BOILER PROTECTION

1
NO POWER AVAILABLE
Any of the boiler protection panel power supply (220 UPS VAC, 48 VDC, 5
volt, +12 volts) is lost.
2
2 I.D. FANS OUT OF OPERATION
When both ID fans are indicated out of service
3
2 F.D. FANS OUT OF OPERATION
When both FD fans are indicated out of service
4
NO COMBUSTION AIR FLOW
Airflow to boiler is less than 25% of a nominal measured value of 2,000
KNm, which equates to 450,000 Nm/hr.
5
NO STEAM EXHAUST
both HP SV not open & HP bypass closed
HP SV closed & HP GV closed
HP SV not open & 3 out of 4 HP GV closed
both IP GV closed & LP bypass closed & RH vent valve closed
at start up: furnace probe in service, furnace gas temperature > 550 C,
BCP header temperature <160 C
6
REGENERATIVE AIR HEATERS OUT OF OPERATION
When both air heaters are recognized as being out of service
7
DRUM LEVEL LOW LOW
less than 600 mm LTX-052A/B, discrepancy between the 2 level transmitter
values greater than 30% (hardwired to boiler protection panel)
8
FURNACE PRESSURE LOW LOW
less than 17.15 mbar, 2 out of 3 FTO-PSLL-001A/B/C
9
CONTROL AIR PRESSURE LOW LOW
instrument air supply reduces to 5 bar, 2 out of 3 Press Switches
10
FURNACE PRESSURE HIGH HIGH
exceeds +14.5 mbar, any 2 of FTO-PSHH-001A/B/C
11
SCANNER COOLING AIR PRESSURE LOW LOW
below 50 mbar( 0.05 bar) for more than 2 min FAR-PSLL-001A/B
12
FLAME DETECTION FAILURE
when one or more coal firing levels fail to detect two flames on any coal firing
level a fireball detection failure will occur
13
R/BACK WITH AT LST 1 MILL IN MAN/STM FLW > 60 %
R/back initiated with 1 out of 3 mills in MAN & not SEL to trip, SF>1140 t/hr
14
BOILER STEAM PRESSURE HIGH HIGH
exceeds 195 bar gage for more than 5 sec, FSR-PT-050A/B
15
NO BOILER CIRCULATION PUMPS IN OPERATION
No BCP in service for more than 5 sec
16
STEAM FLOW >50%, LESS THAN 2 CIRC. PUMPS IN OPER.
SF > 950 t/hr & only 1 BCP in service, TD=10 sec
17
CCR EMERGENCY STOP OPERATION
Location: operators desk or back panel
18
R/BACK WITH FURN PRESS/AIR FLW MEAS FAULT
R/back initiated with 2 out of 3 FTO-PT-057A/B/C fault or
Mill A/B/C/D FT-072A/B, FCA/B-FT-051 airflow measurement fault