Reference Manual

Section 3: Installation

00809-0100-4100, Rev AA

March 2013

3.

Open the equalize valve on


the low pressure
(downstream) side of the
transmitter. The manifold is
now in the proper
configuration for zeroing the
transmitter.

Test
(Plugged)

Test
(Plugged)
Equalize
(open)
Isolate
(open)

Isolate
(closed)

Process

4.

After zeroing the transmitter,


close the equalize valve on
the low pressure
(downstream) side of the
transmitter.

Equalize
(open)

Drain Vent
(closed)

Process

Test
(Plugged)

Test
(Plugged)
Equalize
(open)

Equalize
(closed)

Isolate
(open)

Isolate
(closed)

Process

5.

Close the equalize valve on


the high pressure (upstream)
side.

Drain Vent
(closed)

Process

Test
(Plugged)

Test
(Plugged)
Equalize
(closed)

Equalize
(closed)

Isolate
(open)

Isolate
(closed)

Process

6.

Finally, to return the


transmitter to service, open
the low side isolation valve.

Drain Vent
(closed)

Process

Test
(Plugged)

Test
(Plugged)
Equalize
(closed)

Equalize
(closed)

Isolate
(open)

Process

Installation

Isolate
(open)

Drain Vent
(closed)

Process

53