McQuay Hellas ..
Refrigeration Compressors
Centrifugal Chillers are mainly water cooled chillers
Refrigeration Compressors
There are two basic different compression
technology:
Refrigeration Compressors
REFRIGERATION CHILLER COMPRESSOR
POSITIVE DISPLACEMENT
RECIPROCATING (Pistons)
ROTARY
SCREW
SCROLL
DYNAMIC
CENTRIFUGALS
COMPRESSION
DISCHARGE
Full Load
Impeller
Impeller
Impeller
Reduced discharge
area
Capacity Control
Capacity Control
Hot Gas Bypass
Hot gas bypass is a means of
recirculating hot discharge refrigerant
back into the evaporator applied at
strongly unloaded conditions (below
20%). A disadvantage is that the work
of compression on the recirculated
refrigerant does not generate any
refrigeration effect.
Careful selection of equipment size and using compressor that unload to a
very low percentage of full load capacity (10%), can avoid the need for hot
gas bypass in most HVAC applications.
Capacity Control
Inlet Guide Vanes
Inlet guide vanes are used to control
the capacity of the compressor. As the
inlet guide vanes start to close, they
change the gas entry angle to the
impeller and reduce gas flow and
compressor capacity.
Capacity Control
Variable Frequency Drive
2000 kW Unit
ARI partial load
conditions
Constant
Speed
VFD
6
4
2
0
100
90
80
70
60
50
40
% of cooling capacity
30
20
10
VFD twin
10
Standard twin
IPLV
Standard single
0
S.C
T.C
S.C+VFD
UNIT TYPE
T.C+VFD
0,12
0,45
0,42
0,01
IPLV1 IPLV2
0,46
1,10
2,70
5,40
2,60
3,61
0,05
0,06
5,80
10,17
KWh 1
43342
205875
279830
11438
540485
KWh 2
17960,7
102938
201087
9150
331135
h
/kWh
kW
kWh
Payback period
years
VFD
Standard
1800
0,08715
3050
10,17
331.135
28.858
1800
0,08715
3050
5,8
540.485
47.103
18.245
200.000
150.000
50.000
2,74
50.000
40.000
30.000
Accumulative savings
20.000
10.000
50.000
50.000
50.000
Accumulative savings
18.245
36.490
54.735
=
Improved Performances and reliability !!
END OF PRESENTATION