Table Xil1. General Requirements for Occupant Loads and Exits*
("In all occupancies, floors above the first (1+) storey having an occupant load of more than ten (10)
shall have al least two (2) exits)
Unit Area per Occupant | Minimum of Two (2) Exits Other
Use or Occupancy (aq. meters) than Elevators are Required Where
Number of Occupants is Over
Dwellings 28.0 70
Hotels 78.60 10
Apartments 16.60 10
Dormitories 18.60 10
Classrooms 1.80 50
Conference Rooms 1.40 50
Exhibit Rooms 1.40 50
Gymnasia 1.40 50
School Shops 4.80 50
Vocational Institutions 460 50
Laboratories 4.60 50
Hospitals”, Sanitaria’™ 8.40 5
Nursing Homes" 7.40 5
Children’s Homes" 7.40 5
Homes for the Aged"* 740 5
(Institutional Sleeping
Departments shall be based on
one (1) occupent per 11.00 9q
meters ofthe gross floor area: In-
patient Institutional Treatment
Departments shall be based on
cone (1) occupant per 22.00 9q
meters of gross floor arza)
Nurseries for Children 3.25 6
Dwellings 28.00 10
Sores-Relail Sales Rooms
Basement 280 50
Ground Floor 260 50
Upper Floors 5.60- 10
Offices 9.20 20
Aircraft Hangars (no repair) 48.00 10
Parking Garages 16.60 30
Drinking Establishments 140 20
Kitchens (commercial) 18.60 50
Warehouses 28.00 20
Mechanical Equipment Rooms 28.00 30
Garages 9.30 10
‘Auditoriums 0.65 50
Theaters 065 50
Churches and chapels 065 50
Dance Floors 65 50
Reviewing Stands 065 50
Stadia 0.65 50.