1/1/2016

Anexamplehowtocalculatevoltagedropandsizeofelectricalcable|EEP

Anexamplehowtocalculatevoltage
dropandsizeofelectricalcable

Get
PDF
TOP

SHARE

An example how to calculate voltage drop and size of electrical cable (photo credit:
12voltplanet.co.uk)

Inputinformation//
Electricaldetails:
Electricalloadof80KW,distancebetweensourceandloadis200meters,system
voltage415Vthreephase,powerfactoris0.8, permissiblevoltagedrop is5%,
demandfactoris1.

Cablelayingdetail:
Cableisdirectedburiedingroundintrenchatthedepthof1meter.Ground
temperatureisapproximate35Deg.Numberofcablepertrenchis1.Numberof
runofcableis1run.

Soildetails:
Thermalresistivityofsoilisnotknown.Natureofsoilisdampsoil.
http://electricalengineeringportal.com/anexamplehowtocalculatevoltagedropandsizeofelectricalcable

1/8

1/1/2016

Anexamplehowtocalculatevoltagedropandsizeofelectricalcable|EEP

Ok,letsdiveintocalculations
ConsumedLoad=TotalLoadDemandFactor:
ConsumedLoadinKW=801=80KW
ConsumedLoadinKVA=KW/P.F.:
ConsumedLoadinKVA=80/0.8=100KVA
FullLoadCurrent=(KVA1000)/(1.732Voltage):
FullLoadCurrent=(1001000)/(1.732415)=139Amp.
CalculatingCorrectionFactorofCablefromfollowingdata:
TemperatureCorrectionFactor(K1)WhenCableisintheAir
TemperatureCorrectionFactorinAir:K1
AmbientTemperature

Insulation
PVC

XLPE/EPR

10

1.22

1.15

15

1.17

1.12

20

1.12

1.08

25

1.06

1.04

35

0.94

0.96

40

0.87

0.91

45

0.79

0.87

50

0.71

0.82

55

0.61

0.76

60

0.5

0.71

65

0.65

70

0.58

75

0.5

80

0.41

GroundTemperatureCorrectionFactor(K2)

http://electricalengineeringportal.com/anexamplehowtocalculatevoltagedropandsizeofelectricalcable

2/8

1/1/2016

Anexamplehowtocalculatevoltagedropandsizeofelectricalcable|EEP

GroundTemperatureCorrectionFactor:K2
GroundTemperature

Insulation
PVC

XLPE/EPR

10

1.1

1.07

15

1.05

1.04

20

0.95

0.96

25

0.89

0.93

35

0.77

0.89

40

0.71

0.85

45

0.63

0.8

50

0.55

0.76

55

0.45

0.71

60

0.65

65

0.6

70

0.53

75

0.46

80

0.38

ThermalResistanceCorrectionFactor(K4)forSoil(WhenThermalResistanceofSoilisknown)
SoilThermalResistivity:2.5KM/W
Resistivity

K3

1.18

1.5

1.1

1.05

2.5

0.96

SoilCorrectionFactor(K4)ofSoil(WhenThermalResistanceofSoilisnotknown)

http://electricalengineeringportal.com/anexamplehowtocalculatevoltagedropandsizeofelectricalcable

3/8

1/1/2016

Anexamplehowtocalculatevoltagedropandsizeofelectricalcable|EEP

NatureofSoil

K3

VeryWetSoil

1.21

WetSoil

1.13

DampSoil

1.05

DrySoil

VeryDrySoil

0.86

CableDepthCorrectionFactor(K5)
LayingDepth(Meter)

RatingFactor

0.5

1.1

0.7

1.05

0.9

1.01

1.2

0.98

1.5

0.96

CableDistancecorrectionFactor(K6)
NoofCircuit

Nil

Cablediameter

0.125m

0.25m

0.5m

0.75

0.8

0.85

0.9

0.9

0.65

0.7

0.75

0.8

0.85

0.6

0.6

0.7

0.75

0.8

0.55

0.55

0.65

0.7

0.8

0.5

0.55

0.6

0.7

0.8

CableGroupingFactor(NoofTrayFactor)(K7)

http://electricalengineeringportal.com/anexamplehowtocalculatevoltagedropandsizeofelectricalcable

4/8

1/1/2016

Anexamplehowtocalculatevoltagedropandsizeofelectricalcable|EEP

NoofCable/Tray

0.84

0.8

0.78

0.77

0.76

0.75

0.8

0.76

0.74

0.73

0.72

0.71

0.78

0.74

0.72

0.71

0.7

0.69

0.77

0.73

0.7

0.69

0.68

0.67

0.75

0.71

0.7

0.68

0.68

0.66

0.74

0.69

0.675

0.66

0.66

0.64

0.73

0.69

0.68

0.67

0.66

0.64

Accordingtoabovedetailcorrectionfactors:
Groundtemperaturecorrectionfactor(K2)=0.89
Soilcorrectionfactor (K4)=1.05
Cabledepthcorrectionfactor(K5)=1.0
Cabledistancecorrectionfactor(K6)=1.0
Totalderatingfactor=k1k2k3K4K5K6K7
Totalderatingfactor=0.93

SelectionofCable
Forselectionofpropercablefollowingconditionsshouldbesatisfied:
1.
2.
3.
4.

Cablederatingampshouldbehigherthanfullloadcurrentofload.
Cablevoltagedropshouldbelessthandefinedvoltagedrop.
No.ofcableruns(Fullloadcurrent/Cablederatingcurrent).
Cableshortcircuitcapacity shouldbehigherthansystemshort
circuitcapacityatthatpoint.

SelectionofcableCase#1
Letsselect3.5core70Sq.mmcableforsinglerun.
Currentcapacityof70Sq.mmcableis:170Amp,
Resistance=0.57/Kmand
Reactance=0.077mho/Km
Totalderatingcurrentof70Sq.mmcable=1700.93=159Amp.
http://electricalengineeringportal.com/anexamplehowtocalculatevoltagedropandsizeofelectricalcable

5/8

1/1/2016

Anexamplehowtocalculatevoltagedropandsizeofelectricalcable|EEP

VoltageDropofCable=
(1.732Current(Rcos+jsin)Cablelength100)/(LinevoltageNoof
run1000)=
(1.732139(0.570.8+0.0770.6)200100)/(41511000)=5.8%
Voltagedropofcable=5.8%

Herevoltagedropfor70Sq.mmCable(5.8%)ishigherthandefine
voltagedrop(5%)soeitherselecthighersizeofcableorincreasenoof
cableruns.
Ifweselect2runs,thanvoltagedropis2.8%whichiswithinlimit
(5%)buttouse2runsofcableof70Sq.mmcableisnot
economical,soitsnecessarytousenexthighersizeofcable.

SelectionofcableCase#2
Letsselect3.5core95Sq.mmcableforsinglerun,shortcircuitcapacity=
8.2KA.
Currentcapacityof95Sq.mmcableis200Amp,
Resistance=0.41/Kmand
Reactance=0.074mho/Km
Totalderatingcurrentof70Sq.mmCable=2000.93=187Amp.
Voltagedropofcable=
(1.732139(0.410.8+0.0740.6)200100)/(41511000)=2.2%

Todecide95Sq.mmcable,cableselectionconditionshouldbe
checked.
1. CablederatingAmp(187Amp)ishigherthanfullloadcurrentof
load(139Amp)=O.K
2. CablevoltageDrop(2.2%)islessthandefinedvoltagedrop(5%)
=O.K
3. Numberofcableruns(1)(139A/187A=0.78)=O.K
4. Cableshortcircuitcapacity(8.2KA)ishigherthansystemshort
circuitcapacityatthatpoint(6.0KA)=O.K

http://electricalengineeringportal.com/anexamplehowtocalculatevoltagedropandsizeofelectricalcable

6/8

1/1/2016

Anexamplehowtocalculatevoltagedropandsizeofelectricalcable|EEP

95Sq.mmcablesatisfiedallthree
condition,soitisadvisabletouse
3.5Core95Sq.mmcable.

RecommendedEEstuff//
Sharewithengineers//

AboutAuthor//

Jignesh Parmar
jiguparmarJigneshParmarhascompletedM.Tech(Power
SystemControl),B.E(Electrical).HeismemberofInstitution
ofEngineers(MIE),India.MembershipNo:M1473586.He
hasmorethan13yearsexperienceinTransmission
DistributionElectricalEnergytheftdetectionElectrical
MaintenanceElectricalProjects(PlanningDesigning
TechnicalReviewcoordinationExecution).HeisPresently
associatewithoneoftheleadingbusinessgroupasaDeputyManagerat
Ahmedabad,India.HehaspublishednumbersofTechnicalArticlesin"Electrical
Mirror","ElectricalIndia","LightingIndia","IndustrialElectrix"(AustralianPower
Publications)Magazines.HeisFreelancerProgrammerofAdvanceExceland
designusefulExcelbaseElectricalProgramsasperIS,NEC,IEC,IEEEcodes.He
isTechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.
HewantstoSharehisexperience&Knowledgeandhelptechnicalenthusiaststo
findsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.

2015EEPElectricalEngineeringPortal.AllRightsReserved|PrivacyPolicy|TermsofService |39queriesin