Rectifier Setting for Battery

Parameter

Default Value Value Range Description

Battery Capacity on
Specific Breaker

Work Mode

Safe

The system automatically


activates/deactivates

Free

rectifiers according to this


parameter.

Safe
Save

Float Voltage (V)


Equalized Voltage (V)
Equalized Enabled

53.5
56.4
Enabled
Interval for the system to
carry out the equalized

Equalized Period???
days???

90

0 to 365

charge management. When


it is set to ???0???, it
means that the periodical
equalized charge is
disabled.
Duration for the system to
carry out the appointed

Pre.Equ.Chg.Dura.???h???

0 to 48

equalized charge. When it is


set to ???0???, it means
that the appointed equalized
charge will be
managed according to the
ordinary equalized
charge.
When the system carries out
the floating or

Chg.Curr.Coeff. (C10)

0.15

0.01 to 0.4

equalized charge, it charges


the battery according
to the preset charge current.
When the system carries out
the test
management, it will quit
when the voltage

Test Stop Volt. (V)

46

42 to 50

Test Stop Volt. (V)

46

42 to 50

detected at the busbar is


lower than this
parameter value.
Requirement on the
parameter value:
l MAX (LLVD1 Voltage,
LLVD2 Voltage,
BLVD Voltage) + 2V ???
Batt.Volt.L.Thre. +
1
When the system carries out
the test
management, it will quit
when the effectively

Test Stop Cap. (C10)

0.6

0.4 to 1

minimum battery capacity


that is detected is lower
than this parameter value.
Interval for the system to
carry out periodical

Test Period (days)

0 to 365

tests. When it is set to ???


0???, it means that the
periodical tests are disabled.
If the periodical tests are
enabled, the system

Test Start Time (X:00)

10

0 to 23

will carry out the test


management when the
periods come and the
current time is later than
this parameter value.

Disconnect Mode
BLVD Enabled
BLVD Voltage (V)

Batt.Volt.
Enabled
44

Disabled

When the environment


temperature is lower than
LLTD Env.Temp. (???)

-15

-40 to 10

this parameter value and


LLTD Enabled is set
to ???Enabled???, the
system disconnects the
LLVD1
and LLVD2 loads.

Generator Mode

Auto

Auto
Manual

Generator starting mode

Generator alam voltage

GLO BSB Hisel


600 500

ok

ok

500

ok

54.5 54.5
56.5 56.4
Ok
Ok

53.5
56.4
Ok

180

21

180

10

12 10~12

0.2

0.2

46.8 46.8

0.1

46.8

46.8 46.8

46.8

ok

ok

0.2

ok

ok

180

10~12

ok
44

ok
44

ok
44.4

-10

ok

ok

ok

47.3