Reference Manual

Section 2: Configuration

00809-0100-4100, Rev AA

March 2013

Table 2-1. Variable Mapping


Classic Mapping

Scaled Variable Mapping

PV

Pressure

Scaled Variable

SV

Sensor Temperature

Pressure

TV

Electronics Temperature

Sensor Temperature

QV

Supply Voltage

Supply Voltage

Note
The variable assigned to the primary variable drives the output. This value can be selected as
Pressure or Scaled Variable.

Re-mapping using a Field Communicator


From the HOME screen, enter the fast key sequence

Fast Keys

2, 1, 1, 4

Re-mapping using AMS Device Manager


Right click on the device and select Configure.
1.

Select Manual Setup and click on the HART tab.

2. Assign Primary, secondary, tertiary and quaternary variables under Variable Mapping.
3. Click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.

2.5.2

Set range points


From the HOME screen, enter the fast key sequence

Fast Keys

2, 1, 1, 5

The Range Values command sets the lower and upper range values used for the percent of range
measurement.
Note
Transmitters are shipped from Rosemount Inc. fully calibrated per request or by the factory
default of full scale (span = upper range limit).

14

1.

From the Home screen, select 2: Configure

2.

Select 1: Guided Setup

3.

Select 1: Basic Setup

4.

Select 5: Range Values

Configuration