MANUFACTURER & EXPORTER OF HT & LT PORCELAIN INSULATORS

TEST AND INSPECTION REPORT


Date: 02.03.2011
Ref No: Powercon (Sample)
Buyer: Associated Powercon Equipments Pvt. Ltd.
Pune, India
Item: Bus Duct Insulators
Item Code: RP/ESP-9007 & RP/ESP-9008
Quantity Supplied: 32 Nos Each.

DETAILS OF TEST AND INSPECTION:

Visual Inspection: Appearance is satisfactory, free from


blisters/cracks/ovality/damages.
Dimensional Verification: Tolerance Limit as per the IS: 4318.
Mechanical Tests: Compressive/Bending/Tensile Strength Test Results:
Satisfactory
Mallet Test results: OK. No hair cracking sound heard.
Heat Treatment Results: After completion of temp. Cycle immersion, no
crack or loosening of insulator found.
Temp. Cycle: 90C, 160C, 210C
Electrical Tests: Power Frequency one minute withstand voltage: Dry at
72kV
Porosity Test: No dye-penetration observed on the
unglazed surfaces of the insulators.

K. Chakraborty

Authorized Signatory

Note: This is a computer-generated document and does not require any


signature.