EQUIPMENT SELECTION: SINGLE PACKAGE UNITS (PAC-01)


& SPLIT UNIT (FCU-01)
1. PAC-01
a. CALCULATED TOTAL COOLING LOAD : 79.3 Kw= 270,000 Btu/Hr
b. SENSIBLE COOLING LOAD
: 79.3 Kw = 270,000 Btu/Hr
c. AIRFLOW
: 5589 L/s = 11,842 cfm
d. Ambient Temperature
: 46C
= 115F

Corected Capacity due to Elevation = Required Capacity/Correction Factor

TotalcoolingloadCorectedCapacity=270,000/.99

=273,000Btu/hr

B. UNIT SELECTION CATALOG.


CARRIER (ATTACHED AS CLOUDED)
1. PAC-01 : MODEL NO.
= 50TJ028
a. ENTERING WETBULB TEMPERATURE
b. NOMINAL TOTAL COOLING LOAD
c. NOMINAL SENSIBLE COOLING LOAD
d. AIRFLOW

2. FCU-01 MODEL NO.


a. NOMINAL TOTAL COOLING LOAD
b. For Cooling only

= 72F
= 294,000 Btu/Hr. (25 Tons)
= 170,000 Btu/Hr.
= 11,250 CFM

= 42QG18-C / 38QG18-C
= 18,000 BTU/Hr