General Technical Precautions For Installation of C&I Equipments
General Technical Precautions For Installation of C&I Equipments
General Technical Precautions For Installation of C&I Equipments
Previous Topic
Next Topic
High & Low pressure impulse lines shall not be grouped and run
together. Also impulse lines for explosive & inert gases shall not run
together.
Impulse lines of high pressure steam, harmful gases, etc. shall not be
brought into the control room, as far as possible.
Separate cable routing shall be followed for high and low voltage
lines.
Previous Topic
Index
Next Topic
Next Topic
For pneumatic instruments, air shall be dry & free from oil.
be supplied from oil-free compressors specially erected
purpose. After drying, air must be stored in receiver.
gauges must be provided on each supply line and after the
reducer.
Impulse pipe material shall be identified for each individual pipe prior
to its use at site. For this purpose coloring is to be done immediately
after receipt for identification.
Previous Topic
Index
Air must
for this
Pressure