INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
MEASURING OF INSULATION RESISTANCE
Insulation resistance of the electrical equipment is measured prior to the commissioning. Direct voltage
is used for the measuring with the minimum values shown in the table underneath.
Rated voltage
of circuit

Test voltage

Insulation resistance

SELV and PELV


500 V except the a.m.
systems

250

0,25

500

0,5

Over 500 V

1000

1,0

Resistance is measured using a megger on a dead switchboard and it can be carried out without
connection of the current-using equipment to the network.
Megger must be capable to feed the a.m. test voltage with a current of 1 mA.
In the TN-S network phase and neutral conductors can be connected in parallel and carry out the
measuring between the connected conductors and earth. In the TN-C network the PEN-conductor is
earthed and the measuring is carried out between the connected phase conductors and earth.
For the comprehensive measuring of the switchboard or its part, all mechanical switches, e.g. main
switch and MCBs for outgoing cables, must be in I-position and fuses in place.
If any circuit or part of circuit is equipped with a contactor or analogous device, which disconnects all
the poles of the circuit from the measuring circuit, the circuit after the contactor must be measured
separately.
Use a megger for measurings. Insulation resistance is to be 1 M
NOTE!
Measuring of insulation resistance must be performed only on dead equipment.
Be sure that
supply is switched off
control voltage is switched off
relays are switched off
Be careful not to damage electronic equipment in the measuring circuit (as a rule, new devices
endure). Insulation resistance can be measured only between connected phases and neutrals and
earth.
Do not touch terminals or wires of the gauge during the measuring!
Object with capacitance, e.g. a long cable, is charged up to voltage 500 V during the measuring. Do
not forget to discharge it, if the gauge does not discharge it automatically!
Follow the instructions of the manufacturer of the gauge.

ABB Control Oy

Manual

Low Voltage Systems


Responsible department:

Date:

Language:

KLS/KT

31-08-01

en

Prepared:

Checked:

Approved:

1TFL 328 232


Product:

Revision index:

Page:

2/2
File No:

EsK
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
MEASURING OF INSULATION RESISTANCE

Procedure

Required measurement

Remarks

1 Between the outer conductors


and the protective conductor

2 Between the neutral and


protective conductor

Separate PE- and Nconductors!


This procedure is not required
in the TN-C network

3 Between the outer conductors

4 Between the outer conductors


and neutral conductor

This procedure is not required:

if the cable includes an


earthed conductor or shield

for switching leads of


lighting circuits