qll 3 Qll 4 Qll 5 Qll 6
120+149.3+366.66+661.43+285.942+0=1583.332kwar
S ll ( Pll ) 2 Qll (1637.53)2 +(1583.332)2 =2277.816 kWAR ;
2
GRUPI I
K ça 0.65 ; Pn 200 kw ; cos = 0.8 ; Pn max 20 kw ;
Pn
nef = 2* 2*200/20 = 20
Pn max
Nga tabela per nef= 20 dhe K ça 0.65 gjejme K max 1.15 ;
GRUPI II
K ça 0.2 ; cos = 0.6 ; Pn 400 kw ; Pn max 40 kw ;n=40; Kkr=0.28
Pn
nef = 2* 2*400/40 = 20
Pn max
Nga tabela per nef= 20 dhe K ça 0.2 dhe gjejme K max 1.50 ;
GRUPI i III
5
Pll
S ll 453.75 / 0.6 = 756.25 kWAR ;
cos
GRUPI i IV
K ça 0.55 ; K kr 0.75
; cos = 0.9 ; Pn 1000 kw ;
n = 20 ; Pn max 100 kw ;
Pn
nef = 2* P 2*1000/100 = 20
n max
GRUPI i V
Pni * K çai
K ça 0.343
Pni
Pni * cos
cos 0.691
Pni
3) Te llogaritet fuqia e mjeteve kompesuse qe te kemi cos = 0.9
6
cos 0.8/0.75 0.6/1.33 0.6/1.33 0.9/0.88 0.35/2.67 1/0 4.25/6.96
tg
Pn mes=925kw
tg1 1.482
Imax
Ish >-------- => Imax = Kl * In =5 * 1.340= 6.7A
Kl
Imax
Ish >-------- = 6.7/2.5=2.68 A
Kmb
In = 1.340 A
Ish = 2.68 A
2)- Pn-2
Pn 2 20kw
cos 0.85
0 .9
K ng 1
P
P 3 U I cos I n 39.72
3 U cos
I sh I n K ng 39.72 * 1 39.72 A
I max
I sh I max K L I n 5 * 39.72 198.6 A
Kl
I max 198.6
I sh 79.44 I sh 80
K mb 2.5
8
Ilej p > Ill = 50A S=(3 x 10 )+(2 x6 )
Pn 3 28kw
cos 0.8
0 .9
K ng 1
P
P 3 U I cos I n 59.1
3 U cos
I sh I n K ng 59.1 *1 59.1A
I max
I sh I max K L I n 5 * 59.1 295.4 A
Kl
I max 295.4
I sh 118.2 A
K mb 2 .5
9
Pn 4 40kw
cos 0.8
0 .9
K ng 1
P
P 3 U I cos I n 84.4
3 U cos
I sh I n K ng 84.4 A
I max
I sh I max K L I n 422 A
Kl
I max
I sh 168.8 A
K mb
Pn 5 7kw
cos 0.8
0.9
K ng 1
P
P 3 U I cos I n 14.77 A
3 U cos
I sh I n K ng 14.77 A
I max
I sh I max K L I n 73.85 A
Kl
I max
I sh 29.54 A
K mb
I lej 18.5 A
a)- I lejP 18.5
S= (3 x 2.5 )+(2 x 1.5 )
10
b)- Ilej > Ill =18.5 S=(3 x 2.5 )+(2 x 1.5)
Ilej p 18.5
c)- Rasti i mbrojtjes nga lidhja e shkurter ILsh.
Ilej p > Ill = 18.5A S=(3 x 2.5 )+(2 x 1.5 )
Ilej 0.33*20=6.6 S=(3 x 1)+(2 x 0.5 )
Pn1 14kw
cos 0.75
0.8
K ng 1
P
P 3 U I cos I n 33.4 A
3 U cos
I sh I n K ng 33.4 A
I max
I sh I max K L I n 167 A
Kl
I max
I sh 66.8 A
K mb
I n 70 A
I sh 70 A
Zgjedhim siguresat per 3 rastet.
a)- Kur kur percjellesi eshte vendosur ne rrezik zjarri ose plasje Kmp = 1.25
b)- Rasti vetem ne rrezik zjarri Kmp = 1
c)- Rasti i mbrojtjes vetem nga Ilsh
11
Pn 2 20kw
cos 0.75
0.8
K ng 1
P
P 3 U I cos I n 50.6 A
3 U cos
I sh I n K ng 50.6 A
I max
I sh I max K L I n 253.2 A
Kl
I max
I sh 101.3 A
K mb
I sh 50 A
I n 50 A
Zgjedhim siguresat per 3 rastet.
a)- Kur kur percjellesi eshte vendosur ne rrezik zjarri ose plasje Kmp = 1.25
b)- Rasti vetem ne rrezik zjarri Kmp = 1
c)- Rasti i mbrojtjes vetem nga Ilsh
I lej 63.25 A
a)- I lejP 62.5 A
S= (3 x 16)+(2 x 10 )
S=(3 x 16 )+(2 x 10)
Pn 3 4.8kw
cos 0.75
0.8
K ng 1
P
P 3 U I cos I n 12.15 A
3 U cos
I sh I n K ng 12.5 A
I max
I sh I max K L I n 60.75 A
Kl
I max
I sh 24.3 A
K mb
I n 21A
I sh 21A
Zgjedhim siguresat per 3 rastet.
a)- Kur kur percjellesi eshte vendosur ne rrezik zjarri ose plasje Kmp = 1.25
b)- Rasti vetem ne rrezik zjarri Kmp = 1
c)- Rasti i mbrojtjes vetem nga Ilsh
12
I lej 15.8 A
a)- I lejP 26.25 A
S= (3 x 2.5 )+(2 x 1.5 )
S=(3 x 4 )+(2 x 2.5 )
I lej 13.4 A
a)- I lejP 25 A
S= (3 x 1.5 )+(2 x 1 )
S=(3 x 4)+(2 x 2.5)
13
Pn 5 40kw
cos 0.75
0.85
K ng 1
P
P 3 U I cos I n 81A
3 U cos
I n 80 A
I sh 80 A
I lej 101.25 A
a)- I lejP 1.25 * 80 100 A
S= (3 x 35 )+(2 x 25 )
S=(3 x 35 )+(2 x 25)
Rrymat Pn-1 Pn-2 Pn-3 Pn Pn-4 Pn-5 Pn-1 Pn-2 Pn-3 Pn-4 Pn-5 Pn
E
lejuara Grup Grup
10 20 28 40 7 105 14 20 4.8 4.5 40 8303
In 19.8 39.7 59.1 84.4 14.7 217.8 33.4 50.6 12.1 10.7 81 188.2
Ins 20 80 100 160 20 380 70 50 20 20 80 240
Ish 20 80 100 160 20 380 70 50 20 20 80 240
Pn 1 10kw
P
I 19.61A
3 U cos
I nl I gj I gj I n 19.61A
I ' max 5 * 19.61 98.05 A
I ve 1.25 I max
'
122.5 A
I nAUT 20 A
I K 3kA
14
b)- Ilej p ≥ Kmp * In AUT =20A S=(3 2.5x )+(2 x 1.5)
Pn 2 20kw
P
I 39.72
3 U cos
I nl I gj I gj I n 39.72 A
I ' max 5 * 39.72 198.6 A
I ve 1.25 I max
'
49.65 A
I nAUT 50 A
I K 3kA
Pn 3 28kw
P
I 52.5 A
3 U cos
I nl I gj I gj I n 52.5 A
I ' max 5 * 52.5 262.6 A
I ve 1.25 I max
'
65.6 A
I nAUT 50 A
I K 3kA
Pn 4 40kw
P
I 84.4 A
3 U cos
I nl I gj I gj I n 84.4 A
I ' max 5 * 84.4 422 A
I ve 1.25 I max
'
527.5 A
I nAUT 85 A
I K 3kA
Pn-1 [10kw] Pn-2 [20kw] Pn-3 [28kw] Pn-4 [40kw] Pn-5 [7kw]
In Ilej 19.61 39.72 52.5 84.4 14.77
[A]
In AUT 20 50 63 85 16
[A]
Ik [A] 3000 3000 3000 3000 3000
Seksioni (3x2.5)+(2x1.5) (3x16)+(2x10) (3x10)+(2x6) (3x25)+(2x16) (3x2.5)+(2x1.5)
mm²
Grupi II.
16
Pn 1 14 kw
cos 0.75
0.9
P
I 33.4 A
3 * U * cos *
I nl I gj 33.4 A
'
I max 5 * 33.4 167 A
I ve 1.25 * 167 208.7 A
I nAUT 30 A
I K 3kw
Pn 2 20kw
cos 0.75
0.85
P
I 47.6 A
3 * U * cos *
I nl I gj 47.6 A
'
I max 5 * 47.6 238.3 A
I ve 1.25 * 238.3 297.9 A
I nAUT 63 A
I K 3kw
17
Zgjedhja e seksionit te percjellesit.
Pn 4 4.5kw
cos 0.75
0.85
P
I 10.7 A
3 * U * cos *
I nl I gj 10.7 A
'
I max 53.6 A
I ve 67 A
I nAUT 16 A
I K 3kw
Pn 5 40kw
cos 0.75
0.85
P
I 95.3 A
3 * U * cos *
I nl I gj 95.3 A
'
I max 476.6 A
I ve 595.8 A
I nAUT 100 A
I K 3kw
Zgjedhja e Automateve
Pn-1 Pn-2 Pn-3 Pn-4 Pn-5
18
14 [kw] 20 [kw] 4.8 [kw] 4.5 [kw] 40 [kw]
In [A] 33.4 47.6 11.44 10.7 95.3
In AUT [A] 30 63 20 16 100
IK [A] 3000 3000 3000 3000 3000
Seksioni (3x6)+(2x4) (3x16)+(2x10) (3x2.5)+(2x1) (3x2.5)+(2x1.5) (3x35)+(2x25)
mm²
5)- Llogaritja e rrjetit te ushqimit te kater pikave shperndarese.
a)- Piken e pare e kemi.
Pn 40kw
cos 0.8
0 .9
P
I n' 84.4 A
3 U cos
I 1' 84.4 * 5 422 A
I gj 47.6 11 .44 10.7 95.3 165.1 A
'
I max
I sh I max
'
I 1' I gj 422 165.1 587.1A
2. 5
587.1
I max
'
234.8 A
2. 5
I ns 300 A
I sh 300 A 285 A
Per Ish = 285 A zgjedhim seksionin e percjelesit S=(3x 95)+(2x 70)
19
Per Ilej p = 160 A zgjedhim seksionin e percjelesit S=(3x70 )+(2x50 )
S = 2000 m²
Po = 20 w/m²
KKr = 1
Pndr = Po * S = 20*2000 = 40 kw
Sll = Pll
Pll = Sll = 40 kw
20
21
Copyrights © All rights reserved
22