AVION , PMPC, Philippines

[2015]

FUEL CHANGE-OVER (GAS TO LIQUID), Working Revision-02


IEG

AND

OK

OK

2.) No active signal for Shutdown = OK

OK

3.) GT is in operation = OK

FUEL

SHUTDOWN

AUTO

1.) Selected fuel GAS = OK

MANUAL MODE
BY OPERATOR
(GAS TO LIQUID)

OR

(GAS TO LIQUID)

OK

INITIALIZATION
OF FUEL TRANSFER
(GAS TO LIQUID)

GT is RUNNING

IF PD-PA > 5MW


for more than 2 min

IF PNGR-PNGA > 5bar

AND

START/ACTIVATE
DEMIN WATER PUMPS
OK

[27-03-2015]
[JRSLVK]

Function Group of Demin Water


Pumps 48-P-120-1 and
48-P-120-2 and 48-P-120-3

4.) Functional Group DEMI Water Pumps is WORKING = OK

AND

see chapter 7.7.1

START/ACTIVATE
DEMI Water Pressure Control
OK

Control loop maintaining


pressure at inlet to GTG water
injection skid

5.) Demi Water pressure control = ACTIVE

AND

see chapter 7.8.3

START/ACTIVATE
CDP COOLER STAGE#1
OK

Function Group of Stage-1


of Cooling Pumps on CDP Cooler

6.) Functional Group CDP#1 is WORKING = OK

AND

IF PNGR-PNGA > 5bar


PNGR

see chapter 6.7.1

IF, THEN

Pressure of Natural
Gas REGUIRED

START/ACTIVATE
CDP COOLER STAGE#2
OK

AND

Function Group of Stage-2


of Cooling Pumps on CDP Cooler

7.) Functional Group CDP#2 is WORKING = OK

see chapter 6.7.2

IF PD-PA > 5MW


for more than 2 min

IF, THEN

OK

GE-1.) XN25 > 8400 rpm or above synch

OK

GE-2.) Liquid fuel supply pressure (PT 62043) > L

OK

GE-3.) The liquid fuel shutoff valves ( SOV 62503 and 6211) are closed.

GE internal

OK

GE-4.) The liquid metering valve ( FCV 6202) at min. position

GE internal

OK

GE-5.) No shutdown from valve-driver

GE internal

GE internal

PA=POWER ACTUAL
(measured)

START/
ACTIVATE
Functional Group DIESEL PUMPS is WORKING = OK

Function Group of
Diesel/Liquid
Forwarding Pumps
see chapter 4.7

PD=POWER DEMAND
(by Operator)

PNGA
Pressure of Natural Gas
Actual
(measured)

FUEL
TRANSFER
EXECUTION

GE CONTROL SYSTEM (MICRONET)

Estimated Gas Pressure at different Output Power - Based on Gas fuel as shown on the guarantee
document. - LM6000 PC SPRINT
700
650

Estimated Fuel
Pressure, Psig

600

Est. Gas Fuel Pressure, Psig

550
500
450
400
350
300
250
200
150
100
50
0
2000

7000

12000

17000

22000
27000
32000
Output Power, kW

37000

42000

47000

52000