CLCULO DE QUEDA DE TENSO

SERVIO: LOTEAMENTO TARAUACA CIRCUITO 01 DE 75 KVA


CIRC. N.: TRA 01
PRIM.:13,8 KV
SEC.:220/127 V
TRANSFORMADOR OU ALIMENTADOR

TRECHO
DESIGN.

CARGA
TOTAL

CONDUTORES

F.P. 0,92

QUEDA DE TENSO

COMPRIM

DIST. TR.

FIM TR.

A
PRIM.
SEC.

B
KM
100 m

C
MVA
KVA

D
MVA
KVA

D-C
C-B
B-A
A-0

0.3084
0.3387
0.6778
0.6532

4.8
4.8

0.8
4.8
9.6
20.0

0.25
1.63
8.13
14.63

3#50
3#50
3#70
3#120

0.1551
0.1551
0.1122
0.069

0.04
0.25
0.91
1.01

2.21
2.17
1.92
1.01

E-C

0.3005

0.8

0.24

3#50

0.1551

0.03

2.20

I-H
H-F
F-0

1.049
0.6759
0.9566

6.4
1.6
5.6

3.2
12.0
21.6

6.71
8.65
23.34

3#70
3#120
3#120

0.1122
0.069
0.069

0.75
0.60
1.61

2.96
2.21
1.61

G-F

0.9987

1.6

3.60

3#50

0.1551

0.56

2.17

(C/2+D)B=E
F
MVA x KM
N AWG
KVA x 100

UNIT.

NO TR.

TOTAL

ExG=H

PREP. POR Clevison Fragoso VISTO_____________


OBS: DEMANDA DIVERSIFICADA 6,4 KVA.

EM 02/03/2015

FLHA DE: 01/06

47.2

mm
25
35
50
70
95
120

R
1.4420
1.0043
0.7707
0.3855
0.3855
0.3053

CABOS MULTIPLEXADOS
X
V
0.1045
220
0.1022
220
0.0979
220
0.0960
220
0.0960
220
0.0936
220

FATOR DE POTNCIA DA CARGA

Queda
0.2511
0.2084
0.1551
0.1122
0.0827
0.0690
0.8

30.84
33.87
67.78
65.32
30.05

104.9
67.59
95.66
99.87

120
65.32
67.59
95.66

70
67.78
104.9

50
30.84
33.87
30.05
99.87

TOTAL

228.57

172.68

194.63

CLCULO DE QUEDA DE TENSO


SERVIO:LOTEAMENTO TARAUACA CIRCUITO 01 DE 75 KVA
CIRC. N.: TAR 02
PRIM.:13,8 KV
SEC.:220/127 V
TRANSFORMADOR OU ALIMENTADOR

TRECHO
DESIGN.

CARGA

CONDUTORES

QUEDA DE TENSO

COMPRIM

DIST. TR.

FIM TR.

A
PRIM.
SEC.

B
KM
100 m

C
MVA
KVA

D
MVA
KVA

D-C
C-B
B-A
A-0

0.3065
0.3302
0.6993
1.01

6.4
6.4

0.8
3.2
13.6
24.8

0.25
1.06
11.75
28.28

3#50
3#70
3#120
3#120

0.1551
0.1122
0.069
0.069

0.04
0.11
0.81
1.95

2.91
2.87
2.76
1.95

E-C

0.3111

0.8

0.25

3#50

0.1551

0.03

2.90

G-F
F-0

1.0507
0.9994

4.8
21.6

10.93
24.39

3#70
3#120

0.1122
0.069

1.22
1.68

2.90
1.68

11.2
5.6

TOTAL

F.P. 0,92

(C/2+D)B=E
F
MVA x KM
N AWG
KVA x 100

UNIT.

NO TR.

TOTAL

ExG=H

PREP. POR Clevison Fragoso VISTO_____________


OBS: DEMANDA DIVERSIFICADA 6,4 KVA.

EM 02/03/2015

FLHA DE: 02/06

58.4

mm
25
35
50
70
95
120

R
1.4420
1.0043
0.7707
0.3855
0.3855
0.3053

CABOS MULTIPLEXADOS
X
V
0.1045
220
0.1022
220
0.0979
220
0.0960
220
0.0960
220
0.0936
220

FATOR DE POTNCIA DA CARGA

Queda
0.2511
0.2084
0.1551
0.1122
0.0827
0.0690
0.8

30.65
33.02
69.93
101
31.11
105.07
99.94

120
69.93
101
99.94

70
33.02
105.07

50
30.65
31.11

TOTAL

270.87

138.09

61.76

CLCULO DE QUEDA DE TENSO


SERVIO: LOTEAMENTO TARAUACA CIRCUITO 01 DE 75 KVA
CIRC. N.: TAR. 03
PRIM.:13,8 KV
SEC.:220/127 V
TRANSFORMADOR OU ALIMENTADOR

TRECHO
DESIGN.

CARGA

CONDUTORES

QUEDA DE TENSO

COMPRIM

DIST. TR.

FIM TR.

A
PRIM.
SEC.

B
KM
100 m

C
MVA
KVA

D
MVA
KVA

D-C
C-B
B-A
A-0

0.3029
0.5995
0.6032
0.6009

4.8
4.8
5.6

0.8
3.2
12.8
22.4

0.24
3.36
9.17
15.14

3#50
3#50
3#70
3#120

0.1551
0.1551
0.1122
0.0635

0.04
0.52
1.02
0.96

2.54
2.50
1.98
0.96

E-C

0.3119

0.8

0.25

3#50

0.2012

0.05

2.55

I-H
H-G
G-F
F-0

0.7004
0.6427
0.6025
0.35

3.2
14.4
19.2
27.2

4.20
10.03
12.29
9.52

3#70
3#70
3#120
3#120

0.1122
0.1122
0.0635
0.0635

0.47
1.12
0.78
0.60

2.97
2.50
1.38
0.60

J-F

0.3485

3.2

1.12

3#50

0.1551

0.17

0.77

5.6
2.4
2.4

TOTAL

F.P. 0,92

(C/2+D)B=E
F
MVA x KM
N AWG
KVA x 100

UNIT.

NO TR.

TOTAL

ExG=H

PREP. POR Clevison Fragoso VISTO_____________


OBS: DEMANDA DIVERSIFICADA 6,4 KVA.

EM 02/03/2015

FLHA DE: 03/06

55.2

mm
25
35
50
70
95
120

R
1.4420
1.0043
0.7707
0.3855
0.3855
0.3053

CABOS MULTIPLEXADOS
X
V
0.1045
220
0.1022
220
0.0979
220
0.0960
220
0.0960
220
0.0936
220

FATOR DE POTNCIA DA CARGA

Queda
0.2511
0.2084
0.1551
0.1122
0.0827
0.0690
0.8

30.29
59.95
60.32
60.09
31.19
70.04
64.27
60.25
35
34.85

120
60.09
95.25

70
60.32
69.64
63.87

50
30.29
59.95
31.19

TOTAL

155.34

193.83

121.43

CLCULO DE QUEDA DE TENSO


SERVIO:LOTEAMENTO TARAUACA CIRCUITO 01 DE 75 KVAL
CIRC. N.: TAR 04
PRIM.:13,8 KV
SEC.:220/127 V
TRANSFORMADOR OU ALIMENTADOR

TRECHO
DESIGN.

CARGA
TOTAL

CONDUTORES

F.P. 0,92

QUEDA DE TENSO

COMPRIM

DIST. TR.

FIM TR.

A
PRIM.
SEC.

B
KM
100 m

C
MVA
KVA

D
MVA
KVA

D-C
C-B
B-A
A-0

0.4848
0.6137
0.6866
0.4992

2.4
0.8
4.8
4.8

2.4
7.2
12.8
20.0

1.75
4.66
10.44
11.18

3#70
3#70
3#70
3#120

0.1122
0.1122
0.1122
0.069

0.20
0.52
1.17
0.77

2.66
2.47
1.94
0.77

E-B

0.3018

0.8

0.24

3#70

0.1122

0.03

1.97

H-G
G-F
F-0

0.8538
0.5082
0.5015

1.6
2.4
4

4.0
13.6
20.0

4.10
7.52
11.03

3#50
3#70
3#120

0.1551
0.1122
0.069

0.64
0.84
0.76

2.24
1.61
0.76

I-G

0.6098

3.2

1.6

1.95

3#50

0.1551

0.30

1.91

3#70
0.1122
EM 02/03/2015

0.03

2.49

(C/2+D)B=E
F
MVA x KM
N AWG
KVA x 100

J-C
0.298
0.8
0.24
PREP. POR Clevison Fragoso VISTO_____________
OBS: DEMANDA DIVERSIFICADA 6,4 KVA.

UNIT.

NO TR.

TOTAL

ExG=H

FLHA DE: 04/06

52.8

50
70
95
120

0.7707
0.3855
0.3855
0.3053

0.0979
0.0960
0.0960
0.0936

220
220
220
220

FATOR DE POTNCIA DA CARGA

0.1551
0.1122
0.0827
0.0690
0.8

2.45

48.48
61.37
68.66
49.92

120
49.92
50.15

70
48.48
61.37
68.66
30.18
50.82
29.8

50
85.38
60.98

100.07

289.31

146.36

30.18
85.38
50.82
50.15
60.98
29.8
TOTAL

CLCULO DE QUEDA DE TENSO


SERVIO: LOTEAMENTO TARAUACA CIRCUITO 01 DE 75 KVA
CIRC. N.: TRA 05
PRIM.:13,8 KV
SEC.:220/127 V
TRANSFORMADOR OU ALIMENTADOR

TRECHO
DESIGN.

A
PRIM.
SEC.

CARGA

COMPRIM

DIST. TR.

FIM TR.

B
KM
100 m

C
MVA
KVA

D
MVA
KVA

TOTAL

CONDUTORES

(C/2+D)B=E
F
MVA x KM
N AWG
KVA x 100

F.P. 0,92

QUEDA DE TENSO
UNIT.

NO TR.

TOTAL

ExG=H

C-B
B-A
A-0

0.6044
0.6038
0.8986

4.8
4.8
4

2.4
12.0
21.6

2.90
8.69
21.21

3#70
3#70
3#120

0.1122
0.1122
0.069

0.33
0.98
1.46

2.76
2.44
1.46

F-E
E-D
D-0

0.6989
0.699
0.6624

6.4
5.6
1.6

2.4
14.4
24.0

3.91
12.02
16.43

3#70
3#70
3#120

0.1122
0.1122
0.069

0.43
1.34
1.13

2.90
2.47
1.13

PREP. POR Clevison Fragoso VISTO_____________


OBS: DEMANDA DIVERSIFICADA 6,4 KVA.

EM 02/03/2015

FLHA DE: 05/06

52.8

mm
25
35
50
70
95
120

R
1.4420
1.0043
0.7707
0.3855
0.3855
0.3053

CABOS MULTIPLEXADOS
X
V
0.1045
220
0.1022
220
0.0979
220
0.0960
220
0.0960
220
0.0936
220

FATOR DE POTNCIA DA CARGA

Queda
0.2511
0.2084
0.1551
0.1122
0.0827
0.0690
0.8

60.44
60.38
89.86
69.89
69.9
66.24

120
89.86
66.24

70
60.44
60.38
69.89
69.9

50

TOTAL

156.1

260.61

CLCULO DE QUEDA DE TENSO


SERVIO: LOTEAMENTO TARAUACA CIRCUITO 01 DE 45KVA
CIRC. N.: TRA 06
PRIM.:13,8 KV
SEC.:220/127 V
TRANSFORMADOR OU ALIMENTADOR

TRECHO
DESIGN.

A
PRIM.
SEC.
E-D
D-C
C-B
B-A
A-0

COMPRIM

B
KM
100 m
0.6214
0.7904
0.6097
0.5003
0.2519

G-B
H-A

0.2222
0.2446

C-B
B-A
A-0

0.9069
0.585
0.2498

D-B
E-A
F-D

CARGA
DIST. TR.

FIM TR.

C
MVA
KVA
4.8

D
MVA
KVA
2.4
8.8
9.6
13.6
17.6

0.8
0.8

TOTAL

CONDUTORES

(C/2+D)B=E
F
MVA x KM
N AWG
KVA x 100
2.98
3#70
6.96
3#70
6.10
3#70
7.00
3#95
4.43
3#95

F.P. 0,92

QUEDA DE TENSO
UNIT.

NO TR.

TOTAL

ExG=H

0.1122
0.1122
0.1122
0.0827
0.0827

0.33
0.78
0.68
0.58
0.37

2.75
2.41
1.63
0.95
0.37

1.6
1.6

0.36
0.39

3#50
3#50

0.1551
0.1551

0.05
0.06

1.00
0.43

0.8
6.4
10.4

1.81
3.98
2.60

3#70
3#95
3#95

0.1122
0.0827
0.0827

0.20
0.33
0.21

0.75
0.54
0.21

0.2973
0.2673

1.6
1.6

0.48
0.43

3#50
3#50

0.1551
0.1551

0.07
0.07

0.62
0.28

0.3085

0.8

0.25

3#70

0.1122

0.03

1.66

2.4
0.8

PREP. POR Clevison Fragoso VISTO_____________


OBS: DEMANDA DIVERSIFICADA 6,4 KVA.

EM 02/03/2015

FLHA DE: 06/06

28.0

mm
25
35
50
70
95
120

R
1.4420
1.0043
0.7707
0.3855
0.3855
0.3053

CABOS MULTIPLEXADOS
X
V
0.1045
220
0.1022
220
0.0979
220
0.0960
220
0.0960
220
0.0936
220

FATOR DE POTNCIA DA CARGA

Queda
0.2511
0.2084
0.1551
0.1122
0.0827
0.0690
0.8

62.14
79.04
60.97
50.03
25.19
22.22
24.46
90.69
58.5
24.98
29.73
26.73
30.85

95
50.03
25.19
58.5
24.98

70
62.14
79.04
60.97
90.69
30.85

50
22.22
24.46
29.73
26.73

TOTAL

158.7

323.69

103.14

REDE CONVENCIONAL E COMPACTA DE DISTRIBUIO DE ENERGIA


ELTRICA DO LOTEAMENTO ................................................
LISTA DE MATERIAIS
DESCRIO

UN

LOCAL: R
DATA:
Quant.

ALA PREFORMADA PARA CABO DE AO 6,14

26

ALA PRE-FORMADA DE ESTAI

15

ALA PREFORMADA SERVIO PARA CABO DE AL. MUTIPLEX 50MM

25

ALA PREFORMADA SERVIO PARA CABO DE AL. MUTIPLEX 70MM

38

ALA PREFORMADA SERVIO PARA CABO DE AL. MULTIPLEX 95MM

19

ARMAO SECUNDRIA PESADA DE 01 ESTRIBO COM HASTE E CUPILHA

53

ARMAO SECUNDRIA PESADA DE 02 ESTRIBOS COM HASTE E CUPILHA

136

ARRUELA QUAD. DIAM. 10mm, LADO 34mm, ESP. 3mm, GALV. 3/8;

10

ARRUELA QUAD. DIAM. 16mm, LADO 34mm, ESP. 3mm, GALV. 3/8;

343

10 BASE DE REL FOTOELTRICO INDIVIDUAL 10A - 220V

85

11 BRAO em ao zincado tipo"C", PARA REDE COMPACTA

12 BRAO ANTI-BALANO POLIMRICO

13 BRAO "L", PARA REDE COMPACTA

22

14 BRAO PARA LUMINRIA TIPO CURTO 1,5M TIPO Y 30/1

85

15

CABO BIMETLICO PARA ATERRAMENTO 2 AWG: CABO AO - COBRE 3X7 AWG% LC

342

16 CABO DE COBRE ISOLADO P/ 0,750 KV 120 MM

80

17 CABO DE COBRE ISOLADO P/ 0,750 KV 70 MM

16

18 CANTONEIRA AUXILIAR PARA BRAO TIPO "C", REDE COMPACTA

17

19 CHAVE FUSIVEL DE 15KV 100A, COM DISPOSITIVO PARA ABERTURA EM CARGA

18

20 CABO COBERTO XLPE 2 AWG 35

3106

21 CONECTOR DE DERIVAO PERFURANTE PARA CABO ISOLADO CONDUTOR PRINCIPAL.


16-95, DERIVAO FIO 4-5MM

170

CONECTOR DE DERIVAO PERFURANTE PARA CABO ISOLADO CONDUTOR PRINCIPAL.


25-120, DERIVAO FIO 25-120MM

128

22

23 CONECTOR PARA HASTE DE ATERRAMENTO COBREADO DIAMETRO 1/2

58

24 CONECTOR PARALELO BIMETALICO COM 02 PARAFUSOS E PORCAS 10--2/0AWG

43

25 CONECTOR TIPO CUNHA DE 6,4

15

26 CORDOALHA DE AO ZINCADA A QUENTE 7 FIOS 6.4mm CARGA MINIMA

1035

27 ESPAADOR DE CABOS LOSANGULAR POLIMRICO CLASSE 15 KV

155

28 GRAMPO DE ANCORAGEM POLIMETRICO

45

29 GRAMPO DE LINHA VIVA PARA ALUMINIO

18

30 HASTE DE ATERRAMENTO TIPO COBREADA (COOPERWELD) AO COM REVEST. DE COBRE,


DIAM. 1/2"X2400MM

58

31 ISOLADOR DE ANCORAGEM POLIMRICO CLASSE 15 KV;

45

32 ISOLADOR DE PINO POLIMERICO, COM ANEL DE AMARRAO, CLASSE DE TENSO 15KV.

11

33

ISOLADOR ROLDANA P/ BAIXA TENSO DE PORCELANA MARRON;

325

34 LAO PRE-FORMADO PLASTICO DE PLSTICO PARA ESPAADOR LOSANGULAR E


SEPARADOR DE CABOS, DIMETRO EXTERNO 10,18 A 1,7MM (2AWG).

155

35 LMPADA VAPOR DE SDIO 70W 220V PARA SOQUETE E-27

85

36 LUMINRIA PB. FECHADA SOQUETE E-27

85

37 MANILHA-SAPATILHA

45

38 OLHAL PARA PARAFUSO DE 5/8'' GALVANIZADO;

58

39 PARAFUSO CABEA ABAULADA, M 16 x 50 mm

12

40 PARAFUSO CABEA QUADRADA C/ PORCA 16mm x 350mm RT (5X8 x 14")

220

41 PARAFUSO CABEA ABALUADA C/ PORCA 10mmx 115mm RT (3/8x5")

10

42 PARAFUSO CABEA ABALUADA C/ PORCA 16mmx 250mm RT (5/8x10")

157

43 PARAFUSO ABALUADO, 5/8X 3"


PARA RAIOS DISTRIBUIO DE OXIDO DE ZINCO POLIMRICO 10KA - 12KV COM
44 DISPOSITIVO DE DESLIGAMENTO AUTOMATICO E FERRAGENS PARA FIXAO;
PINO RETO PARA ISOLADOR POLIMERICO DE 15KV, BASE DO PINO COM ROSCA EXTERNA,
45 ARRUELA E PROCA , P/ INSTALAO EM CRUZETA DE FERRO.

18
21

46 POSTE DE CONCRETO ARMADO DT 11/200 KGF

11

47 POSTE DE CONCRETO ARMADO DT 11/400 KGF

18

48 POSTE DE CONCRETO ARMADO DT 9/200 KGF

31

49 POSTE DE CONCRETO ARMADO DT 9/400 KGF

25

Valor Unitrio

50 REATOR PARA LMPADA VS 70W 220V, USO EXTERNO

85

51 REL FOTOELETRICO INDIVIDUAL NF 1200VA/ 220V;

85

52 SAPATILHA

15

53 SUPORTE HORIZONTAL PARA REDE COMPACTA

54 SUPORTE PARA TRANSFORMADOR EM POSTE DE CONCRETO DT 195MM

12

TRANFORMADOR DE DISTRIBUIO TRIFSICO DE 75KVA CLASSE DE TENSO 15KV


55 220/127V

TRANFORMADOR DE DISTRIBUIO TRIFSICO DE 45KVA CLASSE DE TENSO 15KV


56 220/127V

57 CABO MULTIPEXADO 50X50

690

58 CABO MULTIPLEXADO 70X70

1516

59 CABO MULTIPLEXADO 95X70

175

60 CABO MULTIPLEXADO 120X95

1002

6/1/2015
TOTAL

162

180
342