Typical Deck Edge
Typical Deck Edge
3" MAX
1"
1 1/2" MIN
1/2" MIN
NOTES:
#4 CONT
TOC
4-8
2-8
PLACE STUDS ON
BM CL AXIS
3. THE REQUIRED NUMBER OF STUD ROWS SHALL BE DETERMINED AS FOLLOWS (BEAM LENGTH IN FEET):
BENT PL1/4
4"
18"
3"
2-8
CL BM
4. FOR DECK FLUTES PARALLEL TO THE BEAM, THE FIRST STUD (OR STUDS) SHALL BE PLACED 6" FROM THE
BEAM ENDS. FOR DECK FLUTES PERPENDICULAR TO THE BEAM, THE FIRST STUD (OR STUDS) SHALL BE
PLACED IN THE FLUTE CLOSEST TO THE BEAM ENDS.
2-8
L4x3x1/4
6 1 /4 "
18"
3"
6. WHERE WELDED WIRE REINFORCING IS USED AS SLAB REINFORCEMENT, ADDITIONAL REINFORCEMENT SHALL
BE PLACED PERPENDICULAR TO THE BEAM, ACROSS THE BEAM AND CANTILEVERED SPANS AS FOLLOWS:
VARIES,
4" MAX
4 1/2" MIN
2'-0" MAX
TYP
NOTES:
CL BM
1"
1 1/4" MIN
TYP
3"
2. AT ALL ANGLES AND WEBS LESS THAN OR EQUAL TO 1/4 INCH THICK, USE 1/2 INCH
DIAMETER x 4 INCH STUDS AT 12 INCHES ON CENTER.
2-8
2-8
L3x3x1/4
PL 1/4
L3x3x 1/4
3"
BENT PL 1/4 x
2-8
L TO PL
2-8
1 1/2"
2-8
2-8
L3x3x1/4
2-8
1/2" ,TYP
5. FOR CANTILEVER SPANS, STUDS SHALL BE PLACED IN ONE ROW ALONG THE BEAM CENTERLINE AXIS AT
A MAXIMUM SPACING OF 2'-0". STUDS PLACED ON THE CANTILEVER SPAN ARE NOT INCLUDED IN THE
NUMBER OF STUDS SHOWN ON THE DRAWINGS.
2-8
L TO L
VARIES
1 1/4" MIN
TYP
(A36)
3"
1 1 /4 "
4"
BENT PL1/4
L TO
BM FLG
4-8
L3x3x1/4
(A36)
VARIES,
3" MAX
4 1/2" MIN
2'-0" MAX
TYP
4"
3" MIN
L3x3x1/4
3/4" CLR
TO WWR,
TYP
CL BM
AS REQD
2. UNLESS NOTED OTHERWISE, STUDS ARE TO BE EQUALLY SPACED ALONG THE BEAM LENGTH AND PLACED
SYMMETRICALLY ABOUT THE BEAM CENTERLINE AXIS. IF EQUAL SPACING IS NOT POSSIBLE DUE TO DECK
CONFIGURATION, THE STRUCTURAL ENGINEER SHALL BE NOTIFIED.
L TO BM FLG
TYPICAL STUD
4 1/2" MIN
2'-0" MAX
TYP
L4x3x1/4, LLV
2-8
VARIES,
2" MAX
1. SEE PLAN FOR REQUIRED NUMBER OF STUDS. STUDS SHALL BE PLACED AT A MAXIMUM SPACING OF 2'-0"
ALONG THE BEAM AXIS UNLESS NOTED OTHERWISE ON PLAN. SEE "GENERAL NOTES" FOR MINIMUM NUMBER
OF STUDS
AND MINIMUM STEEL COMPOSITE DECK TO STEEL BEAM FASTENING REQUIREMENTS.
1 1/2"
#4 CONT, TYP
2-8
(A36)
2-8
L3x3x1/4 AS REQD
TO SUPPORT DECK
HSS OR WF COL
PER PLAN
SEE PLAN
NOTE 1
COORD STUD
PLACEMENT W/
EDGE FORM. NOTCH
FORM AS REQD, TYP
8 1 /4 "
#4, CONT
STL DECK
DECK SPANS
EITHER DIRECTION
ADD #4 EA SIDE
3/4" CLR
LOWER WWR TO
PLACE TOP BAR
OVERHANG
3' - 0"
#4 CONT
OVERHANG DESIGN
PER DECK SUPPLIER
REINFORCI
NG
0" TO 9"
OVER 9" TO 1'-4"
#4 @ 18"
OVER 1'-4" TO 2'-0" #4 @ 12"
OVER 2'-0" TO 2'-6"
#4 @ 8"
NOTES:
1. SEE "TYPICAL DECK EDGE CONDITIONS" FOR DECK EDGE SUPPORT AT COLUMNS.
SLAB
THICKNESS
(INCHES)
4
4.5
5
5.5
6
6.5
7
7.5
8
20
20
20
20
18
18
16
16
14
20
20
20
18
18
16
16
14
14
20
20
18
18
16
16
14
14
12
20
18
16
16
14
14
12
12
12
18
16
16
14
14
12
12
12
12
18
16
16
14
14
12
12
12
12
16
16
14
14
12
12
12
12
10
OVERHANG (INCH)
7
8
14
14
14
14
12
12
12
10
10
12
12
12
12
12
12
10
10
10
10
11
12
14
16
18
12
12
12
12
10
10
10
10
3/16
12
12
10
10
10
10
10
3/16
3/16
10
10
10
10
10
3/16
3/16
1/4
1/4
10
10
3/16
3/16
3/16
1/4
1/4
1/4
1/4
3/16
3/16
1/4
1/4
1/4
1/4
1/4
5/16
5/16
1/4
1/4
1/4
1/4
1/4
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
3/8
3/8
3/8
SLAB EDGE
PROVIDE MECH
COUPLER AT
CONTR OPTION
SECT
NOTES:
MATERIAL
18 GA & 20 GA
16 GA & 14 GA
12 GA & 10 GA
3/16 " & 1/4 "
5/16 " & 3/8 "
2' - 0"
#4 @ 12" W/
STD HOOK
ANGLE
6" MAX, TYP
DECK SPANS
EITHER DIRECTION
Ld
BM FRAMING
INTO WALL
Ld
15"
15"
SECTION
NOTES:
12
L2x2x3/16
AT EA FLG
13
L2x2x3/16 ES
EXPIRES: 4/30/2016
SLAB EDGE
"D"
2" ,TYP
ANGLE
NOTES:
CJ
2"
CONC WALL
OR BM
SLAB ON DECK.
WELD DECK TO ANGLE
PER "GENERAL NOTES."
15
TABLE K.1
24"
EDGE FORM
PER "TABLE K.1"
SEE NOTE 3
TABLE K
29"
LOWER WWR TO
PLACE TOP BAR
#4 CONT
24"
EA END
3/16
3' - 0"
29"
5 1 /2 "
CL
5 1 /2 "
6"
DECK CLOSURE TO
COL WEB PER
DECK MFR
3/4" CLR
FLOOR FRAMING
EMBED L3x3x1/4 W/
3/4" DIA x6" STUD
@ 12" OC, OR
PER EQUIP MFR
SLAB THK
EDGE CLOSURE
PER DECK SUPPLIER
h
CL
SLAB THK
CL FLUTE
KEY PLAN
PERPENDICULAR
B
16 03.12.2015 GMP
14 01.15.2015 BUILDING PERMIT SET (RESIDENTIAL)
10 11.20.2014 RESIDENTIAL PERMIT
NO.
DATE
DESCRIPTION
SEE NOTE 3
CL CL
OVER 1'-4"
TO 7'-0"
54"
C6
2" TO 6"
ALL AROUND
6"
SECTION
NOTES:
0" TO 1'-6"
6"
C6x8.2
C6x8.2
C6x8.2
OVER 2'-1"
TO 6'-0"
54"
Residential
26"
SECT
24"
90"
0" TO 1'-6"
90"
C6x8.2
60"
W10x12
33"
W10x12
"L"
W10x12
SECTION B
OVER 1'-4"
TO 7'-0"
6" TO
2'-0"
W10x12
"L"
W10
C6x8.2
W10x12
16"
33"
6" TO
1'-4"
6" TO L
16"
1' - 6"
6" TO L
SECT
B
C6
6" TO L
SECTION A
6" TO L
90"
21"
21"
L4x3x1/4 x WIDTH
OF OPNG
SEE NOTE 4
(1) #4 ALL SIDES,
BOT BARS PARALLEL
TO DECK SHALL BE
PLACED 1" CLR FROM
BOT OF DECK
90"
L3x3x3/16
SEE NOTE 3
SEE "TYP DECK EDGE
CONDITIONS" DET
DECK
SPAN
SPOT WELD
EA FLUTE
1 8 5 /8 "
OVER 2'-0"
TO 6'-0"
60"
0" TO 1'-6"
NO ADDED BM REQD.
ADD REINF AS SHOWN
ABOVE.
6"
W10x12
CL CL
2" CLR
4 x LARGEST HOLE
SIZE OR ADD REINF
"L"
1 8 5 /8 "
SECT
A
TYP
3 x LARGEST HOLE
SIZE OR ADD REINF
DECK
SPAN
L3x3x3/16 x WIDTH
OF OPNG + 3'-0"
"L"
TYP
C6x8.2
TYPICAL STEEL
DECK DETAILS
NOTES:
2. REMOVE BLOCKOUT AND CUT DECK AFTER CONCRETE HAS CURED.
1. INSTALL REINFORCING BEFORE CUTTING HOLES.
3. CONTRACTOR SHALL COORDINATE OPENING SIZE AND LOCATION WITH
MECHANICAL AND ELECTRICAL CONTRACTORS AND ARCHITECTURAL DRAWINGS.
PLAN
3/9/2015 5:47:34 PM
18
20
PLAN
Drawn By:
Author
Checked By:
Checker
Project Number:
2013017
Sheet Number:
S442