Wind Load Calculation + Design Criteria

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Design weight of Aluminum Roof sheet covering = 1 x 1 x 0.0009 x 7850 = 7.

06 kg/m2
Weight of the purlins
Assume purlins is

(40+40+10+10+200) x 0.002 x 7850 = 4.71 kg/m2


Assume 4.71 kg/m2
Total load of vertical dead load = 11.77 kg/m2
Service Load
As per QATALUM standard SOW 1.1 is 75 kg/m2
Wind load calculation
As per British Standard
Clause 2.2.32

10.0000

10.7500

10.0281

10.0000

Figure 11 H= 10.75, B= 18m


H B consider building as one part

10 cation Qatar basic wind speed as per QCS = 28 m/s


Clause 2.2.22.2
Assuming that the topography is not considered significant
Sa = 1 + (0.001 x os) assume os = 10m
Sa= 1 + (0.001 x 10) 1.01
Clause: 2.2.2
Site wind speed vs = vb x sa x sd x ss x sp
Page1of7

Assuming sd=ss=sa=1
Vs= 33 x 1.01 = 33.33 m/sec
Clause 2.2.3 table 4
Effective wind speed Ve = vs x sb
Clause 2.2.3.3
He= 10.75m sd=1.85
Ve= 28 x 1.85=51.8 m/s
95= 0.613 x (ve)2 = 0.613 x (51.8)2/1000= 1.64kg/m2
PC= qs x cpe x ca

5.0

5.0

18.0

6.0

6.0

6.0

Roof Is designed As Monopitch Roof

Case (1) Loads on (+ x x)

Page2of7

0.82
roof
(-1.96)

1.39

D/h = 10/10= 1.0


CPC = + 0.85
CPi = -0.5 assume Ca = 1.0
Pe= 1.64 x 0.85 = 1.39 KN/m2
Pi= 1.64 x 0.5 = 0.82 KN/m2
Wind On The Roof
From Table 8
We Will take Zone B
Curved eaves r/b 0.05
Cpe = -1.2
Pei = 1.64x(-1.2)x1 = -1.96 kn/m2

Case (1)

Case (2) (-x+x)

Page3of7

2.13

roof (-1.1)

0.82

From table 5
Isolated zone (A)
Cpe = 1.3
Cpi = 0.85
Pe = 1.64 x1.3= 2.13 kn/m2
Pei = 1.64 x-0.8 = -1.312 kn/m2
From table 9
Load on the roof = 1.1 kn/m2
From table 18
Cpi first side -0.57
Cpe second side + 0.77

pi = 1.64 x(-0.57) = 0.94 kn/m2


pe = 1.64x0.77
= 0.97 kn/m2

Case (3) (-z+ z)

Page4of7

10.0

10.0

10.8

10.0

0.94 roof (-1.1)

Cpe = 1.3
Cpi = 0.5

1.26

pe = 1.64 x 1.3 =2.13 kn/m2 table 5 isolated


pei = 1.64x 0.5 = 0.82 kn/m2 table 5 isolated

Loads on roof
-1.1 kn / m2

Case (4) (+ z z)

Page5of7

1.26

Cpe = 1.3
Cpi = 0.5

10.0

10.0

10.8

10.0

roof (-1.1)

0.94

pe = 1.64 x 1.3 =2.13 kn/m2 table 5 isolated


pei = 1.64x 0.5 = 0.82 kn/m2 table 5 isolated

Loads on roof
-1.1 kn / m2

Foundation design
1- We take in our consideration the effect of the wall on the foundation 3,7,11,15
20.84 kn/m
2- All our design according to BRITISH standards

Page6of7

3- We take the load of the next building in our consideration 5 kn/m2 in foundation
1,13

Page7of7