com/techtopics
TechTopics No. 44
Anatomy of a short-circuit
2.50
S-factor (C37.04-1979)
dc component (in decimal form) (multiply by 100
for %dc component) (C37.04-1999)
2.00
1.50
1.00
0.50
0.00
-0.50
-1.00
-1.50
3,420
3,240
3,060
2,880
2,700
2,520
2,340
2,160
1,980
1,800
1,620
1,440
1,260
1,080
900
720
540
360
180
-2.00
Time (in degrees)
%dc = 100e ( t / )
= ( X / R) / 2f
Item
%dc
Description
dc component expressed in percent
Current
parameters
Comments
Short-circuit
(interrupting)
rating
Closing and
latching current
(for circuit
breakers) or peak
withstand current
(for switchgear)
(in peak amperes)
This is the value of the first peak of the fullyoffset, asymmetrical current, taken from the
instantaneous current curve in the diagram. The
value of the first peak for a 60 Hz system is 2.60,
and is measured at 1/2 cycle of power frequency
(180 electrical degrees). The first peak produces
the most severe mechanical forces between
conductors, and therefore is the critical
mechanical value for bus bars and their supports.
Momentary
current (in rms
amperes)
%dc component
S=
Itotal
Isymmetrical
= 1+2(%dc/100)2
Value from
diagram
Calculated value
Short-circuit interrupting
current
1.000
50.0 kA rms
2.6001
130.0 kA peak
1.550
77.5 kA rms
0.4761
23.8 kA
instantaneous
1.2061
60.3 kA rms
Footnote:
1
Values indicated in current wave on page 1.
47.6 percent
S-factor 1.206.
Since the diagram is referenced to a symmetrical current of
1.000 A rms, the rms asymmetrical (total) current is given by
the S-factor, 1.206 A