160/630 A Multi-Stage Distribution Block
160/630 A Multi-Stage Distribution Block
160/630 A Multi-Stage Distribution Block
distribution block
Distribution
Centralised distribution
The distribution block can be installed horizontally in the device zone or vertically in
the 300 mm wide duct of wall-mounted and floor-standing enclosures (System G).
It is not compatible with Pack enclosures.
PD390659
Cat. no.
15 x 5
20 x 5
32 x 5
32 x 8
04052
04053
04054
04055
DD381341
Electrical characteristics
b rated operational current Ie (40 C):
v 160 A for distribution block 04052
v 250 A for distribution block 04053
v 400 A for distribution block 04054
v 630 A for distribution block 04055
b rated insulation level Ui = 750 V
b rated short-time withstand current Icw:
v 10 kA rms / 1 s for 160 A block
v 13 kA rms / 1 s for 250 A block
v 20 kA rms / 1 s for 400 A block
v 25 kA rms / 1 s for 630 A block
b rated peak withstand current Ipk:
v 30 k for 160 A block
v 30 k for 250 A block
v 40 k for 400 A block
v 40 k for 630 A block
b impulse withstand voltage Uimp = 8 kV.
Supply
b 16 mm2 to 50 mm2 cables with crimped lugs
b 20 x 2 mm flexible bars for NSX100/160
b 20 x 3 mm flexible bars for NSX250
b 32 x 5 mm flexible bars for NSX400
b 32 x 8 mm flexible bars for NSX630.
Distribution
13 outgoers per phase, max. 50 mm2.
DD381343
DD381342
Installation
b screwed horizontally onto the functional uprights of wall-mounted and floorstanding enclosures (System G)
b screwed vertically onto the functional uprights of the 300 mm wide duct (System G)
b screwed to plain or slotted backplate (System G/P)
b screwed onto the adapter 03595 (System P).
100E22050.indd
160/630 A multi-stage
distribution block
Distribution
Centralised distribution
DD381344
Dimensions
100E22050.indd