Elec. Valve Size Select Guide
Elec. Valve Size Select Guide
ventilation, air-conditioning
ELECTRONIC VALVE
SIZING AND SELECTION
V4.1
Coil
A
AB
1 psi
0.7
1.2
1.9
3.0
4.7
7.4
10
12
19
29
31
37
39
46
57
Pressure drop
5 psi
1.7
2.7
4.2
6.7
11
17
22
27
42
64
69
83
87
103
127
10 psi
2.3
3.8
6.0
9.5
15
23
32
38
60
92
98
117
123
145
180
Table of contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
I.
Two-position control of hot and cold water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
II.
Two-way valve modulating control of coil water flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
III.
Two-way valve modulating control of system pump pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
IV.
Three-way valve modulating flow control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
V.
Three-way valve modulating control of temperature with constant flow . . . . . . . . . . . . . . . . . . . . . . . .10
VI.
Other considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
VII.
Steam systems and 2-position control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
VIII. Modulating control of low and high pressure steam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Figures
1a
Two-way valves in 2-position applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1b
Three-way valves in 2-position applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2a
Two-way valves in modulating applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2b
Pressure loss for modulating control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2c
Authority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3
Two-way modulating valves controlling pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
4
Three-way valves in high pressure drop applications flow control . . . . . . . . . . . . . . . . . . . . . . . . . .10
5a
Three-way valve low pressure drop coil runaround pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5b
Control of Condenser Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
5c
Perimeter Loop Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
6
Boiler, Pump, and Piping System Head Pressure Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7
Steam valve applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Tables
A
Characterized Ball Valve Cv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
B
Globe Valve Cv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
C
Butterfly Valve Cv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
D
Glycol specific gravity, g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
E
FL for Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
F
Vapor Pressures Cavitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
G
Specific Volume Steam Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Introduction
The common applications in HVAC valve control, each of
which uses slightly different selection and sizing methods, are
defined in the section headings in the table of contents.
Supply
Coil
V1
Return
Radiator, Convection, Fan Coil
May be modulating also.
Diverting Tee
Large Zone Isolation Valves
Supply
Return
Boiler
SYSTEM CHANGEOVER
AB
Boiler
AB
Mixing Valve
used as 2
position
B Diverting
Chiller
ZONE CHANGEOVER 4 PIPE SYSTEM
AB
Coil
Diverting B 3-Way
Sequenced
2-Position
Control Valves
These are modulating
Return
1 pipe system
HWS CWS
HWR
CWR
Fp & Cv
The Cv of a high capacity valve diminishes significantly as the
pipe size is increased. This is calculated using the piping
geometry factor or Fp. Cvc is corrected Cv. It is found using
Cvc = Cv x Fp.
Fp can be estimated for average concentric reducers using a
formula shown in Belimos Control Valve Applications Guide.
High capacity valves ( standard ball valves and butterfly
valves) have a low Fp; the capacity is greatly reduced. Low
capacity valves like the globe and characterized ball valve
have Fp near 1; there is little reduction in capacity from using
reducers.
In Table A the full port, high capacity valves are marked.
When using them in pipes larger than the valve size the Cvc
table at the bottom of the page should be used to find the corrected Cv.
Cv = GPM / P/g
(g = 1 for water and therefore Cv = GPM / P)
It is typical to select a 2-position valve with a Cv = GPM
required. Examination of the sizing tables shows that line
size valves are usually selected.
Example 1:
A zone isolation valve must pass 10 GPM. The line size is
1. What size valves are acceptable for a ball valve and a
globe valve?
Assume that the pressure drop should be 1 psi at the most.
Select a line size valve. From Table 1 a 1 ball valve in a 1
line has a Cv of 23.
Using Cv = GPM / P and P = 1 and substituting,
Cv = 10 / 1.
Cv = 10. This is the minimum Cv required.
Any valve with Cv equal to or greater than 10 will work.
Now find the globe which fits.
From Table B there are 1 globe valves with Cvs of 10 and
14. The pressure drop is less for the Cv = 14 and normally
it is selected.
Note that the rule of thumb can be that the required Cv is
equal to or greater than the GPM required or line size.
There are other reduced pipe size valves that could also be
used.
Table A: Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
Cv
Maximum
Rating
0.8
1.2
1.9
3.0
4.7
7.4
10
4.7
7.4
10
24
7.4
10
19
30
10
19
25
37
19
29
37
29
46
57
GPM = Cv x
Valve
Inches
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
3/4"
3/4"
3/4"
3/4
1"
1"
1"
1"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
1-1/2"
2"
2"
2"
p
DN
mm
15
15
15
15
15
15
15
20
20
20
20
25
25
25
25
32
32
32
32
40
40
40
50
50
50
Two
Way
Ball
Valve
B209
B210
B211
B212
B213
B214
B215*
B217
B218
B219
B220*
B222
B223
B224
B225*
B229
B230*
B231
B232*
B238
B239
B240*
B248
B249
B250*
Three
Way
Ball
Valve
B309
B310
B311
B312
B313
B315
B317
B318
B320
B322
B323
B325
B329
B330
B331
B332
B338
B339
B340
B348
B349
B350
2psi
1.1
1.7
2.7
4.2
6.6
10
14
6.6
10
14
34
10
14
27
42
14
27
35
52
27
41
52
41
65
81
3psi
1.4
2.1
3.3
6.2
8.1
13
17
8.1
13
17
42
13
17
33
52
17
33
43
64
33
50
64
50
80
99
4psi
1.6
2.4
3.8
6.0
9.4
15
20
9.4
15
20
48
15
20
38
60
20
38
50
74
38
58
74
58
92
114
5psi
1.8
2.7
4.2
6.7
11
17
22
11
17
22
54
17
22
42
67
22
42
56
83
42
65
83
65
103
127
6psi
2.0
2.9
4.7
7.3
12
18
24
12
18
24
59
18
24
47
73
24
47
61
91
47
71
91
71
113
140
7psi
2.1
3.2
5.0
7.9
12
20
26
12
20
26
63
20
26
50
79
26
50
66
98
50
77
98
77
122
151
8 psi
2.3
3.4
5.4
8.5
13
21
28
13
21
28
68
21
28
54
85
28
54
71
105
54
82
105
82
130
161
9psi
2.4
3.6
5.7
9.0
14
22
30
14
22
30
72
22
30
57
90
30
57
75
111
57
87
111
87
138
171
10psi
2.5
3.8
6.0
9.5
15
23
32
15
23
32
76
23
32
60
95
32
60
79
117
60
92
117
92
145
180
1"
6.3
19.0
30.0
-
1-1/4"
16.1
27.3
19.0
37.0
-
Line size
1-1/2"
14.6
24.9
18.8
35.5
37.0
-
2"
21.9
18.2
31.8
35.0
57.0
2-1/2"
17.9
30.0
34.0
56.0
3"
33.0
54.0
4"
52.0
FLOW
X
X should be as short as possible. Length will influence
the resulting Cv value of a full ported ball valve.
Maximum
Rating
0.4
1.3
2.2
4.4
5.5
7.5
10
14
20
28
40
Valve
DN
mm
15
15
15
15
20
20
25
25
32
40
50
Inches
1/2
1/2"
1/2
1/2
3/4
3/4
1
1
1-1/4
1-1/2
2
Two
Way
Globe
Valve
G212
G213
G214
G215
G219
G220
G224
G225
G232
G240
G250
Three
Way
Globe
Valve
G314
G315
G320
G325
G332
G340
G350
Maximum
Rating
0.4
1.3
2.2
4.4
5.5
7.5
10
14
20
28
40
Valve
DN
mm
15
15
15
15
20
20
25
25
32
40
50
Inches
1/2
1/2
1/2
1/2
3/4
3/4
1
1
1-1/4
1-1/2
2
Two
Way
Globe
Valve
G212
G213
G214
G215
G219
G220
G224
G225
G232
G240
G250
Maximum
Rating
0.4
1.3
2.2
4.4
5.5
7.5
10
14
20
28
40
Valve
Inches
1/2
1/2
1/2
1/2
3/4
3/4
1
1
1-1/4
1-1/2
2
DN
mm
15
15
15
15
20
20
25
25
32
40
50
Two
Way
Globe
Valve
G212
G213
G214
G215
G219
G220
G224
G225
G232
G240
G250
3psi
0.7
2.3
3.8
7.6
9.5
13.0
17
24
35
48
69
4psi
0.8
2.6
4.4
8.8
11.0
15.0
20
28
40
56
80
5psi
0.9
2.9
4.9
9.8
12.3
16.7
22
31
45
63
89
6psi
1.0
3.2
5.4
10.8
13.5
18.4
24
34
49
69
98
7psi
1.1
3.4
5.8
11.6
14.5
19.8
26
37
53
74
106
8 psi
1.1
3.7
6.2
12.4
15.6
21.2
28
40
57
79
113
10psi
1.3
4.1
7.0
13.9
17.4
23.7
32
44
63
89
126
10 psi
15 psi
2-position
Modulating 2-position
Modulating
10% of P1
80% of P1
10% of P1
80% of P1
P = 1 psi
P = 8 psi P = 1.5 psi P = 12 psi
5.8
14
7.8
18
19
45
25
56
32
76
43
96
65
153
86
192
80
191
107
240
110
260
146
328
146
347
195
437
204
486
273
612
292
694
390
874
409
971
546
1224
584
1387
780
1749
# / hr. Steam
Inlet - psig
20 psi
25 psi
2-position
Modulating 2-position Modulating
10% of P1
.42 of P1
10% of P1
.42 of P1
P = 2 psi
P = 14 psi P = 2.5 psi P = 16 psi
10
20
12
23
32
67
38
76
53
113
64
129
107
226
127
259
133
283
159
323
182
385
217
441
243
514
289
588
340
719
405
823
485
1028
579
1176
679
1439
810
1646
970
2056
1157
2351
30 psi
35 psi
2-position
Modulating 2-position
Modulating
10% of P1
.42 of P1
10% of P1
.42 of P1
P = 3 psi P = 18 psi P = 3.5 psi P = 20 psi
13
26
15
29
44
86
50
96
74
146
84
162
148
291
168
324
185
364
210
405
252
496
286
552
336
662
381
736
470
927
534
1030
671
1324
763
1472
940
1853
1068
2060
1342
2648
1526
2944
The influence of the pipe reduction factor on the flow for the Belimo electronic globe valves is negligible.
6
9psi
1.2
3.9
6.6
13.2
16.5
22.5
30
42
60
84
120
# / hr. Steam
Inlet - psig
2 psi
5 psi
2-position
Modulating 2-position Modulating
10% of P1
80% of P1 10% of P1
80% of P1
P = .2 psi P = 1.6 psi P = .5 psi P = 4 psi
2.2
5.8
3.7
9.5
7
20
12
30
12
33
21
52
23
65
41
104
30
81
51
131
41
111
70
179
55
148
92
238
77
207
130
333
109
295
186
475
153
413
260
666
218
590
371
951
2psi
0.6
1.8
3.1
6.2
7.8
10.6
14
20
28
40
57
Cv
Valve Flow Rate for Water Applications (GPM) Two-Way Globe Valve
Cv
Valve
Pressure drop across the valve
Maximum
Rating
65
90
170
263
344
DN
mm
65
80
100
125
150
Inches
2-1/2
3
4
5
6
Model
Number
G665
G680
G6100
G6125
G6150
1 psi
65
90
170
263
344
2psi
92
127
240
372
486
3psi
113
156
294
456
596
4psi
130
180
340
526
688
5psi
145
201
380
588
769
6psi
159
220
416
644
843
7psi
172
238
450
696
910
8 psi
184
255
481
744
973
9psi
195
270
510
789
1032
10psi
206
285
538
832
1088
8 psi
192
257
537
792
962
9psi
204
273
570
840
1020
10psi
215
288
601
885
1075
8 psi
192
240
436
552
701
9psi
204
255
462
585
744
10psi
215
269
487
617
784
Valve Flow Rate for Water Applications (GPM) Three-Way Mixing Globe Valve
Cv
Valve
Pressure drop across the valve
Maximum
Rating
68
91
190
280
340
DN
mm
65
80
100
125
150
Inches
2-1/2
3
4
5
6
Model
Number
G765
G780
G7100
G7125
G7150
1 psi
68
91
190
280
340
2psi
96
129
269
396
481
3psi
118
158
329
485
589
4psi
136
182
380
560
680
5psi
152
203
425
626
760
6psi
167
223
465
686
833
7psi
180
241
503
741
900
Valve Flow Rate for Water Applications (GPM) Three-Way Diverting Globe Valve
Cv
Valve
Pressure drop across the valve
Maximum
Rating
68
85
154
195
248
DN
mm
65
80
100
125
150
Inches
2-1/2
3
4
5
6
Model
Number
G765D
G780D
G7100D
G7125D
G7150D
1 psi
68
85
154
195
248
2psi
96
120
218
276
351
3psi
118
147
267
338
430
4psi
136
170
308
390
496
5psi
152
190
344
436
555
6psi
167
208
377
478
607
7psi
180
225
407
516
656
The influence of the pipe reduction factor on the flow for the Belimo electronic globe valves is negligible.
Valve Flow Rate for Low Pressure Steam Applications
Cv
Maximum
Rating
65
90
170
263
344
Valve
Inches
2-1/2
3
4
5
6
DN
mm
65
80
100
125
150
Two
Way
Globe
Valve
G665
G680
G6100
G6125
G6150
2 psi
5 psi
2-position
Modulating 2-position Modulating
10% of P1
80% of P1 10% of P1
80% of P1
P = .2 psi P = 1.6 psi P = .5 psi P = 4 psi
354
958
604
1545
490
1327
836
2139
926
2507
1580
4042
1433
3878
2445
6253
1875
5073
3198
8178
Maximum
Rating
65
90
170
263
344
Valve
Inches
2-1/2
3
4
5
6
DN
mm
65
80
100
125
150
Two
Way
Globe
Valve
G665
G680
G6100
G6125
G6150
20 psi
25 psi
2-position
Modulating 2-position Modulating
10% of P1
.42 of P1
10% of P1
.42 of P1
P = 2 psi
P = 14 psi P = 2.5 psi P = 16 psi
1577
3320
1881
3797
2183
4596
2604
5258
4124
8682
4918
9931
6381
13432
7609
15364
8346
17568
9952
20098
30 psi
35 psi
2-position
Modulating 2-position
Modulating
10% of P1
.42 of P1
10% of P1
.42 of P1
P = 3 psi P = 18 psi P = 3.5 psi P = 20 psi
2181
4275
2480
4753
3020
5919
3433
6580
5704
11181
6485
12430
8825
17297
10033
19230
11543
22624
13123
25152
For example, 600 GPM must flow through a 4 pipe and valve
with a pressure drop of no more than 1 psi.
Valve
Size
Pipe
Size
Full Open 90
Flow in GPM at pressure drop of:
1 psi
2 psi
3 psi
4 psi
5 psi
6 psi
2
2
2
2
2.5
3
66
57
52
93
95
85
166
141
121
166
141
121
235
199
171
288
244
210
332
282
242
371
315
271
407
345
296
2.5
2.5
2.5
2.5
3
4
99
98
93
138
124
98
247
222
175
247
222
175
349
314
247
428
385
303
494
444
350
552
496
391
605
544
429
3
3
3
3
4
5
136
124
127
190
158
135
340
282
241
340
282
241
481
399
341
589
488
417
680
564
482
760
631
539
833
691
590
4
4
4
4
5
6
264
247
255
370
315
270
660
561
482
660
561
482
933
793
682
1143
972
835
1320
1122
964
1476
1254
1078
1617
1374
1181
5
5
5
5
6
8
432
418
388
605
532
411
1080
950
734
1080
950
734
1527
1344
1038
1871
1645
1271
2160
1900
1468
2415
2124
1641
2645
2327
1798
6
6
645
903
1613
1613
2281
2794
6
8
553
704
1258
1258
1779
2179
6
10
553
587
1048
1048
1482
1815
Not rated for steam.
Note: Values for Cv in pipes larger than valve in table above are calculated for average reducers.
3226
2516
2096
3607
2813
2343
3951
3081
2567
Coil
A
AB
Table C
Butterfly Valves
Coil
BV
V1
V2
Return
Boiler
Pump
Pump Head = 45' at 500 GPM
BV = Balancing Valve
1/2 psi
4 psi
5 psi
1/2 psi
Example 2.
Given a heating coil with a 60 GPM modulating requirement
and pipe size of 2 with no other information.
Assume P = 4 psi and required Cv = GPM / 2. Required Cv
= 60 / 2 = 30.
Go to Table A and select valve: the Cv = 31 of the 2 characterized valve is correct, as is Cv = 29 of the 1-1/2 valve.
Alternately the valve may be selected by going to the 4 psi
pressure drop column and reading down comparing pipe
sizes to the Cv. One arrives at the same valve.
Butterfly valves must be frequently limited in amount of rotation. It is common practice to consider the modulating range
of a butterfly to be between 15 and 70. A smaller valve is
used for fine control below useful range of the butterfly.
III. Two-way valve modulating control of system pressure
Coil
Mixing
System Bypass
BV
B
AB
BV
Globe
Ball
Boiler
HWS
The valves here are
bypassing flow back
to the pump in order
to keep the system
pressure at a design
value.
HWR
Coil
Runaround Pump
AB
B
HWS
HWR
Pump
Bypass
Other Considerations
COOLING TOWER
Pressure drop thru
valve should be
N
equal to that from Nozzles
A to N. Pressure
Cooling
at N must be
Tower
sufficient for
nozzles, if used.
3-way
Diverting
B
AB
Condenser
Fig. 5b - Three-way valves in low pressure
drop application Control of Temperature
Cooling tower
In Figure 5b, a 3-way diverting valve is installed for a cooling
tower bypass.
Table D
Ethylene
Glycol
% by
weight
10
20
30
40
Specific
Gravity
% by
volume
9
18
27
37
Propylene
Glycol
% by
% by
weight
volume
7
10
17
20
26
30
37
40
46
50
Freezing
Point
F
1.01
1.03
1.04
1.06
26
17
8
-14
-3
-8
-15
-25
Specific
Gravity
Freezing
Point
F
28
9
9
-5
-18
-2
-13
-13
-21
-28
1.01
1.02
1.02
1.04
1.04
Cavitation
Cavitation does not occur with steam valves. It can be predicted for water valves by solving this equation:
Maximum allowable P = FL2 (P1 - VP)
A
B
Boiler
Supply
3-Way
Mixing
Return
Type Valve
Globes
Control Ball
Butterflies
Butterflies
Standard Ball
Amount Open
All positions
All positions
70 open
90 open
90 open
Table F
VP = Vapor pressure of water
F
psia
40
.12
50
.18
100
.95
150
3.7
175
6.7
190
9.3
200
11.5
212
14.7
See Belimos Valves Control Applications Guide Doc V4.2
for more detail on this subject.
Other considerations
Determining the required valve pressure ratings
Valves have a number of pressure conditions which must be
considered. They have 2 ratings body and stem static rating and disc and seat close-off rating. Static rating is the
amount of total pressure which the body and stem seal must
hold against without leaking. Close off is the differential
across the disc against which the valve can hold without leaking.
Steam valves should be selected for the boiler rating. For
example, if an 18 psi boiler pressure is maintained, then the
valve must hold against 18 psi (and 255F).
Water valves require a bit more consideration.
Coil
V1
4 PSI at 250 GPM
Height = 100'
Coil
V2
4 PSI at 250 GPM
Height = 10'
Expansion
Tank
Boiler
Friction Loss in
piping is at
4' per 100'
Return
Pump
Pump Head = 45' at 500 GPM
Assume 50'
Cv = (W * V ) / (63.3 * h )*Y
W = #/hr
Sometimes written as Q
V = specific volume using psig
h = pressure drop. This is P1, inlet pressure - P2, outlet
pressure.
Y = expansion factor. It is typically .75 for steam valves.
Coil
Supply Header
Trap
P2
Condensate Return
Header
Boiler
Reciever
Superheat
For correction with superheated steam, increase the required
Cv by (1 + superheat x .0007) for each degree F of superheat.
That is
New Cv required = Cv calculated x (1 + .0007 x F
superheat)
Table G
psig
0
10
20
30
40
50
60
70
80
100
120
140
160
200
300
400
Specific Volume
psia
14.7
25
35
45
55
65
75
85
95
115
135
155
175
215
315
415
V^.5
5.2
4
3.4
3.1
2.8
2.6
2.4
2.3
2.1
2
1.8
1.7
1.6
1.5
1.2
1.1
Example 2
5 psig supply. 500 # of steam per hour required for a
modulating valve.
Use h = 80% (P1 - P2) = .8 x (5 - 0) = 4
Go to Table B. Using 5 psig inlet and the 80% column, go
down and find Cv = 28 provides 620# /hr. Select a valve as
close as possible.
Example 3
What Cv is required for 30 psig, 4000#/hr, modulating valve?
It is unnecessary to use h = .42 psia = .42 (30 + 14.7) = 18.8
psia drop through the valve. Table B has already taken this
into account. Go to 30 psig and the .42 column. Read down
30 psig 42% column to find 4275# /hr at a Cv = 65.
14
The valve selected is usually the same in both cases since the
sizes increase in discrete steps. Typically, use line size.
Notes
15
Electronic Accessories
Mechanical Accessories
Application Information
Doc. 5.1
Mounting Methods Guide
Doc. 5.2
Wiring Guide
Doc. 5.3
Damper Applications Guide
Doc. 5.4
Pneumatic vs Electronic Actuation
Doc. 5.5...
Actuator submittal sheets
Product/Application News
Documentation/Price List
Doc. V2.1
Characterized Control Valves
Doc. V2.2
NV Series Actuator, Globe Valves
(1/2-2)
Doc. V2.2-1
Electronic Globe Valves (21/2-6)
Doc. V2.3
Electronic Zone Valves
Doc. V2.4
Electronic Butterfly Valves
Application Information
Doc. V4.1
Sizing and Selection
Doc. V4.2
Valve Applications Guide
Product/Application News
Belimo InterActive