E=
E=
2125 x 47
=301.55 lux
23 x 14.4
No. of Fixtures = 2
Floor Area = 6.78 m2
Use: 13W 800 Lumens CFL
E=
E=
800 x 2
=235.99 lux
6.78
No. of Fixtures = 19
Floor Area = 70.35 m2
Use: 70 W 1400 Lumens Bright Pin Light
E=
E=
1400 x 19
=378.11 lux
70.35
No. of Fixtures = 2
Floor Area = 16.36 m2
Use: 36 T8 RE7 30 24 W 2125 Lumens Fluorescent Lamp
E=
E=
2125 x 2
=259.78 lux
16.36
No. of Fixtures = 5
Floor Area = 14.61 m2
Use: 13W 800 Lumens CFL
E=
E=
800 x 5
=273.79lux
14.61
No. of Fixtures = 2
Floor Area = 29.96 m2
Use: 36 T8 RE7 30 24 W 2125 Lumens Fluorescent Lamp
E=
E=
2125 x 2
=141.86 lux
29.96
No. of Fixtures = 8
Floor Area = 50.92 m2
Use: 36 T8 RE7 30 24 W 2125 Lumens Fluorescent Lamp
E=
E=
2125 x 8
=333.86lux
50.92
No. of Fixtures = 14
Floor Area = 54.67 m2
Use: 70 W 1400 Lumens Bright Pin Light
E=
E=
1400 x 14
=358.51lux
54.67
No. of Fixtures = 12
Floor Area = 34.91 m2
Use: 70 W 1400 Lumens Bright Pin Light
E=
E=
1400 x 12
=481.24 lux
34.91
RCR=
5 (2.8)( 32.81+19.21)
=1.16
32.81(19.21)
CCR=
5 (1)(32.81+19.21)
=0.41
32.81(19.21)
FCR=
5 (0.7)(32.81+19.21)
=0.29
32.81( 19.21)