Professional Documents
Culture Documents
Air Handling Unit
Air Handling Unit
Air Handling Unit
PLATE 2
AIR DISTRIBUTION SYSTEM
AIR HANDLING UNIT 2-2
Mana-ay, Marvin
Maristela, Thomme Justin
Maxino, Denzel
Oabel, Christelle Marie
Pea, Paul Genald
Pealber, Neil
Paet, Daryl
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
I.
`
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
II.
CFM 6420
=
=3.21 Sq . ft
FPM 2000
Duct Size: 24 in x 22 in
From Table 6 - Equivalent Diameter: 25.1 in
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
Air Quantity
(Cfm)
Cfm
Capacity
(%)
Duct
Area (%)
Area
(Sq. ft.)
To A
6420
100
100
3.21
A1
1440
22.43
29.93
0.96
12
13
960
480
14.95
7.48
21.45
12.22
0.69
0.39
AB
4980
77.57
82.57
2.65
B4
1440
22.43
29.93
0.96
45
56
960
480
14.95
7.48
21.45
12.22
0.69
0.39
BC
3540
55.14
63.14
2.03
C7
1440
22.43
29.93
0.96
78
89
960
480
14.95
7.48
21.45
12.22
0.69
0.39
CD
2100
32.71
40.71
1.31
D 10
10 11
11 12
1050
700
350
16.36
10.90
5.45
23.36
17.4
9.68
0.75
0.56
0.31
D 13
13 14
14 15
1050
700
350
16.36
10.90
5.45
23.36
17.4
9.68
0.75
0.56
0.31
Duct
Size
24 X
22
12 X
12
10 X
10
10 X 6
20 X
20
12 X
12
10 X
10
10 X 6
20 X
16
12 X
12
10 X
10
10 X 6
14 X
14
12 X
10
10 X 8
10 X 6
12 X
10
10 X 8
10 X 6
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
Duct
Section
To A
AB
B-C
CD
Items
DUCT
DUCT
DUCT
DUCT
Length(
ft.)
12
9
9
20
Additional
Equivalent
Length of Elbows
(ft.)
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
D 13
DUCT
22
ELBOW
5
13 4
DUCT
3
14 15
DUCT
9
TOTAL
84
5
LONGEST RUN
V.
89
ft
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
0.185 in w.g.
100 ft
6420 cfm
2000 fpm
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
Total Static Pressure (TSP) = (Total Length x FR) + Terminal Loss
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
For Diffusers 1 to 9:
Area=
Q
480
=
=0.768 sq . ft .
V x 0.5 1250 x 0.5
Dimensions= A= 0.768 x
12.
DxD=( 12 x 12 ) .
1 ft .
Q
350
=
=0.56 sq . ft .
V x 0.5 1250 x 0.5
Dimensions= A= 0.56 x
Room
Performance
Analysis
Storage 1
Storage 2
Operation
Control
Division
12.
DxD=( 10 x 10 ).
1 ft .
Total
Room Cfm
No. of
Diffus
ers
CFM/Diffu
ser
Veloc
ity
(fpm)
Area
(Sq.
Ft.)
Size of
Diffuser
4320
480
1250
00.768
12 x 12
350
350
1
1
350
350
1250
1250
0.56
0.56
10 x 10
10 x 10
1400
350
1250
0.56
10 x 10
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2
20 x
2012 x
20 x
1612 x
12
12
12 x
10
10 x 8
10 x
10
10 x
10
10 x
10
10 x 6
Performance
analysis
9 12 x 12
Ceiling diffusers
At 480 CFM
10 x 6
14 x
14
12 x
10
10 x 8
10 x 6
10 x 6 10 x 6
Storage 1
1 10 x 10
Ceiling diffuser
At 350 CFM
Storage 2
1 10 x 10
Ceiling diffuser
At 350 CFM
ME150P-A2
GROUP 2: THREE STOREY BUILDING, SECOND FLOOR
PLATE 2: SUPPLY AND RETURN DUCT DESIGN USING EQUAL
FRICTION METHOD
AHU 2-2