XGB-INV IG5A (RS-485 Modbus RTU)

Sample program

The communication between IG5A and built-in XGB Cnet through ch2 (RS-485).
Reception ( D100, 1word )

XGB Sample Program

Transmission
( M000, M001
2 words )

IG5A Setting : DRV=3(RS-485), FRQ=7(RS-485), I59=0(Modbus RTU),


I60=1(station no.), I61=4(19,200bps), I65=0(Parity:None, Stop Bit:1)
Eg) XGB (D1000 or M000 1 Word data) -> address no. 5 of iG5A inverter
(Frequency reference )
XGB (M001 1 Word data) -> address no. 6 of iG5A inverter
(Run command )

1/ 2

XGB-INV IG5A (RS-485 Modbus RTU)

Sample program

XG-PD Parameter setting


Please set Channel 2 of Active mode to Use P2P settings in using XG-PD of XG5000.

You have to set P2P Channel to Modbus RTU client.

P2P Block setting