Amps X 100 Bus150 (Nom. KV 11,5, Plot Ref. KV 11,5) : GT1 FLA
Amps X 100 Bus150 (Nom. KV 11,5, Plot Ref. KV 11,5) : GT1 FLA
kV=11,5)
,5
10
30
50
100
300
500
1K
3K
5K
1K
500
10K
1K
500
GT 1
FLA
300
300
Relay 46 _1 - Q - 51
OC1
100
100
GE Multilin
SGC21 neg sequence
CT Ratio 10000:5
I^2T
Pickup = 0,296 (0,15 - 0,35 Sec - 5A)
Time Dial = 10
3x = 111,1 s, 5x = 40 s, 8x = 15,6 s
50
30
50
30
Gen_1
114,72 MW
(I2)^2 t = 10
10
10
Relay 50/51 _1
GE Multilin
IFC
CT Ratio 10000:5
Very Inverse (53)
Pickup = 4 (1 - 12 Sec - 5A)
Time Dial = 1
3x = 0,545 s, 5x = 0,277 s, 8x = 0,181 s
Inst = 40 (10 - 50 Sec - 5A)
,5
Relay 87T _1
,3
,5
,3
GT 1
145 MVA
d I>
Gen_1
,1
GT 1
Inrush
No Load
Constant Excitation
Total Fault Current
,05
,1
,05
Relay 50/51 _1
I>
,03
,03
Gen_1
No Load
Constant Excitation
AC Fault Current
Relay 46 _1
I>
Gen_1
114,72 MW
Relay 50/51
46 _1 _1
- 3P- 3P
,01
,5
10
30
50
100
300
500
1K
Date: 23-09-2015
SN:
Rev: Base
Fault: Phase
3K
5K
,01
10K
Seconds
Seconds
GT 1
145 MVA (Secondary) 11 %Z
Wye Solid Grd-Delta