ADDENDUM FOR

208-230/460
VOLT - 3 PHASE UNITS
1/4, 1/2, and 3/4 HP MODELS
Refer to attached Operating Instructions and Parts Manual for all Unpacking, Electrical Connections, Operating, Safety Information and
Maintenance Instructions. When ordering parts it is necessary to specify exact model number and which cabinet you are ordering parts for.

Specifications and performance


AVG. CFM AT NOZZLE FOR MOTOR
SHOWN IN VARIOUS CABINET SIZES

208-230/ 460
50/60Hz
MAX.
AMPS

MAX
FT. PER MIN.
AT NOZZLE

36

38

42

48

60

HP

MAX.
RPM

MAX.
MOTOR
WATTS

1/4

1100

186

.60

2500

1620

1670

1796

2000

2880

1/2

1450

373

1.2

3800

2460

2535

2730

3040

4375

3/4

1725

746

3.2

5250

3400

3500

3770

4200

6035

Two motor unit.

ELECTRICAL CONNECTIONS

7. Unit is ready for operation.

WARNING: ALL AIR CURTAINS SHOULD BE


INSTALLED BY QUALIFIED PERSONNEL.

8. Restore power.

9. Upon completion of all installation, inspect unit for


excessive vibration during operation. If excessive
vibration is noticeable, disconnect power supply,
inspect mounting installation and refer to troubleshoot2. Install all wiring, protection and grounding in accoring Chart for probable cause.
dance with the National Electrical Code (NEC) and all
local requirements.
1. Connect motor per nameplate to correct power supply.
Use adequate size wire for all branch and feeder runs.

/4 H.P. 3 PHASE

WARNING: THIS FAN HAS AN INTERNAL SELFRESETTING THERMAL OVERLOAD PROTECTOR.


ALWAYS DISCONNECT FROM POWER SUPPLY
BEFORE SERVICING.
3. Remove two screws from switch box and remove
cover.
4. Run wires from power supply to switch box using
appropriate wiring according to local code. (Use a flexible connector to allow for possible angle adjustment.)
5. Connect wires from switch box to power supply with
wire nuts (not included). Follow wiring diagrams below for connections. Label on motor indicates voltage
your motor was wired for when shipped. No loose
strands or loose connections should be present. After
splices are made, wires should be spread apart so that
some wires are on one side of outlet box and some
wires are on other side. Turn splices upward and carefully push all wiring into outlet box.
NOTE: If air curtain is to be controlled by hand (on/off
switch), a magnetic motor starter is not required.
When automatic on/off function (micro switch) is
required, Motor Control Panels must be used.
6. Replace switch box cover.
ECR35189
Part No. 5200-2415-0001

03-02

LOW VOLTAGE 208-230V

HIGH VOLTAGE 460V

/2 H.P. 3 PHASE

LOW VOLTAGE 208-230V

HIGH VOLTAGE 460V

3/4 H.P. 3 PHASE


LOW VOLTAGE 208-230V

HIGH VOLTAGE 460V

Wiring Diagram 208-230V or 460V