Professional Documents
Culture Documents
PipeStressAnalysisInformation RevV
PipeStressAnalysisInformation RevV
Changes to: W, p, Eax, Eh, G, Vh/ax, Sigma allow and CTE for Pipe Propts.
Rev
Description
JLK
Issued By
26 June 2013
Date
J. Kendall
B. Hebb
Document No.
Page No.
E-433
Page 1 of 10
E-433
Rev. V
26 June 2013
Table of Contents
1.0
INTRODUCTION
2.0
PIPE PROPERTIES
3.0
FITTINGS
3.1
Elbows
3.2
Reducers
3.3
Tees & Laterals
3.4
Reducing Branches
3.5
Flanges
4
4
5
5
6
6
4.0
7
7
7
7
7
7
5.0
8
8
9
10
Pg. 2
E-433
Rev. V
26 June 2013
1.0
INTRODUCTION
The purpose of this document is to provide piping data and recommendations to carry out
stress analysis of RPS A-150 and P-150 piping in accordance with ASME B31.1 or
B31.3.
2.0
PIPE PROPERTIES
Notes:
1.
2.
3.
Pg. 3
3.0
FITTINGS
3.1
Elbows:
E-433
Rev. V
26 June 2013
Notes:
1.
T includes 0.11 erosion/corrosion liner.
2.
The thicknesses listed above apply to the elbow extrados and are the correct
values to be used in the stress analysis. Intrados thicknesses range from 140% to
200% of the listed values.
3.
For 45 bends, k should be reduced by 30%.
4.
For flanged elbows, reduce k as recommended in ASME B31.
5.
To account for pressure stiffening, divide SIF and k by (Ref. BS7159:1989, Eqn
7.7):
1 + 2.53 x (P / Eh) x (D / (2 x T))2 x (R / T)1/3
where:
P = Design pressure
Eh = Hoop modulus
R = Bend radius
6.
Allowable stresses are based on a maintaining a Design Factor of 6 under
combined loading. Elbows have been analyzed using FEA to verify the required
design factor.
7.
Flexibility factors (k) based on BS7159:1989 Eqn. 7.5 (with minimum value of
1.0).
Pg. 4
3.2
E-433
Rev. V
26 June 2013
Reducers:
The thicknesses of reducers will be no less than those of the pipe. To obtain the thickness
for a specific reducer, average the pipe thicknesses from Section 2.0 for the two sizes of
interest. SIF = 1.3. k = 1.0.
3.3
Pg. 5
3.4
E-433
Rev. V
26 June 2013
Reducing Branches
Reducing branches should be modelled using the appropriate tee thicknesses. The
Flexibility Factor is 1.0 for all sizes and the allowable stresses are the same as for pipe.
SIFs are as follows:
3.5
Flanges
Flanges can be analyzed using SIF = 1.0 and k = 1.0. The allowable stresses are the same
as for pipe. It is recommended that loads on flanges be minimized as much as possible as
the actual stresses in the flanges may be higher than calculated due to less-than-ideal
installation conditions.
Pg. 6
4.0
4.1
General
E-433
Rev. V
26 June 2013
FRP does not yield in the same manner as a ductile material such as steel. It is therefore
not recommended that higher allowable stresses be used for FRP piping when analyzing
displacement-type load cases (eg. thermal load cases). Displacement load cases should
be treated in the same manner as sustained loads such as pressure and weight.
4.2
Load Cases
It is recommended that all operating loads be analyzed as either Operating or Sustained
stress cases. It is not appropriate to use Expansion stress cases for FRP piping, as the
same allowable stress should be used for primary and secondary load cases.
Occasional load cases should be analyzed using Occasional stress cases.
It is recommended that torsional stresses be included in the longitudinal stress
calculation.
4.3
Corrosion Allowance
The piping properties for the total wall, i.e. liner plus structural layers, should be used for
calculation of piping loads, but the piping stresses should be calculated based only on the
structural wall. The liner (or corrosion allowance) should be deducted from the total
wall thickness after the loads have been calculated and prior to calculating piping
stresses.
4.4
Occasional Loads
The allowable stresses listed in Sections 2 and 3 are appropriate for long term loadings,
i.e. sustained loads. When occasional loads such as wind or seismic are combined with
the sustained (operating) loads, it has been RPS practice to increase allowable stresses by
20%.
4.5
Pg. 7
5.0
E-433
Rev. V
26 June 2013
5.1
Column-type Buckling
The restraint of thermal expansion of the pipe will result in compressive loads in the pipe.
It is therefore necessary to ensure that the spacing between guides is adequate to prevent
column-type buckling.
The thermal load is calculated as follows:
Fth
E A T
where:
E = Axial modulus of the pipe
A = Cross-sectional area of pipe
= Coefficient of thermal expansion
T = Change in temperature from installation temp to max operating temp.
The critical
buckling load is calculated as follows:
2
Fcr
Es Is
2
L
where:
If the critical buckling load is less than the thermal load, the spacing between guides
should be reduced. A good rule of thumb is to ensure Fcr is at least 15% higher than Fth.
Pg. 8
5.2
E-433
Rev. V
26 June 2013
Allowable Stress
The allowable stresses listed in Section 3 apply only if the axial stress in the pipe is
tensile. For compressive axial stress, the allowable code stress should be determined as
follows (this will limit the strain to 0.0024):
|0.44
3333|
where:
allow = allowable code stress due to combined loads of pressure, thermal,
weight, etc (kPa)
2 !
2
P = Pressure
TL = liner thickness
TS = structure thickness
Note: The absolute value function in the above formula for the allowable stress is
required if the pipe stress analysis software being used reports the code stress as positive
regardless of whether the axial stress is tensile or compressive.
Pg. 9
5.3
E-433
Rev. V
26 June 2013
$
)
2 !% &' (
4
)
where:
2 !
P = pressure
ID = inside diameter of pipe
TL = liner thickness
TS = structural thickness
At = cross-sectional area of total pipe wall
ha = Poisson ratio (axial strain due to hoop load)
Ea = Axial Modulus
Eh = Hoop Modulus
Pg. 10