DATE: 27TH NOVEMBER, 2015

EQUIPMENT: T1 - 30MVA POWER TRANSFORMER

NAMEPLATE
Make:
Mitsubishi Electric Co
Voltage
(HV/LV): 132000/33000
Cooling
Type:
ONAN/ONAF
S/No:
8662710102
Year:
Jan. 1987
Freq:
50Hz

Vector:

YNd11
11.81

% Z:
Temp
Rise:

Oil-60C, Winding-60C

Rated Power:
Current HV:
LV:

22.5/30MVA
98.4/131 A
394/525 A

EQUIPMENT: T1 - 30MVA POWER TRANSFORMER


1 RATIO TEST OF T1 30MVA POWER TRANSFORMER
TAP POS. MAGNETISING CURRENT
A
B
C
1 1.34
0.68
1.51
2 1.42
0.69
1.60
3 1.44
0.69
1.63
4 1.49
0.72
1.65
5 1.53
0.75
1.70
6 1.53
0.76
1.72
7 1.60
0.79
1.78
8 1.67
0.79
1.82
9 1.67
0.87
1.85
10 1.72
0.89
1.88
11 1.74
0.91
1.95
12 1.79
0.95
1.92
13 1.81
0.95
2.03
14 1.88
0.99
2.07
15 1.86
1.04
2.00
16 1.90
1.09
2.09
17 1.94
1.08
2.18

PRIMARY APPLIED VOLTAGE


AB
BC
CA
421.5
422.7
418.9
421.9
423
418.7
421.2
422.3
418.4
421.1
422
418.2
420.7
421.8
418.1
420.8
422.6
418.5
421.2
422.1
418.2
421.3
422.3
418.4
421.2
422.4
418.4
421.3
422.5
418.6
428.7
430
426.9
429.1
430.2
426.1
428.3
429.5
425.5
428.3
429.4
425.5
428.1
429.4
425.5
427.7
428.8
424.7
427.6
428.8
424.9

SECONDARY MEASURED VOLT.


ab
bc
ca
95.20
95.40
96.10
96.30
96.60
97.20
97.30
97.60
98.20
98.40
98.60
99.30
99.50
99.70
100.50
100.90
101.10
101.90
102.00
102.30
103.10
103.30
103.60
104.30
104.60
104.90
105.60
105.90
106.20
109.00
109.20
109.50
110.20
110.60
111.00
111.80
111.90
112.20
113.00
113.50
113.80
114.60
115.00
115.20
115.90
116.40
116.70
117.50
118.10
118.40
119.10

Comment: IEC 60076-1 Standard specified a tolerance of 0.5% as allowable deviation.

CALCULATE DESIGNED DEVIATION REMARK


D RATIO
RATIO
IN %
4.41
4.40
-0.13
OK
4.36
4.35
-0.10
OK
4.31
4.30
-0.12
OK
4.26
4.25
-0.13
OK
4.21
4.20
-0.15
OK
4.15
4.15
-0.02
OK
4.10
4.10
-0.09
OK
4.06
4.05
-0.09
OK
4.01
4.00
-0.13
OK
3.93
3.95
0.51
see comment
3.91
3.90
-0.23
OK
3.86
3.85
-0.10
OK
3.81
3.80
-0.18
OK
3.75
3.75
-1.44
see comment
3.71
3.70
-1.52
see comment
3.65
3.65
-0.08
OK
3.60
3.60
-0.09
OK

2 SHORT CIRCUIT TEST OF T1 30MVA POWER TRANSFORMER AT MARYLAND T/S


APPLIED
VOLT
TAP. POS.
A
B
C
a
b
c
1 2.95
2.94
2.95
13.08
13.06
13.09
424
9 3.53
3.55
3.54
14.27
14.22
14.19
423
17 4.13
4.14
4.12
14.98
14.97
14.96
423

REMARK
OK
OK
OK

3 INSULATION RESISTANCE TEST OF T1 30MVA TRANSFORMER AT MARYLAND T/S


INSTRUMENT:- KYORITSU 3125, RANGE: 5KV(INJECTED VOLTAGE)
WINDING TEMP: 48C
OIL TEMP.=48C
(a) IR values Before Maintenance
HV LVHV-LV
DURATION G(G) G(G) (G)
0-30 sec
896.0
926.0
892.0
1 min
2 min
3 min
4 min
5 min
6 min
7 min
8 min
9 min
10 min
P.I

1.0

1.0

1.0

REMARK
OK

(b) IR values After Maintenance


HV LV-G(G)
DURATION G(G)
0-30 sec
872.0
856.0

OK

1 min

OK

2 min

OK

3 min

OK

4 min

OK

5 min

OK

6 min

OK

7 min

OK

8 min

OK

9 min

OK

10 min

COMMENT: TRANSFORMER WAS TESTED STAND ALONE

P.I

HV-LV (G) REMARK


871.0
OK

1.0

1.0

1.0

OK
OK
OK
OK
OK
OK
OK
OK
OK
OK