Specification For D G Set - 250 KVA
Specification For D G Set - 250 KVA
2. Concomitant Accessories
2.5.1 The set shall be accompanied by following accessories whose cost shall be
included in the basic price of the unit.
Acoustic enclosure -1 No. / each
Auto-main failure panel (AMF) unit complete with voltage -1 No. / each
sensing unit & time relay and battery charger
2.6 Optional Accessories -DELETED
2.6.1 Deleted
2.7 The total value of the offer will include –
(i) The cost of basic machine
(ii) The cost of the concomitant accessories according to tender
Specification
(iii) Cost of any other offered accessory treated as concomitant accessory,
in addition to other factors, like applicable duties and taxes, insurance,
freight, installation and commissioning, training etc.
3. BASIC DESIGN FEATURES
The general characteristics of the machine shall be as per Schedule-III.
General electrical design shall conform to Schedule-II.
3.1 Specific Characteristics
3.1.1 The Generating set shall be complete with accessories auxiliaries, acoustic
enclosure and control panel etc. Any equipment not specifically mentioned
in the specification but essential for completeness of the equipment, shall be
supplied. The DG set offered shall be fitted with equipment of reputed
manufacturers and liberally designed to ensure reliable and satisfactory
performance. The DG set shall be equipped with Diesel Engine of
Cummins/Ashok Leyland/ Greaves/Perkins make and Alternators of
KEC/Stamford/KEL/CGL make.
3.2 Rated Power Output
3.2.1 The Diesel Generating set shall be capable of delivering continuously on (24
hours basis) and shall be rated for prime power duty as per ISO-8528.
3.2.2 The output available from Diesel Engine under site conditions given in
clause 2.3 should also be specified.
3.3 Diesel Engine
3.3.1 The Diesel Engine conforming to BS-5514 / ISO-3046 (Latest) shall be cold
start, vertical direct injection, 4 stroke cycle, water cooled radiator, electric
battery start, directly coupled to the alternator on a combination base plate
through a flexible coupling. The Engine shall be required to operate on
Diesel fuel oil grade A to IS: 1460.
3.3.2 The Engine shall be complete with accessories and protective devices
including following:
3.3.2.1 Heavy-duty air filters
3.3.2.2 Radiator
3.3.2.3 Radiator fan with guard and accessories
3.3.2.4 Lube oil and fuel oil filters and by pass facilities
3.3.2.5 Fuel injection equipment with electronic Governor
3.3.2.6 Engine speed control unit
3.3.2.7 Turbo Charger
ITEM-6
SCHEDULE I
SPECIFICATION
1. MAKE OF ENGINE
D.G.set prime rating 250 KVA
2. ALTERNATOR
Capacity 250 KVA
Rated voltage 415 v, 3 phase 4 wire 50 HZ
%Regulation N.L. to F.L.. +/- 2.5%
RPM 1500
Class of insulation F / H or better
Type of excitation Brush less, Self exciter self regulated
3. CONTROL PANEL
SHEET thickness (not below 2 mm)
4. BUS BAR RATING
5. FUEL TANK CAPACITY sufficient for 12-hour capacity
subject to maximum 990 ltrs
6. RATING OF BATTERIES 2x12v
LEAD ACID
7. BATTERY CHARGER RATING Suitable for 24V lead acid battery
ITEM-6
ANNEXURE "A" for -SCHEDULE I
TECHNICAL DATA OF DIESEL ENGINE
(To Be Filled In By The Supplier)
1. DIESEL ENGINES
1. Maker's Name
2. Maker's type or size (code) Description
3. Cylinder number
4. R.P.M. normal
5. Rated prime output as per ISO-8528B.H.P. Min.
6. Guaranteed rated output at site (continuous B.H.P.running for 24 hrs.
under the worst atmospheric conditions) at variable load
7. Guaranteed consumption of fuel oil.
a) At 100%,75% & 50% of rated output at
Litres/BHPH
normal temperature and pressure
8. Average B.M.E.P.at full load
9. Mechanical efficiency
10. Type of coupling
12. Net weight of engine including flywheel
but excluding separate accessories.
13. Time required for starting from cold
Minutes.
14. Material of
a) Fuel oil piping.
b) Lubricating oil piping.
15. Particulars of the battery of electrical
starting arrangements
16. Capacity of fuel service tank to -
litres meet the 12-hour requirement
ITEM-6
ANNEXURE "B"FOR - SCHEDULE I
(To Be Filled In By The Supplier)
ALTERNATORS
1. Type and make
2. Normal continuous output
at 0.8 P.F.(100% KVA)
3. Normal continuous output (KW)
4. Overload capacity
25 percent ------ hours
10 percent ------ hours
5. Temperature rise of the ------ deg.C
windings measured by thermometer
after six hours continuous run
at rated voltage frequency and
P.F. with air temperature of
45 degree C.
6. Efficiency of the alternator
at 0.8 P.F.
(a) At 100%, 75% & 50% of rated
alternator capacity
7. Variation in Voltage regulation
from full load to no load with % at unity PF
constant speed and excitation. % at 80% PF
ITEM-6
ANNEXURE "C" FOR - SCHEDULE-I
(To Be Filled In By The Supplier)
ALTERNATOR, CONTROL PANEL AND AMF PANEL
1. Draw-out type ACB (make & capacity)
2. Voltage
3. Normal current rating
4. Three phase breaking capacity ---- Volts
5. Particulars of Earth fault relay.
A. Particulars of KW hour meter in alternator panel.
ITEM-6
FORMATE FOR FURNISHING CLAUSE WISE COMPLIANCE
• We hereby confirm that the M&P schedule Item No. 6 shall conform to all
the clause of technical specification
OR
• We hereby confirm that the M&P schedule Item No. 6 shall conform to all
the clause of technical specification except for the following clauses with
deviation against each-
Reference clause Complied/ Not complied Details of deviation
• strike out which ever is not applicable
Signature of supplier