Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

CT's calculation for cable line bay 33kV

ICC

CT

CORE

Caculated: F. GMEZ
Reviewed: W. CASTAEDA
Approved: M. ROSETY

CLASS

Current
ratio
xxx/1A

DEVICES

R CT BURDEN
(Ohm)
(VA)

Conductor
length
(m)

Conductor
section
(mm2)

#REF!
R Cond.
(Ohm)

R Prot./
(Ohm)

RB
(Ohm)

Vkp

I''cc
(kA)

Ktd

Vk min

Ptot

DOC: 285792710.xlsx
Page: 1 of 4

1500

800
600
300

PX

PX

Caculated: F. GMEZ
Reviewed: W. CASTAEDA
Approved: M. ROSETY

600
300
600
300

RED670

RED670

7SA

7SA

5.30

50

4.0

0.45

0.250

0.70

1300.00

40.00

319.81

0.70

2.80

50

4.0

0.45

0.250

0.70

650.00

40.00

349.64

0.70

6.50

50

4.0

0.45

0.250

0.70

1300.00

10.00

479.76

3.50

50

4.0

0.45

0.250

0.70

650.00

10.00

559.52

6.50

50

4.0

0.45

0.050

0.50

975.00

31.50

1.00

282.55

0.50

3.50

50

4.0

0.45

0.050

0.50

650.00

31.50

1.00

322.79

0.50

3.80

50

4.0

0.45

0.050

0.50

975.00

10.00

4.00

220.33

0.50

3.50

50

4.0

0.45

0.050

0.50

650.00

10.00

4.00

409.89

0.50

DOC: 285792710.xlsx
Page: 2 of 4

ation for cable line bay 33kV

Request:
>25%BURDEN

Caculated: F. GMEZ
Reviewed: W. CASTAEDA
Approved: M. ROSETY

Vkp > Vk min

DOC: 285792710.xlsx
Page: 3 of 4

-o-

OK

-o-

OK
OK
OK

Caculated: F. GMEZ
Reviewed: W. CASTAEDA
Approved: M. ROSETY

-o-

OK

-o-

OK

-o-

OK

-o-

OK

DOC: 285792710.xlsx
Page: 4 of 4

You might also like