LV circuit breakers and


switch-disconnectors
Compact Merlin Gerin
80 to 3200 A
S
mpact N
New Co

Building a New Electric World

colibris
046751
045345

Compact NS 80 A

053100

Compact NS 100 to 250 A

Things

E45151

Compact NS 400 to 630 A

will
the

never be
same
New Compact NS,
setting the standard, once again...

E45178

Compact NS 630 to 1600 A

The launch of Merlin Gerin Compact NS in 1994


revolutionised the world of moulded-case circuit breakers.
Innovative, flexible and attractive, Compact NS rapidly set
the standard in its field.
Today, Schneider Electric continues to innovate, extending
the Compact NS range to high power ratings to offer
a comprehensive and consistent range from 80 to 3200 A.
Equipped with the new generation of Micrologic control
units, Compact NS630b to 3200 circuit breakers integrate
electrical measurement and analysis functions.
The communications option makes it possible to control
power consumption, simplify maintenance and improve
operating comfort.
A wide range of optimised auxiliaries and accessories is
also available to meet the needs of even more applications.

Compact NS, simply a step ahead


Compact NS 1600 to 3200 A

Compact NS,
even more applications...

E20999

Protection of LV distribution systems

push
to
trip

E26988

Protection of motor feeders

p. 14
Protection for:
b distribution systems supplied by transformers
b distribution systems supplied by engine generator sets
b long cables in IT and TN systems.
Installation :
b in power switchboards
b on DIN rails (see page 42)
Special applications:
b single-phase and two-phase systems (see page 34)
b 1000 V distribution systems (see page 36)
b 400 Hz distribution systems (see page 38)
b DC systems (see page 40).
All circuit breakers in the Compact NS range offer positive contact indication
and are suitable for isolation in compliance with standards IEC 60947-1 and 2.

p. 44
When combined with a motor starter, Compact NS circuit breakers protect the
cables and the starter against short-circuits. Equipped with an electronic trip unit,
Compact NS circuit breakers also protect the cables, starter and motor against
overloads.
The exceptional current-limiting capacity of Compact NS circuit breakers
automatically ensures type-2 coordination with the motor starter, in compliance with
standard IEC 60947-4-1.

E44356

Protection of machines

p. 52
The different circuit-breaker versions in the Compact NS range are designed to
meet the specific requirements of machines:
b compliance with international standards IEC 60947-2 and UL 508 / CSA 22-2 No. 14
b compliance with U.S. standard UL 489
b protection against overloads and short-circuits
b positive contact indication
b installation in universal and functional enclosures.

E44357

Earth-leakage protection

M
G

p. 56
Additional earth-leakage protection protects life and property against the risks
of faulty insulation in the installation. Depending on the circuit breaker,
earth-leakage protection is provided by:
b adding a Vigi module to the circuit breaker
b using a specific Micrologic control unit
b using a Vigirex relay and separate toroids.

Schneider Electric

E21272

Switch-disconnectors

p. 60
A switch-disconnector version of Compact NS circuit breakers exists for circuit
control and isolation.
All the additional functions may be combined with the basic switch-disconnector
function, including:
b earth-leakage protection
b motor mechanism
b ammeter, etc.
For information on other switch-disconnector ranges, see the Interpact (offering
positive contact indication and visible break) and Fupact (fuse switch) catalogues.

push
to
trip

p. xx

E56631

Service connection

Compact NS service-connection circuit breakers are specially designed for the


service-connection function:
b lead seals and locking systems
b tripping curves certified by utilities
b fast overload curves to limit the power supplied, etc.
Interpact INV switch-disconnectors offering visible break (see the corresponding
catalogue) can be combined with Compact NS circuit breakers to constitute
the various types of service connections and meet the needs of all installation
configurations.

5...8

push
to
trip

STR
90 %Ir
105

22 DE

50/60Hz

test

Im
.9
.95
.98
.63

push
to
trip

STR
90 %Ir
105

alarm

Ir
.85
.8
.7

3
8
2
1.5

Ir Im

10
xIr

xIn

22 DE

50/60Hz

test

Im
.9
.95
.98
.63

alarm

Ir
.85
.8
.7

3
8
2
1.5

Ir Im

10
xIr

xIn

E32454

Source-changeover systems
N

p. 68 (see also the "Source-changeover systems" catalogue)


To ensure a continuous supply of power, some electrical installations are
connected to two power sources:
b a normal source
b a replacement source on hand to supply the installation when the normal source
is not available.
A mechanical and/or electrical interlocking system between two Interpact, Compact
or Masterpact devices avoids all risk of parallel connection of the sources during
switching.
A source-changeover system can be:
b manual with mechanical interlocking between the devices
b remote operated when an electrical interlocking function in added
b automatic when a controller is added to manage switching from one source to the
other on the basis of external parameters.

UL 489 applications
Compact NS circuit breakers also meet the requirements of applications governed
by standard UL 489 (see the corresponding catalogue).

Schneider Electric

...a solution for all installation


configurations

E27836

Ui750V Uimp8kV

Icu
(kA)

220/240
380/415
440
500
525
660/690
250

Breaking capacity
Icu at 415 V

The rating plates on the front


panel of each device indicate
the breaking capacity
(N, H or L).

compact

NS 250 N
Ue
(V)

Compact NS100 to 630


E58549

The Compact NS range now covers all


ratings from 80 to 3200 A:
b Compact NS80 to 1600 A, fixed,
withdrawable, front or rear connections,
manual or electrical operation.
b Compact NS1600 to 3200 A, fixed, front
connection, manual operation.

85
36
35
30
22
8
50

Ics = 100 % Icu

IEC 947-2

cat A

UTE VDE BS CEI UNE NEMA

E27837

N: standard breaking
capacity

compact

NS 250 H
Ui750V Uimp8kV

Ue
(V)

Icu
(kA)

220/240
380/415
440
500
525
660/690
250

100
70
65
50
35
10
85

Ics = 100 % Icu

Compact NS630b to 1600

IEC 947-2

cat A

UTE VDE BS CEI UNE NEMA

Breaking capacity
Icu at 415 V

E27838

E58550

H: high breaking capacity

compact

NS 250 L
Ui750V Uimp8kV

Ue
(V)

Icu
(kA)

220/240
380/415
440
500
525
660/690
250

150
150
130
70
50
20
100

Ics = 100 % Icu

IEC 947-2

cat A

UTE VDE BS CEI UNE NEMA

L: very high breaking


capacity

E22051

Total discrimination
as standard
Compact NS1600b to 3200

E58551

Breaking capacity
Icu at 415 V

push
to
trip

Discrimination between Compact NS circuit breakers


is total for all types of faults (overloads, high or low shortcircuits) and whatever the type of trip unit used with
the circuit breaker.

Schneider Electric

047313

Compact NS250 with motor


mechanism

Compact NS400 with


electronic trip unit

Plug-in Compact NS250


on base

041879

053100

041625

Manual Compact NS250


with thermal-magnetic
trip unit

E45151

E45163

Withdrawable Compact
NS250 on chassis

Electrically operated Compact NS800

E45178

Manually operated Compact NS800

Compact NS2000 (manually operated only)


Schneider Electric

...simplified installation

046751

045345

053100

5 frame sizes from 80 to 3200 A

80 A

100 to 250 A

400 to 630 A

E45178

E45151

Compact circuit breakers make it possible


to standardise switchboards for faster
installation and fewer errors.
All type L Compact circuit breakers
(150 kA) are housed in the same case
as the type N and type H models
with the same ratings.
Compact circuit breakers up to 1600 A
can be easily installed side-by-side
in a minimum amount of space.

630 to 1600 A

1600 to 3200 A

Numerous connection possibilities, including front and


rear connections for bare cables, cable lugs or bars,
as well as plug-in or withdrawable versions, are
available using accessories that can be rapidly added
to the circuit breaker.

041650

Many connection
possibilities

Connection parts
for Compact NS

Plug-in and withdrawable versions for:


b fast removal or insertion of the circuit breaker
without exposure to live parts
b standby outgoing circuits ready for wiring and circuit
breaker installation at a later date
b visible break possibility.

042788

Plug-in and withdrawable


versions

Compact NS circuit breakers up to 630 A can be


installed in tap-off units of the Telemecanique Canalis
range of busbar trunking.

E32455

Busways

Schneider Electric

...optimised protection
and accurate measurements
Compact NS100 to 630

Each Compact NS circuit breaker provides


different types of protection, depending on
the trip unit or control unit selected.
Additional measurement and indication
functions are available:
b on Compact NS100 to 630, by adding an
electrical auxiliary to the circuit breaker
b on Compact NS630b to 3200, depending
on the Micrologic control unit selected.

041638

041625

048287

On Compact NS100 to NS250 circuit breakers, the thermal-magnetic and


electronic trip units are interchangeable and may be rapidly fitted to the circuit
breakers. It is therefore easy to change the protection of a given circuit following a
modification in an installation.
On Compact NS400 and NS630 circuit breakers, the electronic trip units are
interchangeable, plug-in modules. The STR53UE trip unit offers a large number
of protection settings:
standard:
b specific indication of the different types of faults (overloads, short-circuits, etc.)
optional:
b built-in ammeter
b earth-fault protection
b communication: transmission of all information concerning circuit-breaker
operation to an electrical distribution control, monitoring and automation system via
Digipact modules (see page 72).

TM thermal-magnetic
trip unit

Compact NS250

041641

045212

Voltage presence indication


module

STR electronic trip unit

Ammeter module

Compact NS630b to 3200

Micrologic 2.0, 5.0


Compact NS1600

Schneider Electric

056480

056479

E45151

Compact NS630b to 3200 circuit breakers are equipped with Micrologic control
units that are interchangeable on site.
Micrologic 2.0 and 2.0 A control units offer standard protection. Micrologic 5.0 and
5.0 A control units offer selective protection that can be completed by earth-fault
protection on Micrologic 6.0 A and earth-leakage protection on Micrologic 7.0 A
control units.
The ammeter version of Micrologic control units provides current measurements.
These units are equipped with a digital display and bargraph, used in conjunction
with simple navigation buttons. Access to the desired parameters and settings
is direct and navigation between screens is intuitive. Settings are greatly simplified
by direct display on the screen.

Micrologic 2.0 A,
5.0 A, 6.0 A, 7.0 A

...an optimised range

16
15

12

E24603

A complete system of add-on modules for


Compact NS:
Fewer catalogue numbers means immediate
availability of parts for all solutions.
Trip units, control units, auxiliaries and installation
and connection accessories are the same for a given
frame size and often for a number of frame sizes (e.g.
auxiliary contacts, MN and MX voltage releases, etc.):
b Compact NS800 to NSA160
b Compact NS100 to NS250
b Compact NS400 to NS630
b Compact NS630b to 1600
b Compact 1600b to 3200.

1
8

11
9
10

13

2
2
4
3
6
14

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Breaking unit
Trip units or control units
Vigi earth-leakage protection module
Insulation monitoring module
Voltage presence indicator
Ammeter module
MN and MX voltage releases
Multifunction auxiliary contact
Direct rotary handle
Extended rotary handle
Motor mechanism
Plug-in base
Connection of auxiliary circuits to plug-in base or withdrawable chassis
Connection accessories
Short terminal shields
Long terminal shields

Schneider Electric

...modern products

Equipped with a communications option, Compact NS


circuit breakers fit perfectly in the Digipact installationmanagement system or other supervision systems.
Via a PC or a PLC, the operator can:
b display the status of each circuit breaker and its
settings
b control the circuit breakers
b display faults
b access measurements supplied by the electronic
control units.

E37615

Open communication ...


PM150 power
management

meter

circuit breaker

or other power
actuator

ModBus / JBus

CLS150 indication

and local-control
module
Digipact internal bus

Multi 9 control
DC150 data concentrator

device and ATB 1S


interface

UA150 automatic

source-changeover
controller

RHU residualcurrent relay with


separate toroid
RMH earthleakage monitor

Digipact installation-management system

oiseaux

... and protection of the environment


Schneider Electric fully takes into account environmental requirements, starting
right from the design stage of products through to the end of their service life:
b the materials used for Compact NS are not dangerous for the environment
b the production facilities are non-polluting in compliance with the ISO 14001
standard
b filtered breaking for the high ratings eliminates pollution in the switchboard
b the energy dissipated per pole is low, making energy losses insignificant
b the materials are marked to facilitate sorting for recycling at the end of product
service life.

Schneider Electric

10

Schneider Electric

Compact NS

Selection of a Compact NS circuit breaker


depends on the application requiring protection
(distribution systems, motor feeders, etc.) and on
the prescribed installation conditions (see section
Installation, connection and accessories).

Functions and characteristics

Presentation

General characteristics
Protection of distribution systems

12
14

Overview of solutions
Compact NB circuit breakers up to 600 A
Compact NS circuit breakers up to 630 A
Compact NS circuit breakers from 630 up to 3200 A
TM and STR trip units for Compact NS100 to 250
MP and STR trip units for Compact NS400 to 630
Micrologic control units for Compact NS630b to 3200
Special cases:
b single-phase and two-phase systems
b 1000 V systems
b 400 Hz applications
b circuit breaker selection for DC applications
b incoming circuit breakers in final distribution NSA160

14
16
18
20
22
24
28
34
36
38
40
42

Motor protection

44

Overview of solutions
Compact NS80H-MA
NS100 to 630 circuit breakers with MA magnetic trip units
NS100 to 250 circuit breakers with STR22ME electronic trip unit
NS400 to 630 circuit breakers with STR43ME electronic trip unit

44
46
47
48
50

Protection of industrial control panels

52

Overview of solutions
Circuit breaker NSC100N
Trip units, auxiliaries, installation enclosures
UL508 / CSA 22-2 no. 14 marking

52
53
54
55

Earth-leakage protection

56

Overview of solutions
Add-on Vigi module (Vigicompact) for Compact NS100 to 630

56
57

Control and isolation

58

Overview of solutions
Compact NSA125NA and NSA160NA switch-disconnectors
Compact NSC100 and NS100 to 630NA switch-disconnectors
Compact NS630bNA to 1600NA switch-disconnectors
Compact NS1600b to 3200NA switch-disconnectors

58
60
62
64
66

Source-changeover systems

68

Presentation
Manual source-changeover systems
Remote-operated systems
Controllers

68
69
70
71

Communication

72

Compact NS100 to 630


COM option in Compact
Compact in a communication network

Electrical and mechanical accessories

72
74, 78
76

80

Compact NB50 and 100


80, 82
Compact NB250 to 600
81, 84
Compact NS80H-MA, NSC100N
88, 90
Compact NSA160
89, 90
Compact NS100 to 630 (fixed version)
94,96
Compact NS100 to 630 (plug-in and withdrawable version) 95, 96
Compact NS630b to 1600 (fixed version)
114, 116
Compact NS630b to 1600 (withdrawable version)
115, 116
Compact NS1600b to 3200 (fixed version)
134

Test equipment
Display modules
Installation recommendations
Dimensions, volumes
Connection
Electrical diagrams
Additional characteristics
Catalogue numbers
Schneider Electric

139
140
143
165
205
221
251
267
11

General characteristics

E18567

Functions and
characteristics

Compliance with standards


Compact NS circuit breakers and auxiliaries comply with the following:
b international recommendations:
v IEC 60947-1 - general rules
v IEC 60947-2 - circuit breakers
v IEC 60947-3 - switches, disconnectors, switch-disconnectors, etc.
v IEC 60947-4 - contactors and motor starters
v IEC 60947-5.1 and following - control circuit devices and switching elements;
automatic control components
b European (EN 60947-1 and EN 60947-2) and the corresponding national
standards:
v France NF
v Germany VDE
v U.K. BS
v Australia AS
v Italy CEI
b the specifications of the marine classification companies (Veritas, Lloyds
Register of Shipping, Det Norske Veritas, etc.)
b French standard NF C 79-130 and the recommendations issued by the CNOMO
organisation for the protection of machine tools.
For U.S. UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please
consult us.

compact
NS160 H
Ui 750V. Uimp 8kV.
Ue
(V)
220/240
380/415
440
500/525
660/690
250

Icu
(kA)
100
70
65
50
10
85

Ics = 100% Icu


cat A
IEC 947.2
UTE VDE BS CEI UNE NEMA

Standardised characteristics indicated on the rating plate:


Ui:
rated insulation voltage
Uimp:
rated impulse withstand voltage
Icu:
ultimate breaking capacity, for various values
of the rated operational voltage Ue
cat:
utilisation category
Icw:
rated short-time withstand current
Ics:
service breaking capacity
suitable for isolation

Pollution degree
Compact NS circuit breakers are certified for operation in pollution-degree III
environments as defined by IEC standard 60947 (industrial environments).

Tropicalisation
Compact NS circuit breakers have successfully passed the tests prescribed by the
following standards for extreme atmospheric conditions:
b IEC 68-2-1 - dry cold (-55 C)
b IEC 68-2-2 - dry heat (+85 C)
b IEC 68-2-30 - damp heat (95 % relative humidity at 55 C)
b IEC 68-2-52 - salt mist (severity level 2).

Environmental protection
Compact NS circuit breakers take into account important concerns for
environmental protection. Most components are recyclable and the parts of
Compact NS630b to NS3200 circuit breakers are marked as specified in applicable
standards.

Ambient temperature

b Compact NS circuit breakers may be used between -25 C and +70 C.


For temperatures higher than 40 C (65 C for circuit breakers used to protect
motor feeders), devices must be derated as indicated in the documentation.
b circuit-breakers should be put into service under normal ambient operatingtemperature conditions. Exceptionally, the circuit breaker may be put into service
when the ambient temperature is between -35 C and -25 C.
b the permissible storage-temperature range for Compact NS circuit breakers in
the original packing is -50 C (1) to +85 C.

Discrimination

E22037

As standard, the Compact NS range ensures discrimination between two circuit


breakers positioned in series in an installation.

CB1

CB2

(1) -40 C for Micrologic control units with an LCD screen.

12

Schneider Electric

044 334

Positive contact indication

E18569

All Compact NS circuit breakers are suitable for isolation as defined in IEC
standard 60947-2:
b the isolation position corresponds to the O (OFF) position
b the operating handle cannot indicate the OFF position unless the contacts are
effectively open
b padlocks may not be installed unless the contacts are open.
Installation of a rotary handle or a motor mechanism does not alter the reliability
of the position-indication system.
The isolation function is certified by tests guaranteeing:
b the mechanical reliability of the position indication system
b the absence of leakage currents
b overvoltage withstand capacity between upstream and downstream connections.

Installation in class II switchboards


All Compact NS circuit breakers are class II front face devices. They may be
installed through the door of class II switchboards (as per IEC standard 60664),
without downgrading switchboard insulation. Installation requires no special
operations, even when the circuit breaker is equipped with a rotary handle or a
motor mechanism.

Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102
(IK degree of protection against external mechanical impacts).
E18570

Bare circuit breaker with terminal shields


With toggle

IP40

IK07

With direct rotary handle


standard / VDE

IP40

IK07

With toggle

IP40

IK07

With direct rotary handle


standard / VDE
MCC
CNOMO

IP40

IK07

IP435
IP547

With extended rotary handle

IP55

IK08

With motor mechanism

IP40

IK07

E28439

push
to
trip

ON
I

push
to
trip

O
OFF

E21277

Circuit breaker installed in a switchboard

E28440

push
to
trip

ON
I

push
to
trip

E28441

O
OFF

ON
I

push
to
trip

ON
I

O
OFF

E28442

OFF

push
to
trip

1
manu

/auto

I
push

push

Schneider Electric

ON

OFF

13

Protection of distribution systems


Overview of solutions

E43842

Protection of distribution systems means


protection of:
b systems supplied by a transformer
b systems supplied by an engine
generator set
b long cables in IT and TN systems.

E58563

Functions and
characteristics

E20999

Power distribution
Selection of circuit breakers up to 630 A

page 18

Rated current (A)


push
to
trip

12.5 12.5
160
250

60
400

250
630

NS125E NS100

NS160

NS250

NS400

NS630

36
70
150

36
70
150

45
70
150

45
70
150

045345

053100

Compact

12.5 12.5
125
100

Breaking capacity
(kA rms)
380/415 V

E
N
H
L

16
25
70
150

Accompanying trip units up to 630 A

page 22

Interchangeable thermal-magnetic and electronic trip units for NS100 to 630 and built-in
thermal-magnetic trip unit for Compact NS125E

Selection of circuit breakers from 630 to 3200 A page 20


Rated current (A)
Compact

250 320
630
800

400
1000

500
1250

640
1600

NS630b NS800

NS1000

NS1250

NS1600

50
70
150

50
70
150

50
70
-

50
70
-

E45151

E43843

Special case of DC systems:


TM thermal-magnetic trip units for Compact NS100
to 250 and MP magnetic trip units for Compact
NS400 and 630 may be used to protect DC
distribution systems.

Breaking capacity
(kA rms)
380/415 V

N
H
L

Rated current (A)

640 800 ...


1600
2000

1000 1250
2500
3200

NS1600b NS2000

NS2500

70
85

70
85

NS3200

E45178

Compact

50
70
150

Breaking capacity
(kA rms)
380/415 V

N
H

70
85

Accompanying control units up to 3200 A

page 28

Micrologic electronic control units may be used on all Compact NS630b to NS3200 circuit
breakers and can be changed on site.

14

Schneider Electric

Power distribution (cont.)


Single-phase or two-phase distribution

page 34

Rated current (A)

160 250

125 160

NS100 1P/2P

NS160 1P/2P
NS250 1P
Built-in thermal-magnetic
trip units

Breaking capacity
(kA rms) 220 V

86101

86099

Compact

16 100

1P
25
40

N
H

2P
85
100

1P
25
40

2P
85
100

1000 V distribution

1P
25
-

page 36

Rated current (A)

60 400
NS400 1000V
Breaking capacity:
10 kA rms at 1000 V

053182

Compact

STR23SP electronic trip unit


specially designed for
1000 V applications

E21000

Incoming circuit breakers in final distribution


Rated current (A)

NSA160
048016

Compact installation on
a DIN rail

page 42

16 160
Breaking capacity
(kA rms) 380/415 V:
E : 16 kA
N : 30 kA
Built-in trip unit

Schneider Electric

15

045345

Functions and
characteristics

Protection of distribution systems


Compact NS circuit breakers
up to 630 A
Compact circuit breakers
Number of poles
Control

manual

Connections

electric
fixed

toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
front connection
rear connection

plug-in (on base)


withdrawable (on chassis)

048286

Compact NS250H

Electrical characteristics as per IEC 60947-2 and EN 60947-2


Rated current (A)
In
40 C
65 C
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC
Type of circuit breaker
Ultimate breaking capacity (kA rms)

lcu

AC
50/60 Hz

220/240 V
380/415 V
440 V
500 V
525 V
660/690 V
250 V (1P)
500 V (2P in series)

DC
Service breaking capacity
Suitability for isolation
Utilisation category
Durability (C-O cycles)

lcs

mechanical
electrical

440 V

Electrical characteristics as per NEMA AB1


Breaking capacity (kA)

Compact NS630L

Earth-fault protection
Zone selective interlocking
Add-on earth-leakage protection

In/2
In

240 V
480 V
600 V

Electrical characteristics as per UL508


Breaking capacity (kA)

Protection
Trip units
Overload protection
Short-circuit protection

% Icu

240 V
480 V
600 V

long time
Ir (In x )
short time
lsd (Ir x )
instantaneous Ii (In x )
lg (In x )
ZSI
add-on Vigi module
combination with Vigirex relay

Current measurements
Additional measurement, indication and control auxiliaries
Indication contacts
MX shunt and MN undervoltage releases
Voltage-presence indicator
Current-transformer module and ammeter module
Insulation-monitoring module
Remote communication by bus
Device-status indication
Device remote operation
Transmission of settings
Indication and identification of protection devices and alarms
Transmission of measured current values
Installation
Accessories

(1) 2P in 3P case for type N only


(2) specific trip units are available for operational
voltages > 525 V
(3) operational voltage y 500 V.

18

Dimensions (mm) W x H x D
Weight (kg)

terminal extensions and spreaders


terminal shields and interphase barriers
escutcheons
fixed, front connections
2-3P / 4P
fixed, front connections
3P / 4P

Source changeover system (see section on source changeover systems)


Manual, remote-operated and automatic source changeover systems

Schneider Electric

NS125E

NS100

NS160

NS250

NS400

NS630

3, 4
b
b
b
-

2 (1), 3, 4
b
b
b
b
b
b
b
b
b

2 (1), 3, 4
b
b
b
b
b
b
b
b
b

2 (1), 3, 4
b
b
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b
b
b

125
750
8
500
-

100
100
750
8
690
500

160
150
750
8
690
500

250
220
750
8
690
500

400
320
750
8
690
500

630
500
750
8
690
500

E
25
16/10
10
6
-

H
100
70
65
50
35
10
85
85

L
150
150
130
100
100
75
100
100

N
85
36
35
30
22
8
50
50
100 %
b
A
40000
40000
20000

H
100
70
65
50
35
10
85
85

L
150
150
130
70
50
20
100
100

N
85
36
35
30
22
8
50
50
100 %
b
A
20000
20000
10000

H
100
70
65
50
35
10
85
85

L
150
150
130
70
50
20
100
100

N
85
45
42
30
22
10 (2)
100 %
b
A
15000
12000
6000

H
100
70
65
50
35
20 (2)
85
85

L
150
150
130
100
100
75 (2)
-

N
H
85
100
45
70
42
65
30
50
22
35
10 (2) 20 (2)
85
85
100 % (3)
b
A
15000
8000
4000

L
150
150
130
70
50
35 (2)
-

50 %
b
A
10000
6000
6000

N
85
25
25
18
18
8
50
50
100 %
b
A
50000
50000
30000

E
5
5
-

N
85
25
10

H
100
65
35

L
200
130
50

N
85
35
20

H
100
65
35

L
200
130
50

N
85
35
20

H
100
65
35

L
200
130
50

N
85
42
20

H
100
65
35

L
200
130
50

N
85
42
20

H
100
65
35

L
200
130
50

E
-

N
85
25
10

H
85
65
10

L
-

N
85
35
10

H
85
65
10

L
-

N
85
35
18

H
85
65
18

L
-

N
-

H
-

L
-

N
-

H
-

L
-

non interchangeable
12.5 125 (A)
b
b
-

TM (thermal-magnetic)
b
b
b
b
-

b
b
-

b
b
b
b
b

b
b
-

b
b
b
105 x 161 x 86
1.7 / 2.3

b
b
b
105 x 161 x 86 / 140 x 161 x 86
1.6 to 1.9 / 2.1 to 2.3

b
b
b
140 x 255 x 110 / 185 x 255 x 110
6.0 / 7.8

Schneider Electric

STR22 (electronic)
b
b
b
b
b
-

STR23 (electronic)
b
b
b
b
b
-

STR53 (electronic)
b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
-

b
b
-

b
b
b
b
b

19

Functions and
characteristics

Protection of distribution systems


Compact NS circuit breakers
from 630 up to 3200 A

E45151

Compact circuit breakers


Number of poles
Control

manual

toggle
direct or extended rotary handle

electric
Type of circuit breaker
Connections

fixed
withdrawable (on chassis)

Compact NS800H

front connection
rear connection
front connection
rear connection

Electrical characteristics as per IEC 60947-2 and EN 60947-2


Rated current (A)
In
50 C
65 C (1)
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage (kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC
lcu

AC
50/60 Hz

220/240 V
380/415 V
440 V
500/525 V
660/690 V
250 V
500 V

E45178

Type of circuit breaker


Ultimate breaking capacity (kA rms)

DC
Service breaking capacity (kA rms)
Short-time withstand current (kA rms)
V AC 50/60 Hz
V AC 50/60 Hz
Integrated instantaneous protection
Suitability for isolation
Utilisation category
Durability (C-O cycles)
mechanical
electrical

lcs
lcw

Value or % Icu
0.5 s
1s
3s
kA peak 10 %

440 V

In/2
In
In/2
In

Compact NS2000H
690 V

Compact NS1600bN
Pollution degree
Electrical characteristics as per Nema AB1
Breaking capacity at 60 Hz (kA)

Protection and measurements


Interchangeable control units
Overload protection
Short-circuit protection
Earth-fault protection
Residual earth-leakage protection
Zone selective interlocking
Protection of the fourth pole
Current measurements
Additional indication and control auxiliaries
Indication contacts
Voltage releases

240 V
480 V
600 V

long time
Ir (In x )
short time
Isd (Ir x )
instantaneous Ii (In x )
lg (In x )
In
ZSI

MX shunt release
MN undervoltage release

Remote communication by bus


Device-status indication
Device remote operation
Transmission of settings
Indication and identification of protection devices and alarms
Transmission of measured current values
Installation
Accessories

(1) 65 C with vertical connections. See the temperature


derating tables for other types of connections.
(2) Ics : 100 % Icu for breaking capacity 440V/500V/660V
Ics : 75 % Icu for breaking capacity 220V/380V.

20

terminal extensions and spreaders


terminal shields and interphase barriers
escutcheons
Dimensions fixed devices, front connections (mm)
3P
HxWxD
4P
Weight fixed devices, front connections (kg)
3P
4P
Source changeover system (see section on "source changeover systems")
Manual, remote-operated and automatic source changeover systems

Schneider Electric

NS630b NS800

NS1000

3, 4
b
b
b
N
b
b
b
b

H
b
b
b
b

L
b
b
b
b

630
630
750
8
690
500

800
800

N
H
50
70
50
70
50
65
40
50
30
42
75 % 50 %
25
25
17
17
55
b
B
B
10000
6000
5000
4000
2000
III

L
150
150
130
100
25
100 %
10
7
-

N
50
35
25

L
125
100
-

H
65
50
50

1000
1000

3, 4
b
-

Micrologic 5.0
b
b
b
b
b
b
b
b
b
b
b
b
b

H
b
b
b
b

1250
1250
750
8
690
500

N
b
1600
1510

N
50
50
50
40
30
75 %
25
17
55
b
B
10000
5000
4000
3000
2000
III

H
70
70
65
50
42
50 %
25
17
-

N
50
35
25

H
65
50
50

Micrologic 2.0 A
b
b
b
b
b
b
b

b
b
b
b
b
-

NS1600b NS2000 NS2500 NS3200

3, 4
b
b
b
N
b
b
b
b

Micrologic 2.0
b
b
b
b
b
b
b
b
b
b
b
b

NS1250 NS1600

B
5000
2000
2000
1000

Micrologic 5.0 A

H
b
-

1600
1550
750
8
690
500

2000
1900

N
85
70
65
65
65
100 % (2)
32
130
b
B
5000
3000
2000
2000
1000
III

H
125
85
85
75 %
32
130

N
85
65
50

H
125
85
-

2500
2500

3200
2970

Micrologic 6.0 A Micrologic 7.0 A

b
b
b
b
b
-

b
b
b
b
b

b
b
b
327 x 210 x 147
327 x 280 x 147
14
18

b
b
b
b
b

b
b
b
b

b
b
b
b
b
350 x 420 x 160
350 x 535 x 160
24
36

Schneider Electric

21

Functions and
characteristics

13
E23160

Compact NS100 to 250 circuit breakers,


types N, H and L, may be equipped with
either a TM thermal-magnetic trip unit
or an STR22 electronic trip unit.
A mechanical mismatch-protection system
avoids breaker and trip unit mismatches.

Protection of distribution systems


TM and STR trip units
for Compact NS100 to 250
16

25

40

63

80

100

125

200

250

TM-D
STR22SE
TM-G
STR22GE
TM-D
TM-G

Standard protection

Protection of systems
supplied by generators.
Protection of long
cables

Protection of DC
distribution systems

1
E19528

E58564

TM thermal-magnetic trip units


t

Ir

Im

10
9

.8

.9

1
2

Ir

Im

Ir

x 250A

Im

overload protection threshold


short-circuit protection pick-up

TM thermal-magnetic trip units


Ratings (A)
Circuit breaker

6
8

x 250A
0

TM 250 D
250A / 40C

In at 40 C
Compact NS125 E
Compact NS100
Compact NS160
Compact NS250

Protection
The protection functions may be set using the adjustment dials.
Overload protection
Thermal protection with an adjustable threshold.
Short-circuit protection
Magnetic protection with a fixed or adjustable pick-up, depending on the rating.
Protection of the fourth pole
On four-pole circuit breakers, the trip units can be of the:
4P 3d type (neutral unprotected),
4P 3d + N/2 type (neutral protection at 0.5 In) or 4P 4d type (neutral protection at In).

TM16D to 250D
16
b
b
b
b

25
b
b
b
b

32
b
b
b
b

40
b
b
b
b

50
b
b
b
b

TM16G to 63G
63
b
b
b
b

80
b
b
b
b

100
b
b
b
b

125
b
b
b

160
b
b

200
b

250
b

16
b
b
b
b

25
b
b
b
b

40
b
b
b
b

63
b
b
b
b

Overload protection (thermal)


Current setting (A)

Ir

adjustable from 0.8 to 1 x In

adjustable from 0.8 to 1 x In

Short-circuit protection (magnetic)


Current setting (A)

Im
Compact NS100
Compact NS160/250

fixed
adjustable fixed
190 300 400 500 500 500 640 800
63 80
190 300 400 500 500 500 1000 1250 1250 1250 5 to 10 x In 63 80

80
80

125
125

Protection of the fourth pole


Neutral unprotected
Neutral protection at 0.5 In
Neutral protection at In

22

4P 3d
4P 3d + N/2
4P 4d

no protection

no protection
56

1 x Ir

56

63

0.5 x Ir
1 x Ir

Schneider Electric

E24096

In=100A

STR 22 SE

.8

.9

1
2
3
4
5
6
7

Ir Im

Im

Im

.93
.95

.85

.98

.5
Ir

%Ir
90
105

.88

.9
1

.63

alarm

Ir

Io

.7

E58711

.8

10

x Io

x In

test

x Ir

long-time threshold (overload protection)


long-time tripping delay
short-time pick-up (short-circuit protection)
short-time tripping delay
instantaneous pick-up (short-circuit protection)
test connector
percent load indication

4P 4d

Protection
The protection functions may be set using the adjustment dials.
Overload protection
True rms long-time protection with an adjustable threshold.
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with an adjustable pick-up and fixed tripping delay
b instantaneous protection with fixed pick-up.
Protection of the fourth pole
On four-pole circuit breakers, neutral protection is set using a three-position switch
to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d
(neutral protection at In).

Indications
A LED on the front indicates the percent load:
b ON - load is > 90 % of Ir setting
b flashing - load is > 105 % of Ir setting.

Protection of the fourth pole

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.

STR electronic trip units


Ratings (A)
Circuit breaker

In 20 to 70 C (1)
Compact NS100 N/H/L
Compact NS160 N/H/L
Compact NS250 N/H/L

STR22SE
40
b
b
b

80
b
b

100
b
b
b

STR22GE
160
b
b

250 (1)
b

40
b
b
b

100
b
b
b

250 (1)
b

160
b
b

Overload protection (Long Time)


Current setting

Ir = In x

Time delay (s)


(min.max.)

at 1.5 x Ir
at 6 x Ir
at 7.2 x Ir

0.4...1
48 settings
90...180
5...7.5
3.2...5.0

0.4...1
48 settings
1215
-

2...10
8 settings
fixed
y 40
y 60

2...10
8 settings
fixed
y 40
y 60

fixed u 11 x In

fixed u 11 x In

Short-circuit protection (Short Time)


Pick-up (A)
Accuracy 15 %
Time delay (ms)

Im = Ir x

max. resettable time


max. break time

Short-circuit protection (Instantaneous)


Pick-up (A)

Ii

Protection of the fourth pole


Neutral unprotected
4P 3d
no protection
Neutral protection at 0.5 In
4P 3d + N/2
0.5 x Ir
Neutral protection at In
4P 4d
1 x Ir
(1) If the STR22SE and STR22GE 250 A trip units are used in high-temperature environments, the setting must take into account the thermal limitations of the
circuit breaker. The overload protection setting may not exceed 0.95 at 60 C or 0.9 at 70 C.

Setting example
What is the overload-protection threshold of a
Compact NS250 circuit breaker equipped with an
STR22SE 160 A trip unit set to Io = 0.5 and Ir = 0.8 ?
Answer:
In x Io x Ir = 160 x 0.5 x 0.8 = 64 A.

Schneider Electric

E25979

E58565

STR22 electronic trip units

Io
.8 .9

.7
.63
.5
x In

Ir
.9 .93
1 .88
.95
.98
.85
.8
1
x Io

23

Protection of distribution systems


MP and STR trip units
for Compact NS400 to 630

Functions and
characteristics

60
E23161

Compact NS400 to 630 circuit breakers,


types N, H and L, 3-pole and 4-pole, may
be equipped with any of the STR23SE,
STR23SV, STR53UE and STR53SV
electronic trip units.
The STR53UE and STR53SV trip units
offer a wider range of settings and the
STR53UE offers a number of optional
protection, measurement and
communications functions.
For DC applications, the Compact NS400H
and 630H circuit breakers are equipped
with a built-in MP magnetic trip unit.

250

400

500

630

STR23SE / STR53UE
STR23SE / STR53UE
STR23SV / STR53SV
MP

Standard protection
with selectivity

Protection of systems supplied by


generators. Protection of long cables

Protection of DC
distribution systems

Protection of systems U > 525 V

Selection of the trip unit depends on the type of distribution system protected and
the operational voltage of the circuit breaker.
Protection for all types of circuits, from 60 to 630 A, is possible with only four tripunit catalogue numbers, whatever the circuit-breaker operational voltage:
b U y 525 V: STR23SE or STR53UE
b U > 525 V: STR23SV or STR53SV.
Trip units do not have a predefined rating. The tripping threshold depends on the
circuit breaker rating and the LT (long time) current setting.
For example, for an STR23SE trip unit set to the maximum value, the tripping
threshold is:
v 250 A, when installed on a Compact NS400 250 A
v 630 A, when installed on a Compact NS630.

1
2

STR 23 SE

E24094

E21003

STR23SE (U y 525 V) and STR23SV (U > 525 V)


electronic trip units

Io
.8 .9

.7
.63

x In

1
2
3
4
5
6
7

Ir Im

.5

5
I

long-time threshold (overload protection)


long-time tripping delay
short-time pick-up (short-circuit protection)
short-time tripping delay
instantaneous pick-up (short-circuit protection)
test connector
percent load indication

90
105 %Ir

alarm

Ir
.88
.85
.8

.9 .93
.95
.98
1

Isd
5

4
3
2

x Io

7
8
10
x Ir

Ir

Isd

test

Protection
The protection functions may be set using the adjustment dials.
Overload protection
Long-time protection with an adjustable threshold and fixed tripping delay:
b Io base setting (6-position dial from 0.5 to 1)
b Ir fine adjustment (8-position dial from 0.8 to 1).
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with an adjustable pick-up and fixed tripping delay
b instantaneous protection with fixed pick-up.
Protection of the fourth pole
On four-pole circuit breakers, neutral protection is set using a three-position switch
to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d
(neutral protection at In).

Indications
A LED on the front indicates the percent load:
b ON - load is > 90 % of Ir setting
b flashing - load is > 105 % of Ir setting.

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.

24

Schneider Electric

(*)

7 (*)

1
2

E33944

E21004

STR53UE (U y 525 V) and STR53SV (U > 525 V)


electronic trip units

.7

3
4

STR 53 UE
Io
.8 .9
1

.6

5
Ir

Isd

Ii

long-time threshold (overload protection)


long-time tripping delay
short-time pick-up (short-circuit protection)
short-time tripping delay
instantaneous pick-up (short-circuit protection)
optional earth-fault pick-up
optional earth-fault tripping delay
test connector
battery and lamp test pushbutton

Earth-fault protection (T) (see the Options for


the STR53UE electronic trip unit section on the
following pages).
With the earth-fault option (T) on the STR53UE
electronic trip unit, an external neutral sensor can
be installed (situation for a three-pole circuit
breaker in a distribution system with a neutral).
Available ratings of external neutral sensors: 150,
250, 400, 630 A.

tsd
(s).2

8 16

10

x Ir

0,5

16

(s) @ 6 Ir

1.5

.2
.1
0

0
on

I2t

test

off

fault

P
.5 .6
.4

8
10

.3 .3

.1

>Ig

Ig
4 6

6
8

1.5

x Io

tr

test

3
2

>Isd

Ii
4 5

.95
.98

x In

.9 .93

.8

.5

1
2
3
4
5
6
7
8
9

.88
.85

>Ir

%Ir

Isd

Ir

.7

11

.2

x In

tg
(s) .3

x In

.3

tr

> Im
> Ih

.4 .4

In

tsd

I1

I2

I3

Ir Isd li

.2

.2

.1

.1
on

> Ir

.8

.3

I2t

off

Protection
The protection functions may be set using the adjustment dials.
Overload protection
Long-time protection with adjustable threshold and tripping delay:
b Io base setting (6-position dial from 0.5 to 1)
b Ir fine adjustment (8-position dial from 0.8 to 1).
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with adjustable pick-up and tripping delay,
with or without constant I2t
b instantaneous protection with adjustable pick-up.
Protection of the fourth pole
On four-pole circuit breakers, neutral protection is set using a three-position switch
to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d
(neutral protection at In).

Overload LED (%Ir)


A LED on the front indicates the percent load:
b when ON, the load is > 90 % of Ir setting
b when flashing, the load is > 105 % of Ir setting.

Fault indications
A LED signals the type of fault:
b overload (long-time protection) or abnormal internal temperature (> Ir)
b short-circuit (short-time protection) or instantaneous (> Isd)
b earth fault (if earth-fault protection option installed) (> Ig)
b microprocessor malfunction:
v both (> Ig) and (> Isd) LEDs ON
v (> Ig) LED ON (if earth-fault protection option (T) installed).
Battery powered. Spare batteries are supplied in an adapter box. The LED
indicating the type of fault goes OFF after approximately ten minutes to conserve
battery power. The information is however stored in memory and the LED can be
turned back ON by pressing the battery/LED test pushbutton. The LED
automatically goes OFF and the memory is cleared when the circuit breaker is reset.

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
The test pushbutton tests the battery and the (%Ir), (> Ir), (> Isd) and (> Ig) LEDs.

Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature
is detected.

Options
Four options are available:
b earth-fault protection T
b ammeter I
b zone selective interlocking ZSI
b communications option COM.
Schneider Electric

25

Functions and
characteristics

Protection of distribution systems


MP and STR trip units
for Compact NS400 to 630 (cont.)

Trip units

STR23SE (U y 525V)
STR23SV (U > 525V)

STR53UE (U y 525V)
STR53SV (U > 525V)

150
b
-

150
b
-

Ratings (A)
Circuit breaker

In 20 to 70 C (1)
Compact NS400 N/H/L
Compact NS630 N/H/L

250
b
-

400
b
-

630
b

250
b
-

400
b
-

630
b

Overload protection (Long time)


Current setting
Time delay (s)
(min.max.)

Ir = In x

0.4...1
adjustable, 48 settings
fixed
90...180
5...7.5
3.2...5.0

0.4...1
adjustable, 48 settings
adjustable
8...15
34...50
69...100
0.4...0.5 1.5...2
3...4
0.2...0.74 1...1.4
2...2.8

2...10
adjustable, 8 settings
fixed
y 40
y 60

1.5...10
adjustable, 8 settings
adjustable, 4 settings + "constant I2t" option
y 15
y 60
y 140
y 230
y 60
y 140
y 230
y 350

11
fixed

1.5...11
adjustable, 8 settings

4P 3d
4P 3d + N/2
4P 4d

no protection
0.5 x Ir
1 x Ir

no protection
0.5 x Ir
1 x Ir

ZSI
COM
I
T

b (standard)
b (2)
b (2)
b (2)
b (2)

at 1.5 x Ir
at 6 x Ir
at 7.2 Ir

138...200 277...400
6...8
12...16
4...5.5
8.2...11

Short-circuit protection (Short time)


Pick-up (A)
accuracy 15 %
Time delay (ms)

Isd = Ir x

max. resettable time


max. break time

Short-circuit protection (instantaneous)


Pick-up (A)

Ii = In x

Protection of the fourth pole


Neutral unprotected
Neutral protection at 0.5 In
Neutral protection at In

Options
Indication of fault type
Zone selective interlocking
Communications
Built-in ammeter
Earth-fault protection

Setting example
What is the overload-protection threshold of a
Compact NS400 circuit breaker equipped with
an STR23SE (or STR23SV) trip unit set
to Io = 0.5 and Ir = 0.8 ?
Answer.
In x Io x Ir = 400 x 0.5 x 0.8 = 160 A.
The identical trip unit, with identical settings but
installed on a Compact NS630 circuit breaker, will
have an overload-protection threshold of:
630 x 0.5 x 0.8 = 250 A.

26

E25979

(1) If the trip units are used in high-temperature environments, the setting must take into account the thermal limitations of the circuit breaker. The overload
protection setting may not exceed 0.95 at 60 C or 0.9 at 70 C for the Compact NS400, and 0.95 at 50 C, 0.9 at 60 C or 0.85 at 70 C for the Compact NS630.
(2) This option is not available for the STR53SV trip unit.

Io

Ir

.8 .9

.7
.63

1 .88
.85
.8

.5
x In

.9 .93
.95
.98
1
x Io

Schneider Electric

Options for the STR53UE electronic trip unit

Possible
combinations:
bI
bT
bI+T
b I + COM
b I + T + COM
b ZSI
b ZSI + I
b ZSI + T
b ZSI + I + T
b ZSI +I + COM
b ZSI + I + T + COM

Earth-fault protection (T)


Type
Pick-up
Accuracy 15 %
Time delay
constant I2t function

Residual
Ig = In x

max. resettable time


max. break time

0.2 to 1
adjustable, 8 settings
adjustable, 4 settings
60
140
230
350
y 140 y 230 y 350 y 500

Ammeter (I)
A digital display continuously indicates the current of the phase with the greatest
load. The value of each current (I1, I2, I3, Ineutral) may be successively displayed
by pressing a scroll button.
LEDs indicate the phase for which the current is displayed.
Ammeter display limits:
b minimum current u 0.2 x In. Lower currents are not displayed
b maximum current y 10 x In.

Zone selective interlocking (ZSI)


A number of circuit breakers are interconnected one after another by a pilot wire.
In the event of a short-time or earth fault:
b if a given STR53UE trip unit detects the fault, it informs the upstream circuit
breaker, which applies the set time delay
b if the STR53UE trip unit does not detect the fault, the upstream circuit breaker
trips after its shortest time delay.
In this manner, the fault is cleared rapidly by the nearest circuit breaker.
The thermal stresses on the circuits are minimised and time discrimination is
maintained throughout the installation.
The STR53UE trip unit can handle only the downstream end of a zone selective
interlocking function. Consequently, the ZSI option cannot be implemented
between two Compact NS circuit breakers.
Opto-electronic outputs
Using opto-transistors, these outputs ensure total isolation between the internal
circuits of the trip unit and the circuits wired by the user.

Communications option (COM)


This option transmits data to Digipact distribution monitoring and control modules.
Transmitted data:
b settings
b phase and neutral currents (rms values)
b highest current of the three phases
b overload-condition alarm
b cause of tripping (overload, short-circuit, etc.).

E26028

MP DC trip units
Im(A)
30005000
4400
2500
3500
3800
5700
2000

4000
In Im

Magnetic trip units for Compact NS400/630 three-pole, type H circuit breakers.
These trip units are specifically designed to protect DC distribution systems.
They are not interchangeable. The circuit breaker and trip unit are supplied
fully assembled.
Built-in trip units
Circuit breaker

Compact NS400H
Compact NS630H

Short-circuit protection (magnetic)


Pick-up (A)
Im

Schneider Electric

MP1

MP2

MP3

b
b

b
b

adjustable
800...1600

adjustable
1250...2500

adjustable
2000...4000

27

Protection of distribution systems


Micrologic control units
for Compact NS630b to 3200

Micrologic 2.0 and 5.0 control units protect


power circuits. Micrologic 5.0 offers time
discrimination for short-circuits as well.

Protection

E46026A

Functions and
characteristics

Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection can be cancelled using a specific LT rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2) or
neutral protection at In (4P 4d).

Micrologic 5.0

Indications
Overload indication by alarm LED on the front; the LED goes on when the current
exceeds the long-time trip threshold.

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
setting

tsd
(s)

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

3
2.5
2
1.5

x In

6
8
10

delay

1
2
3
4
5
6

long-time threshold and tripping delay


overload alarm (LED)
short-time pick-up and tripping delay
instantaneous pick-up
fixing screw for long-time rating plug
test connector

Note.
Micrologic control units are equipped with a transparent leadseal cover as standard.

28

Schneider Electric

Micrologic 2.0

Long time
Current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
Time setting (s)
Time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %

Instantaneous
Pick-up (A)
accuracy: 10 %
Time delay

Schneider Electric

20
500
20
13.8

24
600
24
16.6

t
Ir

tr

0
Isd = Ir x

1.5

2.5

10

max resettable time: 20 ms; max break time: 80 ms

Micrologic 5.0

Long time
Current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
Time setting (s)
Time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %

Time delay (ms) at 10 Ir

Isd

Protection

Short time
Pick-up (A)
accuracy: 10 %
Time setting (s)

0.98

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

Micrologic 5.0
0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
0.5 1
2
4
8
12
16
12.5 25
50
100
200
300
400
0.7 (1) 1
2
4
8
12
16
0.7 (2) 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping

20
500
20
13.8

24
600
24
16.6

Ir
tr
Isd
tsd
Ii

Isd = Ir x

1.5

2.5

I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)

0
20
80

0.1
0.1
80
140

0.2
0.2
140
200

0.3
0.3
230
320

0.4
0.4
350
500

Ii = In x

settings

0.98

E46023

Instantaneous
Pick-up (A)
accuracy: 10 %
Time delay

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
0.5 1
2
4
8
12
16
12.5 25
50
100
200
300
400
0.7 (1) 1
2
4
8
12
16
0.7 (2) 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping

E46022

Protection

10

10

12

15

off

max resettable time: 20 ms; max break time: 50 ms

29

Protection of distribution systems


Micrologic A control units
for Compact NS630b to 3200 (cont.)

Micrologic A control units protect power


circuits. They also offer measurements,
display, communication and current
maximeters. Version 6 provides earth-fault
protection, version 7 provides earthleakage protection.

Protection

E46028

Functions and
characteristics

Micrologic 6.0 A

9
10
t= In=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=

MAX
s
kA

11

100 %
12
40 %
13

Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection can be cancelled using a specific LT rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Residual earth-leakage protection (Vigi).
Operation without an external power supply.
q Protected against nuisance tripping.
kDC-component withstand class A up to 10 A.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2),
neutral protection at In (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to
provide total discrimination for short-time and earth-fault protection, without a delay
before tripping.

Overload alarm
A red alarm LED goes on when the current exceeds the long-time trip threshold.

menu

"Ammeter" measurements
long time

Ir
.7

.6
.5
.4

tr

.8

(s) 4
.9
.95 2
.98 1
1
.5

x In

12
16
20
24

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

D
C
B
A

on

I t

off

delay

tg
F
G
H
J

Ii

(s)

setting

Ig

alarm

(s)

on

.2
.1
2

I t

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1

4
3

6
8

0
off

ground fault

1
2
3
4
5
6
7
8
9
10
11
12
13

long-time threshold and tripping delay


overload alarm (LED)
short-time pick-up and tripping delay
instantaneous pick-up
earth-leakage or earth-fault pick-up and tripping delay
earth-leakage or earth-fault test button
long-time rating plug screw
test connector
lamp test, reset and battery test
indication of tripping cause
digital display
three-phase bargraph and ammeter
navigation buttons

Micrologic A control units measure the true (rms) value of currents.


A digital LCD screen continuously displays the most heavily loaded phase (Imax) or
displays the I1, I2, I3, IN, Ig,In, stored-current (maximeter) and setting values by
successively pressing the navigation button. The load on each phase is indicated
continuously by bargraphs.
The optional external power supply makes it possible to display currents < 20% In.

Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
b settings
b all ammeter measurements
b tripping causes
b maximeter readings.

Fault indications
LEDs indicate the type of fault:
b overload (long-time protection) or abnormal internal temperature (Ir)
b short-circuit (short-time protection) or instantaneous (Isd)
b earth fault or earth leakage (Ig or In)
b microprocessor malfunction (Ap).
Battery power
The fault indication LEDs remain on until the test/reset button is pressed. Under
normal operating conditions, the battery supplying the LEDs has a service life of
approximately 10 years.

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units,
the operation of earth-fault or earth-leakage protection can be checked by pressing
the test button located above the test connector.
Note.
Micrologic A control units come with a transparent lead-seal
cover as standard.

30

Schneider Electric

Micrologic 2.0 A

Long time
Current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
Time setting (s)
Time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Isd = Ir x

1.5

Time setting (s)


Time delay (ms)
at In or 1200 A

Ir

tr

2.5

10

menu

I2
I3
IN
I1
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

Micrologic 5.0 / 6.0 / 7.0 A


0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
0.5
1
2
4
8
12
16
12.5 25
50
100
200
300
400
0.7(1) 1
2
4
8
12
16
0.7(2) 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping

20
500
20
13.8

24
600
24
16.6

Ir
tr
Isd
tsd
Ii

Isd = Ir x

1.5

2.5

I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)

0
20
80

0.1
0.1
80
140

0.2
0.2
140
200

0.3
0.3
230
320

0.4
0.4
350
500

Ii = In x

settings

0.98

E46023

Micrologic 5.0 / 6.0 / 7.0 A

Long time
Current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
Time setting (s)
Time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %

10

10

12

15

off

max resettable time: 20 ms ; max break time: 50 ms


Ig = In x
In y 400 A
400 A < In y 1200 A
In > 1200 A
settings
I2t Off
I2t On
tg (max resettable time)
tg (max break time)

Residual earth leakage (Vigi)


Sensitivity (A)
In
0.5
1
accuracy: 0 to -20 %
Time delay (ms)
settings
t (max resettable time)
t (max break time)

Ammeter
Continuous current measurements
Display from 20 to 200 % of In
accuracy: 1.5 % (including sensors)
Maximeters

20
80

Micrologic 6.0 A
B
C
D
0.3
0.4
0.5
0.3
0.4
0.5
640
720
800
0.1
0.2
0.3
0.1
0.2
0.3
80
140
230
140
200
320

Micrologic 7.0 A
3
5

60
60
140

140
140
200

A
0.3
0.2
500
0

230
230
320

350
350
500

E
0.6
0.6
880
0.4
0.4
350
500
7

F
0.7
0.7
960

G
0.8
0.8
1040

H
0.9
0.9
1120

J
1
1
1200

E46024

Earth fault
Pick up (A)
accuracy: 10 %

24
600
24
16.6

Micrologic 2.0 A

Protection

Instantaneous
Pick-up (A)
accuracy: 10 %
Time delay

20
500
20
13.8

max resettable time: 20 ms; max break time: 80 ms

Continuous current measurements


Display from 20 to 200 % of In
accuracy: 1.5 % (including sensors)
Maximeters

Time delay (ms) at 10 Ir

Isd

Ammeter

Short time
Pick-up (A)
accuracy: 10 %
Time setting (s)

0.98

I t on

Ig
2

tg

I t off

10

800
800
1000

Micrologic 5.0 / 6.0 / 7.0 A

20

30

E46243

Instantaneous
Pick-up (A)
accuracy: 10 %
Time delay

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

0.4
0.5
0.6
0.7
0.8
0.9
0.95
other ranges or disable by changing rating plug
0.5 1
2
4
8
12
16
12.5 25
50
100
200
300
400
0.7(1) 1
2
4
8
12
16
0.7(2) 0.69 1.38 2.7
5.5
8.3
11
20 minutes before and after tripping

E46022

Protection

In
t

I
menu

I1
I2
I3
IN
Ig
In
no auxiliary source (where I > 20 % In)
I1 max I2 max I3 max IN max Ig max In max

Note.
All current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.

Schneider Electric

31

Functions and
characteristics

Protection of distribution systems


Micrologic A control units
for Compact NS630b to 3200 (cont.)
Accessories for Micrologic control units

E47477

External sensors

056467

External sensor (CT)

External sensor for earth-fault protection


The sensor is used with 3P circuit breakers and the Micrologic 6.0 A control unit.
It is installed on the neutral conductor for residual type earth-fault protection.
The rating of the sensor (CT) must be compatible with the rating of the circuit
breaker:
b NS630b to NS1600 - 400/1600 CT
b NS1600b to NS3200 - 1000/4000 CT.
Rectangular sensor for earth-leakage protection
The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection.
Rectangular sensors are available in two sizes.
Inside dimensions (mm)
b 280 x 115 up to 1600 A
b 470 x 160 up to 3200 A.
External sensor for source ground return protection
The sensor is installed around the connection of the transformer neutral point to
earth and connects to the Micrologic 6.0 A control unit to provide the source ground
return (SGR) protection.

External sensor for source


ground return protection

Long-time rating plug

056412

Four interchangeable plugs may be used to limit the long-time threshold setting
range for higher accuracy.
As standard, control units are equipped with the 0.4 to 1 plug.
Setting ranges
Standard
Low-setting option
High-setting option
Off plug

Ir = In x 0.4 0.5
0.6
0.7
0.8
0.9
Ir = In x 0.4 0.45 0.50 0.55 0.60 0.65
Ir = In x 0.80 0.82 0.85 0.88 0.90 0.92
no long-time protection - Ir = In for Isd settings

0.95
0.70
0.95

0.98
0.75
0.98

1
0.8
1

External power-supply module


025173

Used in conjunction with the Micrologic A control units, this module maintains three
functions when the circuit breaker is OFF or the current is less than 20 % In:
b display of measurements
b screen backlighting
b operation of maximeters.
Characteristics:
b power supply:
v 110/130, 200/240, 380/415 V AC (+10 % -15 %), consumption 10 VA
v 24/30, 48/60, 100/125 V DC (+20 % -20 %), consumption 10 W
b output voltage: 24 V DC; power delivered: 5 W / 5 VA
b ripple < 5 %
b class 2 isolation.

32

Schneider Electric

056429

Spare parts for Micrologic control units


Lead-seal cover for Micrologic A
A transparent, lead-seal cover controls access to the adjustment dials.
When the cover is closed, it is still possible to access:
b the test connector
b the test button for the earth-fault and earth-leakage protection function.

Spare battery
Lead-seal cover for
Micrologic A

Schneider Electric

A battery supplies power to the LEDs identifying the tripping causes. Battery
service life is approximately ten years.
A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.

33

86099

Functions and
characteristics

Protection of distribution systems


Single-phase and two-phase
systems
Compact circuit breakers
Number of poles
Control

manual

Connections

electric
fixed

toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection

withdrawable

Compact NS160H single-pole

Electrical characteristics as per IEC 60947-2 and EN 60947-2


Rated current (A)
In
40 C
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC

86101

Type of circuit breaker


Ultimate breaking capacity (kA rms)

lcu

AC
50/60 Hz

DC
Service breaking capacity (kA rms)
Suitability for isolation
Utilisation category
Durability (C-O cycles)
mechanical
electrical

Compact NS100N two-pole

lcs

Protection and measurements


Type of trip units
Ratings
Overload protection (thermal)
Short-circuit protection (magnetic)
Add-on earth-leakage protection
Additional indication and control auxiliaries
Indication contacts
Voltages releases

% Icu

277 V

Electrical characteristics as per NEMA AB1


Breaking capacity (kA)
V AC 50/60 Hz

220 V
277 V
380/415 V
440 V
500 V
525 V
660/690 V
250 V (1P)
500 V (2P)

In/2
In

240 V
277 V
480 V
600 V

In
long time
Ir
threshold
instantaneous lm
pickup
add-on Vigi module
combination with Vigirex relay

MX shunt release
MN undervoltage release

Remote communication by bus


Device status indication via communicating auxiliary contacts
Installation
Accessories

Dimensions (mm)
Weight (kg)

terminal extensions and spreaders


terminal shields and interphase barriers
escutcheons
WxHxD

Source changeover system


Interlocking systems

34

Schneider Electric

NS100

NS160

1
b
b
b
-

2
b
b
b
-

100
750
8
277
250
N
25
25
25
100 %
b
A
20000
20000
10000
N
25
25
-

NS250

1
b
b
b
-

2
b
b
b
-

100
750
8
690
500

160
750
8
277
250

1
b
b
b
-

160
750
8
690
500

250
750
8
277
250

H
40
40
40
-

N
85
25
25
18
18
8
50
50
100 %
b
A
20000
20000
10000

H
100
70
65
50
35
10
85
85

N
25
25
25
100 %
b
A
20000
20000
10000

H
40
40
40
-

N
85
36
35
30
22
8
50
50
100 %
b
A
20000
20000
10000

H
100
70
65
50
35
10
85
85

N
25
25
25
100 %
b
A
10000
10000
5000

H
40
40
-

N
85
25
10

H
100
65
35

N
25
25
-

H
40
40
-

N
85
25
10

H
100
65
35

N
25
25
-

built-in thermal-magnetic
16
20
25
30
fixed
16
20
25
30
fixed
190 300
300
300
b

40

50

63

80

100

40

50

63

80

100

500

500

500

640

800

built-in thermal-magnetic
125 160
fixed
125 160
fixed
1000 1250
b

built-in thermal-magnetic
160 200
250
fixed
160 200
250
fixed
850 850
850
b

b
b
b

b
b
b

b
b
b
35 x 161 x 86
0.7

b
b
b
70 x 161 x 86
1.2

b
b
b
35 x 161 x 86
0.7

b
b
b
70 x 161 x 86
1.2

b
b
b
35 x 161 x 86
0.7

Schneider Electric

35

053182

Functions and
characteristics

Protection of distribution systems


1000 V systems

Compact circuit breakers


Number of poles
Rating of sensors (A)
Control

manual

Connections

electric
fixed

toggle
direct or extended rotary handle

plug-in (on base)


withdrawable (on chassis)
Electrical characteristics
Rated operational voltage (V)
Ultimate breaking capacity (kA rms)
Service breaking capacity

1000 V Compact NS400

For ratings above 400 A,


see the Masterpact
catalogue.

Ue
lcu
lcs

front connection
rear connection
front connection
rear connection
front connection
rear connection
AC 50/60 Hz
AC 1000 V
% Icu

Electrical characteristics as per IEC 60947-2 and EN 60947-2


Rated current (A)
In
40 C
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
Ultimate breaking capacity (kA rms)
lcu
AC 1000 V
Service breaking capacity
lcs
% Icu
Suitability for isolation
Short-time withstand current (kA rms)
lcw
0.5 s
V AC 50/60 Hz
1s
Utilisation category
Durability (C-O cycles)
mechanical
electrical
1000 V
In/2
In
Pollution degree
Protection and measurements
Interchangeable trip units
Overload protection
Short-circuit protection
Earth-fault protection
Residual earth-leakage protection
Zone selective interlocking
Protection of the fourth pole
Add-on earth-leakage protection
Current measurements
Additional indication and control auxiliaries
Indication contacts
Voltage releases

long time
Ir (In x )
short time
Isd (Ir x )
instantaneous Ii (In x )
lg (In x )
In
ZSI
combination with Vigirex relay

MX shunt release
MN undervoltage release

Remote communication by bus


Device-status indication
Device remote operation
Transmission of settings
Indication and identification of protection devices and alarms
Transmission of measured current values
Installation
Accessories

Dimensions (mm)
WxHxD
Weight (kg)

terminal extensions and spreaders


terminal shields and interphase barriers
escutcheons
fixed
3P
4P
fixed
3P
4P

Source changeover system


Interlocking systems

36

Schneider Electric

NS400 1000V

For ratings above 400 A, see the Masterpact catalogue

3
150, 250, 400
b
b
b
b
consult us
consult us
consult us
consult us
consult us
1150
10
100 %
150, 250, 400
1250
8
1000
10
100 %
b
standardised
standardised
A
15000
4000
2000
III
STR23SP
b
b
b
b
b
b
b
b
b
b
b
b
b
480 x 140 x 110
13
consult us

Schneider Electric

37

Functions and
characteristics

Protection of distribution systems


400 Hz applications

Tripping thresholds
The 400 Hz current settings are obtained by multiplying the 50 Hz values by the
following coefficient:
b K1 for thermal trip units;
b K2 for magnetic trip units.
On adjustable trip units, these adaptation coefficients are independent of the unit
adjustment knob position.
Thermal trip units
The current settings are lower at 400 Hz than at 50 Hz (K1 < 1).
Magnetic trip units
The current settings are conversely higher at 400 Hz than at 50 Hz (K2 > 1).
Adjustable trip units should be set to minimum, or use Compact circuit breakers
equipped with low magnetic trip units
(type G).
Electronic trip units
The use of electronics offers the advantage of greater operating stability when the
frequency is varied. However, the devices are still subjected to frequency related
temperature effects which may sometimes pose restrictions on their use.
Column K1 of the table gives the maximum permissible current to be used for the
current setting (knob position).

Thermal-magnetic trip units


Circuit breaker
NS100N

NS250N

Trip unit
TM16G
TM25G
TM40G
TM63G
TM16D
TM25D
TM40D
TM63D
TM80D
TM100D
TM125D
TM160D
TM200D
TM250D

Thermal setting K1

Magnetic
setting

K2

16
25
40
63
16
25
40
63
80
100
125
160
200
250

63
80
80
125
240
300
500
500
650
800
1000
1250
1000 (1)
1250 (1)

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

at 40 C

0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.9
0.9
0.9
0.9
0.9
0.9

(1) for TM200D and TM250D, Im must be set to its maximum

Electronic trip units


Compact adaptation coefficients
Circuit breaker Trip unit

NS100N
NS250N
NS400N
NS630N
NS400N
NS630N
C801N
C1001N
C1251N

38

STR22SE
STR22SE
STR23SE
STR23SE
STR53SE
STR53SE
STR25DE
STR35SE/GE
STR25DE
STR35SE/GE
STR25DE
STR35SE/GE

Rating

Long-time

Short-time

Ir at 50 Hz
(A at 40 C)

Ir maxi
K1

Irm at 50 Hz
(A)

40...100
100...250
400
630
400
630
800
800
1000
1000
1250
1250

0.4 to 1
0.4 to 0.9
0.4 to 0.8
0.4 to 0.8
0.4 to 0.8
0.4 to 0.8
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75
0.4 to 0.75

2 to 10 Ir
2 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir
1.5 to 10 Ir

K2

1
1
1
1
1
1
0.97
0.97
0.97
0.97
0.97
0.97

Schneider Electric

Breaking capacity of Compact NS and


Compact circuit breakers at 400 Hz
At 440 V, 400 Hz
Circuit breaker

E22347

NS100N
NS250N
NS400N
NS630N
C801N
C1001N
C1251N

MN or MX auxiliary releases

R
MN/MX
U volt
400 Hz

Connection

Breaking capacity
12 kA
4,5 kA
10 kA
10 kA
25 kA
25 kA
25 kA

125 V CC

For Compact NS100-630


For circuit breakers on 400 Hz systems, only 125 V DC rated releases can be
used. The release must be supplied by the 400 Hz system via a rectifier bridge (to
be selected from the table below) and an additional resistor with characteristics
depending on the system voltage and the type of circuit breaker.
U (V) 400 Hz
220/240 V

380/420 V

Rectifier

Additional resistor

Thomson 110 BHz or


General Instrument W06 or
Semikron SKB at 1,2/1,3
Semikron SKB at 1,2/1,3

4.2 k-5 W

10.7 k-10 W

Note : other models of rectifier bridges can be used if their characteristics are at least
equivalent to those stated above.

For Compact C801-1251


The following auxiliary releases are designed to operate at 400 Hz.
U (V) 400 Hz
MN 110/130 V
MN 208/250 V
MN 380/415 V
MX 380/415 V

Catalogue number
44925
44926
44932
44914

For Compact NS630b-3200


The standard auxiliary releases can be used at 400 Hz, up to an ambiant
temperature of 55 C.

Schneider Electric

39

Protection of distribution systems


Circuit breaker selection for DC
applications

Functions and
characteristics

Selection criteria
The selection of the type of circuit breaker most suitable for protection of a
DC installation depends mainly on the following criteria:
b the rated current, which determines the rating of the equipment
b the rated voltage, which determines the number of poles in series necessary for
breaking
b the maximum short-circuit current at the point of installation, which determines
the breaking capacity
b the type of network (see below).
Insulated systems

a centre point of the DC supply is


earthed
i
a
+

R
B

U/2
+
U/2

Fault effect

fault A
fault B
fault C

E79370

Most unfavorable case


Distribution of the
breaking poles

Isc

max. Isc
the positive polarity
is the only one involved
max. Isc
both polarities are involved
no effect

240 V DC
300 A
500 Ah
Ri = 0.5 m/cell

B
b

Isc close to max. Isc


the positive polarity is the only
one involved, voltage U/2
max. Isc
both polarities are involved
same as fault A but this is the
negative polarity which is involved
faults A and C
on each polarity there must be the
number of poles required to perform
the break of max. Isc at U/2

fault A
the poles required to perform
the break are in series
on the positive polarity

i
+

R
B
b

b C

E22348

E22350

Diagrams
and various
cases of faults

Earthed systems
one polarity of the DC supply is
earthed
i
a

E22349

Type of system

no effect
max. Isc
both polarities are involved
no effect
fault B
the poles required to perform
the break are shared between
the 2 polarities

Calculation the short-circuit current (Isc) across the terminals of a battery


When a short-circuit occurs across its terminals, a battery discharges a current
given by Ohm's law:
Isc =

Vb
Ri

where Vb = the maximum discharge voltage (battery 100 % charged).


and Ri = the internal resistance equivalent to the sum of the cell resistances (figure
generally given by the manufacturer according to the capacity of the battery).
Example
What is the short-circuit current at the terminals of a standing battery with the
following characteristics:
b capacity: 500 Ah
b max. discharge voltage: 240 V
(110 cells of 2.2 V)
b discharge current: 300 A
b autonomy: 1/2 hour
b internal resistance: 0.5 m per cell.
Ri = 110 x 0.5 10-3 = 55 10-3
Isc =

240
= 4.4kA
55 103

As the above calculation shows, the short-circuit current is relatively weak.


Note: If the internal resistance is not known, the following approximate formula can be used:
Isc = kC, where C is the capacity of the battery expressed in Ampere-hours, and k is a
coefficient close to 10 but in any case always lower than 20.

40

Schneider Electric

E79371

Example 1
Determine the protection required for a 80 A feeder on a 125 V DC network with an
earthed negative pole and an Isc of 15 kA.
The table below indicates that a NC100H circuit breaker (30 kA, 2P, 125 V) should
be used.
The table opposite indicates that both circuit breaker poles should be fitted on the
positive pole of the network.
An additional circuit breaker pole can be fitted on the negative pole of the network
for isolation purposes.

+
125 V =
-

NC100 H
3P
80 A

E79372

load

+
250 V =
-

NC100 H
4P
100 A

E79373

load

+
250 V =
-

NS400H
2P
400 A
load

Example 2
Determine the protection required for a 100 A feeder on a 250 V DC network with
an earthed middle point and an Isc of 15 kA.
Each pole will be exposed to a maximum of U/2 = 125 V.
The table below indicates that NC100H (30 kA, 2P, 125 V), NS100N (50 kA, 1P,
125 V) or NS160N (50 kA, 1P, 125 V) circuit breakers should be used.
The table opposite indicates that both circuit breaker poles must take part in the
breaking at a voltage of 125 V.
Example 3
Determine the protection required for a 400 A feeder on an unearthed 250 V DC
network with an Isc of 35 kA.
The table above indicates that NS400H circuit breakers (85 kA, 1P, 250 V) should
be used. At least 2 poles must take part in breaking.
The table opposite indicates that the half the number of circuit breaker poles
required for breaking should be fitted on the positive pole of the network and the
other half on the negative pole.

selection table of DC circuit breakers


Type

NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
NS400H
NS630H
C1251N-DC

Rated current (A)


and
trip units
16-25-40-63-80-100
16-25-40-63-80-100
16-25-40-63-80-100
80-100-125-160
80-100-125-160
80-100-125-160
160-200-250
160-200-250
160-200-250
MP1/MP2/MP3
MP1/MP2/MP3
P21/P41-1250

Schneider Electric

Breaking capacity (kA) (L/R y 0.015 s)


(and number of poles required to perform the break)
24/48 V
125 V
250 V
500 V
750 V
50 (1P)
50 (1P)
50 (1P)
50 (2P)
85 (1P)
85 (1P)
85 (1P)
85 (2P)
100 (1P)
100 (1P)
100 (1P)
100 (2P)
50 (1P)
50 (1P)
50 (1P)
50 (2P)
85 (1P)
85 (1P)
85 (1P)
85 (2P)
100 (1P)
100 (1P)
100 (1P)
100 (2P)
50 (1P)
50 (1P)
50 (1P)
50 (2P)
85 (1P)
85 (1P)
85 (1P)
85 (2P)
100 (1P)
100 (1P)
100 (1P)
100 (2P)
85 (1P)
85 (1P)
85 (1P)
85 (2P)
85 (1P)
85 (1P)
85 (1P)
85 (2P)
50 (1P)
50 (1P)
50 (2P)
50 (3P)
25 (3P)

Protection against Protection against


overloads (thermal) short-circuits (magnetic)
same as for trip units
used on AC systems

no thermal protection: specially designed for DC


an external relay
must be provided

41

Functions and
characteristics

These are incoming circuit breakers,


specially designed to operate upstream
of Multi 9 modular circuit breakers.
Features include:
b reinforced breaking capacity at 380/415 V,
by cascading up to 25 kA
b easy installation in Pragma and Prisma G
enclosures:
v standard 45 mm front cut-out
v circuit breaker clips onto a DIN rail
v reduced depth (82.5 mm).
A switch-disconnector version is also
available (NSA125NA and NSA160NA).

Protection of distribution systems


Incoming circuit breakers in final
distribution
Compact circuit breakers
Number of poles
Control

Mounting on DIN rail


Front-panel cut-out

3, 4
b
b
b
b
height 45 mm

Electrical characteristics as per IEC 60947-2


Rated current (A)
In
40 C
Rated insulation voltage (V)
Ui
Rated impulse withstand volt. (kV) Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC

160
500
8
500
250

Connections

048016

Type of circuit breaker


Ultimate breaking capacity
(kA rms)

Service breaking capacity


Utilisation category
Suitability for isolation
Durability (C-O cycles)

Compact NSA160

42

NSA160

manual (toggle,
direct or extended rotary handle)
electric
fixed
front connection
rear connection
withdrawable front connection
rear connection

Icu

AC
50/60
Hz
DC

Ics

% Icu

220 / 240 V
380 / 415 V
440 V
125 V
250 V (2P)

mechanical
electrical (In - 440 V)

E
25
16
10
5
5
50 %
A
b
10000
5000

N
70
36
18
10
10
100 %

Protection
Built-in thermal-magnetic trip unit
Ratings In
16
25
32
40
50
63
80
100 125 160
Thermal overload protection Ir fixed threshold
16
25
32
40
50
63
80
100 125 160
Magnetic short-circuit
fixed pick-up
protection lm
600 600 600 600 1000 1000 1000 1250 1250 1250
Add-on earth-leakage
add-on Vigi module
protection
combination with Vigirex relay
Indication and control auxiliaries
Indication contacts
Voltage releases

1 OF + 1 SD
MN or MX

Installation and connections


Connections
terminals
Accessories
terminal shields
depth adjuster
Dimensions (mm)
Compact
3-poles
WxHxD
4-poles
Vigicompact 3-poles
4-poles
Weight (kg)
Compact
3-poles
4-poles
Vigicompact 3-poles
4-poles

1.5 to 70 mm2 cables


b
b
90 x 120 x 82.5
120 x 120 x 82.5
210 x 120 x 82.5
240 x 120 x 82.5
1.1
1.4
2.6
3.1

Source changeover system


Interlocking systems

Schneider Electric

048018

Vigi earth-leakage protection module


The Vigi earth-leakage protection module may be installed to the right of the circuit
breaker. Connections with the circuit breaker are possible to the top or bottom
of the Vigi module (two versions). The connection is supplied with the Vigi module.
Characteristics
Number of poles
Sensitivity (A)
Time delay

Vigicompact NSA

3, 4
0.03 / 0.3 / 1 / 3
intentional (ms)
0
60 (1) 150 (1)
max. break time
< 40 < 140 < 150
Rated voltage (V)
50/60 Hz
200 to 440 V
Reset
pushbutton
Test
pushbutton
Protection against nuisance tripping
b
DC-component withstand
class A
(1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

Auxiliaries and accessories


Available auxiliaries include:
b 1 ON/OFF indication contact (OF)
b 1 trip-indication contact (SD)
b 1 voltage release (MN undervoltage release or MX shunt trip)
b 1 extended rotary handle with door locking, directly accessible from outside
the enclosure.
Depth adjuster
This accessory is required to align the front of Multi 9 devices when they are
installed next to a Compact NSA125 or NSA160. Maximum width 324 mm
(36 modules).

Schneider Electric

43

Functions and
characteristics

Motor protection
Overview of solutions

The circuit breakers presented here


provide protection against short circuits
and are suitable for isolation as defined
by standard IEC 60947-2.
For complete protection of the motor and
its control device, overload protection may
be provided by either the circuit breaker or
a separate Telemecanique thermal relay.
The control device may be of the direct
on-line type (with or without reversing)
or of the star-delta type.
Combinations are governed by standard
IEC 60947-4.1.

Motor protection up to 37 kW
Motor rating (kW)

0.37 37
NS80
046751

Compact

Breaking
capacity (kA rms)
380/415 V

70

General circuit-breaker characteristics


page 46
The Compact NS80H-MA circuit breaker is specially designed for motor protection.
Accompanying trip unit
A built-in MA magnetic trip unit provides short-circuit protection.

page 46

E26988

Motor protection up to 250 kW


Motor rating (kW)

1.1 110

18.5250

NS100

NS160/250

25
70
150

36
70
150

NS400/630

041624

045198

Compact

Breaking
capacity (kA rms)
380/415 V

N
H
L

45
70
150

General circuit-breaker characteristics


page 18
Compact NS100 to 630 circuit breakers for motor protection are the same as those for
distribution systems, but are fitted with specific motor trip units.
Accompanying trip units
pages 47 to 51
MA magnetic trip units provide short-circuit protection. Interchangeable ME electronic trip units
provide protection against short-circuits, overloads and phase unbalance.

Motor protection up to 750 kW


Motor rating (kW)

160750

Compact

NS630b to 1600
E45151

Protection coordination (as defined by


IEC 60947-4)
Whatever the power of the motor, the coordination
between the circuit breaker, contactor and relay
can be of either type 1 or 2.
Selection depends on operational requirements
concerning continuity of service and the technical
skills of servicing personnel.
All type 2 Merlin Gerin/Telemecanique combinations
have been tested under the conditions defined by
standards and they are certified ASEFA/LOVAG.

Breaking
capacity (kA rms)
380/415 V

N
H
L

50
70
150

General circuit-breaker characteristics


page 20
Compact NS630b to 1600 circuit breakers equipped with Micrologic control units
are the same as those for distribution systems.
Accompanying control units
page 28
Micrologic electronic control units may be used on all Compact NS630b to 1600 circuit
breakers.
Micrologic 2.0 A and 5.0 A electronic control units provide protection against short-circuits and
overloads. Micrologic 7.0 A provides the same protection functions, plus earth-leakage
protection.

44

Schneider Electric

E26530

Selection of a trip unit or Micrologic control unit


P (kW) (400 V, 50 Hz)
Ir (A)
Compact
NS80H-MA
Compact
NS100 NS250

Compact
NS400 NS630

Compact
NS630b NS1600

Schneider Electric

0.37
1.5

1.1
2.5

5.5
12

18.5
40

50

37
80

100

160

200

110
220

160
320

250
500

800

560
1000

750
1350

MA
MA
STR22ME
MA
STR43ME

Micrologic 2.0 A / 5.0 A / 7.0 A

45

Functions and
characteristics

046751

This circuit breaker is specially designed for


the protection of motors rated up to 37 kW:
b due to its high current-limiting capacity,
it effectively protects motor starters (type-2
coordination as per IEC 60947-4, with
contactors)
b small size for easy installation in motor
control centre (MCC) switchboards.

Compact NS80 H-MA

Motor protection
Compact NS80H-MA

Compact circuit breakers


Number of poles
Control

Connections

manual (toggle,
direct or extended rotary handle)
electric
fixed
front connection
rear connection
withdrawable
front connection
rear connection

Electrical characteristics as per IEC 60947-2


Rated current (A)
In 65 C
Rated insulation
Ui
voltage (V)
Rated impulse
Uimp
withstand voltage (kV)
Rated operational voltage (V)
Ue AC 50/60 Hz
Ultimate breaking
Icu AC 50/60 Hz 220 / 240 V
capacity (kA rms)
380 / 415 V
440 V
500 V
525 V
660/690 V
Service breaking capacity
Ics % Icu
Utilisation category
Suitability for isolation
Durability (C-O cycles)
mechanical
electrical 440 V In/2
In
Electrical characteristics as per Nema AB1
Breaking capacity (kA)

Protection
Magnetic trip unit
Rating In
Instantaneous short-circuit lm
protection
Earth-leakage protection

46

NS80H-MA
3
b
b
b
80
750
8
690
100
70
65
25
25
6
100 %
A
b
20000
10000
7000

240 V
480 V
600 V

built-in
1.5
2.5
6.3
12.5 25
adjustable pick-up
6 14 x In
combination with Vigirex relay

100
65
10

50

80

Indication and control auxiliaries


Indication contacts
Voltage releases

1 OF + 1 SD
MN or MX

Installation and connections


Connections
Terminal extensions and spreaders
Terminal shields
Interphase barriers
DIN rail plate
Dimensions (mm)
WxHxD
Weight (kg)

built-in terminals
b
b
90 x 120 x 80
1.0

Schneider Electric

Compact NS100 to 630 circuit


breakers with MA magnetic trip units
Compact NS100 to 630 circuit breakers,
equipped with an MA magnetic trip unit with
adjustable thresholds, offer:
b short-circuit protection
b suitability for isolation.
Compact NS100 to 630 circuit breakers
and the trip unit are supplied already
assembled.

General circuit-breaker characteristics

page 18

MA trip units
Rating (A)
at 65 C
In
Compact
N/H/L NS100
circuit breaker
NS160
NS250
H/L
NS400
NS630

2.5
b
-

6.3
b
-

12.5
b
-

25
b
b
-

50
b
b
-

100
b
b
b
-

150
b
b
-

220
b
-

320
b
-

500
b

Short-circuit protection (magnetic)


041624

Pick-up

Im

setting
6...14 x In

setting
setting
9...14 x In 9...14 x In

045198

Compact NS250H

Compact NS400H-MA

Schneider Electric

47

Motor protection
Compact NS100 to 250
circuit breakers with STR22ME
electronic trip unit

Compact NS100 to 250 circuit breakers,


equipped with an STR22ME electronic trip
unit with adjustable thresholds, offer:
b short-circuit protection
b phase-unbalance protection
b overload protection
b suitability for isolation.

Compact NS100 to 250 circuit breakers

052163

Functions and
characteristics

See the circuit breakers for distribution systems on page 18.

STR22ME electronic trip unit


Protection
Overload protection
LT (long time) protection with adjustable Ir threshold, in compliance with tripping
class 10 as defined by IEC 60947-4.
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with fixed pick-up (Im = 13 x Ir) and tripping delay
b instantaneous protection with fixed pick-up (15 x In).
Phase-unbalance protection
This function complies with the stipulations of standard IEC 60947-4.1 and trips the
circuit breaker whenever a phase-current unbalance of 40 % or more occurs. The
circuit-breaker opening time is between 3.5 and 6 seconds.

Overload LED (%Ir)


Compact NS250 equipped with an STR22ME electronic trip unit

A LED on the front indicates the percent load:


b OFF: I < 1.05 Ir
b flashing: I u 1.05 Ir.

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.

Optional SDTAM contactor tripping module


(Early-break thermal-fault signal)
This module can be installed in place of the MN or MX release. It operates 300 ms
before the circuit breaker trips on an overload.
The SDTAM module can be used to open a contactor when an overload occurs,
thereby avoiding the opening of the circuit breaker.
It can also be used without a contactor to provide an overload indication on the
STR22ME trip unit, thereby making it possible to differentiate between tripping on
overloads and short-circuits.
Characteristics
b compatible with the following control voltages:
v 24 to 72 V DC and 24 to 48 V AC
v 110 to 240 V AC / DC
b replaces the MN and MX voltage releases.

48

Schneider Electric

1
2

E94521

E26985

Ir
In=50A

ImSTR 22 ME

37.5 40
35.5
42.5

Ir

33.5

1
2
3
4
5
6
7

Ir

13Ir

IEC 947.4 / cl.10

45

31.5

u1,05 Ir

7,2Ir
7,0s

47.5
30

50

Ir

13 Ir

test

long-time threshold
tripping class 10 as defined by IEC 60947-4
short-time pick-up
short-time tripping delay
instantaneous pick-up
test connector
percent load indication

STR22ME trip unit


20 to 70 C
NS100N/H/L
NS160N/H/L
NS250N/H/L

Ratings (A)

20100
b
b
b

150
b
b

220
b

Overload protection (Long Time)


Current setting

Ir

Tripping class
(IEC 60947-4)
Time delay (s)
(minmax.)

adjustable, 10 settings
0.6...1 x In
10
fixed
120320
615
410
LED

at 1.5 x Ir
at 6 x Ir
at 7.2 Ir

Motor-overload indication

Phase-unbalance protection in compliance with IEC 60947-4.1


Tripping threshold
Time delay

u 40 % unbalance
3.5 to 6 seconds

Short-circuit protection (Short Time)


Pick-up

Isd

fixed
13 x Ir
20 %
fixed
10
60

Accuracy
Max. resettable time (ms)
Max. break time

Short-circuit protection (Instantaneous)


Pick-up

Ii

fixed
15 x In

Options
SDTAM module

Overload protection settings (A)


rating (A)
20
25
40
50
80
100
150
220

Schneider Electric

thresholds (A)
12
12.6 13.4
15
15.7 16.7
24
25.5 27
30
31.5 33.5
48
51
54
60
63
67
90
95
101
132
140
148

14.2
17.7
28.5
35.5
57
71
107
157

15
18.7
30
37.5
60
75
113
166

16
20
32
40
64
80
120
177

17
21.2
34
42.5
68
85
127
187

18
22.5
36
45
72
90
135
198

19
23.7
38
47.5
76
95
142
209

20
25
40
50
80
100
150
220

49

Motor protection
Compact NS400 to 630
circuit breakers with STR43ME
electronic trip unit

Compact NS400 to 630 circuit breakers,


equipped with an STR43ME electronic trip
unit with adjustable thresholds, offer:
b short-circuit protection
b phase-unbalance protection
b overload protection
b suitability for isolation.

Compact NS400 to 630 circuit breakers

053192

Functions and
characteristics

See the circuit breakers for distribution systems on page 18.

STR43ME electronic trip unit


Protection
Overload protection
True (rms) long-time protection with an adjustable threshold:
b Io base setting (5 settings from 0.5 to 0.8) and Ir fine adjustment
(8 settings from 0.8 to 1)
b adjustable tripping delay, in compliance with tripping classes 10A, 10 and 20 as
defined by IEC 60947-4.
The STR43ME offers two motor-cooling time constants, associated with the motor
starting class:
b short cooling time constant (the same as the heating time constant), providing
maximum continuity of service and satisfactory motor protection
b long cooling time constant (four times the heating time constant), providing
maximum motor protection.
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with adjustable pick-up and fixed tripping delay
b instantaneous protection with fixed pick-up.
Phase-unbalance protection
This function complies with the stipulations of standard IEC 60947-4.1 and trips
the circuit breaker whenever a phase-current unbalance of 40 % or more occurs.
The circuit-breaker opening time is 4 seconds 10 %.

Compact NS630 equipped with an STR43ME electronic trip unit

Indications: Overload LED (%Ir)


A LED on the front indicates the percent load:
b OFF: I < 1.05 Ir
b flashing: I u 1.05 Ir

Fault indications
LEDs indicate the type of fault that caused tripping:
b overload (long-time protection) or abnormal component temperature (> Ir)
b short-circuit (short-time protection) or instantaneous (> Isd)
b phase unbalance (LED on the right)
b microprocessor malfunction:
v all four (%Ir), (> Ir), (> Isd) and (phase unbalance) LEDs ON.
Battery powered. Spare batteries are supplied in an adapter box. When a fault
occurs, the LED indicating the type of fault goes OFF after approximately ten
minutes to conserve battery power. The information is however stored in memory
and the LED can be turned back ON by pressing the battery/LED test pushbutton.
The LED automatically goes OFF and the memory is cleared when the circuit
breaker is reset.

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
The test pushbutton tests the battery and the LEDs.

Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature is
detected.

Options
Three options are available:
b ammeter (I)
b contactor tripping module (SDTAM)
b communication (COM).

50

Schneider Electric

1
2
E32566

E26987

3
4

.63

.71 .8

.88

1
2
3
4
5
6
7

Isd Ii

.5

long-time threshold
tripping class
short-time pick-up
short-time tripping delay
instantaneous pick-up
test connector
percent load indication

.95
.98

.8

x In

.90 .93

.85
.8

x Io

tr
+

%Ir

>Ir

>Isd

test

9 10
8

11

> Ir

12

7
6

13

tr

> Im

x Ir

> Ih

20 20
10

fault

Isd

Ir

test

Ir

STR 43 ME
Io

.56

5
0

Ir

10

tsd

I1

I2

I3

Ir Isd li

10A

10A

IEC 947-4-1

class

STR43ME trip unit


Ratings (A)
Circuit
breakers

20 to 70 C
NS400N/H/L
NS630N/H/L

120
b
-

200
b
-

320
b
-

500
b

Overload protection (Long Time)


Current setting
Tripping class
(IEC 60947-4)
Time delay (s)
(min. ... max.) at 1.5 x Ir
at 6 x Ir
at 7.2 Ir

Ir

adjustable, 40 settings - 0.4...0.8 x In


10A, 10, 20
adjustable
144198
5.87.3
45

270357
10.913.1
7.39.1

433595
17.421.8
1215

Phase-unbalance protection in compliance with IEC 60947-4.1


Tripping threshold
Time delay

u 40 % unbalance
4 s 10 %

Short-circuit protection (Short Time)


Pick-up
Isd
Accuracy
Time delay (ms)
max. resettable time
max. break time

adjustable, 8 settings - 6...13 x Ir


15 %
fixed
10
60

Short-circuit protection (Instantaneous)


Pick-up

Ii

fixed - 13 x Ir max.

Other functions
Motor-overload LED
Indications module

b
b

Options
Ammeter (I)
SDTAM module
Communication (COM)

b
b
b

Options for STR43ME trip unit


Possible
combinations:
bI
b I + COM
b SDTAM
b SDTAM + I
b SDTAM + I + COM

Ammeter (I)
A digital display continuously indicates the current of the phase with the greatest
load. The value of each current I1, I2, I3 and the long-time current setting Ir may be
successively displayed by pressing a scroll button.
LEDs indicate the phase for which the current is displayed.
Ammeter display limits
b minimum current u 0.2 x In. Lower currents are not displayed
b maximum current y 10 x In.

Optional SDTAM contactor tripping module


(Early-break thermal-fault signal)
See the information on this optional module on page 44.

Communication (COM)
This option transmits data to Digipact distribution monitoring and control modules.
Transmitted data:
b settings
b phase currents (rms values)
b highest current of the three phases
b overload-condition alarm
b cause of tripping (overload, short-circuit, etc.).

Schneider Electric

51

Functions and
characteristics

Protection of industrial
control panels
Overview of solutions

Compact NS circuit breakers are specially


designed to protect incoming feeders and
groups of outgoing circuits on industrial
control panels:
b compliance with standards applicable
worldwide including IEC 60947-2
and UL 508 / CSA 22-2 no. 14
b overload and short-circuit protection
b isolation with positive contact indication,
making it possible to service machines
safely by isolating them from all power
sources
b installation in universal and functional
type enclosures
b NA switch-disconnector version.

Compact NSC100
12.5100
054556

Rated current (A)

UL 508 / IEC 60947-2 / CSA22-2

Breaking
capacity (kA rms)
380/480 V

18

General circuit-breaker characteristics


page 53
Compact NSC100 circuit breakers are specially designed to protect industrial control panels.
Accompanying trip unit
The built-in TMD thermal-magnetic trip unit provides:
b overload protection (adjustable-threshold thermal device)
b short-circuit protection (fixed-pick-up magnetic device).

Compact NS100 to 630


Rated current (A)

E44356

page 54

12.5 ...
250

60...
400

250...
630

NS100

NS250

NS400

NS630

NS160

045198

Compact

12.5 12.5 ...


100
160

041624

push
to
trip

Breaking
capacity (kA rms)
380/480 V

N
H

UL 508 / IEC 60947-2 / CSA22-2

IEC 60947-2

25
65

42
65

35
65

35
65

42
65

General circuit-breaker characteristics


page 18
Compact NS100 to 630 circuit breakers are designed for protection of distribution systems and
are also suitable for protection of industrial control panels.
Accompanying trip unit
page 22 to 27
The trip units are interchangeable.
Compact NS100 to 250 circuit breakers are equipped with TMD thermal-magnetic or STR
electronic trip units.
Compact NS400 to 630 circuit breakers are equipped exclusively with STR electronic trip units.

52

Schneider Electric

Circuit breaker NSC100N


Compact NS100N circuit breakers are
specially designed to protect incoming
feeders and groups of outgoing circuits on
industrial control panels.
The NSC100NA switch-disconnector
version is also available.

Compact circuit breaker


Number of poles
Control

Connections

NSC100N

manual (toggle,
direct or extended rotary handle)
electric
fixed
front connection
rear connection
withfront connection
drawable rear connection

054556

Mounting on DIN rail

Compact NSC100N

Electrical characteristics as per IEC 60947-2


Rated current (A)
In 40 C
Rated insulation
Ui
voltage (V)
Rated impulse
Uimp
withstand voltage (kV)
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC
Ultimate breaking capacity
Icu
AC
220/240 V
(kA rms)
50/60 380/415 V
Hz
440 V
500 V
525 V
DC
125 V
250 V (2P)
Service breaking capacity
Ics
% Icu
Utilisation category
Suitability for isolation
Durability (C-O cycles)
mechanical
electrical 440 V In/2
In
Electrical characteristics as per UL 508
Breaking capacity (kA)
AC 50/60 Hz

240 V
480 V
600 V

3, 4
b
b
b
b
100
750
8
690
250
42
18
18
10
10
5
5
100 %
A
b
20000
10000
7000
42
18
10

054556

Protection
Built-in thermal-magnetic trip unit
Ratings In
16 20 25 32 40 50 63 70 80 100
Instantaneous short-circuit lm fixed pick-up
protection (A)
600 600 600 600 1000 1000 1000 1000 1000 1250
Add-on earth-leakage
add-on Vigi module
protection
combination with Vigirex relay
Indication and control auxiliaries
Auxiliary contacts
Early-make or early-break contact
Voltage releases

b
b
MN or MX

Installation and connections


Connection
built-in terminals
Accessories
terminal shields
interphase barriers
escutcheons
Dimensions (mm)
3P
WxHxD
4P
Weight (kg)
3P
4P

b
b
90 x 120 x 80
120 x 120 x 80
1.0
1.3

Vigi earth-leakage protection module


The Vigi earth-leakage protection module may be installed to the right of the circuit
breaker. Connections with the circuit breaker are possible to the top or bottom of
the Vigi module (two versions). The connection is supplied with the Vigi module.
Characteristics
Number of poles
Sensitivity (A)
Time delay

Vigicompact NSC100N

Schneider Electric

3, 4
0.03 / 0.3 / 1 / 3
intentional (ms)
0
60 (1) 150 (1)
max. break time
< 40 < 140 < 150
Rated voltage (V)
50/60 Hz
200 to 440 V
Reset
pushbutton
Test
pushbutton
Protection against nuisance tripping
b
DC-component withstand
class A
(1) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

53

Protection of industrial
control panels
Trip units, auxiliaries,
installation enclosures

Functions and
characteristics

Trip-unit selection
3
12

E58713

P (hp) (480 V, 3P)


Ir (A)
Compact
NSC100N

10
16

15
25

20
32

30
40

30
48

40
63

50
70

60
80

75
100

125
160

150
205

150
220

250
320

400
500

TMD

Compact
NS100 NS250

STR22ME

Compact
NS400 NS630

STR43ME / STR23SE / STR53UE

STR electronic trip units are designed for:


b short-circuit protection
b overload protection
b phase-failure protection (STR22ME and STR43ME).
TMD thermal-magnetic trip units are designed for:
b short-circuit protection
b overload protection.
Type NA devices are switch-disconnectors which must always be protected
upstream in accordance with applicable installation standards.
trip units

UL/CSA approvals

NSC100N

Circuit breakers

TMD
NA

NS100/160/250 N/H

STR22ME
NA
TMD
STR22SE/GE
STR43ME
NA
STR23SE
STR53UE

Manual Motor Controller:


Across the line starter &
General use
Manual Motor Controller:
Across the line starter
Manual Motor Controller:
General Use

NS400/630 N/H

Auxiliaries
All auxiliaries can be added to the circuit breaker by the user:
b padlocking devices (in the OFF position)
b rotary handle
b status-indication auxiliary contacts (ON, OFF and tripped)
b shunt (MX) or undervoltage (MN) releases
b early-make or early-break contacts.
Rotary handle
Available in direct or extended versions for mounting up to 590 mm behind front.
Versions include:
b black front with black handle
b yellow front with red handle (for machine tools or emergency off as per IEC 204 /
VDE 0013).
All rotary handles can be padlocked in the OFF position.
Optional door interlock, recommended for MCC panels (motor control centres).
Early-make or early-break contacts
These auxiliary contacts make it possible to de-energise the downstream auxiliary
circuits of the control panel as well as the auxiliary circuits supplying the MN
release, if applicable.

E44458

Installation in an enclosure
Compact circuit breakers can be installed in a metal enclosure together with other
devices (contactors, motor-protection circuit breakers, LEDs, etc.)
Minimum enclosure dimensions
Circuit breakers
NSC100N
NS100 N/H
NS160 N/H
NS250 N/H
NS400 N/H
NS630 N/H

Height (mm)
300
457
457
457
-

Depth (mm)
150
130
130
130
-

Width (mm)
200
208
208
208
-

Installation enclosure

54

Schneider Electric

The UL 508 / CSA 22-2 no. 14 approval is


for a Manual Motor Controller (across the
line starter or general use).
The circuit breakers are 100 % rated.

E42651

UL 508 / CSA 22-2 no. 14 marking


LISTED MAN. MOTOR. CTRL.
34XL
NSC100N-NA

UL / CSA logo

This MMC is suitable for use on a circuit capable of delivering


not more than the short-circuit current rating of this MMC
indicated here below, or the upstream protective device
interrupting capability, whichever is less, when protected by
any protective device for Group fusing or Group installation.
SC current rating kA 50/60 Hz
Vac
240
42
480
25
600
10
Vac
115
230
460
575
1 ph 3 ph 1 ph 3 ph 1 ph 3 ph 1 ph 3 ph
hp
ratings (A)
2
2
5
5
1
16
10 7.5 10
5
1.5
15
20
7.5 10
10
3
3
10
15
20
3
3
7.5 10
2
25
10
2
20 15
32
5
5
30
10
5
7.5 10
3
30
20
30
40
15
7.5 10
15
20
30
40
3
25
50
10
40
10
20
30
60
5
25
63
5
40
70
50
15
25
60
10
30
7.5 10
80
15
40 75
60
30
30
10
40
75
50 100
100
20
15
30
tripping current 125%
100% rated
temperature rating
tightening torque
75C
wire size
Nm
lb-inch
14 AWG to 3/0 AWG Cu
50
5.5
12 AWG to 4/0 AWG Al

Breaking capacity

Horsepower rating

Cable cross-section
and tightening torques

E42650

NSC100 device marking


(circuit breaker with built-in trip unit)

LISTED MAN. MOTOR. CTRL.


34XL
NS100-160-250 N/H/NA

UL / CSA logo

Equipped with TMD/DE or STR trip unit


This MMC is suitable for use on a circuit capable of delivering
not more than the short-circuit current rating of this MMC
indicated here below, or the upstream protective device
interrupting capability, whichever is less, when protected by
any protective device for Group fusing or Group installation.
SC current rating kA 50/60 Hz
NS100 NS160 NS250
Vac
N
H
N
H
N
H
240
85
85
85
85
85 85
480
25
65
65
35
65 35
600
10
10
18
10
10 18
tripping current 125%
100% rated
temperature rating
Terminal kit
tightening torque
reference
75C
wire size
4P
Nm
3P
lb-inch
14 AWG to 3/0 AWG Cu
29242 29243
130
11.3
12 AWG to 4/0 AWG Al
4 AWG to 2 AWG Cu,Al

180

20

1 AWG to 350 kcmil Cu,Al

230

26

29259

Breaking capacity

Cable cross-section
and tightening torques

29260

E42651

NS100 to 250 device marking


(circuit breaker with interchangeable trip unit)

In=220A
Ir 166 177

STR 22 ME
7,2 Ir

187
198

157
148
140
132

IEC 947.4 / cl.10


7,0 s

209
220
Ir

> 1,05 Ir

13Ir

220A 1ph 3ph


hp
Vac
115 15 40
230 50 75
460 50 150
575 50 200
100% rated

test

Trip-unit marking

Schneider Electric

55

Functions and
characteristics

Earth-leakage protection
Overview of solutions

Earth-leakage protection is obtained by:


b fitting a Vigi module on the circuit breaker
(Compact NS100 to 630)
b installing a Micrologic 7.0 A control unit
(Compact NS630b to 3200)
b using a Vigirex relay and separate toroids
(all Compact circuit breakers).

Circuit breakers equipped with an add-on Vigi module


(Vigicompact)
Rated current (A)

100 630
NSC100 N
NSA160 N/E
NS125 E

NS100 to 250 N/H/L


NS400 and 630 N/H/L

054556

044333

Vigicompact

General circuit-breaker characteristics


pages 18, 42 and 53
Compact NS100 to 630 and NSA160 circuit breakers are presented in the Protection of
distribution systems section and the Compact NSC100 circuit breaker is presented in the
Protection of industrial control panels section.
Accompanying Vigi modules
Earth-leakage protection is achieved by installing a Vigi module directly on the circuit-breaker
terminals.

Circuit breakers equipped with a control unit offering


integrated earth-leakage protection and an external
rectangular sensor
Rated current (A)

630 3200
NS630b to 1000 N/H/L
NS1250 and 1600 N/H

NS1600b to 3200
E45178

E45151

Compact

General circuit-breaker characteristics


page 20
Compact NS630b to 3200 circuit breakers are presented in the Protection of distribution
systems section.
Accompanying control units
page 30
Micrologic 7.0 A electronic control units offer earth-leakage protection as standard.

Earth-leakage protection using a Vigirex relay


Earth-leakage relay

Separate toroids

044322

051352

Vigirex

Compact circuit breaker + Vigirex relay combination


Vigirex relays may be used to add external earth-leakage protection to Compact NS circuit
breakers. The circuit breakers must be equipped with an MN or MX voltage release. Vigirex
relays are very useful when special time-delay or tripping-threshold values are required, or when
there are major installation constraints (circuit breaker already installed and connected, limited
space available, etc.).
Vigirex-relay characteristics:
b sensitivity adjustable from 30 mA to 250 mA and eight time-delay settings (0 to 1 second)
b closed toroids (30 to 300 mm in diameter) or split toroids (46 to 110 mm in diameter).
Options:
b trip alarm by a fail-safe contact
b pre-alarm LED and contact (threshold = 0.5 x In)
b 400 Hz distribution systems, etc.
Compliance with standards:
b IEC 60947-2, appendix B
b French decree dated 14 November 1988
b IEC 60255-4 and IEC 60801-2 to 5 covering protection against nuisance tripping due to transient
overvoltages, lightning strikes, switching of devices on the distribution system, electrostatic
discharges, radiofrequency interference.
b IEC 60755, class A, immunity to DC components up to 6 mA
b VDE 664, operation down to -25 C.

56

Schneider Electric

Add-on Vigi module (Vigicompact)


for Compact NS100 to 630
044333

Vigicompact NSA160 and NSC100 circuit breakers


with earth-leakage protection
See pages 43 and 53, respectively.

Vigicompact NS100 to 630 circuit breakers


with earth-leakage protection
Addition of the Vigi module does not alter circuit-breaker characteristics:
b compliance with standards
b degree of protection, class II front-face isolation
b positive contact indication
b electrical characteristics
b trip-unit characteristics
b installation and connection modes
b indication, measurement and control auxiliaries
b installation and connection accessories.
Vigicompact NS250N

Dimensions and weights


Dimensions
3 poles
W x H x D (mm)
4 poles
Weight (kg)
3 poles
4 poles

NS100/160
105 x 236 x 86
140 x 236 x 86
2.5
3.2

NS250

2.8
3.4

NS400/630
135 x 355 x 110
180 x 355 x 110
8.8
10.8

E21007

Vigi earth-leakage protection module


avant test dilectrique
enlever ce couvercle
before dielectric test
remove this cover

310
150

t(ms)

60
0

T R

vigi
NS 250
200 / 440 V - 50 / 60 Hz

vigi MH
3

10
N 1 3 5

1
0,3

In(A)

HS 0,03 ( t = 0 )

1
2
3
4
5
6
7

T
2 4 6

sensitivity setting
time-delay setting (for selective earth-fault protection)
lead-seal fixture for controlled access to settings
test button simulating an earth-fault for regular
checks on the tripping function
reset button (reset required after earth-fault tripping)
rating plate
housing for SDV auxiliary contact

Plug-in circuit breaker


The Vigi module can be installed on a plug-in base.
Special accessories are required (see the section
on part numbers).

Compliance with standards:


b IEC 60947-2, appendix B
b French decree dated 14 November 1988
b IEC 60255-4 and IEC 60801-2 to 5 covering protection against nuisance tripping
due to transient overvoltages, lightning strikes, switching of devices on the
distribution system, electrostatic discharges, radiofrequency interference.
b IEC 60755, class A, immunity to DC components up to 6 mA
b VDE 664, operation down to -25 C.
Remote indications
Vigi modules may be equipped with an auxiliary contact (SDV) to remotely signal
tripping due to an earth fault.
Power supply
Vigi modules are self-supplied internally by the distribution-system voltage and
therefore do not require any external source. They continue to function even when
supplied by only two phases.

Vigi module selection table


Number of poles
NS125 E
NS100 N/H/L
NS160 N/H/L
NS250 N/H/L
NS400 N/H/L
NS630 N/H/L

Vigi ME Vigi MH

Vigi MB

3, 4 (1)
b
b
b
-

3, 4 (1)
b
b

3, 4 (1)
b
b
b
b
-

Protection characteristics
Sensitivity
fixed
adjustable
adjustable
In (A)
0.3
0.03 - 0.3 - 1 - 3 - 10
0.3 - 1 - 3 - 10 - 30
Time delay
Intentional
fixed
adjustable
adjustable
delay (ms)
< 40
0
60 (2) 150 (2) 310 (2)
0
60
150
310
Max. breaking
< 40
< 40 <140 <300 <800
< 40 < 140 < 300 < 800
time (ms)
Rated voltage
200...440 200... 440 - 440...550
200...440 - 440...550
V AC 50/60 Hz
(1) Vigi 3P modules may also be used on 3P circuit breakers used for single-phase or twophase protection.
(2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

Note.
The Vigi module for the Compact NSA160 circuit breaker is presented on page 43.

Schneider Electric

57

Control and isolation


Overview of solutions

E94915

Functions and
characteristics

Masterpact
NT

Masterpact
NW

source coupling
switch-disconnector

Masterpact
NW or NT

main power
distribution board for
industrial applications

main power distribution board


for commercial applications

15 -40 kA

y 1000 A

20 -80 kA

y 1600 A

replacement
source
industrial
distribution
board

modular subdistribution board

15 - 25 kA

y 160 A

y 400 A

final distribution
enclosure for
commercial
applications

local
isolation
enclosure

local
isolation
enclosure

automatic
control panel

source
changeover
system

y 160 A : 15 - 25 kA
y 400 A : 20 - 80 kA

local
isolation
enclosure

control panel

y 25 kA

y 10 kA
y 63 A

y 10 kA

y 5 kA

y 40 A
y 630 A

y 63 A

5-15 kA

y 125 A

N.B. adjacent to or built into the machine

Circuit breakerdisconnector

building utilities

building final
distribution

continuous processes

manufacturing processes
and individual machines
Switchdisconnector
standardised symbols

58

Interpact IN

054361

035050

056385

E45182

Compact NS

Interpact INS

Vario

Compact NS

Interpact INS

054629

Compact NS

Masterpact

086106

86087

052164

E58880

056470

Switch-disconnectors

NG125

Multi 9

Schneider Electric

86087

Compact NS250 switch-disconnector

044313

053041

053039

Compact switch-disconnectors are used to


control and isolate electrical distribution
circuits. In addition to these basic
functions, other functions for safety, remote
control and convenience include:
b earth-leakage protection
b auxiliary MN/MX releases
b remote operation
b ammeter, etc.
Compact switch-disconnectors may be
interlocked with another Compact switchdisconnector or circuit breaker to constitute
a source-changeover system.

Compact switch-disconnector
equipped with a Vigi earthleakage module

Schneider Electric

Compact switch-disconnector
equipped with a motor mechanism

MN/MX
voltage
release

59

Functions and
characteristics

Installation standards require upstream


protection. However, due to their high-set
magnetic release, Compact NSA125NA
and NSA160NA switch-disconnectors are
self protected.

Control and disconnection


Compact NSA125NA and NSA160NA
switch-disconnectors
Compact switch-disconnectors
Number of poles
Control

manual

Connections

electric
fixed

toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection

86085

withdrawable
Built-in connectors
Mounting
Front-panel cutout

Compact NSA125NA

for 1.5 to 90 mm2 cables


on DIN rail
45 mm high

Electrical characteristics as per IEC 60947-3 and EN 60947-3


Conventional thermal current (A)
Ith
60 C
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage (kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC
Rated operational current
le
AC 50/60 Hz

Short-circuit making capacity

lcm

(kA peak)

Short-time withstand current

lcw

(A rms)

mechanical
electrical

AC

electrical

AC

Suitability for isolation


Durability (C-O cycles)

220/240 V
380/415 V
440/480 V
500 V
minimum (switch-disconnector alone)
maximum (with protection circuit
breaker upstream)
1s
3s
20 s

690 V
440 V
250 V

AC22A
AC23A
AC23A

Positive contact indication


Pollution degree
Protection
Add-on earth-leakage protection

add-on Vigi module


combination with Vigirex relay

Additional indication and control auxiliaries


Indication contacts
Voltage releases
Installation and connection
Accessories
Dimensions (mm)
WxHxD
Weight (kg)

fixed, front connection


fixed, front connection

2/3P
4P
3P
4P

Source-changeover system (see section on "source-changeover systems")


Manual source-changeover systems

60

Schneider Electric

NSA125NA

NSA160NA

3, 4
b
b
b
b
b
b

3, 4
b
b
b
b
b
b

125
500
8
500
250
AC22A
125
125
125
125
2.1
330

160
500
8
500
250
AC22A
160
160
160
160

AC23A
125
125
125
100

AC23A
160
160
160
125

1500
1500
580
b
10000
5000
5000
5000
b
III
b
b
1 OF + 1 SD
MN or MX
terminal shields
depth adjuster
90 x 120 x 82.5
120 x 120 x 80
1.1
1.4
b

Schneider Electric

61

Functions and
characteristics

Installation standards require upstream


protection. However, due to their high-set
magnetic release, Compact NSC100NA
and NS100NA to 630NA switchdisconnectors are self protected.

Control and disconnection


Compact NSC100NA and
NS100NA to 630NA switchdisconnectors
Compact switch-disconnectors
Number of poles
Control

manual

Connections

electric
fixed

toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
front connection
rear connection

86087

plug-in (on base)


withdrawable (on chassis)
Electrical characteristics as per IEC 60947-3 and EN 60947-3
Conventional thermal current (A)
Ith
60 C
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage (kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC
Rated operational current
le
AC 50/60 Hz

Compact NS100NA

Short-circuit making capacit

lc

(kA peak

Short-time withstand curren

lc

(A rms

Suitability for isolatio


Durability (C-O cycles

mechanica
electrica

A
D

220/240 V
380/415 V
440/480 V (2)
500/525 V
660/690

250 V (1 P
500 V (2 P in series
minimum (switch-disconnector alone
maximum (with protectio
circuit breaker upstream
1
3
20

690
440
250

AC22
AC23
DC23

Positive contact indicatio


Pollution degre
Protectio
Add-on earth-leakage protectio
Additional indication and control auxiliarie
Indication contact
Voltage release

add-on Vigi modul


combination with Vigirex rela

MX shunt releas
MN undervoltage releas

Voltage-presence indicato
Current-transformer modul
Ammeter modul
Insulation-monitoring modul
Remote communication by bu
Device status indications (communicating auxiliary contacts
Device remote operation (communicating motor mechanism
Installatio
Accessorie

Dimensions (mm
W x H x
Weight (kg

terminal extensions and spreader


terminal shields and interphase barrier
escutcheon
fixed, front connectio
2/3
4
fixed, front connectio
3
4

Source-changeover system (see section "on source-changeover systems"


Manual source-changeover system
Remote-operated and automatic source-changeover system

(1) 2P in 3P case
(2) Suitable for 480 V NEMA

62

Schneider Electric

NSC100NA

NS100NA

NS160NA

NS250NA

NS400NA

NS630NA

3, 4
b
b
b
-

2 (1), 3, 4
b
b
b
b
b
b
b
b
b

2 (1), 3, 4
b
b
b
b
b
b
b
b
b

2 (1), 3, 4
b
b
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b
b
b

100
750
8
690
250
AC22A
100
100
100
100
DC22A
2.1
330

100
750
8
690
500
AC22A
100
100
100
100
100
DC22A
100
100
2.6
330

160
750
8
690
500
AC22A
160
160
160
160
160
DC22A
160
160
3.6
330

250
750
8
690
500
AC22A
250
250
250
250
250
DC22A
250
250
4.9
330

400
750
8
690
500
AC22A
400
400
400
400
400
DC22A
400
400
7.1
330

630
750
8
690
500
AC22A
630
630
630
630
630
DC22A
630
630
8.5
330

AC23A
100
100
100
100
DC23A
-

AC23A
100
100
100
100
100
DC23A
100
100

AC23A
160
160
160
160
160
DC23A
160
160

3500
3500
1350
b
20000
20000
10000 (20000 - In/2)
10000 (20000 - In/2)
b
III

AC23A
400
400
400
400
400
DC23A
400
400

1500
1500
580
b
20000
7000
7000
7000
b
III

1800
1800
690
b
50000
50000
30000 (50000 - In/2)
30000 (50000 - In/2)
b
III

b
b

b
b

b
b

b
b
b
-

b
b
b
b
b
b
b

b
b
b
b
b
b
b

b
-

b
b

b
b

b
b
b
90 x 120 x 80
120 x 120 x 80
0.9
1.2

b
b
b
105 x 161 x 86
140 x 161 x 86
1.5 to 1.8
2.0 to 2.2

b
b
b
140 x 255 x 110
185 x 255 x 110
5.2
6.8

b (locking)

b
b

b
b

Schneider Electric

2500
2500
960
b
40000
40000
20000 (40000 - In/2)
20000 (40000 - In/2)
b
III

AC23A
250
250
250
250
250
DC23A
250
250

5000
5000
1930
b
15000
15000
6000 (12000 - In/2)
6000 (12000 - In/2)
b
III

AC23A
630
630
630
630
630
DC23A
630
630

6000
6000
2320
b
15000
15000
4000 (8000 - In/2)
4000 (8000 - In/2)
b
III

63

Functions and
characteristics

E45179

Installation standards require upstream


protection.

Control and disconnection


Compact NS630bNA to NS1600NA
switch-disconnectors
Compact switch-disconnectors
Number of poles
Control

manual

Connections

electric
fixed

toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection

withdrawable (on chassis)


Electrical characteristics as per IEC 60947-3 and EN 60947-3
Conventional thermal current (A)
Ith
60 C
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage (kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC
Rated operational current
le
AC 50/60 Hz

220/240 V
380/415 V
440/480 V (1)
500/525 V
660/690 V
DC

Compact NS800NA

Short-circuit making capacity

lcm

(kA peak)

Short-time withstand current

lcw

(A rms)

mechanical
electrical

AC

Suitability for isolation


Durability (C-O cycles)

250 V (1P)
500 V (2P in series)
minimum (switch-disconnector alone)
maximum (with protection
circuit breaker upstream) (2)
0.5 s
1s
20 s

690 V
440 V

AC22A/In
AC23A/In

Positive contact indication


Pollution degree
Protection
Add-on earth-leakage protection
Additional indication and control auxiliaries
Indication contacts
Voltage releases

combination with Vigirex relay

MX shunt release
MN undervoltage release

Remote communication by bus


Device status indications (communicating auxiliary contacts)
Device remote operation (communicating motor mechanism)
Installation
Accessories

Dimensions (mm)
WxHxD
Weight (kg)

terminal extensions and spreaders


terminal shields and interphase barriers
escutcheons
fixed
3P
4P
fixed
3P
4P

Source-changeover system (see section "on source-changeover systems")


Manual source-changeover systems, remote-operated and automatic

(1) Suitable for 480 V NEMA.


(2) Protection by upstream type NS, NT or NW circuit breaker:
see additional technical information.

64

Schneider Electric

NS630bNA

NS800NA

NS1000NA

NS1250NA

NS1600NA

3, 4
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b

3, 4
b
b
b
b
b
b
b

630
750
8
690
500
AC22A
630
630
630
630
630
DC22A
50
330

800
750
8
690
500
AC22A
800
800
800
800
800
DC22A
50
330

1000
750
8
690
500
AC22A
1000
1000
1000
1000
1000
DC22A
50
330

1250
750
8
690
500
AC22A
1250
1250
1250
1250
1250
DC22A
50
330

1600
750
8
690
500
AC22A
1600
1600
1600
1600
1600
DC22A
50
330

25
17
4
b
10000
2000
2000
b
III

AC23A
630
630
630
630
630
DC23A
-

25
17
4
b
10000
2000
2000
b
III

AC23A
800
800
800
800
800
DC23A
-

25
17
4
b
10000
2000
2000
b
III

AC23A
1000
1000
1000
1000
1000
DC23A
-

25
17
4
b
10000
2000
2000
b
III

AC23A
1250
1250
1250
1250
1250
DC23A
-

AC23A
1600
1600
1600
1600
1520
DC23A
-

25
17
4
b
10000
1000
1000
b
III

b
b
b
b
b
b
b
b
b
327 x 210 x 147
327 x 280 x 147
14
18
b

Schneider Electric

65

Functions and
characteristics

Installation standards require upstream


protection. However, Compact NS1600b to
3200NA switch-disconnectors are selfprotected for all currents higher than
130 kA peak.

Control and disconnection


Compact NS1600b to 3200NA
switch-disconnectors
Compact switch-disconnectors
Number of poles
Control

manual

Connections

electric
fixed

toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection

withdrawable (on chassis)

E45182

Electrical characteristics as per IEC 60947-3 and EN 60947-3


Conventional thermal current (A)
Ith
60 C
Rated insulation voltage (V)
Ui
Rated impulse withstand voltage (kV)
Uimp
Rated operational voltage (V)
Ue
AC 50/60 Hz
DC
Rated operational current
le
AC 50/60 Hz

Short-circuit making capacity

Compact NS2000NA

lcm

(kA peak)

Short-time withstand current


lcw
(A rms)
Integrated instantaneous protection (kA peak 10 %)
0 %) 130
solation

n 1000
ication
II

III
III

130 1
b
b

1000
b
III

b
000

60
1000

600
1000

1000

Prot

ination with Vigirex relay b


nal indication and
dication contact
undervoltage
release b
ccessories esc
(mm) fi
0
W x H

b
60

220/240 V
380/415 V
440/480 V (1)
500/525 V
660/690 V
minimum (switch-disconnector alone)
maximum (with protection
circuit breaker upstream) (2)
3s

ion Add-on earth-leakage prot


Additi
b
MX shunt release b

cheon
3
P
5

Weight (kg) fixed 3P 23


4P 36Source-changeover system (see
ection "on source-changeover systems")Manual source-changeover

(1) Suitable for 480 V NEMA.


(2) Protection by upstream type NS, NT or NW circuit breaker:
see additional technical information.

66

Schneider Electric

NS1600bNA

NS2000NA

NS2500NA

NS3200NA

3, 4
b
b
-

3, 4
b
b
-

3, 4
b
b
-

3, 4
b
b
-

1600
750
8
690
500
AC22A
1600
1600
1600
1600
1600
135
178

2000
750
8
690
500
AC22A
2000
2000
2000
2000
2000
135
178

2500
750
8
690
500
AC22A
2500
2500
2500
2500
2500
135
178

3200
750
8
690
500
AC22A
3200
3200
3200
3200
3200
135
178

32
130
b
6000
1000
1000
b
III

AC23A
1600
1600
1600
1600
1600

32
130
b
6000
1000
1000
b
III

AC23A
2000
2000
2000
2000
2000

32
130
b
6000
1000
1000
b
III

AC23A
2500
2500
2500
2500
2500

AC23A
3200
3200
3200
3200
3200

32
130
b
6000
4000
2000
b
III

b
b
b
b
b
350 x 420 x 160
350 x 535 x 160
23
36
-

Schneider Electric

67

Source-changeover systems
Presentation

For complete, in-depth information, see the


Interpact, Compact, Masterpact sourcechangeover systems catalogue.

Manual source-changeover systems

87921

Functions and
characteristics

This is the most simple type. Intervention by technical personnel is required, i.e.
transfer from the normal source to the replacement source is not immediate.
A manual source-changeover system can be installed on two to three manuallycontrolled circuit breakers or switch-disconnectors. Interlocking is mechanical.
Interlocks prevent connection to both sources at the same time, even momentarily.

Remote-operated source-changeover systems


This is the most commonly employed system. No human intervention is required.
Switching from the normal to the replacement source is controlled electrically.
A remote-operated source-changeover system is made up of two or three circuit
breakers or switch-disconnectors linked by an electrical interlocking system
(different configurations possible). Device operation is backed up by a mechanical
interlocking fixture that prevents parallel connection if the electrical system
malfunctions or if an incorrect manual operation is attempted.

Automatic source-changeover systems

029693

Service sector
b hospital operating rooms
b safety systems for tall buildings
b computer rooms (banks, insurance companies, etc.)
b lighting systems in shopping centres

An automatic controller may be added to the remote-operated source-changeover


system for automatic source control according to programmable operating modes.
This solution ensures optimum energy management:
b switching to a replacement source depending on external requirements
b management of power sources
b regulation
b emergency source replacement, etc.
The automatic controller may be fitted with an option for communication with a
supervisor.

IMG0021

Industry
b assembly lines
b engine rooms on ships
b critical auxiliaries in thermal power stations

Infrastructure
b port and railway installations
b runway lighting systems
b control systems for military installations

68

Schneider Electric

Manual source-changeover systems

A manual source-changeover system can


be installed on two to three manuallyoperated circuit breakers or switchdisconnectors. Interlocking is mechanical.
Interlocks prevent connection to both
sources at the same time, even
momentarily.

Interlocking of two or three toggle-controlled devices


Two devices can be interlocked using this system. Two identical interlocking
systems can be used to interlock three devices installed side by side, in which case
one device is in the ON position and the two others are in the OFF position.
The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).
Combinations of Normal and Replacement devices
There are two interlocking-system models:
b Compact NS100 to 250
b Compact NS400 to 630 (can also be used for a Compact NS100 to 250).
Devices must be either all fixed or all withdrawable.

E21287

Interlocking of two devices with rotary handles


The rotary handles are padlocked with the devices in the OFF position.
The mechanism inhibits the two devices being closed at the same time, but does
allow for both to be open (OFF) at the same time.
Combinations of Normal and Replacement devices
All Compact NS100 to 1600 circuit breakers and switch-disconnectors with rotary
handles can be interlocked. Interlocking of a Compact NS100 to 630 with a
Compact NS630b to 1600 is not possible.
Interlocking of two toggle-controlled devices

Interlocking of a number of devices using keylocks


(captive keys)
Interlocking uses two identical keylocks with a single key. This solution enables
interlocking between two devices that are physically distant or that have
significantly different characteristics, for example between a low and a mediumvoltage device, or between Compact NS circuit breakers and switch-disconnectors.
A system of wall-mounted units with captive keys makes possible a large number
of combinations between many devices.
Combinations of Normal and Replacement devices
All Compact NS100 to 1600 circuit breakers and switch-disconnectors with rotary
handles or motor mechanisms can be interlocked.

E21399

ON
I
ON
I

ON
I

tripped

ON
I
reset

O
OFF

O O FF

tripped

reset

O
OFF

O O FF

Interlocking of two devices with rotary handles

E26766

A base plate designed for two Compact devices can be installed horizontally or
vertically on a mounting rail. Interlocking is carried out on the base plate by a
mechanism located behind the devices. Access to the device controls and trip units
is not blocked.
Combinations of Normal and Replacement devices
All manually operated Compact NS100 to 630 circuit breakers and switchdisconnectors can be interlocked.
Devices must be fixed or plug-in versions, with or without earth-leakage protection
or measurement modules.

ON

ON
I

Interlocking of two devices on a base plate

reset

O
OFF

O
OFF

E33943

Interlocking with keylocks

push
to
trip

push
to
trip

Interlocking on base plates

Schneider Electric

69

Source-changeover systems
Remote-operated systems

Functions and
characteristics

053042

Source-changeover system without a controller


In this case, the automatic-control system to initiate changeovers between the
Normal and Replacement sources under predefined conditions must be provided
by the installation designer.

E32699

Remote-operated source-changeover system


QR

053060

QN

053058

Auxiliary control plate

Source-changeover system with a controller

Controller

E32700

E79368

E79369

In this case, changeovers between the Normal and Replacement sources under
predefined conditions are initiated by a Merlin Gerin controller.

IN
LIN GER
MER

0 . OFF

0 . OFF

R
N

UN =

UN =

0,5s

ON /

OFF

Test

UR

UN

ON /

Test

OFF

0,5s

/O

/O

fault

fault

FFO
hsup

hsup

FFO

test

manu

NO h
sup

R
N

FFO
d e gr

ahcs

id

10

degr
ahcs
id

352

10

B US

352

stop

FFO
hsup

I
NO

IN
LIN GER
MER

N
R

UN =

UN =

UR

UN
ON /
ON /
OFF

OFF

I
/O

/O
fault

fault
auto

stop

manu

test
STOP

rator
gene

R
N

FFO
hsup

NO h
sup

FFO
hsup

NO h
sup

FFO

O
d e gr

ahcs

id

FFO

O
degr
ahcs
id

352

Coupling accessory

10
352

Interlocking by cables
E32701

Compact NS630b to 1600


Interlocking by rods

This accessory may be used with the source-changeover system (with or without a
controller) to facilitate connections.

10

7
A remote-operated source-changeover system is made up of:
1 circuit breaker QN equipped with a motor mechanism and auxiliary contacts, connected to
the Normal source
2 circuit breaker QR equipped with a motor mechanism and auxiliary contacts, connected to
the Replacement source
3 mounting base plate with mechanical interlocking (NS100 to 630) or an interlocking system
using rods or cables (NS630b to 1600)
4 electrical interlocking unit. IVE for NS100 to 630 or an electrical system provided by the
installer for NS630b to 1600. Electrical interlocking system example: part no. 51156903 in the
source-changeover system catalogue.
Switching between sources can be automated by adding:
5 ACP auxiliary control plate
6 BA or UA controller, or an electrical system provided by the installer for NS630b to 1600.
Electrical system example: part no. 51156904 and 51156904 in the sourcechangeover system catalogue.
Accessory:
7 coupling accessory (downstream connection) for NS100 to 630.

70

Schneider Electric

Controllers

When used with a remote-operated sourcechangeover system, the BA or UA


controllers initiate the automatic
changeover operations according to userdefined sequences.

Controller

BA

UA

b
b
b
b

b
b
b
b

b
b
b
b
b

Four-position switch
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources OFF)

Automatic operation
053058R

Monitoring of the Normal source and automatic changeover


Engine generator set start-up control
Delayed shutdown (adjustable) of engine generator set
Load shedding and reconnection of non-priority loads
Changeover to Replacement source if one of the Normalsource phases is absent

Test
By opening of the P25M circuit breaker upstream
of the controller
By pressing the test button on the front of the controller

b
b

Indications
Circuit-breaker status indication on the front
of the controller: ON, OFF, fault trip
Automatic-mode indication contact

Selection of type of Normal source


(single-phase or three-phase)
Voluntary transfer to Replacement source
b
(e.g. energy-management commands)
During peak-tariff periods (energy-management commands),
forced operation on Normal source if Replacement source is
not operational
Additional control contact (not in controller).
b
Transfer to Replacement source only if contact closed
(e.g. UR frequency check)
Replacement-source maximum start-up time setting

Other functions

053058

BA controller

b
b

Options
Communications option

Power supply
Control voltages (1)

220 to 240 V 50/60 Hz


380 to 415 V 50/60 Hz
440 V 60 Hz

b
b
b

b
b
b

0.35 Un y voltage y 0.7 Un b


0.5 Un y voltage y 0.7 Un
voltage u 0.85 Un
b

b
b
b

Operating thresholds
UA controller

Undervoltage
Phase failure
Voltage presence

IP degree of protection against penetration of solid bodies and liquids (EN 60529)
and IK degree of protection against external mechanical impacts (EN 50102)
Front
Side
Connectors
Front

IP40
IP30
IP20
IK07

b
b
b
b

b
b
b
b

Characteristics of output contacts


Rated thermal current (A)
Minimum load

8
10 mA at 12 V

AC
DC
Utilisation category (IEC 60947-5-1)
AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A)
24 V
8
7
5
6
8
2
48 V
8
7
5
5
2
110 V
8
6
4
4
0.6
220/240 V
8
6
4
3
250 V
0.4
380/415 V
5
440 V
4
660/690 V
(1) Power supplied by the ACP auxiliary control plate. The supply voltage must be the same for
the ACP plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the
same as the distribution-system voltage, the Normal and Replacement sources can be used
directly for the power supply. If not, a BC-type or equivalent isolation transformer must be used.

Schneider Electric

71

Communication
Compact NS100 to 630

Integration of the circuit breaker or the


switch-disconnector in a supervison system
requires either the communicating
auxiliaries or the SC150 interface.
Compact devices fit perfectly in the SMS
Powerlogic electrical installation
management system by communicating
using Digipact protocols. An external
gateway offers communication via other
networks including:
b Profibus
b Ethernet

There are two possibilities for the 100 to 630 A range:


b communicating auxiliaries
They replace the standard auxiliaries and connect directly to the Digipact bus.
Three equipment levels:
v communicating auxiliary contacts, comprising:
- OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts
- electronic module
- prefabricated wiring.
v communicating auxiliary contacts and motor-mechanism module, comprising:
- OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts
- motor-mechanism module (220 V AC) (1)
- electronic module
- prefabricated wiring.
v communicating carriage switches for the chassis, comprising:
- CE / CD (connected/disconnected position) contacts
- electronic module
- wiring connector.
b SC150 interface
Using the SC150 interface, it is possible to integrate a device equipped with noncommunicating auxiliaries into a supervison system.
The SC150 interface is used to connect:
v the auxiliary contacts on the circuit breaker (OF, SD, SDE, SDV, CD, CE)
v the remote-operation system (on, off, reset)
v the communication output for the STR53UE and STR43ME electronic trip units
equipped with the COM option
v an unassigned digital input.

053172

Functions and
characteristics

054481

Compact NS equipped with communicating auxiliary contacts


and motor-mechanism module

054516

Withdrawable Compact NS on its chassis equipped with


communicating auxiliary contacts

SC150 indication and control interface

(1) For voltages other than 220 V AC, use a standard motor-mechanism module (noncommunicating) together with an SC150 indication and control interface.

72

Schneider Electric

E94526

Overview of functions
Software

Communication
interface

RS 232C,Ethernet
RS 485

Communication
bus
IN
LIN GER
MERSV
pulsar

JBus
BBus
com

com
error

24V
OK
error

3
N1

N1

Data concentrator
DC150

Device
SC150 indication and
control interface

comp

act

0NH

NB25 Uimp 8kV.


Icu
(kA)
Ue
100
(V)
0
70
220/245
65
380/41
50
440 5
10
500/520
85
660/69
250
0% Icu
Ics=10
cat A
Ui 750V.

Digipact Bus

-2
BS CEI
IEC947
VDE

UNE

2
ed
discharg
compactL
NS250 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V)
150
220/240
130
380/415
70
440
20
500
100
600/690

NEMA

5...8

push
to
trip

Im 10

O OFF

250
250
cat A TM Icu C
100%
Ics = 250A/40

0
125/16

UTE

VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

5
6

Ir

.8
.9

Ir

Im

x 250A

x 250A

auto
manu

O
push

OFF

I
push

ON

comp

Compact NS with
communicating
auxiliary contacts
and motor mechanism

act

0NH

NB25 Uimp 8kV.


Icu
Ui 750V.
(kA)
Ue
100
(V)
0
70
220/245
65
380/41
50
440 5
10
500/520
85
660/69
250
0% Icu
Ics=10
cat A
-2
BS CEI
IEC947
VDE

UNE

2
ed
discharg
compactL
NS250 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V)
150
220/240
130
380/415
70
440
20
500
100
600/690

NEMA

5...8

push
to
trip

Im 10

O OFF

250
250
cat A TM Icu C
100%
Ics = 250A/40

0
125/16

UTE

VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

5
6

Ir

.8
.9

Ir

Im

x 250A

x 250A

auto
manu

O
push

OFF

I
push

ON

: hard wire
: communication bus

Compact circuit breaker with standard


auxiliary contacts and motor mechanism.
Trip unit with the COM option.

Compact with
communicating SC150
auxiliaries
Device identification
Address
Rating

b
-

b
-

b
b
b
b

b
b
b
b

b
b

b
b

Indication of status conditions


OF (on/off)
SD (trip indication)
SDE (fault-trip indication)
CE/CD (connected/disconnected position)

Controls
ON/OFF
LED reset

Protection settings
Reading of the protection settings

Operating and maintenance aids


Measurements:
Fault readings:
Indications:

Schneider Electric

currents
type of fault
operation counter

b
b
b

73

Communication
Compact NS630b to 1600
COM option in Compact

The COM option is required for integration


of the circuit breaker or switchdisconnector in a supervision system.
Compact uses the Digipact or Modbus
communications protocol for full
compatibility with the SMS PowerLogic
electrical-installation management
systems. An external gateway is available
for communication on other networks:
b Profibus
b Ethernet
The eco COM is limited to the transmission
of metering data and does not allow the
control of the circuit breaker.

For fixed circuit breakers, the COM option is made up of:


b a "device" communication module, installed behind the Micrologic control unit
and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually
operated devices; OF, SDE micro-contacts for electrically operated devices) and its
kit for connection to a communicating motor-mechanism module.
For withdrawable circuit breakers, the COM option is made up of:
b a "device" communication module, installed behind the Micrologic control unit
and supplied with its set of sensors (OF, SD, SDE micro-contacts for manually
operated devices; OF, SDE micro-contacts for electrically operated devices) and its
kit for connection to a communicating motor-mechanism module
b a "chassis" communication module supplied separately with its set of sensors
(CE, CD and CT contacts).
Status indication by the COM option is independent of the circuit breaker indication
contacts. These contacts remain available for conventional uses.
Digipact or Modbus "device" communication module
This module is independent of the control unit. It receives and transmits information
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
Consumption: 30 mA, 24 V.
Digipact or Modbus "chassis" communication module
This module is independent of the control unit. The Modbus "chassis"
communication module makes it possible to address the chassis and to maintain
the address when the circuit breaker is in the disconnected position.
Consumption: 30 mA, 24 V.
Communicating motor-mechanism module
A bus link is used to transmit remote ON/OFF orders to the circuit breaker.
A communicating motor-mechanism module must be used.
The remote-tripping function (MX or MN) is independent of the communication option.

056431

Functions and
characteristics

056401

E59437A

Digipact "device"
communication module.

Communication
bus

Communication
bus

Digipact "chassis"
communication module
OF
SD
SDE

OF
SDE

I on

tripped

Communication
bus

++

CD

CCM

modb

C
CT

C
CE

OF
SD
SDE

us

4
C
CE

C
CD

C
CT
OF
SDE

1
E45183

++

us

CT

modb

CD

CT

CCM

Electrically operated
fixed device

CD

Communication
bus

CE

0 OF

CE

056431

reset

Manually operated
fixed device

Modbus "device"
communication module

3
5

Modbus "chassis"
communication module
Electrically operated
drawout device

Manually operated
drawout device

1
2
3

"device" communication module


"chassis" communication module
OF, SD, SDE "device" sensors

4
5

CE, CD and CT "chassis" sensors


communicating motor-mechanism module

Note. eco COM


The eco COM Modbus is intended to fit the circuit breaker with a module display (DMB300,
DMC300).

74

Schneider Electric

POWERLOGIC System Manager Demo


Edit View Setup Control Display Reports

File

Tools Window Help


5 seconds

Sampling Mode : MANUAL

Time

Event

Module

Phase A-N Voltage - Harmonics Analysis


Phase 1-N

1,20

Harmonics(RMS)

Fundamental:

1,00

RMS:
RMS-H:

0,80
% Fundamental

E47071

Overview of functions

Peak:
CF:
THD:

H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07

0,60
OK

0,40

Compact circuit breakers and switch-disconnectors are compatible with the


Digipact or Modbus COM option.
The COM option may be used with all types of control units to:
b identify the device
b indicate status conditions
b control the device.
Depending on the different types of Micrologic (S, A) control units, the COM option
also offers:
b setting of the protections functions
b analysis of the AC-power parameters for operating-assistance and maintenance
purposes

0,20

Switch-disconnector with Circuit breaker with


communication bus
communication bus

0,00
H2

H3

H4

H5

H6

H7

H8

H9

H10

H11

H12

Harmonics

Ready

ONLINE: DEMO

No working system

9:30

Digipact

Modbus

Digipact

Modbus

b
-

b
-

b
b
b
b

b
b
b
b

S
S
S
S

A
A
A
A

S
S
S
S

A
A
A
A

b
-

b
-

Device identification
Address
Rating
Type of device
Type of control unit
Type of long-time rating plug

A
A

A
A
A
A

A
A

Status indications
OF (on/off)
SD (trip indication)
SDE (fault-trip indication)
CE/CD (connected/
disconnected position)

Controls
MX/XF ON/OFF
Spring charging
Reset of the mechanical
indicator

Protections settings
Reading of protections settings

Operating and maintenance aids


Measurements
current
A
Fault readings
type of fault
Note.
S = Micrologic 2.0 and 5.0
A = Micrologic with ammeter
See the description of the Micrologic control units for further details on protection.

Schneider Electric

A
A

75

Communication
Compact NS630b to 1600 (cont.)
Compact in a communication network

E94525

Functions and
characteristics

Software

Communication
interface

RS 232C, Ethernet
RS 485

Communication
bus
IN
LIN GER
MERSV
pulsar

JBus
BBus
com

com
error

24V
OK
error

3
N1

N1

Data concentrator
DC150

Device

Digipact Bus

Modbus Bus
Compact

Compact

Devices
Circuit breakers equipped with Micrologic control units may be connected to either
a Digipact or Modbus communication bus. The information made available
depends on the type of Micrologic control unit (S, A) and on the type of
communication bus (Digipact or Modbus).
Switch-disconnectors may be connected exclusively to the Digipact communication
bus.

Communication bus
Digipact bus
The Digipact bus is the internal bus of the low-voltage switchboard in which the
Digipact communicating devices are installed (Compact with Digipact COM,
PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data
concentrator (see the Powerlogic System catalogue).
Addresses
Addressing is carried out by the DC150 data concentrator.
Number of devices
The maximum number of devices that may be connected to the Digipact bus is
calculated in terms of communication points. These points correspond to the
amount of traffic the bus can handle. The total number of points for the various
devices connected to a single bus must not exceed 100.
If the required devices represent more than 100 points, add a second Digipact
internal bus.
Communicating device
DC150 data concentrator
Micrologic + Digipact COM
PM150
SC150
UA150

Number of points
4
4
4
4
4

Length of bus
The maximum recommended length for the Digipact internal bus is 200 meters.
Bus power source
Power is supplied by the DC150 data concentrator (24 V).

76

Schneider Electric

Modbus bus
The Modbus RS 485 (JBus) system is an open bus on which communicating
Modbus devices (Compact with Modbus COM, PM300, Sepam, Vigilohm, etc.) are
installed. All types of PLCs and microcomputers may be connected to the bus.
Addresses
The software layer of the Modbus protocol can manage up to 255 addresses (1 to 255).
The device communication module comprises three addresses linked to:
b circuit-breaker manager
b measurement manager
b protection manager.
The chassis communication module comprises one address linked to:
b the chassis manager.
The division of the system into four managers secures data exchange with the
supervision system and the circuit-breaker actuators.
The manager addresses are automatically derived from the circuit-breaker address
@xx entered via the Micrologic control unit (the default address is 47).
logic addresses
@xx
@xx + 50
@xx + 200
@xx + 100

Circuit-breaker manager
Chassis manager
Measurement manager
Protection manager

(1 to 47)
(51 to 97)
(201 to 247)
(101 to 147)

Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM300, Sepam,
Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data
exchanged and the desired response time. The RS 485 physical layer offers up to
32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device).
A drawout device uses two connection points (communication modules on the
device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).

Communication interface
The Modbus bus may be connected to the central processing device in any of
three manners:
b direct link to a PLC. The communication interface is not required if the PLC is
equipped with a Modbus port;
b direct link to a computer. The Modbus (RS 485) / Serial port (RS 232)
communication interface is required;
b connection to a TCP/IP (Ethernet) network. The Modbus (RS 485) / TCP/IP
(Ethernet) communication interface is required.

Software
To make use of the information provided by the communicating devices, software
with a Modbus driver must be used.

Micrologic utilities
This is a set of Modbus drivers that may be used with a PC to:
b display the variables (I, U, P, E, etc.) with the RDU (Remote Display Utility)
b read/write the settings with the RSU (Remote Setting Utility)
b remotely control (ON / OFF) the device with the RCU (Remote Control Utility)
These utilities are available on request.

System Manager Software (SMS)


SMS is a power management software for the control and monitoring of LV and MV
electrical installations.
The SMS family includes a number of products for all types of applications, from
standalone systems to networked power management of multiple buildings.
SMS can communicate with all intelligent devices of the electrical installation
including:
b Power Meter and Circuit Monitor products
b LV circuit breakers and switch-disconnectors
b Sepam units.

Schneider Electric

77

The COM option is required for integration


of the circuit breaker or switchdisconnector in a supervision system.
Compact uses the Digipact or Modbus
communications protocol for full
compatibility with the SMS PowerLogic
electrical-installation management
systems. An external gateway is available
for communication on other networks:
b Profibus
b Ethernet

For fixed circuit breakers, the COM option is made up of:


b a "device" communication module, installed behind the Micrologic control unit
and supplied with its set of sensors (OF, SD, SDE micro-contacts).
Status indication by the COM option is independent of the circuit breaker indication
contacts. These contacts remain available for conventional uses.
Digipact or Modbus "device" communication module
This module is independent of the control unit. It receives and transmits information
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
Consumption: 30 mA, 24 V.
E59438

Communication
Compact NS1600b to 3200
COM option in Compact

056431

Functions and
characteristics

Communication
bus

Digipact "device"
communication module.
OF
SD
SDE

2
1

OFF
OFF

056431

COM
module

Modbus "device"
communication module

78

1
2

"Device" communication module


OF, SD, SDE "device" sensors

Schneider Electric

POWERLOGIC System Manager Demo


Edit View Setup Control Display Reports

File

Tools Window Help


5 seconds

Sampling Mode : MANUAL

Time

Event

Module

Phase A-N Voltage - Harmonics Analysis


Phase 1-N

1,20

Harmonics(RMS)

Fundamental:

1,00

RMS:
RMS-H:

0,80
% Fundamental

E47071

Overview of functions

Peak:
CF:
THD:

H1: 118.09
H2: 0.01
H3: 0.45
H4: 0.03
H5: 0.45
H6: 0.04
H7: 1.27
H8: 0.05
H9: 0.42
H10: 0.01
H11: 1.03
H12: 0.07

0,60
OK

0,40

Compact circuit breakers and switch-disconnectors are compatible with the


Digipact or Modbus COM option.
The COM option may be used with all types of control units to:
b identify the device
b indicate status conditions
b control the device.
Depending on the different types of Micrologic (S, A) control units, the COM option
also offers:
b setting of the protections functions
b analysis of the AC-power parameters for operating-assistance and maintenance
purposes

0,20

Switch-disconnector with Circuit breaker with


communication bus
communication bus

0,00
H2

H3

H4

H5

H6

H7

H8

H9

H10

H11

H12

Harmonics

Ready

ONLINE: DEMO

No working system

9:30

Digipact

Modbus

Digipact

Modbus

b
-

b
-

b
b
b

b
b
b

S
S
S

Device identification
Address
Rating
Type of device
Type of control unit
Type of long-time rating plug

A
A

A
A
A
A

A
A

Status indications
OF (on/off)
SD (trip indication)
SDE (fault-trip indication)

A
A
A

S
S
S

A
A
A

Protections settings
Reading of protections settings

Operating and maintenance aids


Measurements
current
A
Fault readings
type of fault
Note.
See the description of the Micrologic control units for further details on protection.

Schneider Electric

A
A

79

Electrical and mechanical


accessories
Compact NS80H-MA
E58516

Functions and
characteristics

Sealable terminal
shield

Direct rotary
handle
Auxiliary
contact

pact

com
A
H-M
.
NS 80 Uimp 8kV
0V.
Icu (kA)
100
Ue (V)
70
220/240
65
380/415
25
440
6
500/525
10
660/690
250

Ui75

ON
I

cat A
Icu
100%
Ics =

DIN-rail
plate

IEC
UTE

2
UNE
947. BS CEI

push
to
trip

VDE

push
to
trip

O
OFF

2
push
to
trip

ON
I

ed
tripp
C2
C1
SHT z
MX/
/50-60H
240V
220-

Voltage release

5...8

t
rese

O
OFF

Sealable terminal
shield

Extended rotary
handle

Auxiliary
contact

88

Schneider Electric

Compact NSC100N, NSA160

E58517

Front accessory for NSC100N (45 mm standard door cutout)

pact

com
.
125E
p 6kV
NSA
V. Uim (kA)
U 500
Icu
25
16
10
5

Ue (V)
220/240
380/415
440
125
Ics =

50%

Icu

CEI
947.2
IEC VDE BS

UNE

UTE

E58518

45 mm front

Sealable terminal
shield

Auxiliary
contact

pact
com

.
125E
p 6kV
NSA
V. Uim (kA)
U 500
Icu
25
Ue (V)
16
220/240
10
380/415
5
440
125
Ics

= 50%

Icu

CEI
947.2
IEC VDE BS

UNE

UTE

ON
I

ed
tripp
C2
C1
SHT z
MX/
/50-60H
240V
220-

Voltage release

5...8

t
rese

O
OFF

Extended rotary
handle

Sealable terminal
shield

Schneider Electric

89

Electrical and mechanical


accessories
Compact NS80H-MA,
NSC100N and NSA160

Functions and
characteristics

Installation

E43597

E43595

Installation positions

E43596

E59278

Compact NS80H-MA and NSC100N circuit breakers may be mounted vertically,


horizontally or flat on their back without any derating of characteristics. They are
designed for easy installation in the various types of switchboards of each market
and country.
Mounting on a DIN rail is possible using a special adapter.
The NSA160 circuit breaker may be mounted exclusively on a DIN rail.
These three circuit breakers are available in the fixed, front-connection version.

OFF

push
to
trip

E54455

NS80H-MA and NSC100N:


mounting on backplate or
mounting plate.

NS80H-MA and NSC100N:


mounting on DIN rail
(optional).
NSA160: mounting on DIN
rail (standard).

Standard 45 mm front,
optional on NSC100N,
standard on NSA160.

Compact NS80H-MA, NSC100N and NSA160 circuit


breakers are equipped as standard with connectors
for bare copper or aluminium cables from 1.5 to
70 mm2.
Distribution connector
This connector screws directly to the standard
connectors. It is used to connect up to three cables:
b flexible cables from 1 to 10 mm2
b rigid cables from 1.5 to 16 mm2
b with crimped or self-crimping ferrules from 1.5 to
4 mm2.

E39432

Front connection of bare cables

Distribution connector

Terminal shields
Insulating accessories used for protection against
direct contact with power circuits (degree of protection
IP40, IK07). They are supplied with sealing
accessories.
For voltages u 500 V, terminal shields are mandatory.

E58553

Insulation of live parts

Terminal shields

90

Schneider Electric

044314

Indication contacts

Indication contacts
Common-point changeover contacts provide remote circuitbreaker status information. They can be used for indications,
electrical locking, relaying, etc.

A single type of contact, complying with the IEC 60947-5 international


recommendation, provides different indication functions, depending on where it is
inserted in the device.
b OF (ON/OFF) - indicates the position of the circuit breaker contacts
b SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault (Compact NSC100N and NSA160)
v operation of a voltage release.
Returns to de-energised state when the circuit breaker is reset.
b SDV (earth-leakage fault indication) - inserted in the Vigi module on Compact
NSC100N and NSA160 devices, it indicates that the circuit breaker has tripped due
to an earth fault. Returns to de-energised state when the circuit breaker is reset.
All the above auxiliary contacts are also available in low-level versions capable of
switching very low loads (e.g. for the control of PLCs or electronic circuits).
Characteristics
Contacts

054550

Rated thermal current (A)


Minimum load
Utilisation category (IEC 60947-5-1)
Operational 24 V
current (A)
48 V
110 V
220/240 V
250 V
380/440 V

Standard

Low level

6
100 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
-

5
2 mA at 15 V DC
AC12 AC15 DC12
5
3
5
5
3
2.5
5
2.5
0.8
5
2
5
0.3
5
1.5
-

DC14
1
0.2
0.05
0.03
-

DC14
1
0.2
0.05
0.03
-

Remote tripping

MX or MN voltage release

Schneider Electric

MX or MN voltage releases are used to trip the circuit breaker.


MN undervoltage release
This release trips the circuit breaker when the control voltage drops below a
tripping threshold:
b tripping threshold between 0.35 and 0.7 times the rated voltage
b circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Circuit breaker tripping by an MN release meets the requirements of standard
IEC 60947-2.
Time-delay unit for an MN release (Compact NS80H-MA)
Eliminates nuisance tripping due to transient voltage dips lasting y 200 ms:
It is used in conjunction with:
b a 250 V DC MN release, control voltage 220/240 V AC
b a 48 V DC MN release, control voltage 48 V AC.
MX shunt release
Trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20 ms) or maintained.
Operation
When the circuit breaker has been tripped by an MN or MX release, it must be
reset locally.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary,
is not possible.
Mechanical characteristics
b endurance is equal to 50 % of the mechanical endurance of the circuit breaker
b the releases clip in behind the front cover
b connection using wires up to 1.5 mm2 to integrated terminal blocks.
Electrical characteristics
b consumption:
v pick-up (MX): < 5 VA
v seal-in (MN): < 5 VA
b response time: < 50 ms.

91

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS80H-MA, NSC100N and
NSA160 (cont.)

054558

Rotary handles

054563

Compact NS80H-MA with a direct rotary handle

Compact NS80H-MA with an extended rotary handle

92

There are two types of rotary handle:


b direct rotary handle
b extended rotary handle.
There are two models:
b standard with a black handle
b VDE with a red handle and yellow front for machine-tool control.
Direct rotary handle (NS80H-MA and NSC100N)
Degree of protection IP40, IK07.
The direct rotary handle maintains:
b visibility of and access to trip unit settings
b suitability for isolation
b indication of the three positions O (OFF), I (ON) and tripped
b access to the push to trip button
b circuit breaker locking capability in the OFF position by one to three padlocks,
shackle diameter 5 to 8 mm (not supplied).
It replaces the circuit-breaker front cover.
Accessories transform the standard direct rotary handle for the following situations:
b motor control centre (MCC) switchboards:
v door opening disabled when the circuit breaker is ON
v circuit-breaker closing is disabled if the door is open
b a higher degree of protection (IP43, IK07)
b machine-tool control, complying with CNOMO E03.81.501, IP54, IK08.
Extended rotary handle
Degree of protection IP55, IK08.
This handle makes it possible to operate circuit breakers installed at the back of
switchboards, from the switchboard front.
It maintains:
b suitability for isolation
b indication of the three positions O (OFF), I (ON) and tripped
b access to trip unit settings, when the switchboard door is open
b circuit breaker locking capability in the OFF position by one to three padlocks,
shackle diameter 5 to 8 mm (not supplied).
The door cannot be opened if the circuit breaker is ON or locked.
The extended rotary handle is made up of:
b a unit that replaces the front cover of the circuit breaker (secured by screws)
b an assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally
b an extension shaft that must be adjusted to the distance (min/max distance
between back of circuit breaker and door is 185/600 mm).

Schneider Electric

Locking systems

E58552

Locking in the OFF position guarantees isolation as per IEC 60947-2.


Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).

Toggle locking using a removable device

Outgoing-circuit identification

E18595

Compact NS80H-MA and NSC100N devices come with clip-in labels for handwritten indications.
It is also possible to use pre-printed Telemecanique labels (part number AB1-** (8 digits).

P
D E P. P O M

.P
DE P

push
to
trip

Identification accessories

Schneider Electric

93

Electrical and mechanical


accessories
Compact NS100 to 630 (fixed version)
E58523

Functions and
characteristics

Sealable terminal
shield
que
dilectri rnes
test
avant ce cache-bo
c test
enlever
dielectri shield
terminal
before
this
L3
remove
L2

L1

0V 220/60

z
50/60H

Voltage-presence
indicator

Rear connector
Connectors
One-piece
spreader

Interphase barriers
2
arged
disch
ct
compa L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V)
0
150
220/245
130
380/41
70
440
20
500 0
100
600/69

ON
I

O OFF
5...8

250
Icu
cat A
100%
Ics =
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

1
5..

.8

auto

NS25 Uimp 8kV.


Ui 750V. Icu(kA)
150
Ue(V)
0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
250
Icu
cat A
100%
Ics =

Icu
(kA)
100
70
65
50
10
85

Ue
(V)
40
220/2
15
380/4
440
25
500/5
90
660/6
250
Icu
00%
Ics=1
cat A
47-2
BS CEI
IEC9
VDE

OFF

I
push

ON

ON
I

com
50NH
NB2 . Uimp 8kV.

Ui 750V

O
push

manu
ct
compa L

pact

UNE

push
to
trip

OFF

VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

NEMA

125/

UTE

Im 10

act
comp L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V) 0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
250
Icu
cat A
100%
Ics =

D
TM 250
40C
250A/

160

push
to
trip

5
6

Ir

reset

.8

Ir

Im

reset
push
to
trip

OFF

Motor-mechanism
module

VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

x 250A

.9

Direct rotary
handle

x 250A

Rear insulating
screens

ON
I

Auxiliary contact
tripped

5..

reset

O
OFF

.8

Extended rotary
handle

Voltage release

80
40

120

Ammeter module

que
dilectri le
test
avant ce couverc
enlever
c test
dilectri
cover
before this
remove

vigi
Hz

NS 250 V-50/60
200/525

-25

310
5

50

t(ms)

60
0

H
vigiM
6
2 4

10

1
In(A)
0,3

HS

0A
160/25

STR

t=0)
0,03(

22 SE

90 %Ir
105

Current-transformer
module

test

Im
.9

0A
In=25

.85

.95

.8
.98
.7
.63

alarm

Ir

8
2
1.5

3
10
xIr

xIn

Ir Im

Insulation-monitoring
module

Trip unit

Sealable terminal
shield

94

Schneider Electric

E58715

Compact NS100 to 630


(plug-in and withdrawable versions)

Sealable terminal
shield
que
dilectri rnes
test
avant ce cache-bo
c test
enlever
dielectri shield
terminal
before
this
L3
remove
L2

L1

0V 220/60

z
50/60H

Voltage-presence
indicator

Terminal extensions and spreaders

Rear connectors
Connectors for
withdrawable
devices

One-piece
spreader

Connectors

Interphase barriers

Plug-in base

2
arged
disch

O OFF

ct
compa L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
150
130
70
20
100
Ue(V)
0
220/245
380/41
440
500 0
600/69

ON
I

5...8

250
Icu
cat A
100%
Ics =
VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

Chassis side
plate

Control-wire
connection
plate

1
2
3
4
5
6
7
8
9

1
5..

.8

auto

push

manu

OFF

I
push

ON

ct

pact
com
H

ON
I

50N
NB2 . Uimp 8kV.
Icu
Ui 750V
(kA)
Ue
100
(V)
40
70
220/2
15
65
380/4
50
440
25
10
500/5
90
85
660/6
250
Icu
00%
Ics=1
A
cat
47-2
BS CEI
IEC9
VDE

UNE

Ui 750V. Icu(kA
150
Ue(V)
0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
250
Icu
cat A
100%
Ics =

reset
push
to
trip

OFF

VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

NEMA

push
to
trip

Im 10

act
comp L
0
NS25 Uimp 8kV.
Ui 750V. Icu(kA)
150
Ue(V) 0
150
220/245
130
380/41
70
440
20
500 0
100
600/69
250
Icu
cat A
100%
Ics =

D
TM 250
40C
250A/

160

125/

UTE

5
6

Ir

compa L
0
NS25 Uimp 8kV.
)

.8

Ir

Im

reset
push
to
trip

OFF

VDE
UTE
947-2UNE NEMA
IEC
CEI
BS

x 250A

.9

Direct rotary
handle

Motor-mechanism
module

x 250A

ON
I

Auxiliary contact

tripped

5..

reset

Circuit-breaker
side plate

O
OFF

.8

Extended rotary
handle

Voltage release

Control-wire
connection
on chassis
80
40

120

que
dilectri le
test
avant ce couverc
enlever
c test
dilectri
cover
before this
remove

Ammeter module

vigi
Hz

NS 250 V-50/60
200/525

-25

310
5

50

t(ms)

60
0

H
vigiM
6
2 4

10

1
In(A)
0,3

HS

0A
160/25

STR

t=0)
0,03(

Current-transformer module

22 SE

90 %Ir
105

test

Im
4

Ir
.9

0A
In=25

.85

.95

.8
.98
.7
.63

alarm

8
1.5

3
2

10
xIr

xIn

Ir Im

Insulation-monitoring
module

Trip unit

Sealable terminal
shield

Schneider Electric

95

Electrical and mechanical


accessories
Compact NS100 to 630

Functions and
characteristics

045345

Installation
Fixed circuit breakers

E58530

E58714

E58529

Compact circuit breakers may be mounted vertically, horizontally or flat on their


back without any derating of characteristics. They are designed for easy installation
in the various types of switchboards of each market and country.

E59278

Fixed Compact NS250H

Mounting on a backplate
(solid or slotted)

Mounting on rails

Mounting on DIN rail (with


adapter)

E18850

Installation positions

Mounting on a Prisma functional mounting plate.

041632

E21019

E21017

E21018

Circuit breaker on a plug-in base

The plug-in configuration makes it


possible to:
b extract and/or rapidly replace the circuit
breaker without having to touch
connections
b allow for the addition of future circuits
at a later date.

Mounting on a backplate

E59279

Compact NS250H on a plug-in base

Installation positions

96

Mounting through a front


panel

Mounting on rails

Protection against direct contacts with power circuits


b circuit breaker plugged in = IP4
b circuit breaker removed = IP2
b circuit breaker removed, base equipped with shutters = IP4
Parts of a plug-in configuration
b Compact circuit breaker
b set of power connectors added to the circuit breaker
b plug-in base for mounting on a backplate or on rails
b insulating screen, for use when the circuit breaker is installed on a backplate with
front connections
b safety trip, installed on the circuit breaker, that causes automatic tripping if the
circuit breaker is ON, before engaging or withdrawing it. The safety trip does not
prevent circuit breaker operation, even when it has been removed.
b mandatory short terminal shields.
Accessories
Insulating accessories can be used to:
b protect against direct contact
b increase insulation between phases.
Schneider Electric

E21282

Circuit breaker on a withdrawable chassis

Connected

Disconnected

Removed

The chassis is made up of two side plates installed on the base and two other
plates mounted on the circuit breaker.
Accessories
b auxiliary contacts for installation on the fixed part, indicating the connected and
disconnected positions
b toggle collar for circuit breakers with a toggle mounted through a front panel,
intended to maintain the degree of protection whatever the position of the circuit
breaker (supplied with a toggle extension)
b keylock which, depending on the bolt fitted, can be used to:
v prevent insertion for connection
v lock the circuit breaker in the connected or disconnected positions.
b telescopic shaft for extended rotary handles.

041879

b disconnected position - the power circuits


are disconnected, but the circuit breaker is
still on the chassis and may still be operated
(ON, OFF, push-to-trip).
b the circuit breaker may be locked using
1 to 3 padlocks (shackle diameter 5 to
8 mm), to prevent connection.
b the auxiliaries can be tested (with manual
auxiliary connector).

E59279

Compact NS250H on a withdrawable chassis

Installation positions

Front and rear connections

E58716

E58733

Fixed, plug-in and withdrawable Compact devices may all be equipped with front
and rear connections.
Fixed device

Front connection

Rear connection

E58718

E58717

E58719

Plug-in and withdrawable devices

Front connection

Schneider Electric

Rear connection

Rear connection through


a backplate

97

Front connection of bars or cables


with lugs

E58535
E58536

Straight terminal extensions


for NS100 to 250

Edgewise terminal
extensions for NS400 to 630

E58537

The Compact NS100 to NS630 devices are equipped


as standard with terminals comprising snap-in nuts
with screws (M8 for NS100 to 250, M10 for NS400 to
630) for direct connection to insulated bars or cables
with lugs.
Additional terminal extensions (right-angle, edgewise,
spreaders) are available for all connection
requirements. Spreaders (52.5 or 70 mm pitch) may
be fitted on the Compact NS400 to 630.
Lugs
Lugs are different for copper and aluminium cables.
They are supplied with interphase barriers and are
compatible with the long terminal shields.
b the small lugs for copper cables may be used for
cables with the following cross-sectional areas:
v 120, 150 or 185 mm2 (NS100 to 250)
v 240 or 300 mm2 (NS400 to 630).
Crimping by hexagonal barrels or punching.
b the small lugs for aluminium cables may be used for
cables with the following cross-sectional areas:
v 150 or 185 mm2 (NS100 to 250)
v 240 or 300 mm2 (NS400 to 630).
Crimping by hexagonal barrels.
Spreaders
Spreaders increase the pitch of the terminals.
They are not compatible with terminal shields on the
Compact NS100 to 250.
The one-piece spreader increases the pitch, thus
making it possible to use the connection accessories
of a larger device (e.g. a Compact NS100 to 250 can
be fitted with the accessories of a Compact NS400 to
630). The one-piece spreader also provides protection
against direct contact (see page 101).

Right-angle terminal
extensions

Small lug for copper cables

Small lug for aluminium


cables

E58539

E58532

E58720

E58531

Connection of fixed devices

E58534

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)

E58538

E54456

Functions and
characteristics

E58533

E58721

Spreaders

98

One-piece spreader

Schneider Electric

E58722

E54468
E54469

1-cable connector
for NS100 to 250

1-cable connector
for NS400 to 630
E54470

E58540

Bare-cable connectors for Compact NS devices may


be used for both copper and aluminium cables.
1-cable connectors for Compact NS100 to 250
The connectors snap directly on to the device
terminals or clip onto right-angle and straight terminal
extensions as well as spreaders.
1-cable and 2-cable connectors for Compact
NS400 to 630
The connectors are screwed to device terminals or
right-angle terminal extensions.
Distribution connectors for Compact NS100 to 250
These connectors are screwed directly to device
terminals. Interphase barriers are supplied with
distribution connectors, but may be replaced by long
terminal shields. Each connector can receive six
cables with cross-sectional areas ranging from 1.5 to
35 mm2 each.
Polybloc distribution block for Compact NS100 to 630
The Polybloc connects directly to the device terminals
and is used to connect up to six or nine flexible or rigid
cables with cross-sectional areas not exceeding
10 mm2, to each pole. Connection is made to spring
terminals without screws.

2-cable connector
for NS400 to 630
E54471

E54457

Front connection of bare cables

E54472

Distribution connector
for NS100 to 250

Rear connections for bars or cables with lugs are


available in two lengths. Bars may be positioned flat,
on edge or at 45 angles depending on how the rear
connections are positioned.
The rear connections are simply fitted to the device
connection terminals. All combinations of rear
connection lengths and positions are possible on a
given device. The device is mounted on a backplate.
For the connection of cables without lugs, the 1-cable
connectors for Compact NS100 to 250 may be simply
clipped onto the rear connections.

Two lengths

E58725

E58723

E54456

Rear connection

E58724

Polybloc distribution block


for NS100 to 250

E58726

Four positions

Connection
of bare cables
to NS100 to 250.

Schneider Electric

99

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)

E54456

Functions and
characteristics

Connection of plug-in devices


Connection of bars or cables with lugs

E58718

E58727

E58717

The plug-in base is equipped with terminals which, depending on their orientation,
serve for front and rear connection. For rear connection of a base mounted on a
backplate, the terminals must be replaced by insulated, long right-angle terminal
extensions.
For Compact NS630 devices, connection most often requires the 52.5 or 70 mm
pitch spreaders.
Connection accessories
See the Connection of fixed devices section.

Front connection with


spreaders

Rear connection

E58719

Front connection

Rear connection of a base


mounted on a backplate
E54457

Connection of bare cables

E58728

E58729

All terminals may be equipped with bare-cable connectors. See the Connection of
fixed devices section.

Plug-in base for Compact


NS100 to 250 equipped with
1-cable connectors

100

Plug-in base for Compact


NS400 to 630 equipped with
2-cable connectors

Schneider Electric

056384

Connection of large cables may require an increase in


the distance between the device terminals. The onepiece spreader is an accessory that can also be fitted
on Interpact INS switch-disconnectors. It offers the
following features:
b increases the pitch of the circuit-breaker terminals to
correspond to that of the next largest frame size
b compatible with all the connection accessories
available for the next largest frame size (connectors,
terminal extensions, etc.)
b enhances insulation between phases in comparison
with standard spreaders.

One-piece spreader

E58730

One-piece spreader

NS100 to 250 NS400 to 630


Pitch without
spreaders (mm)
Pitch with standard
spreaders (mm)
Pitch with one-piece
spreader (mm)

35

45

45

52.5 or 70

45

70

Mounting

E58732

E58731

When equipped with a one-piece spreader, Compact


NS circuit breakers may be installed either at the back
of a switchboard or on the front panel with a raiser.
b devices with different frame sizes can thus be
aligned in the switchboard
b the same mounting plate can be used for all devices
(including Interpact INS switch-disconnectors).

Mounting at the back of a


switchboard

Schneider Electric

Connection and insulation


accessories are identical to
those for Interpact INS
switch-disconnectors

Mounting behind the front


panel with a raiser

101

049221

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)

Compact NS equipped with terminal shields.

Terminal shields are sealable insulating accessories


used for protection against direct contact with power
circuits (degree of protection IP40, IK07). They are
supplied with sealing accessories.
Terminal-shield selection
b fixed circuit breaker, front connection - long terminal
shields
b fixed circuit breaker, rear connection - short terminal
shields
b for voltages u 500 V, terminal shields are mandatory
b for voltages > 600 V, special connection kit with
terminal shields and insulating screens
b for Compact NS400 to 630 with spreaders, special
terminal shields for spreaders
b for withdrawable circuit breaker (plug-in and chassis
type), short terminal shields on the device are
mandatory. Terminal shields on the base are possible.
Long terminal shields for plug-in bases are used to:
b protect against direct contact with power circuits
(degree of protection IP40, IK07)
b increase insulation between phases.
Insulating accessories for plug-in bases include:
b an adapter offering the same connection
possibilities as the circuit breaker
b long terminal shields for the plug-in base.

Terminal shields

E58542

Terminal shields

E58541

Insulation of live parts

Interphase barriers

Safety accessories for maximum insulation at the


power-connection points:
b they clip easily onto the circuit breaker
b not compatible with terminal shields
b special version for plug-in bases.

E58543

Interphase barriers

Rear insulating screens


Safety accessories for insulation between connections
and the backplate. Compatible with terminal shields or
interphase barriers.

Rear insulating screens

102

Schneider Electric

E28443

OF1

SD

Connection of electrical auxiliaries

SDE OF2

Fixed configuration
MN/MX

motor mechanism

Auxiliary circuits exit the device through a knock-out in the front cover.

OR

E18585

rotary handle

SDV

OF1 OF2 OF3

SD

SDE

Plug-in and withdrawable configurations


MN/MX

motor mechanism
E18586

OR

rotary handle

SDV

Compact NS400 to 630

E21398

E21397

Automatic auxiliary connectors


Auxiliary circuits exit the circuit breaker via one to three automatic auxiliary
connectors (nine wires each). These are made up of:
b a moving part, connected to the circuit breaker via a support (one support per
circuit breaker)
b a fixed part, mounted on the plug-in base, equipped with connectors for bare
cables up to 2.5 mm2.
Selection of automatic auxiliary connectors.
For Compact NS400 to 630, connection wires for the options installed with trip unit
STR53UE also exit via the automatic auxiliary connectors.

connector 2
connector 1 OF2/SDV
OF1
SDE/MT
SD
MT
MN/MX

Compact NS100 to 250

connector 3
OF3/SDV
connector 2 COM
connector 1 OF2
T
OF1
SDE/MT
SD
MT
MN/MX

Compact NS400 to 630

Manual auxiliary connector for withdrawable configurations


Withdrawable circuit breakers may be equipped with one to three plugs with nine
wires each. In disconnected position, the auxiliaries remain connected and can
therefore be tested by operating the circuit breaker.
E18587

E28444

Compact NS100/160/250

Each auxiliary is equipped with a terminal block with


numbered terminals for connection of wires up to:
b 1.5 mm2 for auxiliary contacts and voltage releases
b 2.5 mm2 for the motor-mechanism module.

Schneider Electric

Nine-wire manual auxiliary


connector

103

044314

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)
Indication contacts

Changeover contacts

All the auxiliary contacts opposite are also available


in low-level versions capable of switching very low
loads (e.g. for the control of PLCs or electronic
circuits).

Common-point changeover contacts are used to remote circuit-breaker status


information and can thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
b OF (ON/OFF) - indicates the position of the circuit breaker contacts
b SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault
v operation of a voltage release
v operation of the push to trip button
v disconnection when the device is ON.
Returns to de-energised state when the circuit breaker is reset.
b SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
b SDV (Earth-leakage fault indication) - indicates that the circuit breaker has
tripped due to an earth fault.
Returns to de-energised state when the circuit breaker is reset.
b CAM (early-make or early-break function) - indicates the position of the rotary
handle. Used in particular for advanced opening of safety trip devices (early break)
or to energise a control device prior to circuit-breaker closing (early make)
b CE / CD (connected/disconnected position) - microswitch type carriage switches
for withdrawable circuit breakers
Installation
b OF, SD, SDE and SDV functions - a single type of contact provides all these
different indication functions, depending on where it is inserted in the device. The
contacts clip into slots behind the front cover of the circuit breaker (or the Vigi
module for the SDV function).
The SDE function on a circuit breaker equipped with a thermal-magnetic trip unit
requires the SDE actuator.
b CAM function - the contact fits into the rotary-handle unit (direct or extended).
b CE / CD (connected/disconnected) function - two parts must be fitted on the fixed
and moving parts of the chassis.
Electrical characteristics of auxiliary contacts
Contacts
Rated thermal current (A)
Minimum load
Utilisation cat. (IEC 60947-5-1)
Operational 24 V
current (A)
48 V
110 V
220/240 V
250 V
380/440 V
660/690 V

104

Standard

Low level

6
100 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
6
0.1
-

5
2 mA at 15 V DC
AC12 AC15 DC12
5
3
5
5
3
2.5
5
2.5
0.8
5
2
5
0.3
5
1.5
-

DC14
1
0.2
0.05
0.03
-

DC14
1
0.2
0.05
0.03
-

Schneider Electric

045349

Rotary handles
There are two types of rotary handle:
b direct rotary handle
b extended rotary handle.
There are two models:
b standard with a black handle
b VDE with a red handle and yellow front for machine-tool control.

Direct rotary handle

044316

Compact NS250L with a direct rotary handle

Degree of protection IP40, IK07.


The direct rotary handle maintains:
b visibility of and access to trip unit settings
b suitability for isolation
b indication of the three positions O (OFF), I (ON) and tripped
b access to the push to trip button
b circuit breaker locking capability in the OFF position by one to three padlocks,
shackle diameter 5 to 8 mm (not supplied).
It replaces the circuit-breaker front cover.
Accessories transform the standard direct rotary handle for the following situations:
b motor control centre (MCC) switchboards:
v door opening disabled when the circuit breaker is ON
v circuit-breaker closing is disabled if the door is open
b a higher degree of protection (IP43, IK07)
b machine-tool control, complying with CNOMO E03.81.501, IP54, IK08.

Extended rotary handle


Compact NS250L with an extended rotary handle

Schneider Electric

Degree of protection IP 55, IK08.


This handle makes it possible to operate circuit breakers installed at the back of
switchboards, from the switchboard front.
It maintains:
b suitability for isolation
b indication of the three positions O (OFF), I (ON) and tripped
b access to trip unit settings, when the switchboard door is open
b circuit breaker locking capability in the OFF position by one to three padlocks,
shackle diameter 5 to 8 mm (not supplied).
The door cannot be opened if the circuit breaker is ON or locked.
The extended rotary handle is made up of:
b a unit that replaces the front cover of the circuit breaker (secured by screws)
b an assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally
b an extension shaft that must be adjusted to the distance. The min/max distance
between the back of circuit breaker and door is:
v 185 to 600 mm for Compact NS100 to 250
v 210 to 625 mm for Compact NS400 to 630.
For withdrawable configurations, the extended rotary handle is also available with a
telescopic shaft with two stable positions.

105

044313

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)
Remote tripping

MX or MN voltage release

106

MX or MN voltage releases are used to trip the circuit breaker.


MN undervoltage release
This release trips the circuit breaker when the control voltage drops below a
tripping threshold:
b tripping threshold between 0.35 and 0.7 times the rated voltage
b circuit breaker closing is possible if the voltage exceeds 0.85 times the rated
voltage.
For a lower value, circuit breaker closing cannot be guaranteed.
Circuit breaker tripping by an MN release meets the requirements of standard
IEC 60947-2.
Time-delay unit for an MN release
Eliminates nuisance tripping due to transient voltage dips lasting 200 ms.
It is used in conjunction with:
b a 250 V DC MN release, control voltage 220/240 V AC
b a 48 V DC MN release, control voltage 48 V AC.
MX shunt release
Trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20 ms) or maintained.
Operation
When the circuit breaker has been tripped by an MN or MX release, it must be
reset locally.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary,
is not possible.
Mechanical characteristics
b endurance is equal to 50 % of the mechanical endurance of the circuit breaker
b the releases clip in behind the front cover
b connection using wires up to 1.5 mm2, to integrated terminal blocks.
Electrical characteristics
b consumption:
v pick-up (MX): < 10 VA
v seal-in (MN and MNR): < 5 VA.
b response time: < 50 ms.

Schneider Electric

047313

Motor-mechanism module
When equipped with a motor-mechanism module, Compact NS circuit breakers
feature very high mechanical endurance as well as easy and sure operation:
b all circuit-breaker indications and information remain visible and accessible,
including trip-unit settings and indications
b suitability for isolation is maintained and padlocking remains possible
b double insulation of the front face.
Applications
b local motor-driven operation, centralised operation, automatic distribution control
b normal/standby source changeover or switching to a replacement source to
optimise energy costs
b load shedding and reconnection to optimise energy costs
b synchrocoupling.
Automatic operation
b circuit-breaker ON and OFF controlled by two impulse-type or maintained control
signals
b automatic spring charging following voluntary tripping (by MN or MX),
with standard wiring
b mandatory manual reset following tripping due to an electrical fault.
Manual operation
b transfer to manual mode using a switch (9) with possibility of remote mode
indication
b circuit-breaker ON and OFF controlled by 2 pushbuttons
b recharging of stored-energy system by pumping the lever 9 times
b padlocking in OFF position.
Installation and connection
All installation (fixed, plug-in/withdrawable) and connection possibilities are
maintained.
Motor-mechanism module connections are made behind its front cover to
integrated terminals, for cables up to 2.5 mm2.
Accessories
b keylock for locking in OFF position
b operations counter for the Compact NS400 and NS630, indicating the number of
ON and OFF cycles. The counter must be installed on the front of the motormechanism module.
Characteristics

Compact NS250H with motor mechanism

E21006

compact

NS400 H
Ui 750V. Uimp 8kV.
Ue
Icu
(V)
(kA)
220/240
380/415
440
500/525
600/690

100
70
65
50
20

cat A
Ics = 100% Icu

O OFF

charged

IEC 947-2
UTE VDE BS
UNE NEMA

CEI

In = 400A

manu

10

push OFF

push ON

auto

Motor mechanism

MT100 to MT630

Response time (ms)

1
2
3
4
5

contact position indicator (suitability for isolation)


outgoing-circuit identification labels
spring status indicator (charged, discharged)
locking device (keylock)
locking device (OFF position), using 1 to 3 padlocks,
shackle diameter 5 to 8 mm, not supplied
6 manual spring-charging lever
7 I (ON) pushbutton
8 O (OFF) pushbutton
9 manual/auto mode selection switch. The position of this
switch can be indicated remotely
10 operations counter (Compact NS400/630)

opening
closing
cycles/minute max.
DC

Rate
Control voltage (V)

< 600
< 80
4
24/30 - 48/60
110/130 - 250
48 (50 Hz) - 110/130
220/240 - 380/440
y 500
y 500
y 500
y 500

AC 50/60 Hz
Consumption

(1)

DC (W)
AC (VA)

opening
closing
opening
closing

E21300

Electrical endurance
Circuit breaker + motor-mechanism module, in thousands of operations
(IEC 60947-2), at 440 V.

50
40
30

NS100

20

NS160

15
10

NS250

NS400

NS630

0,1

0,2

0,3

0,5

0,7

I/In

(1) For NS100/250, motor "vibratory" type consider inrush


current as 2 In during 10 ms cycling.
Schneider Electric

107

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)

048287

Indications and measurement


Voltage presence indicator
The indicator detects and indicates that circuit breaker terminals are supplied with
power.
Installation
b in the long or short terminal shields, via the knockouts
b not compatible with the motor-mechanism module
b upstream or downstream of the circuit breaker
b degree of protection IP40, IK04.
Electrical characteristics
Operates on all networks with voltages ranging from 220 to 550 V AC.

Current-transformer module

041892

Compact NS630L with voltage-presence indicator

This module enables direct connection of a measurement device such as an


ammeter or a Digipact power meter (not supplied).
Installation
b directly on the downstream circuit-breaker terminals
b degree of protection IP40, IK04
b class II insulation between front and the power circuits
b connection to 6 integrated connectors for cables up to 2.5 mm2.
Electrical characteristics
b transformer with 5 A secondary winding.
b accuracy class 3 for the following output-power consumptions:
v rating 100 A: 1.6 VA
v rating 150 A: 3 VA
v rating 250 A: 5 VA
v rating 400/630A: 8 VA.

Ammeter and Imax ammeter modules

045212

Compact NS630H with current-transformer module

Ammeter module
Measures and displays (dial-type ammeter) the current of each phase (selection of
phases by 3-position switch in front).
Imax ammeter module
Measures and displays (dial-type ammeter) the maximum current flowing in the
middle phase. The Imax value can be reset on the front.
Installation
b identical for both types of ammeter module
b directly on the downstream circuit-breaker terminals
b ammeter clips into module in any of four 90 positions, i.e. can be installed of
devices mounted both vertically and horizontally
b degree of protection IP40, IK04
b class II insulation between front and the power circuits.
Electrical characteristics
b ammeter module: accuracy class 4.5
b Imax ammeter module:
v accuracy 6 %
v maximum currents are displayed only if they last at least 15 minutes.

Compact NS250L with ammeter module

108

Schneider Electric

041896

Insulation-monitoring module
This module detects and indicates an insulation drop on a load circuit (TN-S or TT
systems).
Operation is identical to that of a Vigi module, but without circuit-breaker tripping.
Indication by a red LED in front.
An auxiliary contact may be installed for remote insulation-drop indications.
Installation
b directly on the downstream circuit-breaker terminals
b degree of protection: IP40, IK04
b double insulation of the front face.
Electrical characteristics
b settings: 100, 200, 500 and 1000 mA
b accuracy: -50 +0 %
b time delay following drop: 5 to 10 seconds
b AC-system voltage: 200 to 440 V AC and 440 to 550 V AC.

Compact NS250H with insulation-monitoring module

053172

Communication
Communicating versions of the auxiliary contacts and the motor-mechanism
module also exist for integration in a Digipact communications system. They simply
replace the standard electrical auxiliaries.
Using the STR53UE and STR43ME trip units equipped with the COM
communications option, it is possible to transmit data to Digipact modules:
b settings
b rms values of phase and neutral currents
b current of the most heavily loaded phase
b overload alarm in progress
b tripping cause (overload, short-circuit, etc.).

054481

Compact NS equipped with communicating auxiliary contacts


and motor-mechanism module

Withdrawable Compact NS equipped with communicating


auxiliary contacts

Schneider Electric

109

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)

Functions and
characteristics

Locking systems
Locking in the OFF position guarantees isolation as per IEC 60947-2.
Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device
Toggle

Direct rotary handle

MCC rotary handle


Rotary handle
Extended rotary handle

Means

Required
accessories

lock in OFF position


lock in OFF or
ON position
lock in OFF position

padlock
padlock

removable device
fixed device

lock in OFF position


lock in OFF position
lock in OFF position,
door opening prevented
lock in OFF position,
motor mechanism
locked out

Motor mechanism

padlock
keylock
padlock
padlock
keylock
padlock
keylock

locking
device + keylock

keylock

locking device
(keylock incorporated)

E18620

E58545

E58544

Function

ON
I

pr
of
al
ux

O
OFF

Locking of the toggle using a


removable device

110

Locking of the toggle using a


fixed device

Locking of the rotary handle


using a padlock or a keylock.

Schneider Electric

048803

Individual enclosures

E44458

Heavy-duty insulating individual enclosure for Compact NS

Compact NS and Vigicompact NS devices with two, three or four poles may be
installed in individual enclosures.
All fixed, front connections are possible, except right-angle and edgewise terminal
extensions. Spreaders may be installed in the enclosures intended for Interpact
Compact and Vigicompact NS250 to 630 devices.
There are two models of enclosures:
b heavy-duty metal individual enclosure, with:
v metal enclosure
v door with keylock and cut-out for rotary handle
v direct rotary handle (CNOMO, IP55, IK08)
v device mounting plate
v removable plate (without holes) for cable entry through bottom
b heavy-duty insulating individual enclosure, with:
v insulating enclosure
v transparent cover, screwed, lead sealable, with cut-out for rotary handle
v extended rotary handle
v device mounting plate
v removable plates (without holes) for cable entry through bottom and/or top.
Dimensions (W x H x D in mm)
b metal enclosures:
W
D
v Compact NS100 to 160:
300 x 400 x 200
v Vigicompact NS100 to 160:
400 x 500 x 200
v Compact NS250 to 400:
400 x 600 x 200
v Compact NS630:
600 x 800 x 275
v Vigicompact NS250 to 630:
600 x 800 x 275
b insulating enclosures:
H
v Compact/Vigicompact NS100 to 160: 270 x 360 x 235
v Compact NS250:
270 x 540 x 235
v Compact NS400 to 630:
360 x 720 x 235
v Vigicompact NS250 to 630:
360 x 720 x 235

Schneider Electric

111

Electrical and mechanical


accessories
Compact NS100 to 630 (cont.)

Functions and
characteristics

E23938

E23936

E23935

Escutcheons are an optional feature mounted on the


switchboard door. They increase the degree of
protection to at least IP40, IK07.

E21265

Escutcheons

ON
I

push
to
trip

Toggle cover
b degree of protection IP43,
IK07
b fits on the front of the
circuit breaker.

Front-panel escutcheon for


rotary handle.
Secures to the panel by four
screws, from the front.
For circuit breaker with motor
mechanism and Vigi module,
use the protection collar for
front panel mounting (see
below).

E22039

Front-panel escutcheons for


toggle and Vigi module
(NSA160). Secures to the
panel, from the front.

O
OFF

80
40
0

120

Protection collar for toggle and Vigi


module on withdrawable devices

E21267

Front-panel escutcheons for


ammeter module. Secures to
the panel by four screws,
from the front.

Protection collars maintain the degree of protection,


whatever the position of the device (connected,
disconnected).
b front-panel escutcheons are mandatory (same as
those for rotary handles and ammeter modules)
b collars are mounted on the device using two screws
b escutcheons are attached to the switchboard
b a toggle extension is supplied with the collar.
For the insulation-monitoring module, use the same
elements as for the Vigi module.
Front-panel escutcheons for motor mechanism,
rotary handles, ammeter modules
Same as for fixed devices.

112

Schneider Electric

Outgoing-circuit identification

E18595

Compact NS100 to 630 devices come with clip-in labels for hand-written indications.
It is also possible to use pre-printed Telemecanique labels part number AB1-**:
v Compact NS100 to 250: 8 digits
v Compact NS400 to 630: 16 digits.

P
D E P. P O M

.P
DE P

push
to
trip

Identification accessories

Sealing accessories

E18596

This option includes the elements required to fit lead seals to prevent:
b front removal
b rotary-handle removal
b opening of the motor-mechanism module
b access to auxiliaries
b access to trip-unit settings
b trip-unit removal
b access to earth-leakage protection settings
b terminal-shield removal
b access to power connections.

Sealing accessories

Schneider Electric

113

Electrical and mechanical


accessories
Compact NS630b to 1600
(fixed version)
E59224

Functions and
characteristics

Sealable terminal
shield

Terminal extension for


cables with lugs
Interphase barriers

Connection kit
for connectors

Vertical connection
adapter

Spreader

Phase
barriers
Spreader

Rear connectors

Auxiliary contact

Voltage release

I on

I
O
push

push

ON

Manual control with


front connection

OFF

arged
disch

O OFF

trippe

0 OF

I on

012

53

reset

Manual control with


rear connection

trippe

Direct rotary
handle

reset

0 OF

Electrical control with


mixed connection

tripped

reset

Extended rotary
handle
Communications
module

Connection kit
for connectors

Sealable terminal
shield
Escutcheon

114

Schneider Electric

E59225

Compact NS630 to 1600


(withdrawable version)

Terminal extention for


cables with lugs

Interphase barriers

Vertical connection
adapter
Spreader
Rear connectors

Spreader

Auxiliary contact

Voltage release

Chassis with front or


rear connection

I on

I
O
push

push

ON

Manual operation

OFF

trippe

arged
disch

O OFF

reset

0 OF

I on

012

trippe

53

Direct rotary
handle

reset

0 OF

Electrical operation
tripped

reset

Communications
module

Escutcheon

Schneider Electric

Extended rotary
handle

Transparent cover

115

Electrical and mechanical


accessories
Compact NS630b to 1600

Functions and
characteristics

E45151

Installation
Fixed configuration

E59227A

E59226A

Compact NS630b to 1600 circuit breakers may be installed vertically, horizontally


or flat on their back.

E59278

Fixed Compact NS800H

Mounting on a backplate

Withdrawable configuration

E59228A

E59229A

Compact NS630b to 1600 circuit breakers should be installed vertically only.

E45176

The withdrawable configuration makes it


possible to:
b extract and/or rapidly replace the circuit
breaker without having to touch
connections;
b allow for the addition of future circuits at
a later date.

Mounting on rails

Rear mounting on rails

E59231

E59230

Mounting on a backplate

E59281A

Withdrawable Compact NS800H

Device on mounting plate

116

Device on rails

Schneider Electric

E59232A

Connected

Test

Disconnected

Removed

The multifunctional chassis for Compact NS630b to 1600 devices is particularly


suited for incoming circuit breakers. Features include:
b device connection and disconnection through a door, using a crank that can be
stored in the chassis
b three positions (connected, test and disconnected) that are indicated:
v locally by a position indicator
v remotely by carriage switches (3 for the connected position, 2 for the
disconnected position and 1 for the test position)
b circuit-breaker ON/OFF commands through a switchboard front panel.
Locking
There are extensive locking possibilities:
b chassis locking in connected, disconnected and test positions using three
padlocks and two keylocks, on the switchboard front panel
b door interlock (inhibits door opening with breaker in connected position)
b racking interlock (inhibits racking with door open)
b locking in each of the connected, disconnected and test positions during device
connection or disconnection. Continuation to the next position requires pressing a
release button to free the crank.
Other safety function
Mismatch protection ensures that a circuit breaker is installed only in a chassis with
compatible characteristics.

E59267A

The device may be in one of four positions


on the chassis:
b connected position. The power circuits
and auxiliary contacts are all connected
b test position. The power circuits are
disconnected. The auxiliary contacts are
still connected and the device can be
operated electrically
b disconnected position. The power circuits
and auxiliary contacts are all disconnected,
however the device is still mounted on the
chassis. It can be operated manually (ON,
OFF, "push to trip").
b removed position. All circuits are
disconnected. The device simply rests on
the chassis rails and can be removed.

3
4
5

6
7
8
9
10

1
2
3
4
5
6
7
8
9
10

Schneider Electric

mismatch protection
door interlock
racking interlock
keylock locking
padlock locking
position indicator
chassis front plate (accessible with cubicle door closed)
crank entry
reset button
crank storage

117

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)

Compact NS630b to 1600 fixed and


withdrawable devices can be connected
using:
b horizontal or vertical rear connections
b front connections
b mixed connections
b a combination of front and rear
connections.

Types of connection

E59235

Front connection

Rear connection
Vertical

E59234A

E59233A

Horizontal

Simply turn a horizontal rear connector 90 to make it a vertical connector.

E59237

E59236

Combination of front and rear connections

Note.
Compact circuit breakers can be connected indifferently with
bare-copper, tinned-copper and tinned-aluminium conductors,
requiring no particular treatment.

118

Schneider Electric

Fixed, front-connection Compact NS630b to 1600


devices are equipped with terminals comprising
captive screws for direct connection of bars.
Other connection possibilities for bars include verticalconnection adapters for edgewise bars and spreaders
to increase the pole pitch to 95 mm.
If the vertical connection adapters are front oriented,
then it is mandatory to install the arc chute screen in
order to comply with the safety clearances.

E46426A

Bars

Vertical-connection adapters

E59239A

E59238A

E46431A

E59235

E54540

Front connection of fixed devices

E70750

E59240A

Spreaders.

E59241A

Special sets of connectors and terminal shields may


be used to connect up to four 240 mm2 copper or
aluminium cables for each phase.

E46887A

E54457

Bare cables

4-cable connectors

Cable lug adapters

E59243A

E70751

E59242A

Cable lug adapters are combined with the verticalconnection adapters.


One to four cables with crimped lugs (y 300 mm2) may
be connected.
To ensure stability, spacers must be positioned
between the terminal extensions.
If the cable lug adapters are installed over the top of
the arc chute chambers, then it is mandatory to install
the arc chute screen in order to comply with the safety
clearances.

E46427A

E54456

Cables with lugs

Schneider Electric

119

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)

Functions and
characteristics

E54540

Rear connection of fixed devices

Spreaders.

E54456

E59247A

E59248A

E59257A

E59236

Fixed, rear-connection Compact NS630b to 1600


devices equipped with horizontal or vertical connectors
may be directly connected to flat or edgewise bars,
depending on the position of the connectors.
Spreaders are available to increase the pole pitch to
95 mm.

E46431A

Bars

Cable lug adapters enable connection of one to four


cables with crimped lugs (y 300 mm2).
To ensure stability, spacers must be positioned
between the terminal extensions.

E46427A

Cables with lugs

E59250A

E59249A

Cable lug adapters

120

Schneider Electric

Front connection of withdrawable devices

Vertical-connection adapters

E59253A

E46431A

E59252A

E59280

Withdrawable, front-connection Compact NS630b to


1600 devices are suitable for direct connection of bars.
Other connection possibilities for bars include verticalconnection adapters for edgewise bars and spreaders
to increase the pole pitch to 95 mm.

E46426A

E54540

Bars

E59254A

Spreaders

E54456

Cable lug adapters enable connection of one to four


cables with crimped lugs (y 300 mm2).
To ensure stability, spacers must be positioned
between the terminal extensions.

E46427A

Cables with lugs

Schneider Electric

E59253A

E59255A

Cable lug adapters

121

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)

Functions and
characteristics

E54540

Rear connection of withdrawable devices

Spreaders

Cables with lugs


Cable lug adapters enable connection of one to four
cables with crimped lugs (y 300 mm2).
To ensure stability, spacers must be positioned
between the terminal extensions.

E46427A

E54456

E59260A

E59259A

E59258A

E59282A

Withdrawable, rear-connection Compact NS630b to


1600 devices equipped with horizontal or vertical
connectors may be directly connected to flat or edgewise bars, depending on the position of the connectors.
Spreaders are available to increase the pole pitch to
95 mm.

E46431A

Bars

E59262A

E59261A

Cable lug adapters

122

Schneider Electric

Insulation of live parts


Mounted on fixed, front-connection devices, this shield
insulates power-connection points, particularly when
cables with lugs are used

E59263A

E45190

Connection shield

Connection shield

These barriers are flexible insulated partitions used to


reinforce isolation of connection points in installations
with busbars, whether insulated or not.
Barriers are installed vertically between front or rear
connection terminals.

E79056

Interphase barriers

Interphase barriers for fixed


device, front connection

E79057

Compact NS equipped with connection shield

E59264A

Interphase barriers for fixed


device, rear connection

Interphase barriers for


withdrawable device, rear
connection

Mounted on the chassis, the safety shutters


automatically block access to the disconnecting
contact cluster when the device is in the disconnected
or test positions (degree of protection IP20). When the
device is removed from its chassis, no live parts are
accessible.
The shutters can be padlocked (padlock not supplied)
to:
b prevent connection of the device
b lock the shutters in the closed position.

Schneider Electric

E59265A

Safety shutters

Safety shutters

123

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)

Functions and
characteristics

E59283A

Connection of electrical auxiliaries

rotary handle

Connections are made directly to the auxiliaries once the front has been removed.
Wires exit the circuit breaker through a knock-out in the top.

OF1
OF2
OF3

E59286A

CAO2

CAO1

CAF2

CAF1

Fixed devices

SD
MN
or
MX

SDE

COM

OF1

OF2

OF3

Withdrawable devices
Auxiliary circuits are connected to terminal blocks located in the top part of the
chassis.
The auxiliary terminal block is made up of a fixed and moving part. The two parts
are in contact when the device is in the test and connected positions.
E59287A

COM

MN
ou
or
MX

SDE

E59284A

Manually operated device

CT1

CE1

CE2

CE3

CD1

CD2

E59285A

Electrically operated device

Withdrawable device

124

Schneider Electric

044314

Indication contacts
Contacts installed in the device

OF, SD and SDE changeover contacts

All the auxiliary contacts opposite are also available


in "low-level" versions capable of switching very low
loads (e.g. for the control of PLCs or electronic
circuits).

Changeover contacts are used to remote circuit-breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
b OF (ON/OFF) - indicates the position of the main circuit breaker contacts
b SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
v operation of a voltage release
v operation of the "push to trip" button
v disconnection when the device is ON.
Returns to de-energised state when the circuit breaker is reset.
b SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
b CAF / CAO (early-make or early-break function) - indicates the position of the
rotary handle. Used in particular for advanced opening of safety trip devices (early
break) or to energise a control device prior to circuit-breaker closing (early make).
Installation
b OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker
b CAF / CAO function - the contact fits into the rotary-handle unit (direct or
extended).
Electrical characteristics of the OF/SD/SDE/CAF/CAO auxiliary contacts
Contacts

056456

Rated thermal current (A)


Minimum load
Utilisation cat. (IEC 60947-5-1)
Operational 24 V
current (A)
48 V
110 V
220/240 V
250 V
380/440 V
660/690 V

Standard

Low level

6
100 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
6
0.1
-

5
2 mA at 15 V DC
AC12 AC15 DC12
5
3
5
5
3
2.5
5
2.5
0.8
5
2
5
0.3
5
1.5
-

DC14
1
0.2
0.05
0.03
-

DC14
1
0.2
0.05
0.03
-

Connected, disconnected, test position carriage switches

Carriage switches for connected (CE), disconnected (CD) and


test (CT) positions

A single type of changeover contact can be mounted optionally on the chassis to


indicate, depending on the slot where it is installed:
b the connected (CE) position
b the disconnected (CD) position. This position is indicated when the required
clearance for isolation of the power and auxiliary circuits is reached
b the test (CT) position. In this position, the power circuits are disconnected and
the auxiliary circuits are connected.
Installation
b contacts for the connected (CE), disconnected (CD) and test (CT) positions clip
into the upper front section of the chassis.
Electrical characteristics of the CE/CD/CT auxiliary contacts
Contacts
Rated thermal current (A)
Minimum load
Utilisation cat. (IEC 60947-5-1)
Operational 24 V
current (A)
48 V
110 V
220/240 V
250 V
380/440 V
660/690 V

Schneider Electric

Standard

Low level

8
100 mA at 24 V
AC12 AC15 DC12
8
6
2.5
8
6
2.5
8
5
0.8
8
4
0.3
8
3
6
0.1
-

5
2 mA at 15 V DC
AC12 AC15 DC12
5
3
5
5
3
2.5
5
2.5
0.8
5
2
5
0.3
5
1.5
-

DC14
1
0.2
0.05
0.03
-

DC14
1
0.2
0.05
0.03
-

125

E45159

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)
Rotary handles
There are two types of rotary handle:
b direct rotary handle
b extended rotary handle.
There are two models:
b standard with a black handle
b VDE with a red handle and yellow front for machine-tool control.

Direct rotary handle

E45161

Compact NS with a direct rotary handle

Degree of protection IP40, IK07.


The direct rotary handle maintains:
b visibility of and access to trip unit settings
b suitability for isolation
b indication of the three positions O (OFF), I (ON) and tripped
b access to the "push to trip" button
b circuit breaker locking capability in the OFF position by one to three padlocks,
shackle diameter 5 to 8 mm (not supplied).
It replaces the circuit-breaker front cover.
Accessories transform the standard direct rotary handle for the following situations:
b motor control centre (MCC) switchboards:
v door opening disabled when the circuit breaker is ON;
v circuit-breaker closing is disabled if the door is open;
b a higher degree of protection (IP43, IK07)
b machine-tool control, complying with CNOMO E03.81.501, IP54, IK07.

Extended rotary handle


Compact NS with an extended rotary handle

126

Degree of protection IP55, IK07.


This handle makes it possible to operate circuit breakers installed at the back of
switchboards, from the switchboard front.
It maintains:
b suitability for isolation
b indication of the three positions O (OFF), I (ON) and tripped
b access to trip unit settings, when the switchboard door is open
b circuit breaker locking capability in the OFF position by one to three padlocks,
shackle diameter 5 to 8 mm (not supplied).
The door cannot be opened if the circuit breaker is ON or locked.
The extended rotary handle is made up of:
b a unit that replaces the front cover of the circuit breaker (secured by screws)
b an assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally
b an extension shaft that must be adjusted to the distance. The min/max distance
between the back of circuit breaker and door is 218/605 mm.

Schneider Electric

056421

Remote tripping
This function opens the circuit breaker via an electrical order. It is made up of:
b a shunt release (MX)
b or an undervoltage release (MN)
b or a delayed undervoltage release (MN + delay unit).
These releases (MX or MN) cannot be operated by the communication bus.
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency OFF button to obtain instantaneous opening of the circuit breaker.

opening
order

E46554A

E46553A

Wiring diagram for the remote-tripping function


E59433A

Manually operated circuit breakers may be


equipped with an MX shunt release, an MN
undervoltage release or a delayed
undervoltage release (MN + delay unit).
Electrically operated circuit breakers are
equipped as standard with a remoteoperating mechanism to remotely open or
close the circuit breaker. An MX shunt
release or an MN undervoltage release
(instantaneous or delayed) may be added.

opening
order

delayed
opening
order

MX voltage release

10

12

delay
unit

C2

D2

instantaneous
opening
order
MN

MN

MX
C1

D2

D1

D1

Voltage releases (MX)


When energised, the MX voltage release instantaneously opens the circuit breaker.
A continuous supply of power to the MX locks the circuit breaker in the OFF
position.
Characteristics
Power supply V AC 50/60 Hz
V DC
Operating threshold
Permanent locking function
Consumption (VA or W)
Circuit-breaker response
time at Un

24 - 48 - 100/130 - 200/250 - 277 - 380/480


12 - 24/30 - 48/60 - 100/130 - 200/250
0.7 to 1.1 Un
0.85 to 1.1 Un
pick-up: 200 (200 ms)
hold: 4.5
50 ms 10

Instantaneous voltage releases (MN)


The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35 % and 70 % of its rated voltage. If there is no supply
on the release, it is impossible to close the circuit breaker, either manually or
electrically. Any attempt to close the circuit breaker has no effect on the main
contacts. Circuit-breaker closing is enabled again when the supply voltage of the
release returns to 85 % of its rated value.
Characteristics
Power supply V AC 50/60 Hz
V DC
Operating
opening
threshold
closing
Consumption (VA or W)
MN consumption
with delay unit (VA or W)
Circuit-breaker response
time at Un

24 - 48 - 100/130 - 200/250 - 380/480


24/30 - 48/60 - 100/130 - 200/250
0.35 to 0.7 Un
0.85 Un
pick-up: 200 (200 ms)
hold: 4.5
pick-up: 400 (200 ms)
hold: 4.5
90 ms 5

MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply
V AC 50-60 Hz /DC
Operating threshold
Consumption of delay
unit alone (VA or W)
Circuit-breaker response
time at Un

Schneider Electric

non-adjustable
100/130 - 200/250
adjustable
48/60 - 100/130 - 200/250 - 380/480
opening
0.35 to 0.7 Un
closing
0.85 Un
pick-up: 200 (200 ms)
hold: 4.5
non-adjustable
adjustable

0.25 s
0.5 s - 0.9 s - 1.5 s - 3 s

127

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)

Electrically operated circuit breakers are


equipped as standard with a motor
mechanism module.
Two solutions are available for electrical
operation:
b a point-to-point solution
b a bus solution with the COM
communication option.

Electrically operated circuit breaker

E45163

E59434A

The motor mechanism module is used to remotely open and close the circuit
breaker. It is made up of a spring-charging motor equipped with an opening release
and a closing release.
An electrical operation function is generally combined with:
b device ON/OFF indication (OF)
b "fault-trip" indication (SDE).
Wiring diagram of a point-to-point electrical operation solution

opening
order

closing
order
A4

fault
A2

B4

motor
mechanism
module

82

closed

open
84

12

14

OF1
SDE

A1

81

11

Electrically operated Compact NS circuit breaker

E59435A

Wiring diagram of a bus-type electrical operation solution

opening
order

closing
order
A4

A2

B4

motor
mechanism
module

A1

COM

OF

supervisor

SDE

In the event of simultaneous opening and closing orders, the


mechanism discharges without any movement of the main
contacts.
In the event of maintained opening and closing orders, the
standard electrical operation solution provides an antipumping function by blocking the main contacts in open
position.

128

Schneider Electric

Motor mechanism module


Power supply

V AC 50/60 Hz
V DC
Operating threshold
Consumption (VA or W)
Motor overcurrent
Charging time
Operating frequency

48/60 - 100/130 - 200/240 - 277- 380/415


24/30 - 48/60 - 100/125 - 200/250
0.85 to 1.1 Un
180
2 to 3 In for 0.1 second
maximum 4 seconds
maximum 3 cycles per minute

Electrical closing order


The release remotely closes the circuit breaker if the spring mechanism is charged.
Release electrical characteristics are identical to those of an MX release (see
above), the operating threshold is from 0.85 to 1.1 Un and the circuit-breaker
response time at Un is 60 ms 10.
The Compact NS electrical operation function can be used to implement a synchrocoupling system.
Electrical opening order
The release instantaneously opens the circuit breaker when energised. The supply
can be impulse-type or maintained.
Release electrical characteristics are identical to those of an MX release (see
above).

Schneider Electric

129

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)

E45194

Functions and
characteristics

Locking on manually operated devices

Toggle locked by removable


padlocking device

Locking in the OFF position guarantees isolation as per IEC 60947-2.


Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device
Toggle

Direct rotary handle


E45159

Rotary handle locked by a


keylock

CNOMO direct rotary handle

Extended rotary handle

Function

Means

Required
accessories

lock in OFF position


lock in OFF or ON
position
lock in
b OFF position
b OFF or ON position
lock in
b OFF position
b OFF or ON position
lock in OFF position,
door opening prevented

padlock
padlock

removable device
fixed device

padlock
keylock
padlock
keylock
padlock
keylock

locking
device + keylock
locking
device + keylock
keylock

Locking in ON position does not prevent the device from tripping in the event of a fault or
remote tripping order.

Locking on electrically operated devices


E59436A

056447

Access to pushbuttons
protected by transparent
cover

056446

4
I

Pushbutton locking using a


padlock

O
push

push

ON

OFF

1 reset of mechanical
trip indicator
2 OFF pushbutton
3 OFF position locking
4 ON pushbutton
5 springs charged indication
6 pushbutton locking
7 contact position indication
8 operation counter

ed
harg
disc

O OFF

6
7
012

53

Pushbutton locking
056448

OFF position locking using


padlocks

The transparent cover blocks access to the pushbuttons used to open and close
the device.
It is possible to independently lock the opening OFF button and the closing ON
button.
The pushbuttons may be locked using either:
b three padlocks (not supplied)
b lead seal
b two screws.

Device locking in the OFF position

056449

OFF position locking using a


keylock and padlocks

130

The circuit breaker is locked in the OFF position by physically maintaining the
opening pushbutton pressed down:
b using padlocks (one to three padlocks, not supplied)
b using a keylock (supplied).
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
b one keylock
b one keylock mounted on the device + one identical keylock supplied separately
for interlocking with another device.
A locking kit (without lock) is available for installation of a keylock (Ronis, Profalux,
Kirk or Castell).

Schneider Electric

E59267A

Chassis locking

3
4
5

6
7
8
9

1
2
3
4
5
6
7

mismatch protection
door interlock
racking interlock
keylock locking
padlock locking
position indicator
chassis front plate
(accessible with cubicle
door closed)
8 crank entry
9 reset button
10 crank storage

10

Disconnected position locking

056451

056450

056417

Disconnected position
locking by padlocks

Mounted on the chassis and accessible with the door closed, these devices lock
the circuit breaker in the disconnected position in two manners:
b using padlocks (standard), up to three padlocks (not supplied)
b using keylocks (optional), one or two different keylocks are available.
Profalux and Ronis keylocks are available in different options:
b one keylock
b one keylock mounted on the device + one identical keylock supplied separately,
using the same key, for interlocking with another device
b one (or two) keylocks mounted on the device + one (or two) identical keylocks
supplied separately, for interlocking with another device.
A locking kit (without locks) is available for installation of one or two keylocks
(Ronis, Profalux, Kirk or Castell).
Disconnected position
locking by keylocks

Door interlock

Connected, disconnected and test position locking


The connected, disconnected and test positions are shown by an indicator.
The racking crank blocks when the exact position is obtained.
A release button is used to free it.
On request, the disconnected position locking system may be modified to lock the
circuit breaker in any of the three positions, connected, disconnected and test.

Door interlock

056452

Mounted on the right or left-hand side of the chassis, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the
breaker is put in the connected position with the door open, the door may be closed
without having to disconnect the circuit breaker.
Racking interlock

Racking interlock
This device prevents insertion of the crank when the cubicle door is open (device
cannot be connected).

Mismatch protection

056453

Mismatch protection ensures that a circuit breaker is installed only in a chassis with
compatible characteristics. It is made up of two parts (one on the chassis and one
on the circuit breaker) offering twenty different combinations that the user may
select.
Mismatch protection

Schneider Electric

131

056463

Functions and
characteristics

Auxiliary terminal shield

Electrical and mechanical


accessories
Compact NS630b to 1600 (cont.)
Other accessories
Auxiliary terminal shield (CB)
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.

Operation counter (CDM)


056464

Operation counter

The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible with electrically operated devices.

Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40. It is available in fixed and withdrawable versions.

Transparent cover (CCP) for escutcheon


E45184

Escutcheon

Optional equipment mounted on the escutcheon, the cover is hinged and secured
by a screw. It increases the degree of protection to IP54 and the degree of
protection against mechanical impacts to IK10. It may be used for withdrawable
devices only.

Blanking plate (OP) for escutcheon

E45187

Transparent cover

E59987

Used with the escutcheon, this option closes off the door cutout of a cubicle not yet
equipped with a device. It may be used with the escutcheon for both fixed and
withdrawable devices.

Blanking plate

132

Schneider Electric

Schneider Electric

133

Electrical and mechanical


accessories
Compact NS1600b to 3200
(fixed version)

Functions and
characteristics

OFF
OFF

OFF
OFF

134

Schneider Electric

E45178

Installation
Fixed circuit breakers

E59271A

Compact NS1600b to 3200 circuit breakers should be installed vertically only.

OFF
OFF

Fixed Compact NS
Mounting on rails
E59281A

Connection
Front connection
NS3200

E59272A

E59726A

NS1600 to 2500

OFF

OFF

OFF

OFF

Bars

E59273

E59275A

Bars may be directly connected to the terminals of Compact NS1600b to 3200


circuit breakers.
NS1600b to 2500

OFF
OFF

E59728A

E59727A

E59274A

NS1600b to 2500 with connection for vertical-connection adapters or NS3200

OFF
OFF

Schneider Electric

OFF
OFF

135

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS1600b to 3200 (cont.)

044314

Indication contacts
Contacts installed in the device

OF, SD and SDE changeover contacts

All the auxiliary contacts opposite are also available


in "low-level" versions capable of switching very low
loads (e.g. for the control of PLCs or electronic
circuits).

Changeover contacts are used to remote circuit-breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
b OF (ON/OFF) - indicates the position of the main circuit breaker contacts
b SD (trip indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault
v operation of a voltage release
v operation of the "push to trip" button
Returns to de-energised state when the circuit breaker is reset.
b SDE (fault indication) - indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
Installation
b OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on the position where it is inserted in the device.
The contacts clip into slots behind the front cover of the circuit breaker.
Electrical characteristics of the OF/SD/SDE auxiliary contacts
Contacts
Rated thermal current (A)
Minimum load
Utilisation category (IEC 60947-5-1)
Operational 24 V
current (A)
48 V
110 V
220/240 V
250 V
380/440 V
660/690 V

136

Standard
6
100 mA at 24 V
AC12 AC15 DC12
6
6
2.5
6
6
2.5
6
5
0.8
6
4
0.3
6
3
6
0.1
-

Low level
5
2 mA at 15 V DC
DC14 AC12 AC15 DC12
1
5
3
5
0.2
5
3
2.5
0.05 5
2.5
0.8
5
2
0.03 5
0.3
5
1.5
-

DC14
1
0.2
0.05
0.03
-

Schneider Electric

Remote tripping

056421

Compact NS1600b to 3200 circuit breakers


may be equipped with an MX shunt release,
an MN undervoltage release or a delayed
undervoltage release (MN + delay unit).

This function opens the circuit breaker via an electrical order. It is made up of:
b a shunt release (MX)
b or an undervoltage release (MN)
b or a delayed undervoltage release (MN + delay unit).
These releases (MX or MN) cannot be operated by the communication bus.
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency OFF button to obtain instantaneous opening of the circuit breaker.

MX voltage release

opening
order

E46554A

E46553A

E59433A

Wiring diagram for the remote-tripping function


opening
order

delayed
opening
order

10

12

delay
unit

C2

D2

instantaneous
opening
order
MN

MN

MX
C1

D2

D1

D1

Voltage releases (MX)


When energised, the MX voltage release instantaneously opens the circuit breaker.
A continuous supply of power to the MX locks the circuit breaker in the OFF
position.
Characteristics
Power supply V AC 50/60 Hz
V DC
Operating threshold
Permanent locking function
Consumption (VA or W)
Circuit-breaker response
time at Un

24 - 48 - 100/130 - 200/250 - 277 - 380/480


12 - 24/30 - 48/60 - 100/130 - 200/250
0.7 to 1.1 Un
0.85 to 1.1 Un
pick-up: 200 (200 ms)
hold: 4.5
50 ms 10

Instantaneous voltage releases (MN)


The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35 % and 70 % of its rated voltage. If there is no supply
on the release, it is impossible to close the circuit breaker, either manually or
electrically. Any attempt to close the circuit breaker has no effect on the main
contacts. Circuit-breaker closing is enabled again when the supply voltage of the
release returns to 85 % of its rated value.
Characteristics
Power supply V AC 50/60 Hz
V DC
Operating
opening
threshold
closing
Consumption (VA or W)
MN consumption
with delay unit (VA or W)
Circuit-breaker response
time at Un

24 - 48 - 100/130 - 200/250 - 380/480


24/30 - 48/60 - 100/130 - 200/250
0.35 to 0.7 Un
0.85 Un
pick-up: 200 (200 ms)
hold: 4.5
pick-up: 400 (200 ms)
hold: 4.5
90 ms 5

MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply
V AC 50-60 Hz /DC
Operating threshold
Consumption of delay
unit alone (VA or W)
Circuit-breaker response
time at Un

Schneider Electric

non-adjustable
100/130 - 200/250
adjustable
48/60 - 100/130 - 200/250 - 380/480
opening
0.35 to 0.7 Un
closing
0.85 Un
pick-up: 200 (200 ms)
hold: 4.5
non-adjustable
adjustable

0.25 s
0.5 s - 0.9 s - 1.5 s - 3 s

137

62191

Functions and
characteristics

Electrical and mechanical


accessories
Compact NS1600b to 3200 (cont.)
Device locking
Locking in the OFF position guarantees isolation as per IEC 60947-2.
Padlocking systems can receive up to three padlocks with shackle diameters
ranging from 5 to 8 mm (padlocks not supplied).
Control device
Toggle

Function

Means

Required
accessories

lock in OFF position


lock in OFF or ON
position

padlock
padlock

removable device
fixed device

Interphase barriers
These barriers are flexible insulated partitions used to reinforce isolation of
connection points in installations with busbars, whether insulated or not.
Barriers are installed vertically between front connection terminals.

62190

Compact NS with toggle locked using a fixed device and


padlocks

Escutcheon (CDP)
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40.

E79056

Compact NS with toggle locked using a removable device and


padlocks

E94383

Interphase barriers

Escutcheon

138

Schneider Electric

Test equipment

Mini test kit

052172

047035

Compact NS100 to 630


test equipment for STR electronic trip units
The mini test kit is a portable unit requiring no external power supply, used to check
operation of the electronic trip unit and circuit-breaker tripping.
It connects to the test connector on the front of the circuit breaker.
Required power source: five 9 V alkaline batteries (not supplied).

Portable test kit

Mini test kit

Portable test kit

The portable test kit is used to check all aspects of the protection functions:
b long time protection
b short time protection
b instantaneous protection
b earth-fault protection.
Required power source: 110 or 220 V AC, 50/60 Hz.

Compact NS630b to 3200


test equipment for Micrologic control units
056466

Mini test kit


The autonomous hand-held mini test kit may be used to:
b check operation of the control unit and the tripping and pole-opening system by
sending a signal simulating a short-circuit
b supply power to the control units for settings via the keypad when the circuitbreaker is open (Micrologic P and H control units).
Required power source: standard LR6-AA battery.

Portable test kit

Portable test kit

Schneider Electric

The portable test kit is may be used to check:


b the mechanical operation of the circuit breaker
b the electrical continuity of the connection between the circuit breaker and the
control unit
b operation of the control unit:
v display of settings
v operating tests on the ASIC electronic component
v automatic and manual tests on protection functions
v test on the zone-selective interlocking (ZSI) function
v inhibition of the earth-fault protection
v inhibition of the thermal memory.
Note.
These test kits are identical for all Compact NS630b to 3200 circuit breakers and
all Masterpact NT and NW circuit breakers.
Required power source: 110 or 220 V AC, 50/60 Hz.

139

Display modules

Perfectly integrated in the Compact


and Masterpact ranges, Display modules
are designed for use with Micrologic control
units to provide instant and highly intuitive
access to all the information provided by
the circuit breakers, including device status,
current, voltage and power values, etc.

DMB300 and DMC300 display modules use the power and communications
capabilities of the Micrologic control units to centralise the display of electrical
values, status conditions and alarms of one or more Compact
or Compact circuit breakers.
The mounting and cabling system for the display modules ensures fast,
easy and reliable installation.
Start-up is immediate with no configuration or programming required.
Display modules are high-performance devices combining:
b simple and easy-to-read dials
b powerful and accurate digital processing.
Their small size and extensive communications capabilities make for easy and
flexible installation and operation.

057454

Functions and
characteristics

Display modules

DMB300

DMC300

Associated circuit breakers


Type
Number

Compact or Masterpact equipped with


Micrologic control units
1 to 4
1 to 16

Display
DMB300 display module: basic and harmonic measurements

Screen type
Screen size
Entry

Black and white


240 x 64 pixels
5 buttons

Colour, touch screen


5, 320 x 240 pixels
Touch screen

A
A
A

A
A
A

Information displayed
E79078

Currents (per phase)


Currents I1, I2, I3, IN
Maximum current
Earth-fault and earth-leakage currents
Demand current
Maximum demand current
Total harmonic distortion (THD)
Maximum total harmonic distortion
Amplitudes of individual harmonics
Waveform capture

DMC300 display module: measurements, harmonic analysis,


diagnosis

P
P
P
P
P

H
H
H
H
H
H
H

P
P
P
P
P
P

H
H
H
H
H
H
H
H
H

Power
Active (P), reactive (Q) and apparent (S) power
Power factor and cos
Maximum power (P, Q, S)
Demand power (P, Q, S)
Maximum demand power (P, Q, S)

P
P
P
P
P

Metering
Active, reactive and apparent energy

Voltages
Phase-to-phase voltages (U1-2, U2-3, U3-1)
Minimum/maximum phase-to-phase voltages
Phase-to-neutral voltages (V1-N, V2-N, V3-N)
Minimum/maximum phase-to-neutral voltages
Frequency
Voltage unbalance (% per phase)
Total harmonic distortion (% per phase)
Maximum total harmonic distortion (% per phase)
Amplitudes of individual harmonics

P
P
P
P
P

H
H
H
H
H
H
H
H
H

P
P
P

H
H
H

P
P

H
H
H
H
H

H
H
H
H
H

P
P
P
P
P

H
H
H
H
H

On-line help
On-line help is available for each type
of information supplied by the module
Circuit-breaker diagnostics
Identification of control units
Reading of protections
Circuit-breaker status
Type of trip
Current alarms
Maintenance indicator

Associated Micrologic control unit


A = Micrologic A
P = Micrologic P
H = Micrologic H

140

Installation diagnosis
Indication of faulty devices
Fault log

A
A
A
A

P
P
P
P
P

H
H
H
H
H

A
A
A
A

P
P
P
P
P
P

H
H
H
H
H
H

A
P

P
H

Installation and start-up


Mounting
Connection

Mounted through door, without tools,


using 6 spring-clips supplied with the mod.
Prefabricated wiring systems

Schneider Electric

24 V DC
power

E59178

Connection of DMB300 display module

Wiring system
The wiring system is designed for low-voltage
power switchboards. Installation requires no tools
or special skills.
The prefabricated wiring ensures both data
transmission (Modbus protocol) and 24V DC power
distribution for the display module and the
communications modules on the Micrologic control
units.

2
E59081

ON ON

ON
n 4n 4 4 ON
n
n 3n 3
n 4
n 2n 2 n 3
n 3
n 1n 1 n 2
n 2
OUTOUT n 1
IN IN
T

IN

ON

OU

3
Reset

push
push

70

NX 32

ON

Ir

Ig
Isd I n
Ii

Ap

reset

Icu (kA)
100
100
85
Icw 85kA/1s

cat.B

Ics =

discharge

CDM 303:
Connection cable between
display module and junction
block

H2

Ue (V)
220/440
525
690

OFF

Micrologic

100%

Icu
50/60Hz

O OFF

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE

012

VDE

53

com

DMB300
Digipact

volets
shutters

Test

1
2
I

select

E59180A

NW

1251

12kV

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

H1

Uimp

Ui 1000V
8kV
Uimp

Micrologic

Ir

Ig
Isd I n
Ii

Ap

reset

I ON

OOFF

push

push

discharged

O OFF

ON
Ics =

IEC

100%

Icu

947-2

UTE VDE

012

BS CEI

NEMA

UNE

53

IN

NW

1251

n 2

n 3

n 4

ON

H1

Uimp

Ui 1000V
8kV
Uimp

12kV

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

OUT

n 1

Micrologic

Ir

Ig
Isd I n
Ii

Ap

reset

I ON

OOFF

push

push

discharged

O OFF

Ics =

IEC

100%

947-2

UTE VDE

CJB 306 junction block

Icu

BS CEI

NEMA

UNE

53

E59179

012

Compact circuit breakers equipped with Micrologic control


units and the Modbus eco COM option

CCP 303:
Connection cable between
Masterpact or Compact and
junction block

Connection of DMC300 display module


Maximum distance between module and circuit breaker: 1200 m
5

E59082

E59176A

NW

1251

H1

Uimp

NW

12kV

Ui 1000V
8kV

Ir

Ap

Ir

I ON

OOFF

Ig
Isd I n
Ii

Ap

reset

I ON

push

OOFF

discharged

O OFF

Ics =

IEC

100%

NX 32

ON

d
discharge

Icu (kA)
100
100
85
Icw 85kA/1s

cat.B
Ics =

012

H2

Ue (V)
220/440
25
525
690

OFF

reset

100%

Icu
50/60Hz

O OFF

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE

VDE

Ics =

BS CEI

UNE

NEMA

IEC

012

NW

1251

H1

Uimp

NW

12kV

Ui 1000V
8kV

Ir

I ON

Ig
Isd I n
Ii

Ap

I ON

OOFF

discharged

Ics =

IEC

push
push

NX 32

ON

100%

d
discharge

BS CEI

UNE

NEMA

IEC

100%

947-2

UTE VDE

012

BS CEI

UNE

NEMA

53

Icu (kA)
100
100
85

100%

Icu

NW

50/60Hz

1251

H1

Uimp

NW

12kV

Ui 1000V
8kV

947-2
AS NEMA
IEC
UNE
EN 60947-2
BS CEI
UTE

Ics =

947-2

53

Icu

Icw 85kA/1s

cat.B
Ics =

Icu

H2

Ue (V)
220/440
525
690

OFF

O OFF

push

push

O OFF

UTE VDE

012

reset

12kV

Icu
(kA)
100
85

reset

push

discharged

Ap

CCR 301:
Roll of RS 485 cable
(2 RS 485 wires + 2 power
supply wires)

H1

Uimp

Ue
(V)
220/240
480/690

70

reset

OOFF

70

1251

Uimp

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

Ap

push

Ig
Isd I n
Ii

NEMA

Micrologic

Ig
Isd I n
Ii

O OFF

Reset

UNE

Ui 1000V
8kV

Uimp

70

Ir

Ir

Icu

BS CEI

53

Micrologic

Micrologic

100%

947-2

UTE VDE

53

E59177

Ap

Icu

947-2

UTE VDE

push
push

70

Ig
Isd I n
Ii

push

push

discharged

Reset

12kV

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

reset

push

Ir

H1

Uimp

Uimp

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

Micrologic

Ig
Isd I n
Ii

O OFF

Micrologic

1251

Ui 1000V
8kV

Uimp

70
Micrologic

Ig
Isd I n
Ii

H1

Uimp

Uimp

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70

12kV

Icu
(kA)
100
85

Ue
(V)
220/240
480/690

70
Micrologic

Micrologic

Ir

1251

Ui 1000V
8kV

Uimp

VDE

Ap

reset
Ir

I ON

OOFF

Ig
Isd I n
Ii

Ap

reset

I ON

push

OOFF

push

discharged

O OFF

Ics =

IEC

100%

947-2

UTE VDE

012

push

push

discharged

O OFF

Icu

BS CEI

Ics =

UNE

NEMA

53

IEC

100%

947-2

UTE VDE

012

Icu

BS CEI

UNE

NEMA

53

CSD 309:
SubD 9-pin connector for
colour-coded connection of
wires to screw terminals

Compact circuit breakers equipped with Micrologic control units and the Modbus eco COM option
Schneider Electric

141

142

Schneider Electric

Compact NS

Installation recommendations

Presentation
Functions and characteristics

Operating conditions
Installation in switchboards

144
145

Power supply and weights


Safety clearances and minimum distances
Installation example

145
146
148

Door interlock for Compact NS630b to 1600


Connection of MN and MX voltage releases
for Compact NS630b to 3200
Power connections for Compact NS80H-MA
NSC100N, NSA160
Power connections for Compact NS100 to 630

149
150
151
152

Connection of insulated bars or cables with lugs


Connection of bare cables
Insulation of live parts

152
153
154

Power connections for Compact NS630b to 3200

155

Sizing of bars
Recommended drilling dimensions

157
159

Temperature derating
Power dissipation / Resistance

161
163

Dimensions, volumes
Connection
Electrical diagrams
Additional characteristics
Catalogue numbers

Schneider Electric

2
11

165
205
221
251
267

143

E59432A

Installation
recommendations

Operating conditions

2000 m

Altitude derating
Altitude does not significantly affect circuit-breaker characteristics up to 2000 m.
Above this altitude, it is necessary to take into account the decrease in the dielectric
strength and cooling capacity of air.
The following table gives the corrections to be applied for altitudes above 2000
metres. The breaking capacities remain unchanged.
Compact NS80 to 630
Altitude (m)
Dielectric resistance voltage (V)
3000
Average insulation level (V)
Maximum utilisation voltage (V)
690
Average thermal current (A) at 40 C

2000
2500 2100
750 700
550 480
1 x In

3000

4000

5000

1800
600
420
0.96 x In

0.93 x In

0.9 x In

3000

4000

5000

500

Compact NS630b to 3200


Altitude (m)
Dielectric resistance voltage (V)
3000
Average insulation level (V)
Maximum utilisation voltage (V)
690
Average thermal current (A) at 40 C

2000
2500 2100
750 750
590 520
1 x In

1800
700
460
0.99 x In

600
0.96 x In

0.94 x In

E59571A

Vibrations
Compact NS devices resist electromagnetic or mechanical vibrations.
Tests are carried out in compliance with standard IEC 68-2-6 for the levels required
by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
b 2 13.2 Hz: amplitude 1 mm
b 13.2 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.

Electromagnetic disturbances
E59572A

Compact NS devices are protected against:


b overvoltages caused by devices that generate electromagnetic disturbances
b overvoltages caused by an atmospheric disturbances or by a distribution-system
outage (e.g. failure of a lighting system)
b devices emitting radio waves (radios, walkie-talkies, radar, etc.)
b electrostatic discharges produced by users.
Compact NS devices have successfully passed the electromagnetic-compatibility
tests (EMC) defined by the following international standards:
b IEC 60947-2, appendix F
b IEC 60947-2, appendix B (trip units with Vigi earth-leakage function).
The above tests guarantee that:
b no nuisance tripping occurs
b tripping times are respected.

144

Schneider Electric

Installation in switchboards
Power supply and weights

E23947

Power supply
Compact NS circuit breakers can be supplied from either the top or the bottom
without any reduction in performance. This capability facilitates connection when
installed in a switchboard.

push
to
trip

Weights
Circuit breaker
NS80H-MA
NSC100N

3P/3D
3P/3D
4P/4D
NS100N/H
1P/1D
2P/2D
NS100N
3P/2D
NS100N/H/L
3P/3D
4P/4D
NS125E
3P/3D
4P/4D
NS160N/H
1P/1D
2P/2D
NS160N
3P/2D
NS160N/H/L
3P/3D
4P/4D
NS250N
3P/2D
NS250N/H/L
3P/3D
4P/4D
NS400/630N/H/L
3P/3D
4P/4D
NS630b to 1600
3P
manual operation 4P
NS630b to 1600
3P
electrical operation 4P
NS1600b to 3200
3P
4P

1.09
1
1.3
0.5
1.45
1.79
2.05
2.57
1.8
2.3
0.5
1.45
1.85
2.10
2.58
1.94
2.2
2.78
6.19
8.13
14
18
14
18
24
36

NSA

1.1
1.4
0.7
1.2
1.94
6.19

NB50N
NB100F/N
NB250N
NB400/600N

3P/3D
4P/4D
3P/3D
3P/3D
3P/3D
3P/3D

Plug-in
base

Chassis

Vigi module

Fully visible break block


(Interpact INV)

Motor-mechanism
module

1.5
1.7

0.8
0.8
1.05
0.8
1.1

2.2
2.2
2.2

0.87
0.87
1.13
0.9
1.2

2
2
2.2

1.2
1.2
1.2

0.8
0.8
1.05
0.8
0.8
1.05
2.4
2.8

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
14
18
16
21

0.87
0.87
1.13
0.87
0.87
1.13
2.8
3

2
2
2.2
2
2
2.2
4.6
4.9

1.2
1.2
1.2
1.2
1.2
1.2
2.8
2.8

1.5
1.7

The table above presents the weights (in kg) of the circuit breakers and the main accessories, which must be summed to obtain the total weight of complete
configurations.

Schneider Electric

145

Installation in switchboards
Safety clearances
and minimum distances

Installation
recommendations

Compact NS80 to 630


When installing a circuit breaker, minimum distances (safety clearances) must be
maintained between the device and panels, bars and other protection devices
installed nearby. These distances, which depend on the ultimate breaking capacity,
are defined by tests carried out in accordance with standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
b use insulated bars for circuit-breaker connections
b block off the busbars using insulating screens.
For Compact NS80 to 630 devices, terminal shields, interphase barriers and the
insulation kit are recommended and may be mandatory depending on the utilisation
voltage and the type of installation (fixed, withdrawable). (See page 147.)
Minimal distance between two adjacent circuit breakers

E23942

A1
A2

Minimal distance between


the circuit breaker
and front or rear panels
front
panel

E50700

E50701

Minimal distance between


the circuit breaker and top,
bottom or side panels

F
if F < 8 mm : an
insulating screen
is mandatory

D1

D2

C1
C2

bare or painted sheetmetal;


insulation or insulated bars
Dimensions (mm)

Insulation, insulated bars

Bare sheetmetal

or painted sheet metal


Compact circuit breaker
C1
D1
D2
C2
D1
D2
A1 (2)
A2 (3)
B
NS80H-MA
U y 440 V
0
30
30
5
35
35
0
10
0
NSC100N
U < 600 V
0
30
30
10 (1)
35
35
0
20
0
U u 600 V
0
30
30
20 (1)
35
35
0
40
0
NS100-250
U y 440 V
0
30
30
5
35
35
0
10
0
U < 600 V
0
30
30
10 (1)
35
35
0
20
0
U u 600 V
0
30
30
20 (1)
35
35
0
40
0
NS400-630
U y 440 V
0
30
30
5
60
60
0
10
0
U < 600 V
0
30
30
10 (1)
60
60
0
20
0
U u 600 V
0
30
30
20 (1)
100
100
0
40
0
(1) Distance must be doubled with interphase barriers.
(2) For Compact NS with long or short terminal shields.
(3) For Compact NS without terminal shields.
The mandatory distances when installing Compact NS circuit breakers are calculated from the device case, not taking into account the terminal shields or the
interphase barriers.

146

Schneider Electric

Fixed Compact NS400 1000 V AC, front connection


E94502

E50781

Power supply from the top or bottom. Connection by cables or busbars.


insulation

side panel

150

30

40

insulating kit

40

bare or painted
sheetmetal ;
insulation or
insulated bars

150

B=0

30

Insulating kit is standard.

Compact NS630b to 3200 (fixed devices)


A (*)

A (*)

E59718A

E59717A

146,5

(*) An overhead clearance of 50 mm is required to


remove the arc chutes.

Insulated parts

Metal parts

Live parts

NS630b to 1600
A
0
B
0

120
10

180
60

NS1600b to 3200
A
0
B
0

120
30

180
60

Compact NS630b to 1600 (withdrawable devices)


B

B
C

E59720A

E59719A

40
180
F

Insulated parts
A
B
C

0
10
0

Metal parts

Live parts

0
10
0

30
60
90

F Datum

Schneider Electric

147

Installation in switchboards
Installation example

Installation
recommendations

E50704

painted sheetmetal

Direct connection by
bare cables, devices
with terminal shields.

Connection by cables
with lugs, devices with
terminal shields.

Connection by insulated
bars, devices with
terminal shields.

Rear connection or plug-in


base, devices with terminal
shields.

Minimum dimensions (mm)


Compact circuit breaker
NS80H-MA/NSC100N
NS100-630
NS630b-1600
NS1600b-3200

148

A
0
0
250
300

Schneider Electric

Mounted on the left or right-hand side of the chassis,


this locking device prevents opening of the door if the
circuit breaker is in the connected or test positions. If
the circuit breaker was connected with the door open,
the door may be closed without having to disconnect
the circuit breaker.

E59429A

Door interlock
for Compact NS630b to 1600

4
61
2

(1)

(2)

11

Dimensions (mm)
Type
NS630b to 1600 (3P)
NS630b to 1600 (4P)

(1)
135
205

(2)
168
168

Device in the connected or test positions


E59430A

Door locked
door

F
5
23

Device in the disconnected position

E59431A

Door not locked

Note. The door interlock may be mounted on either the left


or right-hand side of the chassis.
F Datum

Schneider Electric

149

Installation
recommendations

Connection of MN and MX
voltage releases for
Compact NS630b to 3200
Release wiring
During pick-up, the power drawn is approximately 150 to 200 VA. For low supply
voltages (12, 24, 48 V), the maximum cable length therefore depends on the
supply voltage and the size of the cables.
Indicative values for maximum wire lengths (in metres)
12 V

24 V

2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2


MN
100 % U source

58
35
85 % U source

16
10
MX
100 % U source 21
12
115
70
85 % U source
10
6
75
44
Note. The lengths mentioned are for each of the two supply wires.

150

48 V
2.5 mm2
280
75
550
350

1.5 mm2
165
45
330
210

Schneider Electric

E59291A

E54545

Power connections for


Compact NS80H-MA, NSC100N,
NSA160

OFF

L (mm)
S (mm2) Cu / Al
Tightening
torque (Nm)

Standard
device

With distribution
connector

18
1.5 to 70 rigid
1.5 to 50 flexible
5

y 10
1.5 to 16 rigid
1.5 to 10 flexible (1)
2

(1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrule.

E39432

push
to
trip

Distribution connector

Schneider Electric

151

Power connections for


Compact NS100 to 630
Connection of insulated bars or
cables with lugs

Installation
recommendations

L (mm)
I (mm)
d (mm)
e (mm)
(mm)

E59292A

E50702

Bars

400

NS100

NS160/250

NS400/630

y 25
d + 10
y 10
y6
6.5

y 25
d + 10
y 10
y6
8.5

y 32
d + 15
y 15
3 y e y 10
10.5

L
e
push
to
trip

Lugs

L (mm)
y 25
y 25
y 32
(mm)
6.5
8.5
10.5
Tightening torque (Nm) (1)
10
15
50
Tightening torque (Nm) (2)
5
5
20
(1) Tightening torque for lugs or bars on the circuit breaker.
(2) Tightening torque for rear connections or terminal extensions on plug-in base.

Connections with accessories - IEC228


NS100 to 250

NS100 to 250
Spreader
Separate parts
Tinned copper

Pole pitch
Without spreaders
With spreaders

One-piece spreader

Lugs

L (mm)
l (mm)
d (mm)
e (mm)
(mm)
L (mm)
(mm)
(Nm)

y 25
20 y I y 25
y 10
y6
6.5
y 25
6.5
10 (1), 5 (2)

y 25
20 y I y 25
y 10
y6
8.5
y 25
8.5
15 (1), 5 (2)

Tighten.
torque
(1) Tightening torque for spreaders or terminal extensions on the circuit breaker.
(2) Tightening torque for spreaders or terminal extensions on plug-in base.

E18601

E18600

Spreaders, straight and right-angle terminal extensions are supplied with flexible
interphase barriers.

NS400 and 630


Pole pitch
Without spreaders
With spreaders
E50702

Separate spreaders with 52.5 and 70 mm pole


pitches
Tinned copper
Where U > 600 V,
use of the 52.5 mm
spreaders requires a
specific insulation kit.
The 70 mm spreaders
may not be used.
Right-angle terminal
Edgewise terminal
extensions
extension
Tinned copper
Tinned copper
Upstream side
E18600

E18599

NS400 and 600

45 mm
52.5 ou 70 mm

Dimensions
Bars

400

Lugs

L (mm)
l (mm)
d (mm)
e (mm)
(mm)
L (mm)
(mm)
(Nm)

With spreaders

With terminal extensions

y 40
d + 15
y 20
3 y e y 10
12,5
y 40
12,5
50 (1), 20 (2)

y 32
30 y I y 34
y 15
3 y e y 10
10,5
y 32
10,5
50 (1), 20 (2)

Tighten.
torque
(1) Tightening torque for spreaders or terminal extensions on the circuit breaker.
(2) Tightening torque for spreaders or terminal extensions on plug-in base.

Spreaders, straight and right-angle terminal extensions are supplied with flexible
interphase barriers.

E25961

E21276

400

Right-angle terminal
extensions
Tinned copper.
Upstream side.

With spreaders or terminal extensions


NS100
NS160/250
Bars

E50702

E18599

E55599

Dimensions

Where U > 600 V, the mandatory insulation kit


means separate spreaders cannot be used.
The one-piece spreader must be used.
Straight terminal
extensions
Tinned copper.

35 mm
45 mm

Close-up view of two cables


with lugs.

152

Schneider Electric

Connection of bare cables

E54472

E54468

E58540

E59293A

E54471

NS100 to 250

Distribution connector

E54545

1-cable connector

Polybloc distribution block

1-cable connector

Steel
y 160A

Aluminium
y 250A

L (mm)
S (mm2) Cu / Al

20
1.5 to 95 (1)

20
1016

2535

Tightening torque (Nm)

12

15

20

50185
150 max. flex.
26

6-cable distribution connector (copper or aluminium)


L (mm)
S (mm2) Cu / Al
Tightening torque (Nm)

15 or 30
1.5 to 6 (1) 8 to 35
4
6

Polybloc distribution block (6 or 9 cables)


L (mm)
12
S (mm2) Cu / Al
1.5 to 10
(1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrule.

E54469

E54470

NS400 and 630

E54545

1-cable connector

L (mm)
S (mm2) Cu / Al
Tightening torque (Nm)

2-cable connector

1-cable connector
1 cable

2-cable connector
2 cables

20
35 to 300 rigid
240 max. flexible
31

30 or 60
2 x 85 to 2 x 240 rigid
240 max. flexible
31

Conductor materials and electrodynamic stresses


See page 155.

Ties for flexible bars and cables


See page 155.

Schneider Electric

153

Installation
recommendations

Power connections for


Compact NS100 to 630 (cont.)
Insulation of live parts
Fixed Compact NS, front connections
NS100/250N/H/L

NS400/630N/H

NS400/630L

U < 500 V

Interphase barriers
Interphase barriers
or long terminal
or long terminal
shields recommended.
shields recommended.
Insulated bars
Insulated bars
are mandatory.
are mandatory.
500 V y U y 600 V
Interphase barriers
Interphase barriers
Interphase barriers
or long terminal
or long terminal
or long terminal
shields are
shields are
shields are
mandatory.
mandatory.
mandatory.
Insulated bars
Insulated bars
Insulated bars
are mandatory.
are mandatory.
are mandatory.
U > 600 V
Insulation kit
Insulation kit
Insulation kit
and insulated bars
and insulated bars
and insulated bars
are mandatory.
are mandatory.
are mandatory.
The insulation kit is not compatible with:
b separate spreaders for Compact NS100 to 250. The one-piece spreader must be used
b separate spreaders (70 mm) for Compact NS400 and 630. For the 52.5 mm spreaders, there
is a specific insulation kit.

Fixed Compact NS, rear connections


All voltage levels

NS100/250N/H/L

NS400/630N/H

NS400/630L

Short terminal shields


recommended.

Short terminal shields


recommended.

Short terminal shields


recommended.

Withdrawable Compact NS, front and rear connections


NS100/250N/H/L
All voltage levels

NS400/630N/H

NS400/630L

Short terminal shields Short terminal shields


are mandatory.
are mandatory.
Insulated bars
Insulated bars
are mandatory
are mandatory.
for U u 500 V.
Use of an insulating screen (supplied with the plug-in base) is mandatory.

154

Short terminal shields


are mandatory.
Insulated bars
are mandatory.

Schneider Electric

aa
Power connections for
Compact NS630b to 3200

Conductor materials and electrodynamic stresses

E59565A

Compact circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors (flexible or rigid bars, cables.
In the event of a short-circuit, thermal and electrodynamic stresses will be exerted
on the conductors. They must therefore be correctly sized and maintained in place
using supports.
Electrical connection points on all types of devices (switch-disconnectors,
contactors, circuit breakers, etc.) should not be used for mechanical support.
Any partition between upstream and downstream connections of the device must
be made of non-magnetic material.

Ties for flexible bars and cables

The table below indicates the maximum distance between ties depending on the
prospective short-circuit current.
The maximum distance between ties attached to the switchboard frame is 400 mm.
Type of
tie

"Sarel" ties
Width: 9 mm
Maximum load: 90 kg
Colour: black

200

100

50

350

200

100

70

10

15

20

20

27

35

45

aa

"Panduit" ties
Width: 4.5 mm
Maximum load: 22 kg
Colour: white

Maximum distance
between ties (mm)
Short-circuit
current (kA rms)

50 (double
ties)
100

E59567A

E59566A

Note. For cables u 50 mm2, use 9 mm-wide ties.

Connection of bars

Bars must be adjusted to ensure correct positioning on the terminals before bolting (B).
Bars must rest on a support firmly attached to the switchboard frame, such that the
circuit-breaker terminals do not bear any weight (C).
Electrodynamic forces
The first spacer between bars must be positioned within a maximum distance (see
table below) of the connection point to the circuit breaker. This distance is
calculated to resist the electrodynamic stresses exerted between the bars of each
phase during a short-circuit.
Maximum distance A between the circuit-breaker connection
and the first spacer between bars, depending on the short-circuit current
Isc (kA)
30
50
65
80
100
Distance (mm)
350
300
250
150
150

150
150

E59570A

E59569A

E59568A

Schneider Electric

155

Power connections for


Compact NS630b to 3200

Connections

E47665

E47667B

E47668

The quality of bar connections depends, among other things, on the tightening
torques used for the nuts and bolts. Over-tightening may have the same
consequences as under-tightening.
The correct tightening torques for the connection of bars to the circuit-breaker
terminals are indicated in the table below.
The values below are for copper bars (Cu ETP-NFA51-100) and steel nuts and
bolts (class 8.8).
The same values apply to AGS-T52 quality aluminium bars
(French standard NFA 02-104 and American National Standard H-35-1).
Examples of bar connections

6
1 terminal screws, factory tightened to 13 Nm
2 circuit-breaker terminal
3 bars
4 bolt
5 washer
6 nut

Tightening torque for bars


Rated diameter (mm) Drilling (mm)
diameter
10

11

Tightening torque (Nm)


with flat or grower
washers
37.5

Tightening torque (Nm)


with contact or split
washers
50

Bar drilling
E47331A

E47330A

E47329A

Examples

E47680A

Insulation distance

X
Dimensions (mm)
Utilisation voltage
Ui y 600 V
Ui y 1000 V

X minimum
8 mm
14 mm

Bar bending
Bars must be bent according to the table below. A tighter bend may cause cracks.

E47679A

E47678A

Installation
recommendations

r
e

Dimensions (mm)
e
5
10

156

Radius r
Minimum

Recommended

5
15

7.5
18 to 20

Schneider Electric

Sizing of bars
The following tables are based on the following assumptions:
b maximum permissible temperature of bars is 100 C
b Ti: temperature around the circuit breaker and its connections
b busbars made of copper and not painted.
Note.
The values presented in the tables are the result of trials and theoretical calculations on the
basis of the assumptions mentioned above.
These tables are intended as an aid in designing connections, however, the actual values must
be confirmed by tests on the installation.

E59294A

Front or horizontal rear connections

Compact

Maximum
service
current

Ti : 40 C
Number of bars
5 mm thick
10 mm thick

Ti : 50 C
Number of bars
5 mm thick
10 mm thick

Ti : 60 C
Number of bars
5 mm thick
10 mm thick

NS630b
NS630b
NS800
NS1000
NS1250

400
630
800
1000
1250

2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.63 x 5
3b.63 x 5

1b.30 x 10
1b.40 x 10
1b.63 x 10
2b.50 x 10
2b.50 x 10

1400
1600
1800
2000
2200
2500
2800
3000
3200

2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
2b.80 x 5
3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
6b.100 x 5
8b.100 x 5

1b.30 x 10
1b.40 x 10
1b.50 x 10
2b.50 x 10
2b.50 x 10

NS1600 / 1600b
NS1600 / 1600b
NS2000
NS2000
NS2500
NS2500
NS3200
NS3200
NS3200

2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
2b.80 x 5
3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5
6b.100 x 5

2b.50 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
3b.100 x 10

3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.80 x 5
4b.100 x 5
5b.100 x 5
8b.100 x 5

2b.63 x 10
3b.50 x 10
2b.80 x 10
3b.63 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
4b.80 x 10
4b.100 x 10

1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.40 x 10
2b.40 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.80 x 10
3b.100 x 10

Note.
With Compact NS630b to NS1600, it is recommended to use 50 mm wideness bars (see "Recommanded busbars drilling").

Schneider Electric

157

Power connections for


Compact NS630b to 3200
Sizing of bars

Installation
recommendations

E59422A

Vertical rear connections

Compact

Maximum
service
current

Ti : 40 C
Number of bars
5 mm thick
10 mm thick

Ti : 50 C
Number of bars
5 mm thick
10 mm thick

Ti : 60 C
Number of bars
5 mm thick
10 mm thick

NS630b
NS630b
NS800
NS1000
NS1250
NS1600
NS1600

400
630
800
1000
1250
1400
1600

2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
2b.63 x 5
2b.80 x 5
3b.63 x 5

2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
3b.50 x 5
2b.80 x 5
3b.63 x 5

2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.63 x 5
3b.50 x 5
3b.63 x 5
3b.80 x 5

158

1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
1b.63 x 10
1b.80 x 10
2b.50 x 10

1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
2b.40 x 10
2b.50 x 10
2b.50 x 10

1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.50 x 10
2b.63 x 10

Schneider Electric

Power connections for


Compact NS630b to 1600
Recommended drilling dimensions

12,5

12,5

25,5

12,5
12 maxi

25

25

38,5
=

25

9,5 12,5

13,5

25 25

12,5

77
38,5

25

13,5

82 52

12,5

Left or right spreader


for 4P

38,5
=

25

13,5

5 11

15
5 11

5 11

25

25

13,5

=
30

82 52

15

2 11

25

25

52

52

38,5
=

25
30

82 52

15

77

30
82 52

15
5 11

Left or right spreader


for 3P

77

30

60
12,5

15
12 maxi

Middle spreader for 3P

E59326A

E59325A

E59324B

25

77

80
15

12,5
12 maxi

12,5

Middle left or middle


right spreader for 4P

44

E59310A

63

E59328A

25

50

E59327A

12,5
12 maxi

E59309A

50
12,5

Rear connection with spreaders


E59308A

E59308A

Rear connection

52

52

12 maxi

25

E59329B

12,5

12,5

12 maxi

25
12,5

50

12 maxi

25
12,5

12,5

E59315 A

40

E59314A

32

E59313A

E59312A

E59311A

Vertical rear connection


63

12 maxi

25

12,5

80

12 maxi

25

12,5 12,5

12,5

12,5

60
12,5
9,5

12,5

25 44

2 11

12,5
12 maxi

25

44
25

12,5

12,5
12 maxi

25

Bottom terminal

9,5

2 M10 screws

15

25

15

89
= =

63
25,5

80
15

15

12,5
12 maxi

25

12,5

E59310A

50

12,5

Top terminal

E59309A

E59308A

50
12,5

E94518

Front connection with vertical-connection adapter

E59332A

E59308A

Front connection

12,5

12 maxi

25 25

12,5

12,5
15

21
101

21
3 11

2 M10 screws

15

Schneider Electric

25
44

15
9,5

15

20

159

Power connections for


Compact NS1600b to 3200
Recommended drilling dimensions

Installation
recommendations

50
12,5

E59462B

63

12,5
12 maxi

25

25,5

80
15

15

12,5
12 maxi

12,5

25

12 maxi

25 25

12,5

12,5

25

76
= =

13

E59310A

E59309A

E59308A

Front connection (NS1600b to 2500)

=
=
3 11
15

12 maxi

80

12 maxi

12 maxi

25

25

25

25

25

25

25

25

25
12,5

12,5

100

12,5

12,5

12,5

12 maxi
E59734A

63

E59733A

E59732A

E59731A

Front connection with vertical-connection adapter (NS1600b to 2500)

25
25

100

25

12,5

12,5

12,5

E59735A

4 11
25
60 100

25
25
20

20

12,5

45

20
15

25 25

60

80

E59733A

Front connection (NS3200)


100

25

E59734A

12 maxi

12 maxi

25
25

100

25

25

25
12,5

12,5

12,5

12,5

E59735A

4 11
25
60 100

25
25
20
45
60

160

20

12,5

20
15

25 25
80

Schneider Electric

Temperature derating
Compact NS devices equipped
with thermal-magnetic trip units
The values opposite are valid for fixed circuit
breakers equipped with one of the following modules:
b Vigi module
b ammeter module
b insulation-monitoring module
b current-transformer module.
They also apply to plug-in / withdrawable circuit
breakers equipped with one of the following modules:
b ammeter module
b current-transformer module.
However, for plug-in / withdrawable circuit breakers
equipped with a Vigi module or an insulationmonitoring module, the coefficients in the table below
must be applied.
Trip unit
TM16 to TM125
TM160 to TM250

Coefficient
1
0.9

When the ambient temperature is greater than 40 C, overload-protection


characteristics are slightly modified.
To determine tripping times using time/current curves, use Ir values corresponding
to the thermal setting on the device, corrected as indicated in the tables below.

Single-pole and two-pole Compact NS


Rating (A)
16
25
40
63
80
100
125
160
200
250

40 C

45 C

50 C

55 C

60 C

65 C

70 C

16
25
40
63
80
100
125
160
200
250

15.6
24.5
39
61.5
78
97.5
122
156
195
244

15.2
24
38
60
76
95
119
152
190
238

14.8
23.5
37
58
74
92.5
116
147.2
185
231

14.5
23
36
57
72
90
113
144
180
225

14
22
35
55
70
87.5
109
140
175
219

13.8
21
34
54
68
85
106
136
170
213

Compact NS100 to 250 equipped with TM-D and TM-G trip units
Rating (A)
16
25
32
40
50
63
80
100
125
160
200
250

40 C

45 C

50 C

55 C

60 C

65 C

70 C

16
25
32
40
50
63
80
100
125
160
200
250

15.6
24.5
31.3
39
49
61.5
78
97.5
122
156
195
244

15.2
24
30.5
38
48
60
76
95
119
152
190
238

14.8
23.5
30
37
47
58
74
92.5
116
147.2
185
231

14.5
23
29.5
36
46
57
72
90
113
144
180
225

14
22
29
35
45
55
70
87.5
109
140
175
219

13.8
21
28.5
34
44
54
68
85
106
136
170
213

Compact NSA160
Rating (A)
16
25
32
40
50
63
80
100
125
160

40 C

45 C

50 C

55 C

60 C

65 C

70 C

16
25
32
40
50
63
80
100
125
160

15.6
24.5
31.3
39
49
61.5
78
97.5
122
156

15.2
24
30.5
38
48
60
76
95
119
152

14.8
23.5
30
37
47
58
74
92.5
116
147.2

14.5
23
29.5
36
46
57
72
90
113
144

14
22
29
35
45
55
70
87.5
109
140

13.8
21
28.5
34
44
54
68
85
106
136

Compact NB50NB600
NB50 / NB100
NB50N
NB100F/N

NB250N
Rating (A)
125
150
175
200
225

NB400N
Rating (A)
400

NB600N
Rating (A)
600

Schneider Electric

40 C

45 C

50 C

55 C

60 C

1
1

1
1

1
1

1
1

1
1

50 C

55 C

60 C

65 C

70 C

125
150
175
200
225

122
146
171
195
220

119
143
166
190
214

116
139
162
185
208

113
135
158
180
203

50 C

55 C

60 C

65 C

70 C

400

390

380

370

360

50 C

55 C

60 C

65 C

70 C

600

585

570

550

535

161

Installation
recommendations

Temperature derating
Compact NS devices equipped with
electronic trip units

The values opposite are valid for fixed circuit


breakers equipped with one of the following modules:
b Vigi module
b ammeter module
b insulation-monitoring module
b current-transformer module.
They also apply to plug-in / withdrawable circuit
breakers equipped with one of the following modules:
b ammeter module
b current-transformer module.
However, for plug-in / withdrawable circuit breakers
equipped with a Vigi module or an insulationmonitoring module, the coefficients in the table below
must be applied.

Electronic trip units are not affected by variations in temperature. However, the
maximum permissible current in the circuit breaker still depends on the ambient
temperature.

Circuit breaker Trip unit


NS100N/H/L
NS160N/H/L
NS250N/H/L
NS250N/H/L

Compact NS100...NS250
The table below indicates the maximum long-time (LT) protection setting depending
on the ambient temperature.

NS250N/H/L
In: 100 to 160A
Ir max
In: 250A
Ir max

Coeff.

STR22SE/GE 40 to 100
STR22SE/GE 40 to 160
STR22SE/GE 100 and 160
STR22SE/GE 250

1
1
1
0.86

50 C

55 C

no derating
1
1

45 C

40 C

50 C

55 C

60 C

65 C

70 C

1
250
1

1
237.5
0.95

1
237.5
0.95

1
225
0.90

1
225
0.90

45 C

no derating
1
1
250
250
1
1

60 C

65 C

70 C

Compact NS400 and NS630


The table below indicates the maximum long-time (LT) protection setting depending
on the ambient temperature.

The values opposite are valid for fixed or plug-in /


withdrawable circuit breakers equipped with one of
the following modules:
b ammeter module
b current-transformer module.
However, for fixed or plug-in / withdrawable circuit
breakers equipped with a Vigi module or an insulationmonitoring module, the coefficients in the table below
must be applied.
Circuit breaker Trip unit

40 C

NS100-160N/H/L
In: 40 to 160 A
Ir max

Coeff.

NS400N/H/L
Fixed

In: 400A
Io/Ir max
Plug-in /
In: 400
withdrawable Io/Ir max

NS630N/H/L
Fixed

In: 630A
Io/Ir max
Plug-in /
In: 570A
withdrawable Io/Ir max

40 C

45 C

50 C

55 C

60 C

65 C

70 C

400
1/1
400
1/1

400
1/1
390
1/0.98

400
1/1
380
1/0.95

390
1/0.98
370
1/0.93

380
1/0.95
360
1/0.9

370
1/0.93
350
1/0.88

360
1/0.9
340
1/0.85

40 C

45 C

50 C

55 C

60 C

65 C

70 C

630
1/1
570
1/0.9

615
1/0.98
550
1/0.88

600
1/0.95
535
1/0.85

585
1/0.93
520
1/0.83

570
1/0.9
505
1/0.8

550
1/0.88
490
0.8/0.98

535
1/0.85
475
0.8/0.95

NS400N/H/L

STR23SE and 53UE


0.97
STR23SV and 53SV
NS630N/H/L
STR23SE and 53UE
0.9
STR23SV and 53SV
Note. To provide the Visu function, Compact NS circuit
breakers, with or without a Vigi module, are combined with
INV switch-disconnectors. Tripping values for the selected
combination are indicated in the Interpact catalogue.

Compact NS630b to NS1600 (1)


The table below indicates the maximum rated-current value for each type of connection, depending on the ambient temperature.
For mixed connections, use the same derating values as for horizontal connections.
Version
Connection
temp. Ti (2)
NS630b N/H/L
NS800 N/H/L
NS1000 N/H/L
NS1250 N/H
NS1600 N/H

Version
Connection
temp. Ti (2)
NS630b N/H/L
NS800 N/H/L
NS1000 N/H/L
NS1250 N/H
NS1600 N/H

Fixed device
Front or horizontal rear
40
45
50
55

60

65

70

Vertical rear
40
45

50

55

60

65

70

630
800
1000
1250
1600

630
800
1000
1250
1470

630
800
1000
1240
1420

630
800
1000
1090
1360

630
800
1000
1250
1600

630
800
1000
1250
1600

630
800
1000
1250
1600

630
800
1000
1250
1600

630
800
1000
1250
1510

630
800
1000
1180
1460

Withdrawable device
Front or horizontal rear
40
45
50
55

60

65

70

Vertical rear
40
45

50

55

60

65

70

630
800
1000
1250
1600

630
800
1000
1250
1430

630
800
1000
1170
1330

630
800
920
1000
1160

630
800
1000
1250
1600

630
800
1000
1250
1600

630
800
1000
1250
1560

630
800
1000
1250
1510

630
800
1000
1250
1420

630
800
990
1090
1250

60

65

70

Vertical rear
40
45

50

55

60

65

70

630
800
1000
1250
1600

630
800
1000
1250
1600

630
800
1000
1250
1560

630
800
1000
1250
1520

630
800
1000
1250
1510

630
800
1000
1250
1480

630
800
1000
1250
1600

630
800
1000
1250
1600

Compact NS1600b to 3200


Version
Connection
temp. Ti (2)

Fixed device
Front or horizontal rear
40
45
50
55

NS1600b N/H
1600
1600
1600
1600
1500
1450
1400
1600
1600
1600
1600
1600
1550
1500
NS2000 N/H
2000
2000
2000
2000
1900
1800
1700
2000
2000
2000
2000
2000
1900
1800
NS2500 N/H
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
NS3200 N/H
3200
3200
3200
3180
3080
2970
2860
(1) For a circuit breaker mounted in horizontal position, the derating to be applied is equivalent to that of a front or horizontal rear connected circuit breaker.
(2) Ti: temperature around the circuit breaker and its connections.

162

Schneider Electric

Power dissipation / Resistance


Compact NS devices equipped
with thermal-magnetic trip units
Power dissipated per pole (P/pole) in Watts (W).
Resistance per pole (R/pole) in milliohms (m).
Total power dissipation is the value measured at In,
50/60 Hz, for a three-pole or four-pole circuit breaker
(values above power P = 3RI2).

Compact NSC100N
3/4 poles
NSC100N

NSC100NA

Rat. (A)
16
20
25
32
40
50
63
70
80
100
100

Fixed device

Additional modules

R/pole
15
11.2
8
5.4
3.7
2.8
2
2
1.4
1
0.6

Vigi (N, L3)


0.06
0.1
0.16
0.26
0.4
0.63
1
1.3
1.6
2.5
2.5

P/pole
4
4.5
5
5.5
6
7
8
10
9
10
6

Vigi (L1, L2)


0.06
0.1
0.16
0.26
0.4
0.63
1
1.3
1.6
2.5
2.5

Compact NS100 to 250 equipped with TM-D and TM-G trip units
Fixed device
3/4 poles

Rat. (A) R/pole

NS100N/H/L 16
25
32
40
50
63
80
100
NS160N/H/L 80
100
125
160
NS250N/H/L 125
160
200
250

11.42
6.42
3.94
3.42
1.64
2.17
1.37
0.88
1.26
0.77
0.69
0.55
0.61
0.46
0.39
0.3

Additional modules

P/pole

Vigi

Vigi

With-

2.92
4.01
4.03
5.47
4.11
8.61
8.77
8.8
8.06
7.7
10.78
13.95
9.45
11.78
15.4
18.75

(N, L3)
0
0
0.06
0.10
0.15
0.3
0.4
0.7
0.4
0.7
1.1
1.8
1.1
1.8
2.8
4.4

(L1, L2)
0
0
0.03
0.05
0.08
0.15
0.2
0.35
0.2
0.35
0.55
0.9
0.55
0.9
1.4
2.2

drawable module
0
0
0.1
0
0.15
0.1
0.2
0.1
0.3
0.1
0.4
0.1
0.6
0.1
1
0.2
0.6
0.1
1
0.2
1.6
0.3
2.6
0.5
1.6
0.3
2.6
0.5
4
0.8
6.3
1.3

Ammeter Transfo.
module
0
0
0.1
0.1
0.1
0.1
0.1
0.2
0.1
0.2
0.3
0.5
0.3
0.5
0.8
1.3

Compact NS80 and NS100 to 630 equipped with MA trip units


Fixed device
3 poles

Rat. (A) R/pole

NS80H

1.5
2.5
6.3
12.5
25
50
80
NS100N/H/L 2.5
6.3
12.5
25
50
100
NS160N/H/L 150
NS250N/H/L 220
NS400H/L
320
NS630H/L
500

93.3
89.6
75.6
12.8
2.24
1.04
0.94
148.42
99.02
4.05
1.66
0.67
0.52
0.38
0.3
0.12
0.1

P/pole
0.21
0.56
3
2
1.4
2.6
6.02
0.93
3.93
0.63
1.04
1.66
5.2
8.55
14.52
12.29
25

Additional modules
Vigi

Vigi

(N, L3)

(L1, L2) drawable module module

With-

0
0
0
0
0.2
0.7
1.35
2.9
3.2
13.99

0
0
0
0
0.1
0.35
0.68
1.45
1.6
7

0
0
0
0.1
0.3
1
2.6
4.89
6.14
15

Ammeter Transfo.

0
0
0
0
0.1
0.2
0.45
0.97
1.54
3.75

0
0
0
0
0.1
0.2
0.45
0.97
1.54
3.75

Single-pole and two-pole Compact NS100 to 160


Fixed device
1/2 poles
NS100N/H

NS160N/H

Schneider Electric

Rat. (A)
16
20
30
40
50
63
80
100
125
160

R/pole
11.3
6.3
2.9
2.9
1.4
1.4
1.25
0.76
0.63
0.48

P/pole
2.89
2.52
2.61
4.64
3.5
5.56
8
7.6
9.84
12.29

163

Installation
recommendations

Power dissipated per pole (P/pole) in Watts (W).


Resistance per pole (R/pole) in milliohms (m)
(measured cold). Total power dissipation is the value
measured at In, 50/60 Hz, for a three-pole or fourpole circuit breaker (values above power P = 3RI2).

Power dissipation / Resistance


Compact NS devices equipped
with electronic trip units
Compact NS100 to NS630
Fixed device
3/4 poles

Rat. (A) R/pole

Additional modules

P/pole

Vigi

Vigi

With-

Ammeter Transfo.

(N, L3) (L1, L2) drawable module module


NS100N/H/L 40
0.84
1.34
0.1
0.05
0.2
0.1
0.1
100
0.468
4.68
0.7
0.35
1
0.2
0.2
NS160N/H/L 40
0.73
1.17
0.4
0.2
0.6
0.1
0.1
100
0.36
3.58
0.7
0.35
1
0.2
0.2
160
0.36
9.16
1.8
0.9
2.6
0.5
0.5
NS250N/H/L 100
0.27
2.73
1.1
0.55
1.6
0.2
0.2
250
0.28
17.56
4.4
2.2
6.3
1.3
1.3
NS400N/H/L 400
0.12
19.2
3.2
1.6
9.6
2.4
2.4
NS630N/H/L 630 (1)
0.1
39.69
6.5
3.25
19.49
5.95
5.95
(1) The dissipation values for the Vigi modules and withdrawable circuit breakers are given
for 570 A

Compact NSA160
Fixed device
3/4 poles
NSA160

NSA125NA
NSA160NA

Rat. (A) R/pole


16
25
32
40
50
63
80
100
125
160
125
160

15
8
5.4
3.7
2.8
2
1.4
1
0.8
0.6
0.7
0.6

Additional modules

P/pole
4
5
5.5
6
7
8
9
10
12.5
15.4
11
15.4

Vigi

Vigi

(N, L3)
0.06
0.16
0.26
0.4
0.63
1
1.6
2.5
3.9
6.4

(L1, L2)
0.06
0.16
0.26
0.4
0.63
1
1.6
2.5
3.9
6.4

Compact NS630b to 1600


Version

NS630b N/H/L
NS800 N/H/L
NS1000 N/H/L
NS1250 N/H
NS1600 N/H
Version

NS630 N/H/L
NS800 N/H/L
NS1000 N/H/L
NS1250 N/H
NS1600 N/H

Fixed device
Dissipated power

Input/output resistance

N/H

N/H

30
45
65
130
220

45
60
100

0.026
0.026
0.026
0.026
0.026

0.039
0.039
0.039

Withdrawable device
Dissipated power

Input/output resistance

N/H

N/H

55
90
150
250
460

115
120
230

0.038
0.038
0.038
0.036
0.036

0.072
0.072
0.072

Compact NS1600b 3200


Version
NS1600b N/H
NS2000 N/H
NS2500 N/H
NS3200 N/H

164

Fixed device
Dissipated power

Input/output resistance

250
250
300
680

0.019
0.013
0.008
0.008

Schneider Electric

Compact NS

Dimensions, volumes

Presentation
Functions and characteristics
Installation recommendations

Compact NB
Compact NS80H-MA
Compact NSC100
Compact NSA160
Compact NS100 to 630 (fixed version)
Vigicompact NS100 to 630 (fixed version)
Compact NS100 to 630
(plug-in and withdrawable versions)
Vigicompact NS100 to 630
(plug-in and withdrawable versions)
Compact NS100 to 250
(single-pole and two-pole versions)
Visu function for Compact NS100 to 630
(combination with Interpact INV)
Motor-mechanism module for Compact NS100 to 630
Rotary handle for Compact NS100 to 630
Indication and measurement modules
for Compact NS100 to 630
Front accessories for Compact NS100 to 630
Compact NS630b to 1600 (fixed version)

166
168
170
171
172
174
176
178
180
182
184
186
188
190
192

Dimensions
Mounting
Front-panel cutouts
Rotary handle

192
193
194
195

Compact NS630b to 1600 (withdrawable version)

196

Dimensions, mounting and cutouts


Rotary handle

196
197

Compact NS1600b to 3200 (fixed version)

198

Dimensions

198

Compact NS630b to 3200

200

External modules

200

Accessories NS630b to 3200

204

Connection
Electrical diagrams
Additional characteristics
Catalogue numbers

Schneider Electric

2
11
143

205
221
251
267

165

Compact NS80H-MA

Dimensions, volumes

Dimensions

Mounting
On rails

103

30

E94522

30
15

E21873

E21874

E21875

On backplate

15
u 32

120
X
60

100

100

48,5

206

48,5

(a)

64,5
70
80
84
100

45
90

(a) long terminal shields

Front-panel cutouts
E21884

Cutout C

E21883

Cutout B

E21882

E21881

Cutout A

60,5

26

B/C
71
81

68,5
30

30

Y
14,5

29

68,5

46
92

168

Schneider Electric

Standard direct rotary handle

E21887

7,5

65,5

60

E21886

E21885

E21888

Front-panel cutout

ON
I

4,2

28,5

60

68,5

tripped

30

O
OFF

47,5

82,5
112

45
80
90

43

85

86

Extended rotary handle


Front-panel cutout

E21890

E21889

75
37,5

45

7,5

E21891

7,5

50

60
4,2

75

4,2

37,5

4,2

60
Y
Z

36

72

mini 175
L ( maxi 590 )

shaft length = L _ 109

MCC direct rotary handle


Front-panel cutout

E21894

E21892

E21893

120
69,2
7,5

4,2 120

X
X

60

45,8

1 to 3 maxi
Y

116 2

100

Y
51,7

E22046

100

Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.
Schneider Electric

169

Compact NSC100

Dimensions, volumes

Dimensions
Compact NSC100

E43400

4 poles

E43399

E43398

3 poles

103
120
X
60

(a)

(a)

206

90

15

70
80
84
100

Y
45

45

90

120

(a) long terminal shields

Vigicompact NSC

E43402

E43401

4 poles
E43403

3 poles

101,2

103
120

(a)

(a)

X
60
90

206

70
80
84
100

15

45

75

210

240

(a) long terminal shields.

Extended rotary handle

E21890

E21889

Front-panel cutout
75
37,5

45

7,5

E21891

7,5

50

60
4,2

75

4,2

37,5

4,2

60
Y
Z

mini 175
L ( maxi 590 )

72

36

shaft length = L _ 109

Note.
Centre line X indicates the centre of the mounting r ail.

170

Schneider Electric

Compact NSA160

Dimensions
Compact NSA160
4 poles
E21896

E21895

E21897

3 poles

98,5
120
X

X
64,5

45

206

90

(a)
15

(a)

72,5
82,5
89,5
102,5

Y
45

45

90

120

Vigicompact NSA160
3 poles

4 poles
E21902

E21901

E21903

101,2

98,5
120

X
64,5

45

206

90

(a)

15

(a)

72,5
82,5
89,5
102,5

45

75
210

240

Extended rotary handle


Front-panel cutout
E31295

Dimensions
75
E31296

37,5

E31294

45

83
50

60

X
X

75

37,5

4,2

60
Y
Z

72

36

mini 122
maxi 147

Note.
Centre line X indicates the centre of the mounting r ail.

Schneider Electric

171

Compact NS100 to 630


(fixed version)

Dimensions, volumes

Dimensions
E21503

4 poles

E21502

E21504

2 poles or 3 poles

H1

H3

H5

H7

X
H

H2

H4

H6

(a)
(b)
(c)

(a) short terminal shields.


(b) long terminal shields
(available for spreaders on
NS400 to 630, pitch 52.5 :
L1 = 157.5 mm,
L2 = 210 mm).
(c) interphase barriers.

P1
P2
P4

L1

Y
L
L2

Mounting

K1

4 poles
K1

E21508

E21507

On backplate
2 poles or 3 poles
K1

K1

K1
K2

G1

G5

X
G

K1

G4

T4 (d)

(d) for rear connection only. For two-pole circuit breakers,


the centre hole is not necessary.

4 poles

K1
K

U (e)

G1

E21512

E21511

On rails
2 poles or 3 poles

K2
K

X
G

E49738

On DIN rail with adapter plate


G50
G51

G49
X

G48
G47
Z

172

Schneider Electric

Front-panel cutouts
Cutout C

C1

E21604

E21603

Cutout B

E21601

E21600

Fixed or plug-in circuit breaker


Cutout A

B/C

R1

E21602

E21608

With toggle cover

E21609

With escutcheon

C3
C2

Y
R2
R4(3P)
R5(4P)

P5
P6

C2

C3

C7
X C21

C20

C6

Y
R6
R7

P6

Y
R12
R13

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C
29
41.5

C1
76
116

C2
54
92.5

C3
108
184

C6
43
56.5

C7
104
146

C20
34
46.5

C21
86
126

G
62.5
100

G1
125
200

G4
70
113.5

Type
NS100/160/250N/H/L
NS400/630N/H/L

G5
140
227

G47
95

G48
75

G49
13.5

G50
23

G51
17.5

H
80.5
127.5

H1
161
255

H2
94
142.5

H3
188
285

H4
160.5
240

Type
NS100/160/250N/H/L
NS400/630N/H/L

H5
321
480

H6
178.5
237

H7
357
474

K
17.5
22.5

K1
35
45

K2
70
90

L
52.5
70

L1
105
140

L2
140
185

P1
81
95.5

P2
86
110

P6
88
112

R
14.5
31.5

R1
29
63

R2
54
71.5

R4
108
143

R5
143
188

R6
29
46.5

R7
58
93

R12
43
63

Type
P4
P5
NS100/160/250N/H/L
111 (1)
83
NS400/630N/H/L
168
107
(1) : P4 = 126 mm for Compact NS250N/H/L.

E22046

Type
R13
T
T4
U(e)
NS100/160/250N/H/L
86
6
22
y 32
NS400/630N/H/L
126
6
32
y 32
(e) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.

Schneider Electric

173

Vigicompact NS100 to 630


(fixed version)

Dimensions, volumes

Dimensions

E21514

4 poles

E21513

E21515

2 poles or 3 poles

H9 H11 H13 H15


H8 H10 H12 H14

(a)
(b)
(c)
Y

P1
P2
P4

(a) short terminal shields.


(b) long terminal shields.
(c) interphase barriers.

L1

L
L2

Mounting
On backplate
2 poles or 3 poles
K1

E21519

E21518

K1

4 poles
K1

K1

G9

G1

G7

K1 K1
K2
K

X
G
G8

G6
T
T4 (d)

(d) for rear connection only. For two-pole circuit breakers,


the centre hole is not necessary.

U (e)

G7

4 poles
K1
K

E21521

E21520

On rails
2 poles or 3 poles

K2
K

G1
X

X
G
G6
T

174

Schneider Electric

Front-panel cutouts
Fixed or plug-in circuit breaker
Cutout B
E21796

E21605

E21795

Cutout A
R1
R

C1

C3

C4

C2
C5

R28

Y
R28
R26

P5
P6

R4 (3P)
R5 (4P)

R26
R2

With escutcheons

E21610

E21800

R7
R6

C7
X

C6
C18

C19

Y
R27
R11

P6
Z

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C
29
41.5

C1
76
116

C2
130
192

C3
184
276

Type
H8
H9
H10 H11
NS100/160/250N/H/L
155.5 236
169
263
NS400/630N/H/L
227.5 355
242.5 385
(1) P4 = 126 mm for Compact NS250N/H/L.

C4
C5
86
37
147.5 37

C6
43
56.5

C7
104
146

C18
71
132

C19
68
68

C20
34
46.5

C21
86
126

G
62.5
100

G1
125
200

G6
G7
137.5 200
200
300

G8
G9
145
215
213.5 327

H12 H13
235.5 396
340
580

H14 H15
253.5 432
337
574

K
17.5
22.5

K1
35
45

K2
70
90

L
52.5
70

L1
105
140

L2
140
185

P1
81
95.5

P2
86
110

P4
P5
111 (1) 83
168
107

R11
58
58

R12
43
63

R13
86
126

R26
14.5
32

R27
29
47

T
6
6

T4
22
32

U(e)
y 32
y 32

R7
58
93

E22046

Type
P6
R
R1
R2
R4
R5
R6
NS100/160/250N/H/L
88
14.5 29
54
108
143
29
NS400/630N/H/L
112
31.5 29
71.5 143
188
46.5
(e) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.

Schneider Electric

175

Compact NS100 to 630


(plug-in and withdrawable versions)

Dimensions, volumes

Dimensions
Plug-in base
N

2 poles or 3 poles
Z

4 poles

(*)

K1

K1

E21523

E21522

E21524

K1

H17

G11

H16

G10
(*)

P7
P8
P9

P4

Chassis

2 poles or 3 poles

4 poles

E21585

E21584

E21586

L2

L1

H19
X

H18
(*)

(*)

Z
P7
P8
P9

P2
P4

Y
L6
L7
L8

P12

L6
L9
L10

Mounting
Through panel M (plug-in base)
K1
2P, 3P

4P

Through panel M (chassis)


K1
2P, 3P

K2
K

X
G12

Y
K5

K5

On rails (plug-in base or chassis)


2P, 3P

4P

K21
K20

Y
K11

K12

K7

X
G12

G10

K6

K11
K13

K22
K20

E21534

E21533

G13

G11

G10

K
E21588

E21526

E21525

G13

G11

K2

4P

K
E21587

G20
Y
T

176

G21

(*) short terminal shields are mandatory.


Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.

Schneider Electric

E21590

E21589

On backplate N (plug-in base or chassis)


Front connection (insulating screen is mandatory between the backplate and the base, supplied with the base)
2P, 3P
4P
K1
K

K2
K

G15

X
G14

Interior rear connection


2P, 3P

Exterior rear connection


2P, 3P

4P
K K

K2
K K

E21593

T6

4P

K1
K K

K2
E21592

G15

G18

G16

G15
X

G14

G17

K1

G19

G14

Y
K1

K1 K1

Y
K1

T5

K1

Y
K1

K1 K1

Y
K1

Front-panel cutouts
Plug-in base

Chassis with protection collar and escutcheons


E21620

E21619

E21591

K1
K K

E21594

C11

C17

P44
Z
Y
R8
R9

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C11
103
155

C17
42.5
56

G14
77.5
125

G15
155
250

G16
66
101

G17
132
202

G18
82
126

G19
164
252

G20
37.5
75

G21
75
150

G22 G23
111
222
170.5 341

G24
190
283.5

Type
NS100/160/250N/H/L
NS400/630N/H/L

G25
380
567

G26 G27
208
416
318.5 637

H16 H17
102.5 205
157.5 315

H18 H19
103.5 210
140
280

K
17.5
22.5

K1
35
45

K2
70
90

K5
54.5
71.5

K6
109
143

K7
144
188

K11
74
91.5

K12
148
183

K13
183
228

K20
35
50

Type
NS100/160/250N/H/L
NS400/630N/H/L

K21
70
100

K22
105
145

L1
105
140

L6
92.5
110

L7
185
220

L8
216
250

L9
220
265

L10
251
295

P2
86
110

P4
P7
111 (1) 27
168
27

P8
45
45

P9
75
100

P10
64
86

P12
32
32

Type
P44 R8
R9
U (2) T
T5
NS100/160/250N/H/L
123
74
148
y 32 6
24
NS400/630N/H/L
147
90
180
y 32 6
33
(1) P4 = 126 mm for Compact NS250N/H/L
(2) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

T6
30
33

Schneider Electric

G10
95
150

L
52.5
70

G11
190
300

G12
87
137

L2
140
185

G13
174
274

177

Vigicompact NS100 to 630


(plug-in and withdrawable versions)

Dimensions, volumes

Dimensions
Plug-in base

K1

(*)

K1

K1

E21536

4 poles

E21535

E21537

2 poles or 3 poles

H17

G11

G10

H16

(*)

P7
P8
P9

L1

L2

P4

Chassis
See withdrawable Compact, page 176.

Mounting

E21587

E21526

E21525

K1
K

Through panel M (chassis)


2P, 3P

4P
K2
K

G13

G11

Y
K5

K6

K21
K20

G20
Y

K11
K13

K22
K20

G21

Y
K11

4P
E21534

E21533

On rails (plug-in base or chassis)


2P, 3P

Y
K12

K7

X
G12

K5

G13

G10

K2

X
G12

G10

K1
K

G11

4P
E21588

Through panel M (plug-in base)


2P, 3P

(*) short terminal shields are mandatory

178

Schneider Electric

Front-panel cutouts
Chassis with protection collar and escutcheons
R9
R8

E21623

E21813

Plug-in base
See fixed Compact, page 175.

C11

C17

C16

C13

Y
R33

P44
Z

R34

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C11
103
155

C13
84
84

C16
55
116.5

C17
42.5
56

G10
95
150

G11
190
300

G12
87
137

G13
174
274

G20
37.5
75

G21
75
150

H16
102.5
157.5

Type
NS100/160/250N/H/L
NS400/630N/H/L

H17
205
315

K
17.5
22.5

K1
35
45

K2
70
90

K5
54.5
71.5

K6
109
143

K7
144
188

K11
74
91.5

K12
148
183

K13
183
228

K20
35
50

L
52.5
70

L1
105
140

L2
140
185

P4
111 (1)
168

P7
27
27

P8
45
45

P9
75
100

P44
123
147

R8
74
90

Type
K21
K22
NS100/160/250N/H/L
70
105
NS400/630N/H/L
100
145
(1) P4 = 126 mm for Compact NS250N/H/L.

U (2)
y 32
y 32

E22046

Type
R9
R33
R34
T
NS100/160/250N/H/L
148
74
148
6
NS400/630N/H/L
180
91.5
148
6
(2) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.

Schneider Electric

179

Compact NS100 to 250


(single-pole and two-pole versions)

Dimensions, volumes

Dimensions
2 poles

H1

H3

E29215

E29214

E29213

1 pole

H7
X

X
H

H2

H6
(a)
(b)
Y

L3

L3

L5

P1
P2
P4

L4

(a) short terminal shields


(b) interphase barriers

Mounting
On backplate
2 poles
E21506

E29216

1 pole
K1
K

K1
K

G5

G1

G4

T
T4 (c)

(c) for rear connection only

On rails

U (d)

2 poles
K1
K

G1

E21510

E29217

1 pole

X
G T

(d) U y 20 mm if automatic auxiliary connectors are used

180

Schneider Electric

C1

E21604

E29218

E21601

E21600

Front-panel cutout

B/C

R2

R4(1P)
R5(2P)

R1

C3
C2

P5
P6

X
C2

C3

E21608

E21609

With escutcheon

C7
X

C6

Y
R6
R7

P6
Z

Dimensions (mm)
Type
NS100/160/250

C
29

C1
76

C2
54

C3
108

C6
43

C7
104

G
62.5

G1
125

G4
70

G5
140

H
80.5

Type
NS100/160/250

H1
161

H2
94

H3
188

H4
160.5

H6
178.5

H7
357

K
17.5

K1
35

L3
17.5

L4
70

L5
35

Type
NS100/160/250

P1
81

P2
86

P4
111

P5
83

P6
88

R
14.5

R1
29

R2
19

R4
38

R5
73

R6
29

U(d)
y 32

E22046

Type
R7
T
T4
NS100/160/250
58
6
22
(d) U y 20 mm if automatic auxiliary connectors are used

Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.

Schneider Electric

181

Visu function
for Compact NS100 to 630
(combination with Interpact INV)

Dimensions, volumes

Fixed Compact NS100 to 250 with Visu function Interpact INV100 to 250
3 poles

E62427

510
474

4 poles

E62429

140

E62428

(a)
314 for front
connection.
316.5 for rear
connection.
322.5 with
connectors.
(b)
80.5 for front
connection.
83 for rear
connection.
89 with connectors.

138
131
96
86

52,5
35

35

35

140
52,5
35

35

35

215

215

(a)

277,5
X

X
93,7

277,5
X

(b)

178,5 160,5

Y
52,5

52,5

105

140

Mounting on rails
4 poles
E62431

3 poles
E62430

70
35
7 6

35
9 6

17,5

100

70
17,5

100

50

50
22,3

22,3

157,5

157,5

125

125

62,5

62,5

132

E62433A

E62432A

Front-panel cutout
86

65,5

84

17,5
115,5
X

76
29

14,5
29

182

Schneider Electric

Fixed Compact NS400 to 630 with Visu function

E62434

110

522,5
717,5
(a)
X

142,5

(b)

240

4 poles

185

E62436

160,4
120

(a)
492.5 for front
connection
493.5 for rear
connection
512.5 with right-angle
terminal extensions
536.5 with edgewise
terminal extensions
532.5 with spreaders
525 with 2-cable
connectors.
(b)
127.5 for front
connection
128.5 for rear
connection
147.5 with right-angle
terminal extensions
171.5 with edgewise
terminal extensions
167.5 with spreaders
160 with 2-cable
connectors.

E62435

3 poles
162

70
45

45

185
70

45

45

45

45

241

241

341

341

70
Z

70

140

185

Mounting on rails
4 poles
E62438

E62437

3 poles
90
45
7 6

90
45
7 6

22,5

22,5

75

75

150

241

33

241

33

200

150

200

100

100

E62440

E62439

Front-panel cutout

110

172
86

127

22,5
177,5

116

41,5

Y
Z

31,5
63

Schneider Electric

183

Motor-mechanism module for


Compact NS100 to 630

Dimensions, volumes

Dimensions
4 poles

E21597

E21598

E21599

3 poles

H22
X

H20
H21

H23
Y

L
L2

L12
L11
L1

P33
P32
Z

Front-panel cutouts

R9
R8

E21621

E21612

E21614

E21813

With IP40, IK07 escutcheons and protection collar


for Vigi module

C23

C11

C17

C22
Y
R14
R15

C16

C13

P45

P45

R33
R34

E22046

Note.
Door cutout dimensions are given for a device position in the
enclosure where u 100 + (h x 5) with respect to the door
hinge.

184

Schneider Electric

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C11
103
155

C13
84
84

C16
56
116.5

C17
42.5
56

C22
29
41.5

C23
76
126

H20
62.5
100

H21
97
152

H22
45.5
83

H23
73
123

L
52.5
70

L1
105
140

Type
NS100/160/250N/H/L
NS400/630N/H/L

L2
140
185

L11
91
123

L12
45.5
61.5

P32
178
250

P33
143
215

P45
145
217

R8
74
90

R9
148
180

R14
48.5
64.5

R15
97
129

R33
74
91.5

R34
148
148

Schneider Electric

185

Rotary handle
for Compact NS100 to 630

Dimensions, volumes

direct rotary handle


4 poles

E21625

E21627

3 poles

E21626

L12

60

H23
X

60

H24

DD

H20

60

(a) sans se
(b) avec se
(c) avec se

DD

60

X
O

L15
P34
P35 (a)
Z

L2

L
L11
L1

P36 (b)
P37 (c)

(a) without keylock


(b) with Ronis keylock
(c) with Profalux keylock

Front-panel cutouts
Fixed or plug-in circuit breaker

E21615

E21613

E21805

Vigicompact
E21614

Compact

C23

C23

C22
C4

C22
Y
R14
R15

P43
Z

C5

Y
Z

P43

R28
R26

R14
R15

Withdrawable circuit breaker

E21620

E21622

E21813

Vigicompact

E21618

Compact

C11

R9
R8

C17

C11

C17

C16

C13

P44
Z
Y

Y
R8

R9

An escutcheon is mandatory

186

R33

P44
Z

R34

Protection collar for Vigi module is mandatory.


Escutcheons are mandatory for rotary handles and Vigi protection collars.

Schneider Electric

MCC direct rotary handle


Front-panel cutout

E21632

L8

E21634

E21633

L7
L12

H24 H10
X

G38

H9

1 to 3 maxi
P422

G39

Y
K14
K15

Extended rotary handle

E21628

Withdrawable circuit breaker


Cut shaft at length:
P40-122 mm (NS100 to 250)
P40-150 mm (NS400 to 630)

E21629

Fixed or plug-in circuit breaker


Cut shaft at length:
P38-126 mm (NS100 to 250)
P38-150 mm (NS400 to 630)

L14
L13

E21630

L12

10

60
I

H24 H26

H25

60

Y
P38

E21631

Front-panel cutout
45

L12

T7
H24
X
T6
G36
G37

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C4
C5
86
37
147.5 37

C11
103
155

C13
84
84

C16 C17
55
42,5
116.5 56

C22
29
41.5

C23
76
126

G36
36
36

G37
72
72

G38
41
51

G39
100
145

H9
60
83

H10
120
160

H20
28
40

H23
73
123

H24
9
24.5

Type
NS100/160/250N/H/L
NS400/630N/H/L

H25
37.5
37.5

H26
75
75

K14
50
72.5

K15
100
145

L
52.5
70

L1
105
140

L2
140
185

L7
69
85

L8
120
160

L11
91
123

L12
9.25
5

L13
37.5
37.5

L14
75
75

L15
55
66.5

P34
121
145

P35
155
179

P36
156
180

Type
NS100/160/250N/H/L
NS400/630N/H/L

P37
164
188

P38(1) P40(1) P42


u 185 u 248 125
u 209 u 272 149

P43
89
112

P44
123
147

R1
29
29

R8
74
90

R9
148
180

R14
48.5
64.5

R15
97
129

R26
14.5
32

R33
74
91.5

R34
148
148

T6
4.2
4.2

T7
50
50

(1) y 600 mm.


Note.
Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5)
with respect to the door hinge.
Schneider Electric

187

Indication
and measurement modules
for Compact NS100 to 630

Dimensions, volumes

Dimensions
Circuit breaker with current-transformer module
E21516

E21517

Circuit breaker with ammeter module

X
H9 H11 H13 H15

H9 H11 H13 H15

H8 H10 H12 H14

H8 H10 H12 H14

P1
P2
P47

P1
P2
P4

Mounting
4 poles

K1

E21519

E21518

On backplate
2 poles or 3 poles
K1
K1

K1

G7

K1 K1
K2
K

G9

G1

X
G
G8

G6
T
T4 (d)

(d) for rear connection only. For two-pole circuit breakers,


the centre hole is not necessary.

U (e)

G7

4 poles
K1
K

E21521

E21520

On rails
2 poles or 3 poles

K2
K

G1
X

X
G
G6
T

188

Schneider Electric

Front-panel cutout
Circuit breaker with ammeter module and voltage-presence indicator
E21673

E21674

T8

C30
C1

C
C28
C27

T8

E21677

E21678

Y
R
R1
R16
R17

P6

C30

C23
C22
C28
C27

Y
R16
R17
R14
R15

P43
Z

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C
28
41.5

C1
76
116

C22
28
41.5

Type
NS100/160/250N/H/L
NS400/630N/H/L

H11
263
385

H12 H13
235.5 396
340
580

Type
NS100/160/250N/H/L
NS400/630N/H/L

R14
48.5
64.5

R15
97
129

R16
46.5
64.5

C23
76
126

C27
56.5
56.5

C28 C29
124
30
185.5 30

C30
78.5
122

G
62.5
100

G1
125
200

G6
G7
137.5 200
200
300

G8
G9
145
215
213.5 327

H8
H9
155.5 236
227.5 355

H10
169
242.5

H14 H15
253.5 432
337
574

K
17.5
22.5

K1
35
45

K2
70
90

P1
81
95.5

P2
86
110

P4
P6
111 (1) 88
168
112

P43
89
112

P48
128
154

R1
29
63

R17
93
93

T4
22
32

U (2)
y 32
y 32

T
6
6

P47
137
162

R
14.5
31.5

(1) P4 = 126 mm for Compact NS 250N/H/L


(2) U y 20 mm if automatic auxiliary connectors are used (NS100 to 250).

Schneider Electric

189

Front accessories
for Compact NS100 to 630

Dimensions, volumes

Protection collar

E21637

E21635

E21636

Toggle protection collar

E21640

E21638

Circuit breaker with


motor-mechanism
module
E21464

Circuit breaker with


toggle or rotary handle
E21639

Vigi-module protection collar

52,4

91

53

35

E21653

E21654

E21655

Toggle cover

M8

D3

A3

Front-panel escutcheons
E21643

E21641

E21642

For toggle

M3

M2

A1

D1

D2

E21644

E21645

E21646

For Vigi module

79

69

190

64

3,5

6,5

Schneider Electric

Front-panel escutcheons

E21647

E21649

E21648

For protection collar, motor mechanism or rotary handle

M6

M7

A2

D1

D2

E21650

E21652

E21651

For Vigi module with protection collar or ammeter module

93,5

80,5

157

3,5

6,5

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

Schneider Electric

A
91
123

A1
69
102

A2
157
189

A3
94
35

D
35
134

D1
3.5
3.5

D2
6.5
6.5

D3
40
60

M
73
123

M2
115
155

M3
102
142

M6
114
164

M7
101
151

M8
94
134

191

Compact NS630b to 1600


(fixed version)
Dimensions

Dimensions,
volumes

Manual control

E47973A

E47972B

Front connection

(1)

163,5

327

254

508

200

100

107,5

99,5 (3P)
169,5 (4P)

205

99,5

(1) terminal shields are


optional

E47914A

Rear connection
105 (3P)
175 (4P)

105
188
94

E47913A

123
105
234

113
92,5

117

210

123

35

107,5

70

140,5
146,5
14

205

Electrical control

E47897A

Front and rear connection


105 (3P)
175 (4P)

105
188
94

E47896A

123
105

210

234

200

117

100

123

F : Datum
107,5

35

169,5
175,5
F

192

70
99,5 (3P)
169,5 (4P)

99,5

Note.
Dimensions for front and rear
connection on electrically
operated devices are
identical to those for
manually operated devices.

Schneider Electric

Mounting
Front connection
On backplate

On rails

E47898A

4 6,5

E47899A

4 6,5

200

100

100

99,5 (3P)
169,5 (4P)
99,5 (3P)
169,5 (4P)

200

99,5

99,5

Rear connection
On backplate or rails
3P

4P
4 6,5

6 6,5

Y
E47970A

E47969A

106

106
44

44

234

44
106

106 117

117

35

35
70

70

70
100

100
200

234
44

270

Note.
Mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 3-pole device
Z is the back plane of the device.

Schneider Electric

193

Compact NS630b to 1600


(fixed version) (cont.)
Front-panel cutouts

Dimensions,
volumes

124 mini
(1) (2)

Door cutout
A

150
(2)

194 mini (3P)


264 mini (4P)

B
E59201B

(A)
(B)
(C)

E47901A

E59368

Toggle control

194 mini

194 mini (3P)


264 mini (4P)

194 mini

201 (1)

216 (1)
266 (2)

100,5 (1)

108 (1)
133 (2)

90,5 (1)

107,5

194 (1)
244 (2)

140,5
146,5

97 (1)
122 (2)

181 (1)

E59200A

C 194 mini (3P)


264 mini (4P)

194 mini

Y
119 (1)
144 (2)

95,5 (1)
108 (2)

F : Datum.
(1) Without escutcheon.
(2) With escutcheon.

35,5 (1)
60,5 (2)

71 (1)
121 (2)

Electrical control

(A)

150 mini
(1) (2)

E47901A

E59369

Door cutout
A
194 mini (3P)
264 mini (4P)

194 mini

216 (1)
266 (2)

108 (1)
133 (2)

107,5

194 (1)
244 (2)

169,5
175,5

97 (1)
122 (2)

F : Datum.
(1) Without escutcheon.
(2) With escutcheon.

194

Schneider Electric

Rotary handle
Direct rotary handle
Dimensions
124 mini
(1) (2)

(A)
(B)
(D)

180 mini
(2)
E47955A

E47954

195

60
R80

24

60

25

107,5
154,5
160,5
189,5
229,5

194 mini

194 mini (3P)


264 mini (4P)

E47956A

194 mini (3P)


264 mini (4P)

B
E47957

E47901A

Door cutout
A

194 mini

194 mini

201 (1)

216 (1)
266 (2)

201 (1)

100,5 (1)

100,5 (1)
108 (1)
133 (2)
194 (1)
244 (2)

90,5 (1)

90,5 (1)

97 (1)
122 (2)

130 (1)

181 (1)

(1) Without escutcheon.


(2) With escutcheon.

Extended rotary handle


Dimensions

Door cutout

E47960A

E47959A

E47958A

Y
60

51

R100

25,5

X
60

212,5
231,5 mini
605,5 maxi

F : Datum

Schneider Electric

24

51

24
5

25

25
25,5

Note.
X and Y are the symmetry planes for a 3-pole device
Z is the back plane of the device.

51

195

Compact NS630b to 1600


(withdrawable version)
Dimensions, mounting and cutouts

Dimensions,
volumes

Dimensions
Electrical control

210
mini

E59370B

E47943B

210
mini

127,5 (3P)
197,5 (4P)

E47944A

Manual control

160,5
188
94

Y
70 (*)

46 (*)

199

X
45,5

69
5

123

60 mini

90 (3P)
160 (4P)

60 mini
F

90

(*) Withdrawable position

Mounting
Vertical on uprights or backplate

E47937A

E47945

E47175B

Bottom mounting on base plate or rails

4 6,5

6 6,5

X
25

24

150

50

25 100

100
216
231
F

90 (3P)
160 (4P)

90

109 (3P)
179 (4P)

109

Cutouts

E47177B

170 mini (3P)


240 mini (4P)

Rear panel cutout


E47178A

Door cutout
230 mini

259 (1)
303 (2)

234
117

109 (1)
130,8 (2)
161 (1)
183 (2)

102,5 (3P)
172,5 (4P)

102,5

259 (1)
307 (2)

(1) Without escutcheon.


(2) With escutcheon.
F : Datum

196

Note.
X and Y are the symmetry planes for a 3-pole device.

Schneider Electric

Rotary handle
Direct rotary handle
Dimensions
210
mini

E47963A

E47962A

Y
136 (*)

60
R80

X
93

60

24

60 mini

25

(*) Withdrawable position.

E47964B

Door cutout
170 mini (3P)
240 mini (4P)

230 mini

259 (1)
303 (2)

X
109 (1)
130,8 (2)

259 (1)
307 (2)

161 (1)
183 (2)

(1) Without escutcheon.


(2) With escutcheon.

Extended rotary handle


Dimensions

Door cutout
E47966A

R200

51

E47967A

E47965A

E47966A

Y
60

25,5

24

60

207 mini
447 maxi

17

51

24
5

25

25
25,5

51

Note.
X and Y are the symmetry planes for a 3-pole device.

Schneider Electric

197

Compact NS1600b to 3200


(fixed version)
Dimensions

Dimensions,
volumes

Dimensions
132 mini

Y
E59440

E59439

(A)
(B)
(C)

165
105
330

150

210

75

18,5

163

38,5

170

132

340
180 (3P)
195 (3P) 295 (4P)
310 (4P)
210 (3P)
325 (4P)

162,5
168,5
222,5

368

180
195
210

E59456A

Mounting on rails
Y
4 12

150
75

195 (3P)
310 (4P)

F : Datum

198

195

Note.
X and Y are the symmetry planes for a 3-pole device

Schneider Electric

Door cutout
A

Y
E59729A

E59457

216 (1)
267 (2)
108 (1)
133,5 (2)

201

100,5

173 (1)
198,5 (2)

166
332

346 (1)
397 (2)

C
E59458

119
95,9

73
146

Note.
X and Y are the symmetry planes for a 3-pole device

Schneider Electric

199

Compact NS630b to 3200


External modules

Dimensions,
volumes

E47684A

E47683A

Control-wire connections to terminal block


S : 0,6 mm2
S : 2,5 mm2

1
8

3,5
Only one wire per terminal.

External power-supply module (AD)


E47690A

60

L4
L3

AD 22

t
Inpu C
24VD
ut
Outp C
24VD

0A

2 6

60

73

+
G2

112

E47691A

G1

75

L4
L3

t
Inpu C
24VD
ut
Outp C
24VD

0A
AD 22

+
G2

G1

Battery module (BAT)

E47692A

60

2 6

60
H4
H3

24V
BAT

t
Inpu C
24VD

73

ut
Outp C
24VD H1

112

75

E47693A

H2

H4
H3

24V
BAT

t
Inpu C
24VD

ut
Outp C
24VD H1

H2

200

Schneider Electric

MN delay unit

E47694A

57
1

4 5

81

S
3 6
0.5

10 12

73,5

73

E47695A

66

42

1.5
3
MN
r de R
UV
dateu
Retardelay for
Time

MN
UVR
30 V
100/1C
AC/D

2 4,2

4 5

72
S
3 6
0.5

30 V
100/1C
AC/D

1.5
3
MN
r de R
UV
dateu
Retardelay for
Time

MN
UVR

10 12

46

Chassis communication module


Digipact

E47686A

E47685A

Modbus

90

us
modb
CCM
Fault
Com.

CE

CD

CT

ss
Addre
.
sync

58

Disjoncteur

Rseau
shield
B B
A A
B B
A A
Breaker
Network

++

45

54

External sensor for source ground return (SGR) protection


"MDGF" summing module

200

E47687A

E58561

External sensor

90

130
45
F
MDG

45

76
150

Schneider Electric

58

106

201

Compact NS630b to 3200


External modules (cont.)

Dimensions,
volumes

External sensor for neutral


400/1600 A (NS630b to 1600)

E47699

4 14
GND VN VC

H1

H2
35 76
T4 T3 T1 T2

177
208

1000/4000 A (NS1600b to 3200)

E47701

8 14
H1

H2
VC
VN
GND
T4
T3
T1
T2

44

174

44 127

44

295

Installation
400/1600 (NS630b to NS1600)
E47696

E47697A

1000/4000 A (NS1600b to NS3200)

202

Schneider Electric

Rectangular sensor for earth leakage protection (Vigi)

E94309

E90300

280 x 115 mm window

E94310

E90301

470 x 160 mm window

Busbars
Window (mm)
Weight (kg)

I y 1600 A

I y 3200 A

280 x 115
14

470 x 160
18

Busbars path
280 x 115 window
Busbars spaced 70 mm centre-to-centre

470 x 160 window


Busbars spaced 115 mm centre-to-centre
E90307

E94311

M1 M2 M3

2 bars 50 x 10
4 bars 100 x 5

E90364

E94312

M1 M2 M3

2 bars 100 x 5
4 bars 125 x 5

Schneider Electric

203

Accessories NS630b to 3200

Dimensions,
volumes

Escutcheon
NS630b to NS1600 (fixed control)
C

(C)
E59885A

E59891A

A
(A)

E59886A

275

154

27
27

27

131

27
253

E59892A

NS630b to NS1600 (withdrawable control)

E59887A

313

X
27

27

13

27

317

NS1600b to NS3200 (fixed control)

E94264

E94263

Y
27

275

X
137,5

202,5

27
405

204

Schneider Electric

Compact NS

Connection

Presentation
Functions and characteristics
Installation recommendations
Dimensions, volumes

Compact NS80H-MA, NSC100N and NSA160


Compact, Vigicompact NS100 to 630 (fixed version)
Compact, Vigicompact NS100 to 630 (plug-in and
withdrawable versions)
Compact NS630b to 1600 (fixed version)

206
208

Bars
Cables with lugs and bare cables

212
215

Compact NS630b to 1600


(plug-in and withdrawable versions)

216

Bars
Cables with lugs

216
218

Compact NS1600b to 3200 (fixed version)

219

Electrical diagrams
Additional characteristics
Catalogue numbers

Schneider Electric

2
11
143
165

210
212

221
251
267

205

Compact NS80H-MA,
NSC100N and NSA160

Connection

E21877

E21878

Compact NS80H-MA

97

48,5

Y
29,2 29,2

32
Z

Compact NSC100N
34,5

30
E43406

E43405

30

48,5
X

48,5

34,5

45

83

90
Z

30

30

30

30

E21900

30

E62454

E21898

Compact NSA160

44

44

X
53

Y
90

34,5

53

45

45

34,5

120

83
Z

206

Schneider Electric

Vigicompact NSC and NSA

30

60,8
30

4 poles
30

30

E43407

E62455

Bottom connection
3 poles
30

30

30

60,8
30

30

30

30

incoming

incoming

outgoing

outgoing

30

60,8
30

incoming

4 poles

30

30

30

E43408

E62456

Top connection
3 poles

outgoing

30

30

60,8
30

incoming

Schneider Electric

30

30

30

outgoing

207

Compact, Vigicompact
NS100 to 630 (fixed version)

Connection

P21
P13

E21747

E21748

Connection dimensions

G4
X

G5
G19

Y
Z

K1

K1

K1

Front connection
Terminals
NS100/160/250
E21554

10,5

E21750

NS400/630
Z

E35578

14
70

113,5

Connectors
NS100/160/250
E21751

E21553

E21752

NS400/630
Z

19

Z
46,5

14

70

113,5

113,5

X
X

Rear connection
NS400/630

10
8,6

E21756

E21755

E21561

NS100/160/250
20

15

13

23,2

13
18

14
30

70
43 short RC
88 long RC

208

50 short RC
115 long RC

X
Z

113,5
Z

Schneider Electric

Connection with accessories


Right-angle terminal extensions (upstream only)

Straight or edgewise terminal extensions


NS100/160/250

NS100/160/250
4

E21556

E21563

37,5
39,5 (b)

41 Z

E35577

20,5

70

70
E35580

Z
X

30

(b) Vigi module or NS250.

E21754

NS400/630

E21758

NS400/630
8

61

View F

58

42

Z
34

8
113,5

113,5
X

E21557

E21565

E21558

Spreader

Distribution connectors (interphase barriers mandatory)


NS100/160/250

K10
K8

K8

K8

K9
K8

K8

G27

X
G26
E21566

70
X

41

64,5
66,5 (b)

(b) Vigi module or NS250.

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

G4
70
113.5

G5
140
227

G19
215
327

G26
30
39
52,5

G27
41
54
67,5

K1
35
45

K8
45
52.5
70

K9
159
187.5
240

K10
114
135
170

P13
19.5 (1)
26

P21
44

(1) P13 = 21.5 mm for NS250N/H/L and Vigi MH module

Note.
For dimensions of conductors, see pages 98 and 99.

Schneider Electric

209

Compact, Vigicompact NS100 to 630


(plug-in and withdrawable versions)

Connection

Plug-in base or chassis


K1

K1

E21569

E21570

K1

Front connection
Terminals
NS400/630
With spreaders
E21939

E21571

NS100/160/250
Mounting on backplate or on rails (1)

(*)

E21572

P21

42
P21

Z
G32
G31
195,5
210,5

G32
G31

(1) For backplate mounting, the insulating screen, supplied


with the plug-in base, must be installed.

Connectors
NS400/630
With spreaders
94

E21941

NS100/160/250
Mounting on backplate or on rails (1)
(*)

68

E21580

E21581

Z
P28

Z
G31

G32
202

G34

(*) short terminal shields are mandatory.

210

Schneider Electric

E21583

Connectors
NS100/160/250
Mounting through backplate or on rails

109

E21942

(*)

NS400/630

83

P29
P30
E21582

G32
G34

66
94

Rear connection

(*)

E21574

E21573

Mounting through backplate or on rails


P22
P23

G35

P24
P25

G33

P26
P27

Long, insulated right-angle


terminal extensions are
mandatory.

E21576

(*)

E21577

Mounting on backplate
Right-angle extensions (mounted down and out)

G33
X

E21578

(*)

E21579

Right-angle extensions (mounted up and out)


P26
P27

G35

(*) short terminal shields are mandatory.

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

Schneider Electric

E
4
6

G31 G32 G33


108.5 100
63.5
171
156.5 104

G34
110

G35
80.5
129

K1
35
45

P21
19
26

P22 P23 P24


75.5 67
49
114.5 100.5 82.5

P25
57.5
96.5

P26 P27
75.5 67
108.5 94.5

P28
26.5

P29
54.5

P30
36.5

211

Compact NS630b to 1600


(fixed version)
Bars

Connection

E47905A

E47904A

Horizontal rear connection


43,5

70

70

70

E47918A

15
123
67,5

N
44

E47201B

X
67,5

Y
25

9,5 12,5

123
60

15
12,5

31
2 11

Vertical rear connection


70

E47908A

E47919A

E47907A

43,5

70

70
15
View A

97

E47205B

97

60
12,5
9,5

12,5
31

44

25
2 11

View A detail.

70

163,5
129

70

70
30

E47911B

E47916A

E47910A

Front connection

Y
View A

163,5

16,5

E47971A

Top terminal
129

44

9,5

25

15

2 vis M10

15

Bottom terminal
2 vis M10

25
44

15

15
9,5

View A detail.

F : Datum.
Note.
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.

212

Schneider Electric

E47922A

E47920A

E47921A

Front connection with spreaders


70

70

25

25

196
181
15

Y
View A

E47923A

X
181
196

95

95
70

95

70

70

12,5

31,5

12,5

15

Y
View A

98

95

E47926A

E47924A

E47925A

Rear connection with spreaders


95

70

70

123
15

15

82,5

52,5

Y
E47927A

123

83

95

95
70

95

70

70

12,5

12,5

Spreader detail

25

38,5

13,5

25

13,5

15
5 11

13,5

15

5 11

13,5

=
30

82 52

15
5 11

5 11

25
52

38,5
=

30
82 52

15

77
25

30
82 52

25
52

38,5
25

30
82 52

77

Left or right spreader for 3P


E47294A

77

Left or right spreader for 4P


E47293A

77
38,5

Middle spreader for 3P


E47292A

E47234A

Middle left or middle right


spreader for 4P

25

25
52

52

View A detail

F : Datum.

Schneider Electric

Note.
X and Y are the symmetry planes for a 3-pole device.

213

Compact NS630b to 1600


(fixed version) (cont.)
Bars

Connection

E47930A

E47928A

E47929A

Front connection with vertical-connection adapters


70

70

70
15
View A

200

200

E47218A

430

25

89
= =

12,5

21 (1)
101

15

21
3 11

10
62,5

15

20

View A detail.

F : Datum.
Note.
(1) two mounting possibilities for vertical-connection adapters
(pitch 21 mm).
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.

214

Schneider Electric

Cables with lugs and bare cables

E47932A

E47931

15

E47933A

Front connection with vertical-connection adapters and cable-lug adapters


70

70

70

View A

250
200

Y
15

530
E47230A

200
250

184
17

50

50

50

50

80
5 13

5 11

View A detail.

15
10
150
F

Fixed circuit breaker with 4-cable bare-cable connectors (240 mm2)


70

70

E59204A

E59202A

E59203A

70

199

206,5

N
398

413

199

206,5

E59205A

4 21,5

26 63

26
16,5

54

35
61

F : Datum.

Schneider Electric

215

Compact NS630b to 1600

Connection

(plug-in and withdrawable versions)

Bars

E47181A

E47948A

E47179A

Horizontal rear connection


49

70

70

70

15

67,5
228

N
E47201B

67,5
114

44
25

9,5 12,5

15

267,5

60

F
12,5
2 11

70

E47940A

E47182A

Vertical rear connection


70

70
15

49

97

E47184A

View A

X
N
E47205B

97

267,5

60
12,5
9,5

12,5

F
44
25
2 11

View A detail.

15

12,5

70

E47187A

E47185A

E47941A

Front connection
70

View A

70

171

N
X

Top terminal
25

37,9
26

83

131

52

26
37,9

9,5

100

2 11

25

F : Datum.

9,5

2 11

E47188B

9,5

12,5

Bottom terminal

44

140

235

336

44

9,5

View A detail.

Note.
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.

216

Schneider Electric

E47225A

E47952A

E47223A

Front connection with spreaders


95

95

70

View A

70

238
223

Y
E47226A

X
207

95

95

70

192

95

70

70
View A

12,5

12,5

250
F

Spreader detail

25

38,5

13,5

25

13,5

15
5 11

13,5

15

5 11

13,5

=
30

82 52

15
5 11

5 11

25
52

38,5
=

30
82 52

15

77
25

30
82 52

25
52

38,5
25

30
82 52

77

Left or right spreader for 3P


E47294A

77

Left or right spreader for 4P


E47293A

77
38,5

Middle spreader for 3P


E47292A

E47234A

Middle left or middle right


spreader for 4P

25

25
52

52

View A detail.

F : Datum.

Schneider Electric

217

Compact NS630b to 1600

Connection

(plug-in and withdrawable versions) (cont.)

Cables with lugs


Front connection with vertical-connection adapters and cable-lug adapters
70

70

70
View A

15

50
E47229A

E47227

E47953A

15

71
292
21

171

184

583

E47230A

17
140
21
261

50

50

50

50

80
5 13

71

15

5 11

View A detail
50

193,5

15

F : Datum.
Note.
X and Y are the symmetry planes for a 3-pole device.
Tightening torque: 50 Nm with contact washer.
X and Y are the symmetry planes for a 3-pole device.

218

Schneider Electric

Compact NS1600b to 3200


(fixed version)

Front connection (NS1600b to 2500)

165
150

E59459A

115

115

E59461A

E59460

115

View A

OFF

150

13

E59462B

OFF

25

76
= =

165

=
=
3 11

View A detail

20

15

E94968

E59737

E59736A

Front connection with vertical-connection adapters (NS1600b to 2500)


115
80

115
80

115
80

80

230
142,5

View A

OFF

142,5
230

4 11
E59735

OFF

25
60 100

25
25
F

25

20

40

20

12,5

45

20
15

25 25

60

80

View A detail.

E59740

Front connection (NS3200)

230

115

115

E59741A

E59739A

115

142,5

Z
230

E59735

142,5

25
60 100

25
25

Note.
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.

Schneider Electric

20

25
40

View A

4 11

OFF
OFF

45
60

20

12,5

20
15

25 25
80

View A detail.

219

220

Schneider Electric

Compact NS

Electrical diagrams

Presentation
Functions and characteristics
Installation recommendations
Dimensions, volumes
Connection

Schneider Electric

2
11
143
165
205

Compact NSC100, Compact NS80H-MA

222

Indication contacts
Early-make contacts

222
223

Compact NSA160

224

Indication contacts

224

Compact NS100 to 630

226

Indication contacts
Motor mechanism (automatic reset)
Motor mechanism (remote reset)
Motor mechanism (local reset)
Early-make contacts
Motor protection - Trip unit STR22/43ME

226
228
230
232
234
236

Compact NS630b to 1600

240

Fixed circuit breakers


Plug-in / withdrawable circuit breakers

240
242

Compact NS630b to 3200

244

Communications option 24 V DC external power supply


Earth-fault and earth-leakage protection, neutral protection,
zone selective interlocking
Fixed circuit breakers

244
246

Additional characteristics
Catalogue numbers

251
267

248

221

Compact NSC100
Compact NS80H-MA
Indication contacts

Electrical diagrams

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
With OF1 and CAF1/CAF2

C1

92

94 12

12

RD

WH

14

14

E43822

E43821

D1

VT

YE

With OF1 and CAO1

OF1

CAO1

OF1

CAF2

CAF1

trip unit
MN (1)
SD

11

11
GY

91

RD

D4 C2

WH

MX

(1) MN or MX (MN: D1, D4; MX: C1, C2)

CN1

- CN 1 +
CN2

- CN 2

E43824

With MX

E43823

With MN

CN1

CN2

F1

- CN 2

F1

tripping order

tripping order

H1

H1
D1

92

C1

94

92

94

trip unit

trip unit

MX

MN

SD

SD

D4

C2

91

Symbols
Q
Compact NS
SD
trip indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
XI
terminal block for CAF wiring (must be ordered)
F1
breaker for the protection of MN/MX
H1
lamp signalling tripped position

222

- CN 1 +

91

Colour code for auxiliary wiring


RD
red
GN
green
BK
black
BL
blue
WH
white

Schneider Electric

Early-make contacts
Following tripping due to an electrical fault,
reset must be carried out locally and
manually.

With MN
CN1

- CN1 +

CN2

- CN2

tripping
unit

(1)

X1

RD

BL

WH

RD

D1

WH

WH

E43831

WH

D1 C1

CAF1

CAF2

trip unit

BL

MN

D4

D4

With MN + SD
CN1

- CN1 +

CN2

- CN2

trippinng
order

(1)

X1

D1 C1

RD
BK

WH
BL

94

WH

92

RD

GN

WH

E43830

D1

RD

GN

WH

92

94

CAF1

CAF2

trip unit
MN
SD

91

BL

BL

D4

D4

91

(1) independent auxiliary source.


Remark
NS80H-MA and NSC100 circuit breakers are not plug-in or
withdrawable devices. As a result, there is no automatic
auxiliary connector. Connections are made directly to the
device.
Schneider Electric

223

Compact NSA160
Indication contacts

Electrical diagrams

With OF1
D1

C1

92

94 12

14

E62467

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

OF1

CAO1

trip unit
MN (1)
MX

D4 C2

SD

91

11

(1) MN or MX (MN: D1, D4; MX: C1, C2)

Symbols
Q
Compact NS
SD
trip indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
XI
terminal block for CAF wiring (must be ordered)
F1
breaker for the protection of MN/MX
H1
lamp signalling tripped position
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
BL
blue
WH
white

224

Schneider Electric

E43823

With MN
CN1

- CN 1 +
CN2

- CN 2

F1

tripping order
H1
D1

92

94

trip unit
MN
SD

D4

91

E43824

With MX

CN1

- CN 1 +
CN2

- CN 2

F1

tripping order

H1
C1

92

94

trip unit
MX
SD

C2

Schneider Electric

91

225

Electrical diagrams

Compact NS100 to 630


Indication contacts

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

Compact NS100 to 250

D1 C1

82

VT

GN

24

14 22

94 12

92

YE

14 22

24 72

74 82

VT

84

OF2

OF1

YE

84

RD

94 12

RD
YE

GN

CE

92

VT

D1 C1

354

WH

314 312 352

RD

WH

VT

GY
GY

VT

E18916

Manually operated circuit breaker

CAF1

CAF2

CAO1

trip unit
MN (1)

(2)

SDE

MX SD

Id

SDV
91

71

81
BK

GY

GY

BL

21

11

BK

C2
OR

D4

CD
91

11

81

21

RD

WH

C2

GY

D4

351
YE

YE

311

(1) MN or MX (MN: D1, D4; MX: C1, C2).


(2) for the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in the
circuit breaker, but only one can be connected to the automatic auxiliary connectors.

VT

GY
GY

92

VT

GN (3)
24 72

74 82

WH

A2

B2

84

A2

A4

B4

BL

84

OR

24

14 22

94 12

YE

VT

14 22

RD

D1 C1

94 12

RD

CE

92

YE

D1 C1

354

WH

314 312 352

GN

E18917

VT

Circuit breaker with motor mechanism

A4

B4

OF2

OF

MT

trip unit
MN (1)

(2)

SDE

MX SD
BK (3)

Id

71

81

A1

GN

21

BK

11

GY

91

GY

C2

OR

BL

D4

BK

SDV
L1

CD
D4

351

C2

91

A1

21

11

L1

YE

YE

311

(1) MN or MX (MN: D1, D4; MX: C1, C2).


(2) for the withdrawable and plug-in versions, SDV and OF2 contacts can be installed in the
circuit breaker, but only one can be connected to the automatic auxiliary connectors.
(3) wires supplied, must be connected to ensure correct operation.

226

11
91

12
92

14

21

94

81

71
A1

22
82

72
L1

24

74

84

E43817

Auxiliary wiring for plug-in / withdrawable circuit breaker


Automatic auxiliary connectors
Manual auxiliary connectors
(wires 0.75 to 2.5 mm2)
(wires 0.75 to 2.5 mm2)
E43816

Symbols
Q
Compact NS100 to 250
SD
trip indication contact
SDE fault indication contact
SDV earth-fault indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
MT
motor-mechanism module
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
CE
connected-position carriage switch
CD
disconnected-position carriage switch
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
VT
violet
YE
yellow
GY
grey
BL
blue
OR
orange
WH
white

B4

24

A4

22

A2

21

74
72
71

84
82

L1

81
A1

D4

14

94

C2

12

92

D1
C1

11

91

Fixed part (rear view).


D1

C1

C2

D4

A2

A4

B4

Fixed part
(front view looking into base)

Schneider Electric

Compact NS400 to 630

OF1

OF2

84

RD

GN

92 94 12 14 22 24 32

D1 C1

82

34

VT

VT

YE

24 32

14 22

VT
YE

RD

YE

92 94 12

GN

GN
OR

BK

CE

WH

Z11 e+ T1 D1 C1

314 312 352 354

VT

RD
YE

WH

VT

VT

GY
GY

E22042

Manually operated circuit breaker

34 72 74 82

84

OF3

CAF1

CAF2

CAO1

trip unit (3)


MN (1)

SDE

(2)

MX SD

Id
21

31

71

GY

GY

11
GY

C2

BK

OR

91

BL

C2

e- T2 D4

RD
BL

WH

SDV
D4

81

CD
91

11

81

31

RD

WH

21

GY

Z12

351
YE

YE

311

(1) MN or MX (MN: D1, D4; MX: C1, C2).


(2) for the withdrawable and plug-in versions, SDV and OF3 contacts can be installed in the
circuit breaker, but only one can be connected to the automatic auxiliary connectors.
(3) options available with trip unit STR53UE only.

92 94 12 14 22 24 32

D1 C1

OF1

OR

WH

GN (4)
34 72 74 82

BL

A2 A4 B4

84

RD

YE

34

VT

24 32

VT

14 22

YE

RD

94 12

VT

92

GN

GN
OR

BK

CE

WH

Z11 e+ T1 D1 C1

314 312 352 354

YE

VT

VT

GY
GY

E22043

Circuit breaker with motor mechanism

B2 A2 A4

84

B4

OF3

OF2

MT

trip unit (3)


MN (1)

SDE

(2)

MX SD

BK (4)

Id

A1
BK

81

GN

71

GY

C2

31

21

11
GY

e- T2 D4

BK

OR

91

BL

C2

GY

D4
RD
BL

WH

SDV
L1

CD
351

Z12

91

11

A1

31

21

L1

YE

YE

311

(1) MN or MX (MN: D1, D4; MX: C1, C2).


(2) for the withdrawable and plug-in versions, SDV and OF3 contacts can be installed in the
circuit breaker, but only one can be connected to the automatic auxiliary connectors.
(3) options available with trip unit STR53UE only.
(4) wires supplied, must be connected to ensure correct operation.

Schneider Electric

11
91

12
92

14
94

21
81

A1

22
82

L1

24
84

31

71

Z11

32

72

e+

34

E43817

Auxiliary wiring for plug-in / withdrawable circuit breaker


Automatic auxiliary connectors
Manual auxiliary connectors
(wires 0.75 to 2.5 mm2)
(wires 0.75 to 2.5 mm2)
E43818

Symbols
Q
Compact NS100 to 250
SD
trip indication contact
SDE fault indication contact
SDV earth-fault indication contact
OF
ON / OFF indication contact
MN
undervoltage release
MX
shunt release
MT
motor-mechanism module
CAO early-break contact of rotary handle
CAF early-make contact of rotary handle
CE
connected-position carriage switch
CD
disconnected-position carriage switch
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
VT
violet
YE
yellow
GY
grey
BL
blue
OR
orange
WH
white

74

T2

24

_
e

_
e

T1

22

e+

Z12

21

Z11

B4
D1

C1

C2

D4

A2

A4

B4

Fixed part
(front view looking into base)

Z12 T1 R1 T2 R2

34

A4

32

A2

31

74
72
71

84
82
81

D4

14

94

L1

C2

12

92

A1

D1
C1

11

91

Fixed part (rear view).

227

Compact NS100 to 630


Motor mechanism
(automatic reset)

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

Automatic reset with MN


E43825

Electrical diagrams

- CN1 +

CN1

CN2

- CN2

Following tripping due to an electrical fault,


reset must be carried out locally and
manually.

F1

H2

H1

WH

RD

WH
D1

GN (1)

82

84

B2

A4

OR

A2

D1

A2

B4

BL

tripping
order
(2)

A4

B4

Q
MT

trip unit
SDE
MN
BK (1)

A1

D4

GN

81

BK

BL

D4

A1

L1

L1

(1) wires supplied, must be connected to ensure correct operation.


(2) the tripping order must lock out the closing order.

E43826

Automatic reset with MX


- CN1 +

CN1

CN2

- CN2

F1

H2

A2

C1

228

82

OR

GN (1)
84

WH

WH

RD

C1

B2 A2

A4

B4

BL

tripping
order (2)

A4

B4

Q
MT

trip unit
SDE

MX

81

A1

BK

C2

C2

A1

GN

BK (1)

OR

Symbols
Q
Compact NS100 to 630
SDE fault indication contact
MT
motor-mechanism module
F1
breaker for protection of motor-mechanism module circuits
H1
lamp signalling an electrical fault
H2
lamp signalling motor mechanism in manual position
F
closing order
O
opening order
orders must not be simultaneous
(must be > 150 ms)
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
BL
blue
OR
orange
WH
white

H1

L1

L1

(1) wires supplied, must be connected to ensure correct operation.


(2) the tripping order must lock out the closing order.
Schneider Electric

E43827

Automatic reset without auxiliary


- CN1 +

CN1

CN2

- CN2

F1

H1

O
H2

82

B2

A2

A4

B4

BL

GN (1)
84

OR

WH

RD

A2

A4

B4

MT

trip unit
SDE

81
BK

A1

GN

BK (1)

A1

L1

L1

(1) wires supplied, must be connected to ensure correct operation.

Control via switch or relay


With MN/MX
Controlled by switch
E43838

E43839

Controlled by relay

locked by
tripping
order

locked by
tripping
order

B2

A2

A4

B2

B4

A2

A4

B4

MT

MT
82

82

81

Without auxiliary
Controlled by switch

81

E43840

E43841

Controlled by relay

B2

A2

A4

B4

B2

MT
82

Schneider Electric

A2

A4

B4

MT
81

82

81

229

Compact NS100 to 630


Motor mechanism
(remote reset)

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

Remote reset with MN


E43834

Electrical diagrams

- CN1 +

CN1

CN2

- CN2

Following tripping due to an electrical fault,


reset must be carried out locally and
manually.

F1

O
H2

tripping
order
(3)
84

84

BL

(1)
82

OR

WH

RD
D1

A2 A4 B4
WH

D1

B2 A2 A4

B4

Q
MT

trip unit

(2)

SDE

MN

BK

BL

A1

GN

81

D4

A1

D4

L1

L1

E43835

Remote reset with MX


- CN1 +

CN1

CN2

- CN2

F1

O
H2

tripping
order
(3)

230

(1)
82

84

B2

OR

WH

WH

RD
C1

A2

A4

B4

A4

B4

Q
MT

trip unit
(2)

SDE

C2

81

A1

A1

GN

C2

BK

MX

OR

(1) wires supplied, must be connected to ensure correct


operation.
(2) connect SDE terminal 81 to auxiliary-connector terminal 84.
(3) the tripping order must lock out the closing order.
Symbols
Q
Compact NS100 to 630
SDE fault indication contact
MN
undervoltage release
MX
shunt release
MT
motor-mechanism module
F1
breaker for protection of motor-mechanism module
circuits and MN/MX
H2
lamp signalling motor mechanism in manual position
R
reset order
(must be > 150 ms)
orders
F
closing order
must not
O
opening order
be simultaneous
(must be > 150 ms,
has priority over F order)
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
BL
blue
OR
orange
WH
white

A2

BL

84

C1

L1

L1

Schneider Electric

E43836

Remote reset without auxiliary


CN1

(1) wires supplied, must be connected to ensure correct


operation.
(2) connect SDE terminal 81 to auxiliary-connector terminal 84.

- CN1 +
- CN2

CN2

F1

H2

(1)
82

84

B2

A4

OR

WH

RD

A2

A2

B4

BL

84

A4

B4

Q
MT

trip unit
SDE

A1

GN

81

BK

(2)

A1

L1

L1

Control via switch or relay


With MN/MX
Controlled by switch
E43914

E43915

Controlled by relay

A2

A4

R
locked by
tripping
order

locked by
tripping
order
B2

A2

A4

B4

B2

MT

B4

MT
81

81

Without auxiliary
Controlled by switch
E43916

E43917

Controlled by relay

A2

A4

B2

B4

A2

A4

B4

MT

MT
81

Schneider Electric

B2

81

231

Compact NS100 to 630


Motor mechanism
(local reset)

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

Local reset with MN


E43837

Electrical diagrams

- CN1 +

CN1

CN2

- CN2

Following tripping due to an electrical fault,


reset must be carried out locally and
manually.

F1

H1

H2

WH

RD

WH

D1

82

84

BL

A2 A4 B4

84

D1

OR

tripping
order

B2 A2 A4

B4

Q
MT

trip unit

SDE
(2)

MN

BL

A1

GN

81

D4

BK

(1)

A1

D4

L1

L1

E43919

Local reset with MX


- CN1 +

CN1

CN2

- CN2

F1

H1

WH

RD

D1

82

84

BL

A2 A4 B4

84

D1

WH

H2

OR

tripping
order

B2 A2 A4

B4

Q
MT

trip unit

232

MX

D4

81

A1

A1

GN

D4

BK

(1)

BL

(1) (2) required to ensure correct indication of an electrical


fault.
Symbols
Q
Compact NS100 to 630
SDE fault indication contact
MN
undervoltage release
MX
shunt release
MT
motor-mechanism module
F1
breaker for protection of motor-mechanism module
circuits and MN/MX
H1
lamp signalling an electrical fault
H2
lamp signalling motor mechanism in manual position
F
closing order
orders
O
opening order
must not
(must be > 150 ms,
be simultaneous
has priority over F order)
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
BL
blue
OR
orange
WH
white

SDE
(2)

L1

L1

Schneider Electric

E43920

Local reset without auxiliary


CN1

- CN1 +
CN2

(1) (2) required to ensure correct indication of an electrical


fault.

- CN2

F1

H1

H2

84

BL

WH

RD

82

OR

A2 A4 B4

84

B2 A2 A4

B4

Q
MT

trip unit

SDE
(2)

A1

A1

GN

81

BK

(1)

L1

L1

Control via switch or relay

E43844

E43845

With MN/MX

locked by
tripping
order

locked by
tripping
order

B2

A2

A4

B2

B4

A2

A4

B4

MT

MT

81

81

Without auxiliary
Controlled by switch
E43913

E43912

Controlled by relay

B2

A2

A4

B4

B2

MT

A2

A4

B4

MT

81

Schneider Electric

81

233

Compact NS100 to 630


Early-make contacts

Electrical diagrams

With MN
E43831

CN1

- CN1 +

CN2

- CN2

tripping
order

(1)

Following tripping due to an electrical fault,


reset must be carried out locally and
manually.

X1

RD

BL

WH

RD

D1

WH

WH

WH

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

D1 C1

CAF1

CAF2

trip unit

BL

MN

D4

D4

(1) independent auxiliary source

Symbols
Q
Compact NS
SD
trip indication contact
MN
undervoltage release
CAF early-make contact of rotary handle
XI
terminal block for CAF wiring
(must be ordered)
Colour code for auxiliary wiring
RD
red
GN
green
BK
black
BL
blue
WH
white

234

Schneider Electric

E43830

With MN + SD
CN1

- CN1 +

CN2

- CN2

trippinng
order

(1)

X1

D1 C1

RD
BK

WH
BL

94

WH

92

RD

GN

WH

D1

RD

GN

WH

92

94

CAF1

CAF2

trip unit
MN
SD

91

BL

BL

D4

D4

91

(1) independent auxiliary source.

Schneider Electric

235

Electrical diagrams

Compact NS100 to 630


Motor protection
Trip unit STR22/43ME

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

E28434

Thermal-fault indication
CN1

- CN1 +
CN2

- CN2

F1

D1

WH

BP1
13

97
KA1

14

43

KA1

44

trip unit
SDTAM

BL

98

D4

A1
KAI

X1
H1

A2

X2

Symbols
Q
F1
SDTAM
BP1
KA1

Compact NS100 to 630


breaker for protection of the auxiliary circuit
thermal-fault early-break signal
SDTAM reset button
auxiliary relay - Telemecanique
CA...DN31 or CA...DN22
H1
lamp signalling SDTAM fault
Colour code for auxiliary wiring
BL
blue
WH
white

236

Schneider Electric

E28435

Automatic operation

overload
SDTAM

I
O
I
O

BP1
H1
Q

I
O
I
O
I
O
300 ms

IQ

tr

tr
overload (long-time) protection tripping time
overload
current greater than Ir (long-time tripping threshold)
IQ
closing order for circuit breaker Q
Note.
For a short-circuit or earth fault, only circuit breaker Q opens.
The above automatic control sequence is not run.

Schneider Electric

Legend
b O: OFF (circuit open)
b I: ON (circuit closed)
b
: either ON or OFF

237

Electrical diagrams

Compact NS100 to 630


Motor protection
Trip unit STR22/43ME

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

E43828

Thermal-fault indication and tripping


CN1

- CN1 +
CN2

- CN2

F1

WH

D1

97

21

42

Q
BP1

KA1

22

KA1

44

trip unit
SDTAM

(1)

BL

98

D4

E1

A1

A1

KA1
KM1

KM1
A2

KA2

X1
H1

A2

X2

E2

(1) KM1 operating conditions must be inserted between 22 and A1.

Symbols
Q
F1
SDTAM
BP1
KA1

Compact NS100 to 630


breaker for protection of the auxiliary circuit
thermal-fault early-break signal
SDTAM reset button
auxiliary relay - Telemecanique
CA...DN31 or CA...DN22
KA2
mechanical latching unit Telemecanique LA6 DK1
RHK
bistable relay - Telemecanique
RHK-41
H1
lamp signalling SDTAM fault
KM1
power contactor
Colour code for auxiliary wiring
BL
blue
WH
white

238

Schneider Electric

E28437

Automatic operation
I

overload

tr

SDTAM

O
I

BP1

O
I

H1

O
I

KM1

O
I

tr overload (long-time) protection tripping time


overload current greater than Ir (long-time tripping threshold)
Note.
For a short-circuit or earth fault, only circuit breaker Q opens.
The above automatic control sequence is not run.

Legend
b O: OFF (circuit open)
b I: ON (circuit closed)
b
: either ON or OFF

E43829

Same automatic system using a bistable relay


CN1

- CN1 +
CN2

- CN2

F1

D1

BP1
D4

E4

RHK

12 11 14

22 21 24

(1)

A1

X1
H1

KM1
A2

X2

(1) KM1 operating conditions must be inserted between


12 and A1.

Schneider Electric

239

Compact NS630b to 1600


Fixed circuit breakers

Electrical diagrams

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Control unit

Z5

A4

C2

MN

BPF

B4

BPO

D2

Z5

Z4

Z3

Z2

Z1

AT

A2

Z4

Z3

downstream cb
Z5

Z4

L3

Z3

upstream cb
L2

Z2

L1

Z1

Z2

power

Remote operation

Z1

Power

motor-mechanism
module

MX

Micrologic

A1

C1

D1

F2+

T4/F1

T3

T2

T1/M3

M2

M1

E59040

E59041

or

24 V DC

Control unit

E1-E6 communication

Z1-Z5 zone selective interlocking:


Z1 = ZSI OUT SOURCE
Z2 = ZSI OUT; Z3 ZSI IN SOURCE
Z4 = ZSI IN ST (short time)
Z5 = ZSI IN GF (earth fault)
M1 = Vigi module input
(Micrologic 7)
T1, T2, T3, T4 = external neutral;
M2, M3 = Vigi module input
(Micrologic 7)

F2+, F1- external 24 V DC


power supply

Remote operation
MN
or
MX

undervoltage release

shunt release

Motor-mechanism module (*)


A4
:
electrical opening order
A2
:
electrical closing order
B4, A1 :
power supply for control devices and gear motor
(*) Spring-charging motor 440/480 V AC
(380 V motor + additional resistor)
E59039A

(basic) A

CN1

- 440/480 V

9 11
R

A4

A2

B4

: basic Micrologic control unit.


A: digital ammeter.
motor-mechanism
module

A1
CN2

240

- 440/480 V

Schneider Electric

fault

fault

closed

white
yellow
brown
black
red

E59043

E59296A

closed

open

blue

Terminal-block marking (manual operation)

Indication contacts

open

512

MN/MX

F1 F2
M1M2 M3
Z1 Z2 Z3 Z4 Z5
T1 T2 T3 T4

514

522

524

532

534

542

544

94

92

84

82

12

14

22

24

32

34

E6 E5 E4 E3 E2 E1

OF1

D1/C1
D2/C2

OF2
OF3
SD

CAO1

531

SD

trip indication contact


(manual operation)

CAF2/CAF1

early-make contact
(rotary handle)

CAO2 / CAO1

early-break contact
(rotary handle)

541

511

82

521

532

542

512

522

534

544

514

524

84
SDE

white
yellow
brown
black
red

fault-trip indication contact


(short-circuit, overload, earth fault)

blue

SDE

91 92 94

Terminal-block marking (electrical operation)


E59044

Indication contacts
indication contacts

31 32 34

81

CAF1 CAF2 CAO1 CAO2

OF3 / OF2 / OF1 :

21 22 24

511

CAO2

521

CAF1

531

CAF2

541

SD

81

11

SDE

91

OF1

21

OF2

31

OF3

11 12 14

E6 E5 E4 E3 E2 E1

MN/MX

F1 F2
M1M2 M3
Z1 Z2 Z3 Z4 Z5
T1 T2 T3 T4

D1/C1
D2/C2

SDE OF3 OF2 OF1


81

31

21

11

82

32

22

12

84

34

24

14

B4 A4 A2 A1

Schneider Electric

241

Compact NS630b to 1600


Plug-in / withdrawable
circuit breakers

Electrical diagrams

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.

Z5

A4

C2

Q
MN

BPF

B4

BPO

D2

Z5

Z4

Z3

Z2

Z1

AT

A2

Z4

Z3

Z1

downstream cb
Z5

L3

Z4

upstream cb
L2

Z3

L1

Z2

Z1

E59730

power

Remote operation
E59037B

Control unit

Z2

Power

motor-mechanism
module

MX

Micrologic

A1

C1

D1

F2+

T4/F1

T3

T2

T1/M3

M2

M1

or

24 V DC

Control unit
Terminal-block marking

Com UC1

UC2

E5 E6 Z5 M1 M2 M3

Remote operation
UC3

MN / MX

F2+

D2

MT2
C2

MT1

A4

A2

E3 E4 Z3 Z4 T3 T4
E1 E2 Z1 Z2 T1 T2

F1

Control unit

Com: E1-E6 communication

UC1 : Z1-Z5 zone selective interlocking:


Z1 = ZSI OUT SOURCE
Z2 = ZSI OUT; Z3 ZSI IN SOURCE
Z4 = ZSI IN ST (short time)
Z5 = ZSI IN GF (earth fault)
M1 = Vigi module input
(Micrologic 7)
UC2 : T1, T2, T3, T4 = external neutral;
M2, M3 = Vigi module input
(Micrologic 7)

D1

UC3 : F2+, F1- external 24 V DC


power supply

: basic Micrologic control unit.


A: digital ammeter.

C1

A1

Remote operation
MN
or
MX

undervoltage release

shunt release

Motor-mechanism module (*)


MT2 : A4 :
electrical opening order
MT1 : A2 :
electrical closing order
B4, A1 : power supply for control devices
and gear motor (MCH)
(*) Spring-charging motor 440/480 V AC
(380 V motor + additional resistor)
E59039

(basic) A

B4

CN1

- 440/480 V

9 11
R

A4

A2

B4

motor-mechanism
module

A1
CN2

242

- 440/480 V
Schneider Electric

E47074A

Indication contacts

912

914

314

312

324

322

334

332

CT1

CE1

911

CE2

311

CE3

CD1

821

511

521

531

541

91

81

11

21

31

814

CAO1
CD2

CAF2 CAF1

812

824

822

512

514

524

532

522

CAO2

CAF1

Test

321

CAF2

connected

disconnected

open

534

542

SD

SDE

closed

544

94

92

fault

331

OF1

84

82

12

14

22

OF2

fault

811

OF3

closed

24

32

34

open

E46134A

E47075A

Carriage switches

E59295A

Indication contacts

Carriage switches

SDE

SD

CAO2 CAO1

OF3

OF2

OF1

CD2

CD1

CE3

CE2

CE1

CT1

544

534

84

94

524

514

34

24

14

824

814

334

324

314

914

542

532

82

92

522

512

32

22

12

822

812

332

322

312

912

541

531

81

91

521

511

31

21

11

821

811

331

321

311

911

Indication contacts
OF3 / OF2 / OF1 :

indication contacts

SDE

fault-trip indication contact


(short-circuit, overload, earth fault)

SD

trip indication contact


(manual operation)

CAF2/CAF1

early-make contact
(rotary handle)

CAO2 / CAO1

early-break contact
(rotary handle)

Carriage switches
CD2 : disconnected CE3 : connected CT1 : test
CD1 position
CE2 position
position
CE1

Legend
Connected
(only one wire per connection point).
Schneider Electric

243

Compact NS630b to 3200


Communications option
24 V DC external power supply

Electrical diagrams

E59303

Connection of the communications option


motor-mechanism
module
L1

L2

914

manual
operation

L3

Z5

Z4

Z3

Z2

912 812

314

SDE

OF

SD

SDE

911

811

CT

device
communication
module

Micrologic

CD

CE

CE

Digipact
COM craddle
BB
BB

B' A' B A

E6

E5

E4

E3

E2

E1

F2+

T4/F1

T3

T2

T1/M3

311

CD

CT
+

+
(2)

CCP 303
M2

811

911

Modbus
COM craddle

shield

311

B'
A'
B
A

M1

312

closing order

OF

Z1

812

opening order

BB
BB

CCP 303

5
4

H1 H2

Modbus
junction
block
CJB306

BAT
module

(1)

H3 H4

(2)

E1 E2 E3 E4
+
A B
+
/
/
E3 / E4
E5 / E6

L3 L4

110/240 V AC
24/125 V DC

blue

white

yellow

brown

red

AD
module

black

G1 G2

Digipact
junction
block

E5 E6
A' B'
Modbus
BB BB + Digipact
twisted pair
twisted pair

24 V
0V

0V
24 VDC
1A

communication
power supply

24 V

24 VDC
DC 150

None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power supply (AD module) is
required for certain operating configurations as indicated in the table below.
Circuit breaker
Protection function
Display function
Circuit-breaker status indications and control
communications bus

(1) Drawout device equipped with Com chassis modbus.


(2) Fixed device or draw-out device without Com chassis
Digipact.
(3) except if current < 20 % In.

244

Closed

Open

no
no (3)
no

no
yes
no

The communications bus requires its own 24 V DC power source (E1, E2). This source is not
the same as the 24 V DC external power-supply module (F1-, F2+).
If the 24 V DC external power supply (AD module) is used, the maximum cable length between
the 24 V DC external power supply (G1, G2) and the Micrologic control unit (F1-, F2+) is ten
metres.
The BAT battery module, mounted in series upstream of the AD module, ensures an
uninterrupted supply of power if the AD module power supply fails.

Schneider Electric

Examples using the COM communications option


Switchboard display unit
E47976

CDM303 + CSD309

This architecture provides remote display of the


variables managed by Micrologic control units
equipped with the eco COM Modbus module.
b I (Micrologic A)
No programming is required.
For Micrologic A control unit (if current < 20 % In), it is
recommended to use the 24 VDC external power
supply (AD module).

d < 1 km
DMB300

2
3
4

CCP303

switchboard
display unit

1
0
24 V
0V

Modbus
junction
block
CJB 306

24 VDC
1A

power circuit
breaker

Communicating switchboard

E94381

This configuration provides remote display and control


of Compact equipped with the Modbus or Digipact
COM module. The Digipact bus can be combined with
the Modbus bus.

Software

PC running

PC running

Micrologic utilities
SMS

Micrologic utilities
SMS

PLC

PLC

TCP/IP

Communication
interface

Bus Modbus

communication
Bus

Data
concentrator

RS 232C

Ethernet

RS 485

RS 485
Bus Modbus

DC150

Device

UA150
source
change-ower

Digipact Bus

Schneider Electric

SC150
control
interface

PM150
measure

Compact
COM Digipact

Compact
COM Modbus

PM500
measure

Sepam

Vigilohm

Altivar

Modbus Bus

245

Compact NS630b to 3200


Earth-fault and earth-leakage protection
Neutral protection
Zone selective interlocking

Electrical diagrams

Z5

Z4

Z3

Z2

V1

Z1

L3
V3

L2

V2

L1

VN

Q
I
Micrologic 6

F2+

F1

T3

T2

T1

M3

M2

M1

Connection of current-transformer secondary


circuit for external neutral
Compact equipped with a Micrologic 6 A:
b shielded cable with 2 twisted pairs
b T1 twisted with T2
b T3 twisted with T4
b shielding connected to GND on one end only
b maximum length 10 meters
b cable cross-sectional area 0.4 to 1.5 mm2
b recommended cable: Belden 9552 or equivalent.
If supply is via the top, follow the shematics.
If supply is via the bottom, control wiring is identical;
for the power wiring, H1 is connected to the source
side, H2 to the load side.
For four-pole versions, for residual earth-fault
protection, the current transformer for the external
neutral is not necessary.

E59305

External sensor (CT) for residual earth-fault protection

H2
VC

VN GND T4

T3

T1

T2

H1

Z4
F1 /T4

Z5

Z3
T3

Z1

Connection of the secondary circuit


Compact equipped with a Micrologic 6 A:
b unshielded cable with 1 twisted pair
b maximum length 150 metres
b cable cross-sectional area 0.4 to 1.5 mm2
b recommended cable: Belden 9409 or equivalent.

Z2

External transformer for source ground return (SGR) earth-fault protection

Q
I

E59306

H1

246

H2

X1

12 5
1
3

X2

MDGF module
13 14

F2+

T2

M3/T1

M2

M1

Micrologic 6

10 11
9
8

PE

Schneider Electric

Earth-leakage protection

Z4

Z5

Z3

F1 /T4

L3

Z2

L2

Z1

L1

T3

E59307A

Connection of the rectangular-sensor secondary


circuit
Compact equipped with a Micrologic 7 A:
use the cable shipped with the rectangular sensor.

Q
I
Micrologic 7

F2+

T2

M3/T1

M2

M1

M1
M2
M3

Neutral protection
b three pole circuit breaker:
v neutral protection is impossible.
b four pole circuit breaker:
v Compact equipped with Micrologic A
v the current transformer for external neutral is not
necessary.

A pilot wire interconnects a number of circuit breakers


equipped with Micrologic A control units, as illustrated in the
diagram above.
The control unit detecting a fault sends a signal upstream and
checks for a signal arriving from downstream. If there is a
signal from downstream, the circuit breaker remains closed
for the full duration of its tripping delay. If there is no signal
from downstream, the circuit breaker opens immediately,
whatever the tripping-delay setting.
Fault 1.
Only circuit breaker A detects the fault. Because it receives no
signal from downstream, it immediately opens in spite of its
tripping delay set to 0.3.
Fault 2.
Circuit breakers A and B detect the fault. Circuit breaker A
receives a signal from B and remains closed for the full
duration of its tripping delay set to 0.3. Circuit breaker B does
not receive a signal from downstream and opens immediately,
in spite of its tripping delay set to 0.2.

E47975B

Zone selective interlocking


upstream
circuit breaker

Z1
Z2
Z3
Z4
Z5

tsd = 0,3

fault 1

Z1
Z2
Z3
Z4
Z5

tsd = 0,2

fault 2

Z1
Z2
Z3
Z4
Z5

downstream
circuit breaker

Z1
Z2
Z3
Z4
Z5

Note. The maximum permissible distance between two


devices is 3000 metres and the maximum number of devices
is 100.
Schneider Electric

247

Compact NS1600b to 3200


Fixed circuit breakers

Electrical diagrams

The diagram is shown with circuits deenergised, all devices open, connected and
charged and relays in the normal position.
Control unit

Z5

Z4

Z3

downstream cb
Z5

Z4

L3

Z3

upstream cb
L2

Z2

L1

Z1

Z2

power

Remote operation

Z1

Power

C2

D2

Z5

Z4

Z3

Z2

Z1

AT

MN

MX

Micrologic

C1

D1

F2+

T4/F1

T3

T2

T1/M3

M2

M1

E59040

E59463A

or

24 V DC

(basic) A
b

Control unit

E1-E6 communication

Z1-Z5 zone selective interlocking:


Z1 = ZSI OUT SOURCE
Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE
Z4 = ZSI IN ST (short time)
Z5 = ZSI IN GF (earth fault)
M1 = Vigi module input
(Micrologic 7)
T1, T2, T3, T4 = external neutral;
M2, M3 = Vigi module input
(Micrologic 7)

Remote operation
MN
or
MX

undervoltage release

shunt release

F2+, F1- external 24 V DC power


supply

: basic Micrologic control unit.


A: digital ammeter.

248

Schneider Electric

Terminal-block marking
E59465A

E59464A

Indication contacts

94

fault

92

84

82

12

fault

14

22

closed

24

32

34

open

E6 E5 E4 E3 E2 E1
F1 F2
M1M2 M3
Z1 Z2 Z3 Z4 Z5
T1 T2 T3 T4

MN/MX

OF1

D1/C1
D2/C2

OF2
OF3
SD

21 22 24
31 32 34
91 92 94

SD

91

11

SDE

81

OF1

21

OF2

31

OF3

11 12 14

81
82
84
SDE

Indication contacts
OF3 / OF2 / OF1 :

ON / OFF indication contacts

SDE

fault-trip indication contact


(short-circuit, overload, earth fault)

SD

trip indication contact

Schneider Electric

249

250

Schneider Electric

Compact NS

Additional characteristics

Presentation
Functions and characteristics
Installation recommendations
Dimensions, volumes
Connection
Electrical diagrams

Tripping curves

252

Compact NSC100
Compact NS80H-MA
Compact NSA160
Compact NB100 to 600
Compact NS100 to 250
Compact NS100 to 250 protection of distribution systems
Compact NS100 to 250 motor-starter protection
Compact NS400 to 630 protection of distribution systems
Compact NS400 to 630 motor-starter protection
Compact NS630b to 3200
Reflex tripping

252
253
254
255
256
258
259
260
261
262
263

Current-limiting curves

264

Catalogue numbers

Schneider Electric

2
11
143
165
205
221

267

251

Additional characteristics

Tripping curves
Compact NSC100

5080 A
E94504

E94503

1640 A
10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10
5

5
t(s)

t(s)

2
1

16 A : Im = 37,5 x In

.5

20 A : Im = 30 x In

1
.5

.2

25 A : Im = 24 x In

.2

.1
.05

32 A : Im = 19 x In

.1
.05

40 A : Im = 15 x In

.02
.01

.02
.01

.005

.005

.002
.001
.5 .7 1

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

50 A : Im = 20 x In
63 A : Im = 16 x In
70 A : Im = 14,3 x In
80 A : Im = 12,5 x In

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

I / Ir

E94505

100 A
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
100 A : Im = 12,5 x In

1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

252

Schneider Electric

Compact NS80H-MA

E28466

MA1.5MA80
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
Im = 614 x In

1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Schneider Electric

253

Additional characteristics

Tripping curves
Compact NSA160

5080 A
E94507

E94506

1640 A
10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10
5

5
t(s)

t(s)

2
1

16 A : Im = 37,5 x In

.5

.5

50 A : Im = 20 x In

25 A : Im = 24 x In

.2

.2

32 A : Im = 19 x In

.1
.05

40 A : Im = 15 x In

.02
.01

.02
.01

.005

.005

.002
.001
.5 .7 1

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

63 A : Im = 16 x In

.1
.05

200 300

80 A : Im = 12,5 x In

50 70 100

200 300

125160 A
E94509

100 A
E94508

20 30

I / Ir

I / Ir

10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10

160 A : Im = 7,8 x In

t(s)

t(s)
2

2
100 A : Im = 12,5 x In

.5

.5

.2

.2

.1
.05

.1
.05

.02
.01

.02
.01

.005

.005

.002
.001
.5 .7 1

.002
.001
.5 .7 1

3 4 5 7 10
I / Ir

254

3 4 5 7 10

20 30

50 70 100

200 300

125 A : Im = 10 x In

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Schneider Electric

Additional characteristics

Tripping curves
Compact NS100 to 250
Protection of distribution systems

TM magnetic trip units


TM25D / TM25G
E28453

E28452

TM16D / TM16G
10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10

t(s)

t(s)
2

TM16D : 12 x In

TM25D : 12 x In

.5

.5

.2

.2
TM16G : 4 x In

.1
.05
.02
.01

.02
.01

reflex tripping :
t < 10 ms

.005

.005

.002
.001
.5 .7 1

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

TM25G :
3.2 x In

.1
.05

200 300

reflex tripping :
t < 10 ms

3 4 5 7 10

10 000
5 000

E28455

E28454

50 70 100

200 300

TM50D / TM63D / TM63G

TM32D / TM40D / TM40G

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10
5

5
t(s)

t(s)
2

TM40D : 12 x In

.5
TM50D : 10 x In

TM32D : 12,5 x In

.2

.2

TM40G :
2 x In

.1
.05

.02
.01

reflex tripping :
t < 10 ms

.005

TM63G :
2 x In

.1
.05

.02
.01

.002
.001
.5 .7 1

TM63D : 8 x In

.5

3 4 5 7 10
I / Ir

256

20 30

I / Ir

I / Ir

20 30

50 70 100

reflex tripping :
t < 10 ms

.005

200 300

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Schneider Electric

TM magnetic trip units (cont.)


TM125D / TM160D
E28457

E28456

TM80D / TM100D
10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10

t(s)

TM125D
10 x In

t(s)
2

NS160/250
Im = 12,5 x In

.5

.5
NS100
Im = 8 x In

.2

.2

.1
.05

TM160D
8 x In

.1
.05

.02
.01

.02
.01

reflex tripping:
t < 10 ms

.005

.005

.002
.001
.5 .7 1

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

reflex tripping :
t < 10 ms

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

E28458

TM200D / TM250D
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
t(s)
2
Im = 5 10 x In

1
.5
.2
.1
.05
.02
.01

reflex tripping :
t < 10 ms

.005
.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Schneider Electric

257

Tripping curves
Compact NS100 to 250
Protection of distribution systems (cont.)

Additional characteristics

STR22SE and STR22GE electronic trip units


STR22SE - 160250 A
E28460

E28459

STR22SE - 40100 A
10 000
5 000
2 000

10 000
5 000
2 000

Ir = 0.41 x In

1 000

1 000

500

500

200

200

100

100

50

50

20

20

10

10

Ir = 0.41 x In

t(s)

t(s)
2

2
Im = 210 x Ir

.5

.2

.2

.1
.05

.1
.05

.02
.01

.02
.01

reflex tripping
t < 10 ms

.005
.002
.001
.5 .7 1

Im = 210 x Ir

.5

reflex tripping
t < 10 ms

.005
I = 11 x In

3 4 5 7 10

20 30

50 70 100

.002
.001
.5 .7 1

200 300

I = 11 x In

3 4 5 7 10

I / Ir

10 000
5 000

200 300

10 000
5 000
2 000

Ir = 0.41 x In

1 000

50 70 100

STR22GE - 160250 A
E28410

E28409

STR22GE - 40100 A

2 000

20 30

I / Ir

1 000

500

500

200

200

100

100

50

50

20

20

10

10

Ir = 0.41 x In

t(s)

t(s)
2

.5

.5
Im = 210 x Ir

.2

.2

Im = 210 x Ir

.1
.05

.1
.05

.02
.01

.02
.01

reflex tripping :
t < 10 ms

.005
.002
.001
.5 .7 1

.005
I = 11 x In

3 4 5 7 10
I / Ir

258

reflex tripping :
t < 10 ms

20 30

50 70 100

200 300

.002
.001
.5 .7 1

I = 11 x In

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Schneider Electric

Compact NS100 to 250


Motor-starter protection
MA magnetic trip units
MA150 and MA220

E30212

MA2,5MA100
E28467

10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200
thermal withstand

100

thermal withstand
MA220
MA150

100

50

50

20

20

10

10

t(s)

t(s)
2

2
Im = 6 14 x In

1
.5

.5

.2

.2

.1
.05

.1
.05

.02
.01

.02
.01

reflex tripping :
t < 10 ms

.005

.005

.002
.001
.5 .7 1

.002
.001
.5 .7 1

3 4 5 7 10

20 30

50 70 100

Im = 9 14 x In

200 300

I / Ir

reflex tripping :
t < 10 ms

3 4 5 7 10

20 30

50 70 100

200 300

I / In

STR22ME electronic trip units


E28370

STR22ME - 10220 A
10 000
5 000
2 000

Ir

1 000
500
200
100
50
class 10 (IEC 60947-4)

20
10
5
t(s)
2
1
.5
.2

Im = 13 x Ir

.1
.05
.02
.01

reflex tripping :
t < 10 ms

.005
.002
.001
.5 .7 1

I = 15 x In

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Schneider Electric

259

Tripping curves
Compact NS400 to 630
Protection of distribution systems

Additional characteristics

STR23 and STR53 electronic trip units


STR53UE / STR53SV

10 000
5 000

E94513

E28461

STR23SE / STR23SV

10 000
5 000
2 000

2 000

Ir = 0.41 x In

1 000

Ir = 0.41 x In

1 000

500

500

200

200

100

100

50

50

20

20

10

10

tr = 0.516 s
Ii = 1.511 x In

5
t(s)

t(s)

2
Isd = 210 x Ir

.5

.5

.2

.2

.1
.05

.1
.05

.02
.01

l 2 t OFF

0.3
0.2
0.1
0

.02
.01

reflex tripping
t < 10 ms

.005

.005
.002
.001
.5 .7 1

Isd = 1.510 x Ir
l 2 t OFF

I = 11 x In

3 4 5 7 10

20 30

50 70 100

200 300

.002
.001
.5 .7 1

reflex tripping :
t < 10 ms

3 4 5 7 10
I / Ir

I / Ir

20

5 7 10

20 30

50

I / In

Options for STR53UE


E28371

Earth-fault protection
10 000
5 000
2 000
Ig = 0.21 x In

1 000
500
200
100
50
20
10

I2t ON

5
t(s)
2
1
.5

0.4
0.3

.2
.1
.05

0.2
0.1

I2t OFF

.02
.01
.005
.002
.001
.05 .07 .1

.2

.3 .4 .5 .7 1

7 10

20 30

I / In

260

Schneider Electric

Compact NS400 to 630


Motor-starter protection
MA magnetic and STR43ME electronic trip units
STR43ME - 120 to 500 A - class 10 A
E28369

E28468

MA320MA500
10 000
5 000

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200
thermal withstand

100

100

50

50

20

20

10

10

class 10 A

t(s)

t(s)
2

hot tripping curve

cold tripping curve

.5

.5
Isd = 613 x Ir

.2

.2
Im = 9 ... 14 x In

.1
.05
.02
.01

.02
.01

reflex tripping :
t < 10 ms

.005
.002
.001
.5 .7 1

.1
.05

3 4 5 7 10

20 30

50 70 100

reflex tripping
t < 10 ms

.005
.002
.001
.5 .7 1

200 300

Ii = 10,4 x In

3 4 5 7 10

I / In

200 300

STR43ME - 120 to 500 A - class 20

10 000
5 000

E38946

E38879

50 70 100

I / Ir

STR43ME - 120 to 500 A - class 10

10 000
5 000

2 000

2 000

1 000

1 000

500

500

200

200

100

100

50

20 30

class 20

50

class 10

20

20

10

10

t(s)

t(s)
2
1

hot tripping curve

hot tripping curve

cold tripping curve

cold tripping curve

.5

.5
Isd = 613 x Ir

Isd = 613 x Ir

.2

.2

.1
.05

.1
.05

.02
.01

.02
.01

reflex tripping
t < 10 ms

.005
.002
.001
.5 .7 1

reflex tripping
t < 10 ms

.005
Ii = 10,4 x In

3 4 5 7 10

20 30

I / Ir

50 70 100

200 300

.002
.001
.5 .7 1

Ii = 10,4 x In

3 4 5 7 10

20 30

50 70 100

200 300

I / Ir

Thermal-withstand capacities are given for circuit


breakers operating in an ambient temperature of 65 C.
Schneider Electric

261

Tripping curves
Compact NS630b to 3200

Additional characteristics

Micrologic electronic control units


Micrologic 5.0, 6.0, 7.0 - Micrologic 5.0A, 6.0A, 7.0A

10 000
5 000

10 000
5 000

E46276

E46350

Micrologic 2.0
Ir = 0,41 x In

2 000

2 000

1 000

1 000

500

500

200

200

100

Ir = 0,41 x In

100

tr = 0,5...24 s

50

50

20

20

10

10

tr = 0,524 s

t(s)

t(s)
2
1

Isd = 1,510 x Ir

Isd = 1,510 x Ir

.5

.5

.2

.2

I2t ON

0,2

.02
.01

.02
.01

.005

.005

.002
.001
.5 .7 1

.002
.001
.5 .7 1

20 30

50 70 100

200 300

0,2

0,1

.1
.05

3 4 5 7 10

0,3

0,3

.1
.05

0,4

0,4

0,1

I t OFF

Ii = 215 x In . OFF

3 4 5 7 10

20

7 10

x Ir

I / Ir

20 30

x In

Options for Micrologic electronic control units


E46266

Earth-fault protection (Micrologic 6.0)


10 000
5 000
2 000

Ig = AJ x In (1)
1200 A max.

1 000
500
200
100
50
20
10
5
t(s)

I2t ON

2
1
.5
.2
.1
.05

I2t

0.4

0.4

0.3
0.2
0.1

0.3
0.2
0.1

OFF

.02
.01
.005
.002
.001
.05.07 .1

(1)

Ig = In x
.2 .3 .4 .5 .7 1
I / In

262

7 10

200 300

Ig < 400 A
400 A y Ig y 1200 A
Ig > 1200 A

0.3
0.2
500

0.3
0.3
640

0.4
0.4
720

0.5
0.5
800

0.6
0.6
880

0.7
0.7
960

0.8 0.9 1
0.8 0.9 1
1040 1120 1200

Schneider Electric

Compact NS100 to 630 devices


incorporate the exclusive reflex-tripping
system.
This system breaks very high fault currents
by mechanically tripping the device via a
"piston" actuated directly by the pressure
produced in the breaking units resulting
from a short-circuit.
For high short-circuits, this system provides
a faster break and a trip guarantee, as well
as natural total discrimination.
Reflex-tripping curves are exclusively a
function of the circuit-breaker rating.

E28463

Reflex tripping

TM160D...TM250D
STR22SE250

20

NS630
STR22SE160

NS400
NS250
10

TM160D

8
t
(ms) 7

TM16D...TM100D
STR22SE40... 100

NS100-NS160

5
4

3
2

10

20

30

40

60

100

200

kA rms

Schneider Electric

263

E28800

Additional characteristics

Current-limiting curves

The limiting capacity of a circuit breaker is


its aptitude to limit short-circuit currents.

Ics = 100 % Icu

Isc
prospective
Isc peak
prospective
current
prospective
Isc
limited Isc
peak
limited
Isc
tc

The exceptional limiting capacity of the Compact NS range greatly reduces the
forces created by fault currents in devices.
The result is a major increase in breaking performance. In particular, the service
breaking capacity Ics is equal to 100% of Icu.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
the following operations:
b break three times consecutively a fault current equal to 100 % of Icu
b check that the device continues to function normally:
v it conducts the rated current without abnormal temperature rise
v protection functions perform within the limits specified by the standard
v suitability for isolation is not impaired.

Longer service life of electrical installations

actual
current

The exceptional limiting capacity of the Compact NS range is


due to the rotating double-break technique (very rapid natural
repulsion of contacts and the appearance of two arc voltages
in-series with a very steep wave front).

Current-limiting circuit breakers greatly reduce the negative effects of short-circuits


on installations.
Thermal effects
Less temperature rise in conductors, therefore longer service life for cables.
Mechanical effects
Reduced electrodynamic forces, therefore less risk of electrical contacts or bus
bars being deformed or broken.
Electromagnetic effects
Less disturbances for measuring devices located near electrical circuits.

Economy by means of cascading


Cascading is a technique directly derived from current limiting. Circuit breakers with
breaking capacities less than the prospective short-circuit current may be installed
downstream of a limiting circuit breaker. The breaking capacity is reinforced by the
limiting capacity of the upstream device.
It follows that substantial savings can be made on downstream equipment and
enclosures.

Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which
are a function of the prospective short-circuit current (the current which would flow
if no protection devices were installed):
b the actual peak current (limited current),
b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 .
Example
What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak)
limited by an NS250L upstream ?
Answer: 30 kA peak (see next page).

Maximum permissible cable stresses


The table below indicates the maximum permissible thermal stresses for cables
depending on their insulation, conductor (Cu or Al) and their cross-sectional area
(CSA). CSA values are given in mm2 and thermal stresses in A2s.
CSA (mm2)
PVC Cu
Al
PRC Cu
Al
CSA (mm2)
PVC Cu
Al
PRC Cu
Al

1.5
2.97 x 104

2.5
8.26 x 104

4
2.12 x 105

6
4.76 x 105

4.10 x 104

1.39 x 105

2.92 x 105

6.56 x 105

16
3.4 x 106
1.39 x 106
4.69 x 106
1.93 x 106

25
8.26 x 106
3.38 x 106
1.39 x 107
4.70 x 106

35
1.62 x 107
6.64 x 106
2.23 x 107
9.23 x 106

50
3.31 x 107
1.35 x 107
4.56 x 107
1.88 x 107

10
1.32 x 106
5.41 x 105
1.82 x 106
7.52 x 105

Example
Is a Cu/PVC cable with a CSA of 10 mm2 adequately protected by an NS160N?
The table above indicates that the permissible stress is 1.32x106 A2s.
All short-circuit currents at the point where an NS160N (Icu = 35 kA) is installed are
limited with a thermal stress less than 6 x 105 A2s (see next page).
Cable protection is therefore ensured up to the limit of the breaking capacity of the
circuit breaker.

264

Schneider Electric

Current-limiting curves
Voltage 380/415 V AC

Voltage 660/690 V AC

200

NS630bH
NS800H
NS1000H
NS1250H
NS1600H

NS630bN
NS800N
NS1000N
NS1250N
NS1600N

100
80
70
60
50
kA peak40

146

NS630
NS400

H
N

L
H

20

NS250
NS160
NS100

30

TM32...250

20

10

20

NS400

NS630

TC150/250/400

NS100

NS250

TM40100
TM 25

NH

10
8
7
6
5
4

NSA160

NS630bH
NS800H
NS1000H
NS1250H
NS1600H

NS160

TM16

NS630bN
NS800N
NS1000N
NS1250N
NS1600N
NS630bL
NS800L
NS1000L

100
80
70
60
50
kA peak 40

TM25

NS1600bN
NS2000N
NS2500N
NS3200N

200

NS630bL
NS800L
NS1000L

30

10
8
7
6
5
4

300

E90272

E58557

300

30 40

60

100

200 300

TM 16

10

20

30 40

60
65

kA rms

kA rms

100

200 300

Thermal-stress curves
Voltage 380/415 V AC

Voltage 660/690 V AC

10

E90271

E58556

10
5

3
2

NS630bN
NS800N
NS1000N
NS1250N
NS1600N

10
5

3
2
1,41
8
10

NS630bH
NS800H
NS1000H
NS1250H
NS1600H

NS1600bN
NS2000N
NS2500N
NS3200N

NS630bN
NS800N
NS1000N
NS1250N
NS1600N

3
2

3
2
7

10
2

As 5

3
2

N
6

10

5
3
2

NS1000L
NS630bL
L NS800L
NS630
L
NS400

10

NS250
NS160
NS100

TM32250

NSA160

TM25

NS630bL
NS800L
NS1000L
NS630
L

As 5

3
2
6

10

H
N

TC150/250/400

NS250

NS100
TM 40100

NS160

L NS400

3
2

TM 25
TM 16

10

TM16

10

3
2

3
2

NS630bH
NS800H
NS1000H
NS1250H
NS1600H

10

20

30 40

kA rms

Schneider Electric

60

100 150 200 300

10

20

30 40

kA rms

60
65

100 150 200 300

265

Schneider Electric

550E5100.fm/17

Compact NS

Complementary technical information

Cascading
Cascading, network 220/240 V
Cascading, network 380/415 V
Cascading, network 440 V
Motor protection cascading
Cascading for installations with several
transformers in parallel
Protections discrimination
Motor protection discrimination
Cascading and enhanced discrimination
Protection of motor circuits
Circuit breaker/contactor coordination
Using the circuit breaker/contactor coordination tables

Schneider Electric

2
4
7
10
12
14
15
97
106
117
117, 125
122

Type coordination 2
Type coordination 1
Use of LV switches

127
148
152

Switch-disconnectors protection

156

Protection of LV/LV transformers


Coordination tables between Merlin/Gerin with
the circuit breaker and Telemecanique Canalis
electrical busbar trunking

164

Cascading and reinforced discrimination

182

167

Complementary
technical information

Cascading

Summary
Application
Distribution cascading

Network
220/240 V
380/415 V
440 V

Motor protection cascading

220/240 V
380/415 V
440 V

Upstream device
Compact NS
Compact NS and Masterpact
Compact NS
Compact NS and Masterpact
Compact NS
Compact NS and Masterpact
Compact NS
Compact NS
Compact NS

Downstream device
Compact and Multi 9
Compact and Multi 9
Compact and Multi 9
Compact and Multi 9
Compact and Multi 9
Compact NS
Compact NS, Integral, GVM
Compact NS, Integral, GVM
Compact NS, Integral

Cascading for installations with 2


or 3 transformers in parallel

Tableau page
4
6
7
9
10
11
12
12
13
14

What is cascading?
Cascading is the use of the current limiting capacity of circuit breakers at a given
point to permit installation of lower-rated and therefore lower-cost circuit breakers
downstream.
The upstream Compact circuit breakers acts as a barrier against short-circuit
currents. In this way, downstream circuit breakers with lower breaking capacities
than the prospective short-circuit (at their point of installation) operate under their
normal breaking conditions.
Since the current is limited throughout the circuit controlled by the limiting circuit
breaker, cascading applies to all switchgear downstream. It is not restricted to two
consecutive devices.

General use of cascading


With cascading, the devices can be installed in different switchboards. Thus, in
general, cascading refers to any combination of circuit breakers where a circuit
breaker with a breaking capacity less than the prospective Isc at its point of
installation can be used. Of course, the breaking capacity of the upstream circuit
breaker must be greater than or equal to the prospective short-circuit current at its
point of installation.
The combination of two circuit breakers in cascading configuration is covered by
the following standards:
b IEC 60947-2 (construction)
b NF C 15-100, 434.3.1 (installation).

Coordination between circuit breakers


The use of a protective device possessing a breaking capacity less than the
prospective short-circuit current at its installation point is permitted as long as
another device is installed upstream with at least the necessary breaking capacity.
In this case, the characteristics of the two devices must be coordinated in such a
way that the energy let through by the upstream device is not more than that which
can be withstood by the downstream device and the cables protected by these
devices without damage.
Cascading can only be checked by laboratory tests and the possible combinations
can be specified only by the circuit breaker manufacturer.

Cascading and protection discrimination


In cascading configurations, due to the Roto-active breaking technique,
discrimination is maintained and , in some cases, even enhanced. Consult the
enhanced discrimination tables on pages 82 to 90 for data on discrimination limits

Cascading tables
Merlin Gerin cascading tables are:
b drawn up on the basis of calculations (comparison between the energy limited
by the upstream device and the maximum permissible thermal stress for the
downstream device)
b verified experimentally in accordance with IEC standard 60947-2.
For distribution systems with 220/240 V, 400/415 V and 440 V between phases,
the tables of the following pages indicate cascading possibilities between upstream
Compact and downstream Multi 9 and Compact circuit breakers as well as
between upstream Masterpact and downstream Compact circuit breakers.

Schneider Electric

Cascading

E45057

Complementary
technical information

220/240 V network downstream from


a 380/415 V network

E88004

For 1P + N or 2P circuit breakers connected between the phase and neutral on a


380/415 V network, with a TT or TNS neutral system, consult the 220/240 V
cascading table to determinate cascading possibilities between upstream and
downstream circuit breakers.

N
1
2

E45030

E88005

For 1P circuit breakers connected to one phase of a 380/415 V network used


together with the neutral to supply a single-phase circuit, consult the cascading
tables for 380/415 V networks to determine the cascading possibilities between
upstream and downstream circuit breakers.

Example of three level cascading

A
Isc = 80 kA
NS250L
220 A
B
Isc = 50 kA
NS100N
63 A
C
Isc = 24 kA
C60N
25 A

Schneider Electric

Consider three circuit breakers A, B and C connected in series. The criteria for
cascading are fulfilled in the following two cases:
b the upstream device A is coordinated for cascading with both devices B and C
(even if the cascading criteria are not fulfilled between B and C). It is simply
necessary to check that the combinations A + B and A + C have the required
breaking capacity
b each pair of successive devices is coordinated, i.e. A with B and B with C (even
if the cascading criteria are not fulfilled between A and C). It is simply necessary to
check that the combinations A + B and B + C have the required breaking capacity.
The upstream breaker A is a NS250L (breaking capacity 150 kA) for a prospective
lsc of 80 kA across its output terminals.
A NS100N (breaking capacity 25 kA) can be used for circuit breaker B for a
prospective lsc of 50 kA across its output terminals, since the "reinforced" breaking
capacity provided by cascading with the upstream NS250L is 150 kA.
A C60N (breaking capacity 10 kA) can be used for circuit breaker C for a
prospective lsc of 24 kA across its output terminals since the "reinforced" breaking
capacity provided by cascading with the upstream NS250L is 30 kA.
Note that the "reinforced" breaking capacity of the C60N with the NS100N
upstream is only 25 kA, but:
b A + B = 150 kA
b A + C = 30 kA.

Cascading, network 220/240 V


Upstream: Compact NS
Downstream: Compact and Multi 9

Complementary
technical information

Upstream
Breaking capacity kA rms
Downstream
C32
C32
DPN/DPNN
C60a
C60N
C60H
C60L y 25 A
C60L y 40 A
C60L y 63 A
XC/SC40
PM25 u 14 A
NC100H/NC125H
NC100L
NC100LS
NC100LH/LMA
C120N
C120H
NG125a
NG125N
NG125H
NG125L/LMA
NSA160N
NS80HMA
NSC100N
NS100N
NS100H
NS160NE
NS160N
NS160H

Upstream
Breaking capacity kA rms
Downstream
C32
C32
C60a
C60N
C60H
C60L y 25 A
C60L y 40 A
C60L y 63 A
XC/SC40
PM25 u 14 A
NC100H/NC125H
NC100L
NC100LS
NC100LH/LMA
C120N/H
NG125a
NG125N
NG125H
NG125L/LMA
NSA160N
NS80HMA
NSC100N
NS100N
NS100H
NS160NE
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H

NSC100N

NSA160N

NS100N

42
50
85
Breaking capacity (kA rms)
40
40
40
42
50
50
15
15
15
30
30
30
40
40
40
42
50
50
65
42
50
65
42
50
65
40
40
85
42
50
65
65
85
42
42
40

40
40
40

50

40
40
40
60
85

85

NS100H

NS100L

NS160NE

NS160N

NS160H

NS160L

100

150

85

85

100

150

40
50
15
80
100
100
100
100
100
40
100
100
70
100

40
50
15
80
100
100
100
100
100
40
100
100
100
150
150
70
70
70
85
100
150

40
50

40
50

40
50

40
50

30
40
50
65
65
65
40
85
65
65
85

30
40
50
65
65
65
40
85
65
65
85

40
60
80
80
80
80
40
100
100
70
100

40
40
40
60
85

40
40
40
60
85

50
50
50
70
85

85

85

100

85

85

100
100

40
60
80
80
80
80
40
100
100
100
150
150
70
70
70
85
100
150
100
150
100
150
150
150
150
150

50
50
50
70
85

100
100

150
100
150
150

100
100

NS250N

NS250H

NS250L

85
100
150
Breaking capacity (kA rm
40
40
40
42
50
50
30
40
40
40
60
60
50
65
65
65
80
80
65
80
80
50
65
65
40
40
40
65
65
85

100
70
100

40
40
60
85

50
50
70
85

85

100

85

100
100
100
100
100

100
100
150
150
70
70
85
100
150
100
150
100
150
150
150
150
150
150
150

NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

85

100

150

85

100

150

85

100

85

100

85

100
100

100
150
100
150
150
150
150
150
150
150
150
150

85

100
100

100
150
100
150
150
150
150
150
150
150
150
150
150
150

100
100
100
100

100
100
100
100
100

Schneider Electric

Cascading, network 220/240 V


Upstream: Compact NS
Downstream: Compact and Multi 9

Complementary
technical information

Upstream
Breaking capacity kA rms
Downstream
NS125E
NSA160E
NB50N
NB100F
NB100N

Upstream
Breaking capacity kA rms
Downstream
NS125E
NSA160E
NB50N
NB100F
NB100N
NB225N
NB400N
NB600N

Schneider Electric

NSC100N

NSA160N

NS100N

42
50
85
Breaking capacity (kA rms)
50
50
20
20
20
20
20
20
30
30
30

NS250N

NS250H

NS250L

85
100
150
Breaking capacity (kA rms)
50
60
60
50
60
60
20
30
30
20
30
30
30
40
40
50
60
60

NS100H

NS100L

NS160NE

NS160N

NS160H

NS160L

100

150

85

85

100

150

30
30
40

30
30
40

50
50
20
20
30

50
50
20
20
30

60
60
30
30
40

60
60
30
30
40

NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

85

100

150

85

100

150

50
50

60
60

60
60

50
50

60
60

60
60

50
50

60
60

60
60

50
50
50

60
60
60

60
60
60

Cascading, network 220/240 V


Upstream: Compact NS, Masterpact
Downstream: Compact NS, NB and
Multi 9

Complementary
technical information

Upstream
Breaking capacity kA rms
Downstream
NS100N
NS100H
NS160NE
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H
NS630bN
NS630bH
NS800N
NS800H
NS1000N
NS1000H
NS1250N

Upstream
Breaking capacity kA rms
Downstream
NB225N
NB400N
NB600N

Upstream
Breaking capacity kA rms
Downstream
DPN/DPNN
C60H
C60a
C60N
NC100H/NC125H

NS630bL

NS800L

150
150
Breaking capacity (kA rms)
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

NS1000L

Masterpact NT L1

Masterpact NW L1

150

150

150

150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

100
100
100
100
100
100

NS630bL

NS800L

150
150
Breaking capacity (kA rms)
60
50
60
50
60
50

NS125E

NS1000L

Masterpact NT L1

Masterpact NW L1

150

150

150

60
60
60

60
60
60

NSA160E

16
16
Breaking capacity (kA rms)
15
15
25
25
25
25
25
25
25
25

Schneider Electric

Cascading, network 380/415 V (1)


Upstream: Compact NS
Downstream: Compact and Multi 9

Complementary
technical information

Upstream
Breaking capacity kA rms
Downstream
C32
C60a
C60N
C60H
C60L y 25 A
C60L y 40 A
C60L y 63 A
XC/SC40
PM25 u 14 A
NC100H/NC125H
NC100L
NC100LS
NC100LH/LMA
NG125a
NG125N
NG125H
NG125L/LMA
C120N/H
NSA160N
NS80HMA
NSC100N
NS100N
NS100H
NS160NE
NS160N
NS160H

Upstream

NSC100N

NSA160N

NS100N

18
30
25
Breaking capacity (kA rms)
15
15
15
15
15
15
18
25
25
18
30
25
30
30
25
30
25
18
25
25
18
25
25
18
25
25

18

25

25

25

25

25

NS250N

NS250H

NS250L

NS100H

NS100L

NS160NE

NS160N

NS160H

NS160L

70

150

25

36

70

150

20
20
30
40
40
40
40
30
50
30
50
70
70
25
36
50
70
25

20
20
30
40
40
40
40
30
50
30
70
100
150
25
70
100
150
25

15
15
25
25

20
15
25
30
30
30
30
25
25
25

20
20
25
40
40
40
40
30

50
70

150
50
150
150

NS400N

NS400H

25

25
36

25

25
36

20
20
30
40
40
40
40
30
30
30
50
70
70
25
36
50
70
25
50

25

36
36

50
70

36

70
70

NS630N

NS630H

25
25
25
25
25

NS400L

Breaking capacity kA rms


36
70
150
45
70
150
45
70
Downstream
Breaking capacity (kA rms)
C32
15
20
20
20
20
15
20
20
C60a
15
20
20
C60N
25
30
30
C60H
30
30
30
C60L y 25 A
40
40
C60L y 40 A
30
40
40
C60L y 63 A
30
30
30
XC/SC40
25
30
30
NC100H/NC125H
25
30
30
NC100L
50
70
NC100LS
70
100
NC100LH/LMA
70
150
NG125a
25
25
25
NG125N
36
36
70
NG125H
50
100
NG125L/LMA
70
150
C120N/H
25
25
25
NSA160N
36
50
50
36
50
50
36
50
NS80HMA
150
150
NSC100N
36
50
50
45
50
50
45
50
NS100N
36
70
150
45
70
150
45
70
NS100H
150
150
NS160NE
36
70
150
45
70
150
45
70
NS160N
70
150
45
70
150
45
70
NS160H
150
150
NS250N
70
150
45
70
150
45
70
NS250H
150
150
NS400N
70
150
70
NS400H
150
NS630N
70
NS630H
(1) With single pole, single pole + neutral and two pole circuit breakers, with TT or TNS systems, see cascading table for 220/240 V network.

Schneider Electric

30
70
100
150
25
70
100
150
25
50
150
50
150
150
150
150
150

NS630L
150
20

50
150
50
150
150
150
150
150
150
150
150
150
150
150

Cascading, network 380/415 V (1)


Upstream: Compact NS
Downstream: Compact and Multi 9

Complementary
technical information

Upstream
Breaking capacity kA rms
Downstream
NS125E
NSA160E
NB50N
NB100F
NB100N

Upstream

NSC100N

NSA160N

NS100N

18
30
25
Breaking capacity (kA rms)

15
15
18

NS250N

NS250H

NS100H

NS100L

NS160NE

NS160N

NS160H

NS160L

70

150

25

36

70

150

25
25
15
15
20

30
30
15
15
20

30
30
15
15
20

NS630N

NS630H

NS630L

15
15
20

15
15
20

15
15
20

25
25
15
15
20

NS250L

NS400N

NS400H

NS400L

Breaking capacity kA rms


36
70
150
45
70
150
45
70
Downstream
Breaking capacity (kA rms)
NS125E
25
30
30
25
30
30
25
30
NSA160E
25
30
30
25
30
30
25
30
NB50N
15
15
15
NB100F
15
15
15
NB100N
20
20
20
NB225N
25
50
50
25
50
50
25
50
NB400N
36
50
50
36
50
NB600N
36
50
(1) With single pole, single pole + neutral and two pole circuit breakers, with TT or TNS systems, see cascading table for 220/240 V network.

150
30
30

50
50
50

Schneider Electric

Cascading, network 380/415 V (1)


Upstream: Compact NS, Masterpact
Downstream: Compact and Multi 9

Complementary
technical information

Upstream

NS630bN

NS630bH

NS630bL

NS800H

NS800L

NS1000H

NS1000L

NS1250H

NS1600H

Breaking capacity to NS1600N


kA rms
Downstream
NS100N
NS100H
NS160NE
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H
NS630bN
NS630bH
NS800N
NS800H
NS1000N
NS1000H
NS1250N

Upstream

50
70
150
Breaking capacity (kA rms)
50
70
150
150
50
70
150
50
70
150
150
50
70
150
150
50
70
150
150
50
70
150
150

150

70

150

70

70

150

150

70

150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

70

150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

70

70

70
70

70
70

70

70

70

70

100

70

70

70

70

70

70

150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

70

70

100

70

70

100

NS1250H

NS1600N

Masterpact Masterpact

NS1600H

70
70
70
70
70

70

70
70
70
70
70
70
70
70

NS630bH

NS630bL

NS800H

NS800L

NS1000H

NS1000L

Breaking capacity to NS1250N


kA rms
Downstream
NB225N
NB400N
NB600N

Upstream

50
70
150
Breaking capacity (kA rms)
25
50
50
36
50
50
36
50
50

NS125E

NW L1

70

70

NS630bN

Masterpact Masterpact
NT L1

100
100
100

NT L1

NW L1

70

150

70

150

70

50/70

150

150

50
50
50

50
50
50

50
50
50

50
50
50

50
50
50

50
50
50

60
60
60

NSA160E

Breaking capacity kA rms


16
16
Downstream
Breaking capacity (kA rms)
C60a
15
15
C60N
16
16
C60H
16
16
XC/SC40
16
16
PM25 u 14 A
16
16
NC100H/NC125H
16
16
(1) With single pole, single pole + neutral and two pole circuit breakers, with TT or TNS
systems, see cascading table for 220/240 V network.

Schneider Electric

Cascading, network 440 V


Upstream: Compact NS
Downstream: Compact and Multi 9

Complementary
technical information

Upstream
Breaking capacity kA rms
Downstream
NC100L
NC100LS
NC100LH/LMA
NS80HMA
NSC100N
NS100N
NS100H
NS160NE
NS160N
NS160H

Upstream
Breaking capacity kA rms
Downstream
NC100L
NC100LS
NC100LH/LMA
NS80HMA
NSC100N
NS100N
NS100H
NS160NE
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H

10

NS100N

NS100H

NS100L

25
65
130
Breaking capacity (kA rms)
50
70
65
100
65
130
150
25
50
50
65
130
130

NS250N

NS250H

NS250L

35
65
130
Breaking capacity (kA rms)
50
70
65
100
65
130
150
35
50
50
35
65
130
130
35
65
130
65
130
130
65
130
130

NS160NE

NS160N

NS160H

NS160L

25

25

65

130

50
65
65

70
100
130
150
50
130
130
130
130
130

25

35
35

50
65

35

65
65

NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

42

65

130

42

65

130

42
42

50
65

42
42

50
65

42
42

65
65

42
42

65
65

42

65

42

65

65

150
50
130
130
130
130
130
130
130
130
130

65
65

150
50
130
130
130
130
130
130
130
130
130
130
130

Schneider Electric

Cascading, network 440 V


Upstream: Compact NS, Masterpact
Downstream: Compact NS

Complementary
technical information

Upstream
Breaking capacity kA rms
Downstream
NS100N
NS100H
NS160NE
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H
NS630bN
NS630bH
NS800N
NS800H
NS1000N
NS1000H
NS1250N

Schneider Electric

NS630bL NS800N

NS800H

130
50
65
Breaking capacity (kA rms)
130
50
65
130
130
50
65
130
50
65
130
130
50
65
130
130
50
65
130
130
50
65
130
65
65

NS800L

NS1000N NS1000H NS1000L NS1250N NS1250H NS1600H Masterpact

130

50

65

130

50

65

130
130
130
130
130
130
130
130
130
130
130
130
130
130
130

50

65

50

65

50
50

65
65

50
50

65
65

50

65

50

65

50

65

50

65

50

65

130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130
130

50

65

65
65
65

65

65

65

65

65

65

65

65

65

NT L1

NW L1

150

150

100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100

65
65
65
65

11

Protection discrimination
Upstream: Compact NS
Downstream: Compact NS, Integral
and GVM

Complementary
technical information

Network 220/240 V
Upstream
Breaking capacity kA rms
Downstream
NS80HMA
NS100N
NS100H
NS160N
NS160H
GV2M u 23 A
Integral 18 u 10 A
Integral 32 u 25 A
Integral 63 u 32 A
Upstream
Breaking capacity kA rms
Downstream
NS80HMA
NS100N
NS100H
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H
Integral 18 u 10 A
Integral 32 u 25 A
Integral 63 u 32 A

NS100N

NS100H

NS100L

85
100
150
Breaking capacity (kA rms)
150
100
150
150

NS160N

NS160H

NS160L

85

100

150

85
85
85
85

100
100
100
100

100
150
150
150

85
85
85
85

100
100
100
100

150
150
150
150
150
100
150
150
150

NS250N

NS250H

NS250L

NS400H

NS400L

NS630H

NS630L

100

150

100

150

100
100

85
100
150
Breaking capacity (kA rms)
150
100
150
150
100
150
150
100
150
150

100
100
100
100

150
150
150
150
150
150
150
150
150

100
100
100
100
100

85
85
85

100
100
100

150
150
150

NSC100N

NSA160N

NS100N

150
150
150
150
150
150
150
150
150
150
150

150

Network 380/415 V
Upstream
Breaking capacity kA rms
Downstream
NS80HMA
NS100N
NS100H
NS160N
NS160H
GV2M u 14 A
GV2L u 18 A
GV2P u 18 A
GV3M
Integral 18 u 10 A
Integral 32 u 25 A
Integral 63 u 32 A
Upstream
Breaking capacity kA rms
Downstream
NS80HMA
NS100N
NS100H
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H
GV3M
Integral 18 u 10 A
Integral 32 u 25 A
Integral 63 u 32 A
Upstream
Breaking capacity kA rms
Downstream
GV2M u 14 A

12

18
30
25
Breaking capacity (kA rms)

NS100H

NS100L

NS160N

NS160H

NS160L

70

150

36

70

150

70

150
150
150

36

70
70

18

NS250N

30

NS250H

25

NS250L

36
70
150
Breaking capacity (kA rms)
150
36
70
150
150
70
150
150
70
150
150

150
150
150
150
150

50
70
70
70
70
70
70

50
150
150
150
150
150
150

70
70
70
70

150
150
150
150

150
150
150
150

NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

45

70

150

45

70

150

45

70

45

70

45

70

45

70

45

70

45

70

70

150
150
150
150
150
150
150
150
150

70
70

70
70
70
70
NS125E

150
150
150
150

70

150
150
150
150
150
150
150
150
150
150
150

150

NSA160E

16
16
Breaking capacity (kA rms)
16
16

Schneider Electric

Protection discrimination
Upstream: Compact NS
Downstream: Compact NS,Integral

Complementary
technical information

Network 440 V
Upstream
Breaking capacity kA rms
Downstream
NS80HMA
NS100N
NS100H
NS160N
NS160H
Integral 32 u 16 A
Integral 63 u 25 A

Upstream
Breaking capacity kA rms
Downstream
NS80HMA
NS100N
NS100H
NS160N
NS160H
NS250N
NS250H
NS400N
NS400H
NS630N
NS630H
Integral 32 u 16 A
Integral 63 u 25 A

Schneider Electric

NS100N

NS100H

NS100L

25
65
130
Breaking capacity (kA rms)
150
65
130
130

NS160NE

NS160N

NS160H

NS160L

25

25

65

130

35

65

65
65

150
130
130
130
130
130
130

65

NS250N

65
65

130
130

NS250H

NS250L

35
65
130
Breaking capacity (kA rms)
150
35
65
130
130
65
130
130
65
130
130

NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

42

65

130

42

65

130

42

65

42

65

42

65

42

65

42

65

42

65

65

150
130
130
130
130
130
130
130
130

65
65

65
65

130
130

65

150
130
130
130
130
130
130
130
130
130
130

130

13

Cascading for installations


with several transformers
in parallel

Complementary
technical information

The following table indicates the types of circuit breakers to be installed on the
source feeders and main feeders of an installation with 2 or 3 transformers
connected in parallel (1).
The following assumptions are made:
b upstream network short-circuit power of 500 MVA
b the transformers are all identical, 20 kV/410 V and with a normal short-circuit
voltage level
b the short-circuit current on the busbars does not take into account the connection
impedances (the worst case)
b the equipment is installed in a switchboard with an ambient temperature of 30 C
b to connect several transformers in parallel, the transformers must have:
v the same Usc
v the same transformation ratio
v the same type of connection
v a maximum power ratio of 2 between any two of the transformers
v Isc is given only as a general indication and may vary depending on the percent
Usc values given by the transformer manufacturers; the values for breaking
capacities reinforced by cascading are therefore given for higher values.

E45068

Installations with 2 transformers in parallel

D1

D2

D4

Icc

Example: Consider 2 parallel 800 kVA transformers. The source protection devices
are two C125N circuit breakers equipped with STR25DE trip units set at 1250 A.
The installation has two feeders rated 125 A and 630 A respectively. Isc max
downstream of CB4 is 49600 A.
The 630 A feeder will be protected by a NS630N circuit breaker (a breaking
capacity of 50 kA with cascading).
The 125 A feeder will be equipped with a NS160H circuit breaker as cascading is
not possible with an NS160N.

Transformer rating (kVA)

250

315

400

500

500

630

630

800

800

Icc maxi upstream from D4

17600

22200

28200

35200

35200

44400

44400

37500

37500

Nominal transformer current (kVA)

352

444

564

704

704

887

887

1126

1126

Circuit breaker D1 or D2

NS400N

NS630N

NS630N

NS800N

NS800H

NS1000N

NS1000H

NS1250N

NS1250H

50

70

50

70

50

70

50
50
50
50

50
70
70
70

50
50
50

50
70
70
70

50
50

70
70
70
70

Breaking capacity (kA)


Circuit breaker D4
NS100N
NS160N
NS250N
NS400N
NS630N
NS800N
NS1000N

45
45
45
Reinforced breaking capacity (kA)
45
45
45
45
45
45
45
45
45

E45069

Installations with 3 transformers in parallel

D1

D2

D4

D3

Isc

Transformer rating (kVA)

250

315

400

500

500

630

630

800

800

Icc maxi downstream form D4

26400

33300

42300

52800

52800

66600

66600

56300

56300

Nominal transformer current (kVA)

352

444

564

704

704

887

887

1126

1126

Circuit breaker D1 or D2

NS400N

NS630N

NS630H

NS800N

NS800H

NS1000N

NS1000H

NS1250N

NS1250H

50

70

50

70

50

70

50
50

70
70

50
50

50
50
70

50
50

50
50
70
70

Breaking capacity (kA)


Circuit breaker D4
NS160N
NS250N
NS400N
NS630N
NS800N
NS1000N

14

45
45
70
Reinforced breaking capacity (kA)
45
45
45
45
45
45
70

Schneider Electric

Complementary
technical information

Protection discrimination

Contents
Using the tables
Two circuit breakers offer total discrimination when the corresponding box in the
discrimination table is shaded or contains the letter T.
When discrimination is partial for the combination, the corresponding box indicates
the maximum value of the fault current for which discrimination is provided. For
fault currents above this value, the two circuit breakers trip simultaneously.
Application
Discrimination: distribution circuit-breakers

Discriminination: motor protection

Discriminination reinforced by cascading


distribution circuit-breakers

Discriminination reinforced by cascading


motor protection

Schneider Electric

Upstream device
C60

Downstream device
B curve
C curve
B, C curves
D, K curves
B curve
C curve
B, C, D curves
D curve

C60
C60
DPN, TC16, SC-XC40
C60
NC100, NC125
C60
C60
NC100
DPN, TC16, SC-XC40
C60
C60L
C60L
NC100,NC125
B, C curves
NC100
NC100
D curve
NC100
B, C curves
C60 and C45
NSC100N, NSA160, NS125E
Multi 9
NSA160
Compact NS100 to 630
Multi 9
Compact NS100 to 630
Compact NS630b to 3200
Multi 9, Compact NS100 to 250
Compact NS400 to 630
Compact NS630b to 3200
Compact C801 to C1251, CM
Compact C, CM
Multi 9, Compact NS100 to 250
Multi 9, Compact NS400 to 630
Compact C, CM, Masterpact
Masterpact NT
Multi 9, Compact NS100 to 250
Compact NS400 to 630
Compact C801 to C1251, Masterpact
Masterpact NW
Multi 9, Compact NS100 to 630
Compact NS630b to 3200
Compact C801 to 1001, CM
Masterpact NT, NW, Masterpact
Masterpact
Multi 9, Compact NS100 to 630
Compact NS630b to 3200
Masterpact NT, NW
Compact C, CM, Masterpact
Masterpact NT, NW
Compact NSC100N
GV2, Integral 18, 32
Compact NS100 to 630
GV2, GV3
Integral 18, 32, 63
Multi 9, Compact NS80HMA
Compact NS100 to 1600
NS100 to 630
Compact NS1600, Masterpact NT, NW NS630 to 1250
Compact NS100 to 1600
Multi 9, Integral, GV2, NS100 to 630
NSC100N, NSA160
Multi 9
Compact NS160 to 250
Multi 9
Compact NS250 to 630b
NSA160N, NSC100N, NS100 to 250
Compact NS800 to 1600
NSA160N, NSC100N, NS100 to 630
Compact NS160 to 400
Integral 18 to 63
Compact NS160
GV2 M
GV2 P
GV2 L

Table
page
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
38
44
47
50
53
56
58
60
62
64
66
68
72
76
80
84
87
90
92
95
97
98
100
102
104
105
106
107
108
110
111
112
113
114
115

15

Protection discrimination

Complementary
technical information

Protection discrimination is an essential element that must be taken into account


starting at the design stage of a low voltage installation to ensure the highest level
of availability for users.
Discrimination is important in all installations for the comfort of users, however it is
fundamental in installations requiring a high level of service continuity, e.g.
industrial manufacturing processes.
Industrial installations without discrimination run a series of risks of varying
importance including:
b production deadline overruns
b interruption in manufacturing, entailing:
v production or finished-product losses
v risk of damage to production machines in continuous processes
b restarting of machines, one by one, following a general power outage
b shutdown of vital safety equipment such as lubrification pumps, smoke fans, etc.

E26366

What is discrimination?
Discrimination, also called selectivity, is the coordination of automatic protection
devices in such a manner that a fault appearing at a given point in a network is
cleared by the protection device installed immediately upstream of the fault, and by
that device alone.
b total discrimination
Discrimination is said to be total if, for all fault current values, from overloads up to
the non-resistive short-circuit current, circuit breaker D2 opens and D1 remains
closed.
b partial discrimination
Discrimination is partial if the above condition is not respected up to the full shortcircuit current, but only to a lesser value termed the selectivity limit current (Is).
b no discrimination
In the event of a fault, both circuit breakers D1 and D2 open.

D1

D2

Total discrimination as standard with the


new Masterpact NT/NW circuit breakers
Thanks to their highly innovative design and the exeptional performance of their
control units, the new Masterpact NT and NW circuit breakers offer total
discrimination with downstream Compact NS devices up to 630 A as standard (1).

Natural discrimination with Compact NS


circuit breakers
Due to the Roto-active breaking technique employed by the Compact NS, the
combined use of Merlin Gerin circuit breakers provides an exceptional level of
protection discrimination.
This is the result of the implementation and optimisation of three different
techniques:
b current discrimination
b time discrimination
b energy discrimination.

E26406

NS100 NS250
100A 250A
10 000
5 000
2 000
1 000
500

Overload protection: current discrimination


Discrimination is ensured if the ratio between setting thresholds is greater than 1.6
(for distribution circuit breakers).
Low short-circuit protection: current discrimination

200
100
50
20
10

Tripping of the upstream device is slightly delayed to ensure that the downstream
device trips first.
Discrimination is ensured if the ratio between the short-circuit thresholds is greater than 1.5.
High short-circuit protection: time discrimination

t(s)
2
1
.5
.2
.1
.05

This protection system combines the exceptional current limiting capacity of the Compact
NS and the advantages of reflex tripping, sensitive to the energy dissipated in the device by the
short-circuit. In the event of a high short-circuit detected by two circuit breakers, the
downstream device limits it sharply. The energy dissipated in the upstream device is not
sufficient to trip it, i.e. discrimination is total for all short-circuit currents.
Discrimination is ensured if the ratio between the circuit breaker ratings is greater than 2.

.02
.01
.005
.002
.001
.5 .7 1

3 4 5 7 10

I / Ir

16

20 30

50 70 100

200 300

(1) Except for the L1 performance level on Masterpact NT and subject to the discrimination
rules on page 17.
Schneider Electric

Protection discrimination

E34281

Complementary
technical information

How to use the discrimination tables


D1

D2

E34282

Discrimination between two distribution circuit


breakers.

b for discrimination between 2 distribution circuit breakers


Combinations providing total discrimination are indicated by coloured zones or the
symbol T on a coloured background.
If discrimination is partial, the table indicates the maximum fault current value for
which discrimination is ensured. For fault currents above this value, the 2 circuit
breakers trip simultaneously.
b for discrimination between a circuit breaker and a motor control and
protection assembly
If discrimination is partial, the table indicates the maximum fault current value for
which discrimination is ensured. For fault currents above this value, the 2 devices
trip simultaneously.

D1

D2

Discrimination between circuit breakers used for


motor protection.

Requisite conditions
The values indicated in the tables (for 220, 380, 415 and 440 V) are guaranteed if
the following conditions are respected:

D1

Application

D2

Ratio between upstream and downstream settings


Thermal protection

Magnetic protection

Ir up/ Ir down
Im up/ Im down
TMD
Distribution
TMD or Multi9
u 1.6
u2
STRSE/GE
u 1.6
u 1.5
Motor
MA + separate therm. relay
u3
u2
Thermal-magnetic motor type
u3
u2
STRME
u3
u 1.5
STR2.. or 3..
Distribution
TMD or Multi9
u 2.5
u 1.5
fixed long time delay
STRSE/GE
u 1.6
u 1.5
Motor
MA + separate therm. relay
u3
u 1.5
Thermal-magnetic motor type
u3
u 1.5
STRME
u3
u 1.5
Micrologic 2/5/6/7.0
Distribution
TMD or Multi9
u 1.6
u 1.5
STR5.. or 6..
STRSE/GE Micrologic 2/5/6/7.0 u 1.2
u 1.5
with adjustable long time
Motor
MA + separate therm. relay
u3
u 1.5
delay (1)
Thermal-magnetic motor type
u3
u 1.5
STRME, Micrologic 2/5/6/7.0
u3
u 1.5
(1) When upstream and / or downstream control units have adjustable long time delays, adjustement must be such as upstream delay is longer than downstream
delay (1 step difference).

Schneider Electric

17

Protection discrimination
Upstream: C60 B curve
Downstream: C60

Complementary
technical information

Upstream C60a, N, H, L
B curve
Downstream
C60a, N, H, L
B curve

C60a, N, H, L
C curve

C60N, H
D curve
C60L
K curve

In (A)
(A)
0.5
0.75
1
2
3
4
6
10
16
20
25
32
40
(A)
0.5
0.75
1
2
3
4
6
10
16
20
(A)
0.5
0.75
1
2
3
4
6
10
16

2
8

3
12

4
16

6
24

10
40

16
64

20
80

25
100

32
128

40
160

50
200

63
252

12

16

24

40

64

80

100

128

160

200

252

12

16

24

40

64

80

100

128

160

200

252

Discrimination zone

18

Schneider Electric

Protection discrimination
Upstream: C60 C curve
Downstream: C60

Complementary
technical information

Upstream

C60a, N, H, L
C curve

Downstream
C60a, N, H, L
B curve

C60a, N, H, L
C curve

C60, N, H
D curve
C60L
K curve

In (A)
(A)
0.5
0.75
1
2
3
4
6
10
16
20
25
32
40
50
(A)
0.5
0.75
1
2
3
4
6
10
16
20
25
32
(A)
0.5
0.75
1
1.6
2
3
4
6
10
16
20

2
15

3
23

4
30

6
45

10
75

16
120

20
150

25
188

32
240

40
300

50
375

63
473

15

23

30

45

75

120

150

188

240

300

375

473

15

23

30

45

75

120

150

188

240

300

375

473

Discrimination zone

Schneider Electric

19

Protection discrimination
Upstream: C60 B, C curves
Downstream: DPN, TC16, SC-XC40

Complementary
technical information

Upstream

C60a, N, H, L
B curve

Downstream
DPN
SC-XC40
B curve

DPN
TC16
SC-XC40
C curve

DPN
SC-XC40
B curve

DPN
TC16
SC-XC40
C curve

In (A)
(A)
6
10
16
20
25
32
40
(A)
1
2
3
4
5
6
10
16
20
(A)
6
10
16
20
25
32
38
(A)
1
2
3
4
5
6
10
15
20
25
32

10
40

16
64

20
80

25
100

32
128

40
160

50
200

12

16

24

40

64

80

100

128

160

200

252

75

120

150

188

240

300

375

473

75

120

150

188

240

300

375

473

15

23

30

45

63
252

Discrimination zone

20

Schneider Electric

Protection discrimination
Upstream: C60 D, K curves
Downstream: C60

Complementary
technical information

Upstream

C60a, N, H D curve
C60L K curve

Downstream
C60a, N, H, L
B curve

C60a, N, H, L
C curve

C60, N, H
D curve
C60L
K curve

In (A)
(A)
0.5
0.75
1
2
3
4
6
10
16
20
25
32
40
50
(A)
0.5
0.75
1
2
3
4
6
10
16
20
25
32
40
50
(A)
0.5 / 0.75
1
1.6
2
3
4
6
10
16
20
25
32
40
Upstream

2
24

3
36

4
48

6
72

10
120

16
192

20
240

25
300

32
384

40
480

50
600

63
756

24

36

48

72

120

192

240

300

384

480

600

756

24

36

48

72

120

192

240

300

384

480

600

756

C60
D or K curves

Downstream
DPN
SX-XC40
B curve

DPN/DPN Vigi
TC 16
SC-XC40
C curve

In (A)
(A)
6 / 10
16
20
25
32
40
(A)
1
2
3
4
5

10
120

16
192

20
240

25
300

32
384

40
480

50
600

63
756

24

36

48

72

120

192

240

300

384

480

600

756

6
10
16
20
25
32

Discrimination zone
Schneider Electric

21

Protection discrimination
Upstream: NC100, NC125 B curve
Downstream: C60

Complementary
technical information

Upstream
Downstream
C60a, N, H, L
B curve

C60a, N, H, L
C curve

C60, N, H
D curve
C60L
K curve

C60L
Z curve

In (A)
(A)
1
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
1.6
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63

NC100H, L, LS, LH

NC125H

B curve

B curve

10
40

16
64

20
80

25
100

32
128

40
160

50
200

63
252

80
320

100
400

125
500

40

64

80

100

128

160

200

252

320

400

500

40

64

80

100

128

160

200

252

320

400

500

40

64

80

100

128

160

200

252

320

400

500

Discrimination zone

22

Schneider Electric

Protection discrimination
Upstream: NC100, NC125 C curve
Downstream: C60

Complementary
technical information

Upstream

NC100H, L, LS, LH

NC125H

C curve
Downstream
C60a, N, H, L
B curve

C60a, N, H, L
C curve

C60, N, H
D curve
C60L
K curve

C60L
Z curve

C60LMA

Schneider Electric

In (A)
(A)
1
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
1.6
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
(A)
1.6
2.5
4
6.3
10
12.5
16
25/40

C curve

10
75

16
120

20
150

25
188

32
240

40
300

50
375

63
473

80
600

100
750

125
1000

75

120

150

188

240

300

375

473

600

750

1000

75

120

150

188

240

300

375

473

600

750

1000

75

120

150

188

240

300

375

473

600

750

1000

75

120

150

190

240

300

375

470

23

Protection discrimination
Upstream: NC100 B, C, D curves
Downstream: DPN, TC16, SC-XC40

Complementary
technical information

Upstream NC100H, L, LS, LH

NC100H, L, LS, LH

B curve
Downstream
DPN
SC40-XC40
B curve

DPN
TC16
SC40-XC40
C curve

In (A)
(A)
6
10
16
20
25
32
40
(A)
1
2
3
4
5
6
10
16
20
25
32
40

C curve

10

16
64

20
80

25
100

32
128

40
160

50
200

63
252

80
320

100
400

10

16
120

20
150

25
188

32
240

40
300

50
375

63
473

80
600

100
750

40

64

80

100

128

160

200

252

320

400

75

120

150

188

240

300

375

473

600

750

4
5

Upstream NC100
D curve
Downstream
DPN
SC-XC40
B curve

DPN
TC16
SC-XC40
C curve

In (A)
(A)
5
10
16
20
25
32
38
(A)
1
2
3
4
5
10
16
20
25
32
40

10
20

16
192

20
240

25
300

32
384

40
480

50
600

63
756

80
960

100
1200

120

192

240

300

384

480

600

756

960

1200

Discrimination zone

24

Schneider Electric

Protection discrimination
Upstream: NC100 D curve
Downstream: C60

Complementary
technical information

Upstream NC100H, LS
D curve
Downstream
C60a, N, H, L
B curve

C60a, N, H, L
C curve

C60, N, H
D curve
C60L
K curve

C60L
Z curve

C60LMA

Schneider Electric

In (A)
(A)
1
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
1.6
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
63
(A)
1.6
2.5
4
6.3
10
12.5
16
25/40

10
120

16
192

20
240

25
300

32
384

40
480

50
600

63
756

80
960

100
1200

120

192

240

300

384

480

600

756

960

1200

120

192

240

300

384

480

600

756

960

1200

120

192

240

300

384

480

600

756

960

1200

120

190

240

300

384

480

600

756

25

Protection discrimination
Upstream: C60L
Downstream: C60L

Complementary
technical information

Upstream
Downstream
C60L
Z curve

In (A)
(A)
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
Upstream

Downstream
C60L
Z curve

In (A)
(A)
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50
Upstream

C60L
B curve
2
8

3
12

4
16

6
24

10
40

16
64

20
80

25
100

32
128

40
160

50
200

63
240

C60L
C curve
2
15

3
23

4
30

6
45

10
75

16
120

20
150

25
188

32
240

40
300

50
375

63
450

3
36

4
48

6
72

10
120

16
192

20
240

25
300

32
384

40
480

50
600

63
720

C60
K curve

Downstream
C60L
Z curve

Downstream
C60L
Z curve

26

In (A)
(A)
1
1.6
2
3
4
6
8
10
16
20
25
32
40
50

2
24

Upstream

C60L
Z curve
1.6
2
4
8.6

In (A)
(A)
1
1.6
2
3
4
6
8
10
16
20
25
32
40/5

3
9

4
12

6
18

8
24

10
30

16
48

20
60

25
75

32
96

40
120

50
150

63
189

Schneider Electric

Protection discrimination
Upstream: NC100, NC125
B, C curves
Downstream: NC100

Complementary
technical information

Upstream
Downstream
NC100H, L
NC100LS, LH
B curve

NC100H, L
NC100LS, LH
C curve

NC100H, L
NC100LS, LH
D curve

Downstream
NC100H, L
NC100LS, LH
B curve

NC100H, L
NC100LS, LH
C curve

NC100H, L
NC100LS, LH
D curve

NC100H, L, LS, LH

NC125H

B curve

B curve

In (A)
(A)
10
16
20
25
32
40
50
63
80
100
(A)
10
16
20
25
32
40
50
63
80
100
(A)
10
16
20
25
32
40
50
63
80
100

10
40

Upstream

NC100H, L, LS, LH

NC125H

C curve

C curve

In (A)
(A)
10
16
20
25
32
40
50
63
80
100
(A)
10
16
20
25
32
40
50
63
80
100
(A)
10
16
20
25
32
40/50
63
80/100

10

16
64

16
120

20
80

25
100

32
128

40
160

50
200

63
252

80
320

100
400

125
500

128

160

200

252

320

400

500

200

252

320

400

500

20
150

25
188

32
240

40
300

50
375

63
473

80
600

100
750

125
1000

150

188

240

300

375

473

600

750

1000

240

300

375

473

600

750

1000

Discrimination zone
Schneider Electric

27

Protection discrimination
Upstream: NC100 D curve
Downstream: NC100

Complementary
technical information

Upstream

NC100H, L, LS, LH
D curve

Downstream
NC100H, L
NC100LS, LH
B curve

NC100H, L
NC100LS, LH
C curve

NC100H, L
NC100LS, LH
D curve

In (A)
(A)
10
16
20
25
32
40
50
63
80
100
(A)
10
16
20
25
32
40
50
63
80
100
(A)
10
16
20
25
32
40
50
63
80
100

10

16
192

20
240

25
300

32
384

40
480

50
600

63
720

80
960

100
1200

192

240

300

384

480

600

720

960

1200

240

300

384

480

600

720

960

1200

Discrimination zone

28

Schneider Electric

Protection discrimination
Upstream: NC 100 B and C curves
Downstream: C60 and C45

Complementary
technical information

Upstream NC100H, L, LS, LH

NC100H, L, LS, LH

B curve
Downstream
C60N-C45N
B curve
Type 2

C60a, N, H, L
C curve
C45N-C60H
Type 3

C60, N, H
D curve
C60L
K curve
C60H
Type 4
C45AD

In (A)
(A)
1
2
3
4
6
10
16
20
25
32
40
50
63
(A)
1
2
3
4
6
10
16
20
25
32
40
50
(A)
1
2
3
4
6
10
16
20
25
32

C curve

10
40

16
64

20
80

25
100

32
128

40
160

50
200

63
252

80
320

100
400

10
75

16
120

20
150

25
188

32
240

40
300

50
375

63
473

80
600

100
750

40

64

80

100

128

160

200

252

320

400

75

120

150

188

240

300

375

473

600

750

40

64

80

100

128

160

200

252

320

400

75

120

150

188

240

300

375

473

600

750

Discrimination zone

Schneider Electric

29

Protection discrimination
Upstream: NSC100N, NSA160, NS125E
Downstream: DPN, DPN N, XC40, C60,
NC100

Complementary
technical information

Upstream NSC100N
Downstream
DPN
B, C curves

DPN N
C, D curves

XC40
L-U curves

C60a
C curve

C60N
B, C, D curves

C60H
C curve

C60L
B, C curves
K curve
Z curve

NC100H
B, C curves

NC100H
D curve

NC100L
NC100LS

NC100LH
C curve

30

Rating (A)
Setting Ir
y 10
16
20
25
32
y 10
16
20
25
32
40
y 10
16
20
25
32
38
40
y 10
16
20
25
32
40
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 50
63
80
100
y 50
63
80
100
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63

NSA160E/N

16

25

32

40

50

63

70

80

100 16

25

32

40

50

63

80

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

3
3
3
3

3
3
3
3
3

0.6 0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T

T
T
T
T
T

0.6 0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T

T
T
T
T
6

T
T
T
T
T
T
T
T
T
T
T
3
3
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
6
6

T
T
T
T
T
T
T
T
T
T
T
3
3
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
6
6

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T

T
T
T
T
6

T
T
T
T
6
6

T
T
T
T
6
6

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T

T
T
T
T
6

T
T
T
T
6
6

T
T
T
T
6
6

T
T
T
T
T
T
T
T
T
T
T
3
3
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
1.25
1.25

0.6 0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.6 0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

3
3
3
3
3

3
3
3
3
3
3

0.6 0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T

T
T
T
T
T

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T

T
T
T
T
6

T
T
T
T
T
T
T
T
T
T
T
3
3
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
6
6

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

T
T
T
T

T
T
T
T
6

T
T
T
T
6
6

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

15
15
15
15

15
15
15
15
6

15
15
15
15
6
6

1.25
1.25

0.6

0.6

0.6
0.6

0.6
0.6
0.6

T
15
15

T
15
15
15

T
15
15
15
8

T
15
15
15
8

0.6

0.6

0.6
0.6

0.6
0.6
0.6

T
15
15

T
15
15
15

T
15
15
15
8

T
15
15
15
8

T
T
T
T
T
T
T
T
T
T
T
T
T
T

0.6

0.6

0.6
0.6

0.6
0.6
0.6

T
15
15

T
15
15
15

T
15
15
15
8

0.6

0.6

0.6
0.6

0.6
0.6
0.6

T
15
15

T
15
15
15

T
15
15
15
8

NS125E
Trip unit TM-D
100 125 160 80
100 125
T
T
T
T
T
T
T
T
T
T
T
3
3
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
1.25
1.25

T
T
T
T
T
T
T
T
T
T
T
3
3
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
1.25
1.25
1.25

1.25 1.25 1.25 0.63 0.8


1.25 1.25 1.25
0.8
1.25 1.25
0.8

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

T
T
T
T
T
T
T
T
T
T
T
T
T
T

1
1
1
1
1
1
1
1
1
1
1
1
1
1

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
3
3
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
T
T
T
T
8
8
6
6
1.25
1.25
1.25

T
T
T
T
T
T
T
T
T
T
T
T
T
T

0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63
0.63

0.63
0.63
0.63
0.63
0.63
0.63

0.63

0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Schneider Electric

Protection discrimination
Upstream: NSC100N, NSA160,
NS125E
Downstream: NSA160

Complementary
technical information

Upstream NSC100N

NSA160E/N

NS125E

Trip unit TM-D


Downstream
NSA160N

Rating (A) 16
Setting Ir
16
25
32
40
50
63
80
100
125
160

Schneider Electric

25

32

Trip unit TM-D


40

50

63

70

80

100 16

25

32

40

50

63

80

100 125 160 80

100 125

1.25 1.25 1.25 0.63 0.8


1.25 1.25
0.8

1
1

31

Protection discrimination
Upstream: NS100 to 250 - Trip unit TMD
Downstream: DPN, DPN N, XC40, C60,
NC100

Complementary
technical information

Upstream
Downstream
DPN
B, C curves

DPN N
C, D curves

XC40
L-U curves

C60a
C curve

C60N
B, C. D curves

C60H
C curve

C60L
B, C curves
K curve
Z curve

NC100H
B, C curves

NC100H
D curve

NC100L
NC100LS

NC100LH
C curve

32

Rating (A)
Setting Ir
y 10
16
20
25
32
y 10
16
20
25
32
40
y 10
16
20
25
32
38
40
y 10
16
20
25
32
40
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 50
63
80
100
y 50
63
80
100
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63

NS100N/H/L

NS160N/H/L

NS250N/H/L

Trip unit TM-D

Trip unit TM-D

Trip unit TM-D

16

25

32

40

50

63

80

100

80

100

125

160

160

200

250

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63

T
T
T
T
T
T
T
T
T
T
T
4
4
4
4
4
4
4
T
T
T
T
T
T
T
T
T
T
T
T
T

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
T
T
T
T
T
T
T
T
5
5
5
5
5
5
5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.5
2.5

T
T
T
T
T
T
T
T
T
T
T
5
5
5
5
5
5
5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.5
2.5
2.5

0.63

0.8
0.8

2.5

2.5
2.5

2.5
2.5
2.5

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
5
5
5
5
5
5
5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

0.63

0.4
0.4

0.5
0.5

0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63

0.4
0.4

0.5
0.5

0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63

T
T
T
T
T
T
T
T
T
T
T
15
15
15
2.5

T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: NS100 to 250
Trip unit TMD
Downstream: NC125H, NG125

Complementary
technical information

Upstream
Downstream
NC125H
NG125a
C curve
NG125N, Ns, H
B, C curves

NG125N, Ns, H
D curve

NG125L
B, C curves

NG125L
D curve

Schneider Electric

Rating (A)
Setting Ir
125
80
100
125
y 20
25, 32
40
50
63
80
100
125
y 20
25, 32
40
50
63
80
100
125
y 16
20
25, 32
40
50
63
80
y 16
20
25, 32
40
50
63
80

NS100N/H/L

NS160N/H/L

NS250N/H/L

Trip unit TM-D

Trip unit TM-D

Trip unit TM-D

16

25

32

40

50

63

80

100

80

100

125

160

160

2.5
2.5

T
T

0.4

0.5

0.5

0.5
0.5

0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8

T
T
T
2.5

T
T
T
2.5
2.5

T
T
T
2.5
2.5

T
T
T
2.5
2.5
2.5
2.5

T
T
T
T
T
T
T

0.4

0.5

0.5

0.5
0.5

0.63
0.63
0.63

0.8
0.8
0.8
0.8

T
T
T
2.5

T
T
T
2.5
2.5

T
T
T
2.5
2.5

T
T
T
2.5
2.5
2.5
2.5

T
T
T
T
T
T

0.3

0.4
0.4

0.5
0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
T
2.5

T
T
T
T
2.5
2.5

T
T
T
T
2.5
2.5

0.3

0.4
0.4

0.5
0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8

T
T
T
T
2.5

T
T
T
T
2.5
2.5

T
T
T
T
2.5
2.5

T
T
T
T
2.5
2.5
2.5
T
T
T
T
2.5
2.5
2.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T

200

250

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

33

Protection discrimination
Upstream: NS100 to 160 - Trip unit STR
Downstream: DPN, DPN N, XC40, C60,
NC100

Complementary
technical information

Upstream

NS100N/H/L

NS160N/H/L

Trip unit STR22SE


Downstream
DPN
B, C curves

DPN N
C, D curves

XC40
L, U curves

C60a
C curve

C60N
B, C, D curves

C60H
C curve

C60L
B, C curve
K curve
Z curve

NC100H
B, C curves

NC100H
D curve

NC100L
NC100LS

NC100LH
C curve

34

Rating (A)

40

Setting Ir
y 10
16
20
25
32
y 10
16
20
25
32
40
y 10
16
20
25
32
38
40
y 10
16
20
25
32
40
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 50
63
80
100
y 50
63
80
100
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63

16

Trip unit STR22SE


100

80

25
0.4

40
0.4
0.4

40
1.2
1.2

63
1.2
1.2
1.2
1.2

80
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2

0.4

0.4
0.4

1.2
1.2

1.2
1.2
1.2
1.2

0.4

0.4
0.4

1.2
1.2

1.2
1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2
1.2

0.4

0.4
0.4

1.2
1.2

1.2
1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2

0.4

0.4
0.4

1.2
1.2

1.2
1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2

0.4

0.4
0.4

1.2
1.2

1.2
1.2
1.2

0.4

0.4
0.4

1.2
1.2

1.2
1.2
1.2
1.2

160

100
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2

32
T

40
T
T

50
T
T
T

63
T
T
T
T

80
T
T
T
T
T
T
T
T
T
T

63
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T

T
T
T
T
T

1.2
1.2
1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2
1.2

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T

1.2
1.2
1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2
1.2

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T

T
T
T
T

80
T
T
T
T
T
T
T
T
T
T

100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T
T

160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

0.4

1.2

1.2
1.2
1.2

1.2
1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

0.4

1.2

1.2
1.2
1.2

1.2
1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: NS250 to 630 - Trip unit STR
Downstream: DPN, DPN N, XC40, C60,
NC100

Complementary
technical information

Upstream
Downstream
DPN
B, C curves

DPN N
C, D curves

XC40
L, U curves

C60a
C curve

C60N
B, C, D curves

C60H
C curve

C60L
B, C curves
K curve
Z curve

NC100H
B, C curves

NC100H
D curve

NC100L
NC100LS

NC100LH
C curve

Schneider Electric

NS250N/H/L

NS400N/H/L

NS630N/H/L

Trip unit STR22SE

Trip unit STR23SE/53UE

Trip unit STR23SE/53UE

Rating (A)

250

400

Setting Ir
y 10
16
20
25
32
y 10
16
20
25
32
40
y 10
16
20
25
32
38
40
y 10
16
20
25
32
40
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63
y 50
63
80
100
y 50
63
80
100
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63

100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

125
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T
T

160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

35

Protection discrimination
Upstream: NS100 to 160
Trip unit STR
Downstream: NC125H, NG125

Complementary
technical information

Upstream

NS100N/H/L

NS160N/H/L

Trip unit STR22SE


Downstream
NC125H
NG125a
C curve
NG125N, Ns, H
B, C curves

NG125N, Ns, H
D curve

NG125L
B, C curves

NG125L
D curve

36

Rating (A)

40

Setting Ir
125
80
100
125
y 20
25, 32
40
50
63
80
100
125
y 20
25, 32
40
50
63
80
100
125
y 16
20
25, 32
40
50
63
80
y 16
20
25, 32
40
50
63
80

16

Trip unit STR22SE


100

25

40

40

80
63

80

100

0.63

0.8
0.8

1
1
1

32

160
40

50

63

80

63

80

100

125

160

T
T

T
T
T

T
T
T
2

T
T
T
2.5
2.5

T
T

T
T
T

T
T
T
2.5

T
T
T
2.5
2.5

0.63

0.8
0.8

1
1
1

0.63

0.8
0.8

1
1
1

T
T

T
T
T

T
T
T
T

T
T
T
T
2.5

T
T
T
T
2.5
2.5

0.63

0.8
0.8

1
1
1

T
T

T
T
T

T
T
T
T

T
T
T
T
2.5

T
T
T
T
2.5
2.5

Schneider Electric

Protection discrimination
Upstream: NS250 to 630
Trip unit STR
Downstream: NC125H, NG125

Complementary
technical information

Upstream
Downstream
NC125H
NG125a
C curve
NG125N, Ns, H
B, C curves

NG125N, Ns, H
D curve

NG125L
B, C curves

NG125L
D curve

Schneider Electric

NS250N/H/L

NS400N/H/L

NS630N/H/L

Trip unit STR22SE

Trip unit STR23SE/53UE

Trip unit STR23SE/53UE

Rating (A)

250

400

Setting Ir
125
80
100
125
y 20
25, 32
40
50
63
80
100
125
y 20
25, 32
40
50
63
80
100
125
y 16
20
25, 32
40
50
63
80
y 16
20
25, 32
40
50
63
80

100

125

160

200

250

T
T
T
T
T
T
T
T
T
T

160

630
200

250

T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

37

Protection discrimination
Upstream: NS100 to 250
Trip unit TMD
Downstream: NS100 to 250

Complementary
technical information

Upstream
Downstream

Rating (A)

Setting Ir
NS100N
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100H
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100L
16
Trip unit TM-D
25
32
40
50
63
80
100
y 63
NS160NE/N
Trip unit TM-D
80
100
125
160
y 63
NS160H
Trip unit TM-D
80
100
125
160
y 63
NS160L
Trip unit TM-D
80
100
125
160
y 100
NS250N
Trip unit TM-D
125
160
200
250
y 100
NS250H/L
Trip unit TM-D
125
160
200
250
NS100N
40
Trip unit STR22SE100
NS100H/L
40
Trip unit STR22SE 100
NS160N
40
Trip unit STR22SE 100
160
NS160H/L
40
Trip unit STR22SE 100
160
y 100
NS250N
Trip unit STR22SE 160
250
y 100
NS250H/L
Trip unit STR22SE 160
250

38

NS100N/H/L

NS160N/H/L

NS250N/H/L

Trip unit TM-D

Trip unit TM-D

Trip unit TM-D

16

25

32

40

50

63

80

100

80

100

125

160

160

200

250

0.4

0.5
0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

1
1
1
1
1

2
2
2
2
2
2

2
2
2
2
2
2
1.25

0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

1
1
1
1
1

2
2
2
2
2
2

2
2
2
2
2
2
1.25

0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

1
1
1
1
1

2
2
2
2
2
2

2
2
2
2
2
2
1.25

2
2
2
2
2
2
1.25
1.25
2
2
2
2
2
2
1.25
1.25
2
2
2
2
2
2
1.25
1.25
1.25
1.25
1.25

T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
T
T
36
36
36
36
36
36
2.6
2.6
2.6

T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
T
T
36
36
36
36
36
36
4
4
4
4

1.25
1.25

1.25
1.25
1.25

2.6
2.6
2.6

4
4
4
4

1.25
1.25

1.25
1.25
1.25

2.6
2.6
2.6

4
4
4
4

1.6

2
2

T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
T
T
36
36
36
36
36
36
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2.5
2.5
2.5

1.6

2
2

2.5
2.5
2.5

1.25
1.25
1.25
1.25
1.25
1.25

T
T
36
36
1.6
1.6

T
T
36
36
2
2

1.25
1.25

1.6
1.6

2
2

1.6

T
T
36
36
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

1.6

1.25
1.25

0.63

0.8

1.25

1.25

0.63

0.8

1.25

1.25

0.63

0.8

1.25

1.25

0.63

0.8

1.25

1.25

2.5
2.5

Schneider Electric

Protection discrimination
Upstream: NS100 to 250 - Trip unit TMD
Downstream: NSC100N, NS125E,
NSA160N, NB225N

Complementary
technical information

Upstream
Downstream
NSC100N

NS125E

NSA160N

NB225N

Schneider Electric

Rating (A)
Setting Ir
15
20
25
32
40
50
63
70
80
100
16
25
40
63
80
100
125
16
25
32
40
50
63
80
100
125
160
100
125
150
175
200
225

NS100N/H/L

NS160N/H/L

NS250N/H/L

Trip unit TM-D

Trip unit TM-D

Trip unit TM-D

16

25

32

40

50

63

80

100

80

100

125

160

160

200

250

0.3

0.4
0.4

0.5
0.5

0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8
0.8

2
2
2
2
2

2
2
2
2
2
2
2

2
2
2
2
2
2
2
2
1.25

1
1
1

2
2
2
2

2
2
2
2
1.25

2
2
2
2
2
2
2
2
1.25
1.25
2
2
2
2
1.25
1.25

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2
2
2
2
2

2
2
2
2
2
2

2
2
2
2
2
2
1.25

2
2
2
2
2
2
1.25
1.25

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5
T
T
T
T
T
T
T
T
T
T

0.4

0.5
0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

39

Protection discrimination
Upstream: NS100 to 160
Trip unit STR
Downstream: NS100 to 160

Complementary
technical information

Upstream

NS100N/H/L

NS160N/H/L

Trip unit STR22SE


Downstream

Rating (A)

Setting Ir
NS100N
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100H
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100L
16
Trip unit TM-D
25
32
40
50
63
80
100
y 63
NS160NE/N
Trip unit TM-D
80
100
125
160
y 63
NS160H
Trip unit TM-D
80
100
125
160
y 63
NS160L
Trip unit TM-D
80
100
125
160
NS100N
40
Trip unit STR22SE 100
NS100H/L
40
Trip unit STR22SE 100
NS160N
40
Trip unit STR22SE 100
160
NS160H/L
40
Trip unit STR22SE 100
160

40

40
16

Trip unit STR22SE


100

25

40

40

80
63
1.2
1.2

80
1.2
1.2
1.2

100
1.2
1.2
1.2
1.2
1.2

1.2
1.2

1.2
1.2
1.2

1.2
1.2

32

160
40

50

63

80

63
2
2

80
2
2
2

100
2
2
2
2

125
2
2
2
2
2

160
2
2
2
2
2
2

1.2
1.2
1.2
1.2
1.2

2
2

2
2
2

2
2
2

2
2
2
2
2

2
2
2
2
2
2

1.2
1.2
1.2

1.2
1.2
1.2
1.2
1.2

2
2

2
2
2

2
2
2

2
2
2
2
2

2
2
2
2
2
2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

2
2
2
2
2
2

1.2

1.2

1.2

2
2

2
2

Schneider Electric

Protection discrimination
Upstream: NS250 to 630
Trip unit STR
Downstream: NS100 to 160

Complementary
technical information

Upstream
Downstream
NS100N
Trip unit TM-D

NS100H
Trip unit TM-D

NS100L
Trip unit TM-D

NS160NE/N
Trip unit TM-D

NS160H
Trip unit TM-D

NS160L
Trip unit TM-D

NS250N
Trip unit TM-D

NS250H/L
Trip unit TM-D

NS100N
Trip unit STR22SE
NS100H/L
Trip unit STR22SE
NS160N
Trip unit STR22SE
NS160H/L
Trip unit STR22SE
NS250N
Trip unit STR22SE
NS250H/L
Trip unit STR22SE

Schneider Electric

NS250N/H/L

NS400N/H/L

NS630N/H/L

Trip unit STR22SE

Trip unit STR23SE/53UE

Trip unit STR23SE/53UE

Rating (A)

250

400

Setting Ir
16
25
32
40
50
63
80
100
16
25
32
40
50
63
80
100
16
25
32
40
50
63
80
100
y 63
80
100
125
160
y 63
80
100
125
160
y 63
80
100
125
160
y 100
125
160
200
250
y 100
125
160
200
250
40
100
40
100
40
100
160
40
100
160
y 100
160
250
y 100
160
250

100
T
T
T
T

125
T
T
T
T
T

160
T
T
T
T
T
T

200
T
T
T
T
T
T
T

T
T
36
36

T
T
36
36
36

T
T
36
36
36
36

T
T
36
36
36
36
36

T
T
36
36

T
T
36
36
36

T
T
36
36
36
36

T
T
36
36
36
36
36

3
3

3
3

3
3

36

36

T
T
36
36
3
3

T
T
36
36
3
3

3
3

3
3

250
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
T
T
36
36
36
36
36
36
3
3
3

630

160
T
T
T
T
T
T

200
T
T
T
T
T
T
T

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T

3
3
3

3
3
3

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

5
5

T
T
T
T
T
T

3
3

T
T
36
36
3
3
3
3
3
3
3
3

T
T
T
T
T
T
T
T
T
T
5

3
3

3
3

T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5
5
5

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5
5

5
5
5

T
T

T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T
5
5

T
T
T
T
T
T
T
T
T
T
5
5

5
5

5
5

T
T
T
T
T
T
T
T
T
T
5
5
5
5
5
5

T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T

T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

41

Protection discrimination
Upstream: NS100 to 160 - Trip unit STR
Downstream: NSC100N, NS125E,
NSA160N, NB225N

Complementary
technical information

Upstream

NS100N/H/L

NS160N/H/L

Trip unit STR22SE


Downstream
NSC100N

NS125E

NSA160N

NB225N

42

Rating (A)

40

Setting Ir
15
20
25
32
40
50
63
70
80
100
16
25
40
63
80
100
125
16
25
32
40
50
63
80
100
125
160
100
125
150
175
200
225

16

Trip unit STR22SE


100

25

80

40
0.4

40
0.4

63
0.63
0.63
0.63

80
0.8
0.8
0.8
0.8

100
1
1
1
1
1

0.4

0.4

0.63
0.63

0.8
0.8
0.8

1
1
1
1

32

160
40

50

63

80

63
2
2
2

80
2
2
2
2

100
2
2
2
2
2

125
2
2
2
2
2
2

160
2
2
2
2
2
2
2

2
2

2
2
2

2
2
2
2

2
2
2
2
2

2
2
2
2
2
2

Schneider Electric

Protection discrimination
Upstream: NS250 to 630 - Trip unit STR
Downstream: NS400 to 630, NSC100N,
NS125E, NSA160N, NB225N to 600

Complementary
technical information

Upstream
Downstream
NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

NSC100N

NS125E

NSA160N

NB225N

NB400N

NB600N

Schneider Electric

NS250N/H/L

NS400N/H/L

NS630N/H/L

Trip unit STR22SE

Trip unit STR23SE/53UE

Trip unit STR23SE/53UE

Rating (A)

250

400

Setting Ir
160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

100

y 25
32
40
50
63
70
80
100
y 25
40
63
80
100
125
y 25
32
40
50
63
80
100
125
160
100
125
150
175
200
225
250
300
350
400
500
600

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T
T

T
T

T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

125

160

200

250

160

630
200

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T

T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

250

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5
5

400

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5
5
5

250
8

320
8
8

400
8
8
8

500
8
8
8
8

8
8

8
8
8

8
8
8
8

8
8

8
8
8

8
8
8
8

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

43

Protection discrimination
Upstream: NS630b to 1600N/H
Downstream: Multi 9, NS100 to NS250

Complementary
technical information

Upstream

NS630b/NS800/NS1000/NS1250/1600N/H

NS630b/NS800/NS1000/NS1250/1600N/H

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A)

630

Downstream
Setting Ir
DPN, DPN N, XC40, C60
NC100/125, C120, NG125
NS100N
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100H/L
16
Trip unit TM-D
25
32
40
50
63
80
100
y 63
NS160N/NE
Trip unit TM-D
80
100
125
160
y 63
NS160H/L
Trip unit TM-D
80
100
125
160
y 100
NS250N
Trip unit TM-D
125
160
200
250
y 100
NS250H/L
Trip unit TM-D
125
160
200
250
NS100N
40
STR22SE
100
NS100H/L
40
STR22SE
100
NS160N
40
STR22SE
80
100
160
NS160H/L
40
STR22SE
100
160
y 100
NS250N
STR22SE
160
250
y 100
NS250H/L
STR22SE
160
250

44

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800

1000 1250 1600 630

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800

1000 1250 1600

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: NS630b to NS1000L,
NS1600b to 3200N
Downstream: Multi 9, NS100 to NS250

Complementary
technical information

Upstream NS630b/NS800/NS1000L

NS1600b/NS2000/NS2500/NS3200N NS1600b/NS2000/NS2500/

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

NS3200N
Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 630


Downstream
Setting Ir
DPN, DPN N, XC40, C60
NC100/125, C120, NG125
NS100N
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100H/L
16
Trip unit TM-D
25
32
40
50
63
80
100
y 63
NS160N/NE
Trip unit TM-D
80
100
125
160
y 63
NS160H/L
Trip unit TM-D
80
100
125
160
y 100
NS250N
Trip unit TM-D
125
160
200
250
y 100
NS250H/L
Trip unit TM-D
125
160
200
250
NS100N
40
STR22SE
100
NS100H/L
40
STR22SE
100
NS160N
40
STR22SE
80
100
160
NS160H/L
40
STR22SE
100
160
y 100
NS250N
STR22SE
160
250
y 100
NS250H/L
STR22SE
160
250

Schneider Electric

250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800

1000

1600

2000

2500

3200

1600

2000

2500

3200

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

45

Protection discrimination
Upstream: NS1600b to 3200H
Downstream: Multi 9, NS100 to NS250

Complementary
technical information

Upstream NS1600b/NS2000/NS2500/NS3200H
Trip unit

Micrologic 2.0 - Isd: 10 Ir

Rating (A) 1600


Downstream
Setting Ir
DPN, DPN N, XC40, C60
NC100/125, C120, NG125
NS100N
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100H/L
16
Trip unit TM-D
25
32
40
50
63
80
100
y 63
NS160N/NE
Trip unit TM-D
80
100
125
160
y 63
NS160H/L
Trip unit TM-D
80
100
125
160
y 100
NS250N
Trip unit TM-D
125
160
200
250
y 100
NS250H/L
Trip unit TM-D
125
160
200
250
NS100N
40
STR22SE
100
NS100H/L
40
STR22SE
100
NS160N
40
STR22SE
80
100
160
NS160H/L
40
STR22SE
100
160
y 100
NS250N
STR22SE
160
250
y 100
NS250H/L
STR22SE
160
250

46

1600
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

NS1600b/NS2000/NS2500/NS3200H
Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

2000

2500

3200

1600

2000

2500

3200

2000
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

2500
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

3200
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

1600
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

2000
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

2500
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

3200
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
T
T
40
40
T
T
T
T
40
40
40
T
T
T
40
40
40

Schneider Electric

Protection discrimination
Upstream: NS630b to 1600N/H
Downstream: NS400 to 630

Complementary
technical information

Upstream NS630b/NS800/NS1000/NS1250/1600N/H
Trip unit

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 630


Downstream
NS400N
STR23SE
STR53UE

NS400H
STR23SE
STR53UE

NS400L
STR23SE
STR53UE

NS630N
STR23SE
STR53UE

NS630H
STR23SE
STR53UE

NS630L
STR23SE
STR53UE

NSC100N

NS125E
Trip unit TM-D

NSA160N

NS225E

NS400NB

NS600NB

Schneider Electric

NS630b/NS800/NS1000/NS1250/1600N/H

Micrologic 2.0 - Isd: 10 Ir


800

1000 1250 1600 630

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

250
T

320
T
T

400
T
T
T

500
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

Setting Ir
160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

250
T

320
T
T

400
T
T
T

500
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

y 25
32
40
50
63
70
80
100
y 25
40
63
80
100
125
y 25
32
40
50
63
80
100
125
160
100
125
150
175
200
225
250
300
350
400
500
600

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800

1000 1250 1600

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

47

Protection discrimination
Upstream: NS630b to 1000L,
NS1600b to 3200N
Downstream: NS400 to NS630

Complementary
technical information

Upstream NS630b/NS800/NS1000L
Trip unit

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 630


Downstream
NS400N
STR23SE
STR53UE

NS400H
STR23SE
STR53UE

NS400L
STR23SE
STR53UE

NS630N
STR23SE
STR53UE

NS630H
STR23SE
STR53UE

NS630L
STR23SE
STR53UE

NSC100N

NS125E
Trip unit TM-D

NSA160N

NS225E

NS400NB

NS600NB

48

Micrologic 2.0 - Isd: 10 Ir


2000

2500

3200

1600

2000

2500

3200

630
18
18
18
18
18
18
18
18
18
18
30
30
30
30
30
12
12
12

800
18
18
18
18
18
18
18
18
18
18
30
30
30
30
30
12
12
12
12

1000
18
18
18
18
18
18
18
18
18
18
30
30
30
30
30
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
18
18
18

500
18
18
18
18

18

18
18

18
18
18

18
18
18
18

30

30
30

30
30
30

30
30
30
30

12

12
12

12

12
12

12
12
12

12
12
12
12

12

12
12

12
12
12

12
12
12
12

y 25
32
40
50
63
70
80
100
y 25
40
63
80
100
125
y 25
32
40
50
63
80
100
125
160
100
125
150
175
200
225
250
300
350
400
500
600

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

18
18

18
18
18

18
18
18
18

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12

T
T

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

1600

320
18
18

NS2500/NS3200N

1000

250
18

T
T
T
T
T
T
T

NS1600b/NS2000/

NS2500/NS3200N
800

Setting Ir
160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NS1600b/NS2000/

Schneider Electric

Protection discrimination
Upstream: NS1600b to 3200H
Downstream: NS400 to 630

Complementary
technical information

Upstream NS1600b/NS2000/NS2500/NS3200H
Trip unit
Downstream
NS400N
STR23SE
STR53UE

NS400H
STR23SE
STR53UE

NS400L
STR23SE
STR53UE

NS630N
STR23SE
STR53UE

NS630H
STR23SE
STR53UE

NS630L
STR23SE
STR53UE

NSC100N

NS125E
Trip unit TM-D

NSA160N

NS225E

NS400NB

NS600NB

Schneider Electric

Micrologic 2.0 - Isd: 10 Ir

NS1600b/NS2000/NS2500/NS3200H
Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 1600

2000

2500

3200

1600

2000

2500

3200

Setting Ir
160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

1600
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2000
40
40
40
40
40
35
35
35
35
35
35
35
35
35
35
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

2500
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

3200
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

1600
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2000
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2500
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

3200
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

y 25
32
40
50
63
70
80
100
y 25
40
63
80
100
125
y 25
32
40
50
63
80
100
125
160
100
125
150
175
200
225
250
300
350
400
500
600

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

49

Protection discrimination
Upstream: NS630b to 1600N/H
Downstream: NS630b to 3200

Complementary
technical information

Upstream NS630b/NS800/NS1000/NS1250/1600N/H
Trip unit

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 630


Downstream
NS630bN/H

Setting Ir
250
320
400
500
630
NS630bL
250
320
400
500
630
NS800N
320
400
500
630
800
NS800H
320
400
500
630
800
NS800L
320
400
500
630
800
NS1000N
400
500
630
800
1000
NS1000H
400
500
630
800
1000
NS1000L
400
500
630
800
1000
NS1250N
500
630
800
1000
1250
NS1250H
500
630
800
1000
1250
NS1600N
640
800
960
1250
1600
NS1600H
640
800
960
1250
1600
NS1600b/3200 1250
N/H
1600
2000
2500
3200

50

NS630b/NS800/NS1000/NS1250/1600N/H

Micrologic 2.0 - Isd: 10 Ir


250

320

800

1000 1250 1600 630


1000
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1250
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

800

1000 1250 1600

400
25

500
25
25

630
25
25
25

800
25
25
25
25

70

70
70

70
70
70

70
70
70
70

25

25
25

25
25
25

1000
25
25
25
25
25
70
70
70
70
70
25
25
25
25

25

25
25

25
25
25

25
25
25
25

70

70
70

70
70
70

70
70
70
70

25

25
25

25
25
25

25

25
25

25
25
25

25
25
25
25

70

70
70

70
70
70

70
70
70
70

25

25
25

25
25
25

25

25
25

25
25
25

25
25
25
25

16
16
16

25

25
25

25
25
25

16
16
16

25

25
25

25
25
25

400
4

500
5
5

630
6.3
6.3
6.3

800
8
8
8
8

1600 250
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

5
5

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3
6.3

8
8
8

10
10
10
10

6.3
6.3

8
8
8

10
10
10
10

6.3

8
8

10
10
10

6.3

8
8

10
10
10

12.5
12.5
12.5
12.5

6.3

8
8

10
10
10

12.5
12.5
12.5
12.5

10
10

12.5
12.5
12.5

10
10

12.5
12.5
12.5

16
16
16
16

10

12.5
12.5

10

12.5
12.5

320

1250
25
25
25
25
25
70
70
70
70
70
25
25
25
25
25
25
25
25
25
25
70
70
70
70
70
25
25
25
25

1600
25
25
25
25
25
70
70
70
70
70
25
25
25
25
25
25
25
25
25
25
70
70
70
70
70
25
25
25
25
25
25
25
25
25
25
70
70
70
70
70
25
25
25
25

Schneider Electric

Protection discrimination
Upstream: NS630b to 1000L,
NS1600b to 3200N
Downstream: NS630b to 3200

Complementary
technical information

Upstream NS630b/NS800/NS1000L
Trip unit

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 630


Downstream
NS630bN/L

NS630bH

NS800N/L

NS800H

NS1000N/L

NS1000H

NS1250N

NS1250H

NS1600N

NS1600H

NS1600b/3200
N/H

Schneider Electric

Setting Ir
250
320
400
500
630
250
320
400
500
630
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
640
800
960
1250
1600
640
800
960
1250
1600
1250
1600
2000
2500
3200

250

320

NS1600b/NS2000/

NS1600b/NS2000/

NS2500/NS3200N

NS2500/NS3200N

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

800

1000

1600

2000

2500

3200

1600

2000

2500

3200

1000
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

1600
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T

2000
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T

2500
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
60
60

3200
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
60
60
60

400
10

500
10
10

630
10
10
10

800
10
10
10
10

10

10
10

10
10
10

10
10
10
10

10

10
10

10
10
10

10

10
10

10
10
10

10
10
10
10

10

10
10

10
10
10

10

10
10

10
10
10

16
16
16
16
16
16
16

16
16
16

20
20
20
20
20

60
60
60
60
T
T
T

60
60
60

60
60
60
60
60

51

Protection discrimination
Upstream: NS1600b to 3200H
Downstream: NS630b to 3200

Complementary
technical information

Upstream NS1600b/NS2000/NS2500/NS3200H
Trip unit
Downstream
NS630bN/H

NS630bL

NS800N

NS800H

NS800L

NS1000N

NS1000H

NS1000L

NS1250N

NS1250H

NS1600N

NS1600H

NS1600b/3200
N/H

52

Micrologic 2.0 - Isd: 10 Ir

S1600b/NS2000/NS2500/NS3200H
Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 1600

2000

2500

3200

1600

2000

2500

3200

Setting Ir
250
320
400
500
630
250
320
400
500
630
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
640
800
960
1250
1600
640
800
960
1250
1600
1250
1600
2000
2500
3200

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
40
40
40
40
40
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
40
40
40
40
40
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
40
40
40
40
40
32
32
32
32
32
32
32
32
32
32
40
40
40
40
40
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

1600
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2000
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2500
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

3200
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

16
16
16

20
20
20
20
20

40
40
40
40
40
40
40

40
40
40

40
40
40
40
40

Schneider Electric

Protection discrimination
Upstream: NS630b to 1600N/H
Downstream: C801 to 1251, CM

Complementary
technical information

Upstream NS630b/NS800/NS1000/NS1250/1600N/H
Trip unit

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 630


Downstream
C801N/H
STR25DE

C801L
STR25DE

C1001N/H
STR25DE

C1001L
STR25DE

C1251N
STR25DE

CM
N/H
ST-CM1

Schneider Electric

Setting Ir
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
1250
1600
2000
T00
3200

NS630b/NS800/NS1000/NS1250/1600N/H

Micrologic 2.0 - Isd: 10 Ir


250

320

400

500
5

630
6.3
6.3

800

1000 1250 1600 630

800
8
8
8

1000
10
10
10
10

8
8

10
10
10

10
10

1250
12.5
12.5
12.5
12.5

12.5
12.5
12.5
12.5

12.5
12.5
12.5

1600 250
16
16
16
16
16

16
16
16
16
16

16
16
16
16

320

400

800

1000 1250 1600

500
25

630
25
25

800
25
25
25

1000
25
25
25
25

1250
25
25
25
25

40

40
40

40
40
40

40
40
40
40

40
40
40
40

25

25
25

25
25
25

25
25
25
25

40

40
40

40
40
40

40
40
40
40

25

25
25

25
25
25

1600
25
25
25
25
25
40
40
40
40
40
25
25
25
25
25
40
40
40
40
40
25
25
25
25

53

Protection discrimination
Upstream: NS630b to 1000L,
NS1600b to 3200N
Downstream: C801 to 1251, CM

Complementary
technical information

Upstream NS630b/NS800/NS1000L
Trip unit

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 630


Downstream
C801N/H

C801L
STR25DE

C1001N/H
STR25DE

C1001L
STR25DE

C1251N
STR25DE

CM
N/H
ST-CM1

54

Setting Ir
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
1250
1600
2000
T00
3200

250

320

400

NS1600b/NS2000/

NS1600b/NS2000/

NS2500/NS3200N

NS2500/NS3200N

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

800

1000

1600

2000

2500

3200

1600

2000

2500

3200

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
36
36
36
36
36
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
62
62
62
62
62
32
32
32
32
32
36
36
36
36
36
32
32
32
32
32

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
10

630
10
10

800
10
10
10

1000
10
10
10
10

10

10
10

10
10
10

10
10
10
10

10

10
10

10
10
10

10

10
10

10
10
10

Schneider Electric

Protection discrimination
Upstream: NS1600b to 3200H
Downstream: C801 to 1251, CM

Complementary
technical information

Trip unit
Downstream
C801N/H
STR25DE

C801L
STR25DE

C1001N/H
STR25DE

C1001L
STR25DE

C1251N
STR25DE

CM
N/H
ST-CM1

Schneider Electric

Upstream NS1600b/NS2000/NS2500/NS3200H

NS1600b/NS2000/NS2500/NS3200H

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A) 1600

2000

2500

3200

1600

2000

2500

3200

Setting Ir
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
1250
1600
2000
T00
3200

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
36
36
36
36
36
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
40
40
40
40
40
32
32
32
32
32
36
36
36
36
36
32
32
32
32
32

1600
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2000
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2500
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

3200
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

55

Protection discrimination
Upstream: C801 to C1251
Downstream: DPN, DPN N, XC40, C60,
NC100, NC125, NG125, NS100 to 250

Complementary
technical information

Upstream C801N/H/C1001N/H/C1251N/H

C801N/H

Trip unit STR25DE


Downstream

Rating (A) 800

Setting Ir 320
DPN, DPN N, XC40, C60
T
NC100/125, NG125
T
NS100N
16
3.2
Trip unit TM-D
25
3.2
32
3.2
40
3.2
50
3.2
63
3.2
80
3.2
100
3.2
NS100H
16
3.2
Trip unit TM-D
25
3.2
32
3.2
40
3.2
50
3.2
63
3.2
80
3.2
100
3.2
NS100L
16
3.2
Trip unit TM-D
25
3.2
32
3.2
40
3.2
50
3.2
63
3.2
80
3.2
100
3.2
y 63
NS160NE/N
3.2
Trip unit TM-D
80
3.2
100
3.2
125
3.2
160
y 63
NS160H
3.2
Trip unit TM-D
80
3.2
100
3.2
125
3.2
160
y 63
NS160L
3.2
Trip unit TM-D
80
3.2
100
3.2
125
3.2
160
y 100
NS250N
3.2
Trip unit TM-D
125
160
200
250
y 100
NS250H/L
3.2
Trip unit TM-D
125
160
200
250
NS100N
40
3.2
Trip unit STR22SE
100
3.2
NS100H/L
40
3.2
Trip unit STR22SE
100
3.2
NS160N
40
3.2
Trip unit STR22SE
100
3.2
160
3.2
NS160H/L
40
3.2
Trip unit STR22SE
100
3.2
160
3.2
y 100
NS250N
3.2
Trip unit STR22SE
160
3.2
250
y 100
NS250H/L
3.2
Trip unit STR22SE
160
3.2
250

56

C1001N/H/C1251N/H

Trip unit STR35SE/GE/ME/55UE Trip unit STR35SE/GE/ME/55UE


1000 1250 800

400
T
T
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

500
T
T
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5

630
T
T
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3

4
4

5
5
5

6.3
6.3
6.3
6.3

4
4
4
4
4
4
4
4
4
4
4
4

5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5

6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3

4
4

800
T
T
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
8
8
8
8
8
8
8
8
8
8
10
10
10
10
10
10
10
10
10
10
8
8
8
8
8
8

1000
T
T
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
15
15
15
15
15
15
15
15
15
15
18
18
18
18
18
18
18
18
18
18
15
15
15
15
15
15

1250
T
T
T
T
T
T
T
T
T
T
30
30
T
30
T
30
30
30
30
30
T
30
T
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
24
24
24
24
24
24
24
24
24
24
T
T
30
30
30
30
30
30
30
30
24
24
24
24
24
24

1000

320
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
T

400
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
T
T
T

500
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
T
T
T
T

40

40
40
40

40
40
40
40

T
T
50
50
T
T
T
45
45
45
T
T

T
T
50
50
T
T
T
45
45
45
T
T

40
40

40
40

T
T
50
50
T
T
T
45
45
45
T
T
T
40
40
40

630
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
T
T
T
T
T
40
40
40
40
40
T
T
50
50
T
T
T
45
45
45
T
T
T
40
40
40

800
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
T
T
T
T
T
40
40
40
40
40
T
T
50
50
T
T
T
45
45
45
T
T
T
40
40
40

1250

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: C801 to C1251, CM
Downstream: DPN, DPN N, XC40, C60,
NC100, NC125, NG125, NS100 to 250

Complementary
technical information

Upstream C801N/H
Trip unit STR45AE

C1001N/H/C1251N/H

C801L

C1001L

CM

Trip unit STR45AE

Trip unit

Trip unit

N/H (1)

STR35SE/GE/ME/55UE
Downstream

Rating (A) 800


Setting Ir

DPN, DPN N, XC40, C60


NC100/125, NG125
NS100N
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100H
16
Trip unit TM-D
25
32
40
50
63
80
100
NS100L
16
Trip unit TM-D
25
32
40
50
63
80
100
y 63
NS160NE/N
Trip unit TM-D
80
100
125
160
y 63
NS160H
Trip unit TM-D
80
100
125
160
y 63
NS160L
Trip unit TM-D
80
100
125
160
y 100
NS250N
Trip unit TM-D
125
160
200
250
y 100
NS250H/L
Trip unit TM-D
125
160
200
250
NS100N
40
Trip unit STR22SE
100
NS100H/L
40
Trip unit STR22SE
100
NS160N
40
Trip unit STR22SE
100
160
NS160H/L
40
Trip unit STR22SE
100
160
y 100
NS250N
Trip unit STR22SE
160
250
y 100
NS250H/L
Trip unit STR22SE
160
250

320
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

STR35SE/GE/ME/55UE

1000 1250 800


500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000 1250 320


T
T
T
T
T
T
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
T
T
T
T
6.4
T
T
6.4
T
T
6.4
T
T
T
T
T
T
6.4
T
T
6.4
T
T
6.4
T
T
T
T
T
T
6.4
T
T
T
T
T
T
T
T
T
T
6.4
T
T
T
T
T
T
T
T
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
6.4
T
T
T
T
6.4
T
T
6.4
T
T
T
T
6.4
T
T
6.4
T
T

1000
400
T
T
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

500
T
T
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

630
T
T
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

6.4
6.4

6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

800
T
T
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

400
T
T
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
3.2
3.2
3.2
3.2
3.2
3.2

all
500
T
T
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4
4
4
4
4
4

630
T
T
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
5
5
5
5
5
5

800
T
T
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6.3
6.3
6.3
6.3
6.3
6.3

1000
T
T
T
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T
8
T

(1) With trip unit STCM2-STCM3.


Schneider Electric

57

Protection discrimination
Upstream: C801 to C1251
Downstream: DPN, DPN N, XC40, C60,
NC100, NC125, NG125, NS400 to 630

Complementary
technical information

Upstream
Downstream Rating (A)
NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

NSC100N

NS125E

NSA160N

NB225N

NB400N

NB600N

58

C801N/H/C1001N/H/C1251N/H

C801N/H

Trip unit STR25DE

Trip unit STR35SE/GE/ME/55UE

Trip unit STR35SE/GE/ME/55UE


1000

800

Setting Ir
160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

320
3.2
3.2

400
4
4
4

500
5
5
5
5

630
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3

800
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

3.2
3.2

4
4
4

5
5
5
5

3.2
3.2

4
4
4

5
5
5
5

5
5

5
5

6.3
6.3
6.3

8
8
8
8

5
5

6.3
6.3
6.3

8
8
8
8

y 25
32
40
50
63
70
80
100
y 25
40
63
80
100
125
y 25
32
40
50
63
80
100
125
160
100
125
150
175
200
225
250
300
350
400
500
600

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

10
10
10
10
10
10
10
10
5
5
5
5
5
5
10
10
10
10
10
10
10
10
10
5
5
5
5

15
15
15
15
15
15
15
15
6.3
6.3
6.3
6.3
6.3
6.3
15
15
15
15
15
15
15
15
15
6.3
6.3
6.3
6.3
6.3

T
T
T
T
T
T
T
T
10
10
10
10
10
10
T
T
T
T
T
T
T
T
T
8
8
8
8
8
8

C1001N/H/C1251N/H

1000

1250

800

1000
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1250
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

320
12
12

400
12
12
12

500
12
12
12
12

12
12

12
12
12

12
12
12
12

12
12

12
12
12

12
12
12
12

12

12
12

12

T
T
T
T
T
T
T
T
18
18
18
18
18
18
T
T
T
T
T
T
T
T
T
15
15
15
15
15
15

T
T
T
T
T
T
T
T
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
24
24
24
24
24
24

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250

630
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

800
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

400
T
T

500
T
T
T

630
T
T
T
T

800
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
40
40
40
40

45
45

45
45
45

45
45
45
45

45
45

45
45
45

45
45
45
45

40

40
40

40
40
40

12
12

12
12
12

12
12
12
12

40

40
40

40
40
40

40
40
40
40

12

12
12

12
12
12

12
12
12
12

40

40
40

40
40
40

40
40
40
40

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

1250
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: C801 to C1251, CM
Downstream: DPN, DPN N, XC40, C60,
NC100, NC125, NG125, NS400 to 630

Complementary
technical information

Upstream

C801N/H

C1001N/H/C1251N/H

C801L

C1001L

CM

Trip unit STR45AE

Trip unit STR45AE

Trip unit

Trip unit

N/H (1)

STR35SE/GE/ME/55UE
Downstream Rating (A)
NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

NSC100N

NS125E

NSA160N

NB225N

NB400N

NB600N

800

1000 1250 800

Setting Ir
160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
630
250
320
400
500
630
250
320
400
500
630

320 400 500


35
35
35
35
35
35

630
35
35
35
35

35

35
35

35
35
35

35
35
35
35

35

35
35

35
35
35

35
35
35
35

28

28
28

28
28

28
28
28

28

28
28

28
28
28

28
28
28
28

28

28
28

28
28
28

28
28
28
28

y 25
32
40
50
63
70
80
100
y 25
40
63
80
100
125
y 25
32
40
50
63
80
100
125
160
100
125
150
175
200
225
250
300
350
400
500
600

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
28
28
28
28
28
28
28
28
28
28
28
28
28
28

400
T
T
T
T

500
T
T
T
T

630
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T

800
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T
T

T
T
T
T

T
T
T
T

70
70
70
70

70
70
70
70

T
T

T
T

T
T
T

T
T
T
T

65

65
65

65
65
65

65
65
65
65

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
35
35
35
35
28
28

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T
T
T
T
T
T
T
T
65
65
65
65
65

1250
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T
T
T
T
T
T
T
T
65
65
65
65
65

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

STR35SE/GE/ME/55UE
1000

320 400 500


6.4 6.4 6.4
6.4 6.4 6.4
6.4 6.4
6.4

630
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

800
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

400
8
8
8
8
8
8
8
8

all
500
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

630
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

800
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

6.4
6.4

6.4
6.4
6.4

6.4
6.4
6.4
6.4

6.4
6.4

6.4
6.4
6.4

6.4
6.4
6.4
6.4

6.4

6.4
6.4

6.4

6.4
6.4

6.4
6.4
6.4

6.4
6.4
6.4
6.4

8
8

8
8
8

8
8
8
8

6.4

6.4
6.4

6.4
6.4
6.4

6.4
6.4
6.4
6.4

8
8

8
8
8

8
8
8
8

T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4
6.4
T
T
T
T
T
T
T
T
T
6.4

T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4
6.4
T
T
T
T
T
T
T
T
T
6.4
6.4

T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4
6.4
T
T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4

T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4
6.4
T
T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4

6.4
6.4
6.4
6.4
6.4
6.4

T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4
6.4
T
T
T
T
T
T
T
T
T
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4

T
T
T
T
T
T
T
T
8
8
8
8
8
8
T
T
T
T
T
T
T
T
T
8
8
8
8
8
8
8
8
8
8
8
8

T
T
T
T
T
T
T
T
8
8
8
8
8
8
T
T
T
T
T
T
T
T
T
8
8
8
8
8
8
8
8
8
8
8
8

T
T
T
T
T
T
T
T
8
8
8
8
8
8
T
T
T
T
T
T
T
T
T
8
8
8
8
8
8
8
8
8
8
8
8

T
T
T
T
T
T
T
T
8
8
8
8
8
8
T
T
T
T
T
T
T
T
T
8
8
8
8
8
8
8
8
8
8
8
8

8
8
8
8
8

1000
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
8
8
8
8
8
8
T
T
T
T
T
T
T
T
T
8
8
8
8
8
8
8
8
8
8
8
8

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

(1) With trip unit STCM2-STCM3.

Schneider Electric

59

Protection discrimination
Upstream: C801 to C1251
Downstream: C801 to C1251, CM,
Masterpact

Complementary
technical information

Upstream
Downstream
C801N
Trip unit STR25DE

C801H
Trip unit STR25DE

C801L

C1001N
Trip unit STR25DE

C1001H
Trip unit STR25DE

C1001L

C1251N
Trip unit STR25DE

C1251H
Trip unit STR25DE

CM

Masterpact
N1/H1/H2
STR28D

Masterpact L
STR28D

C801N/H/C1001N/H/C1251N/H

C801N/H

Trip unit STR25DE

Trip unit STR35SE/GE/ME/55UE Trip unit STR35SE/GE/ME/55UE

Rating (A)

800

Setting Ir
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
1250
1600
2000
2500
3200
M08
M10
M12
M16
M20
M25
M32
M40
M50
M63
M08
M10
M12
M16
M20
M25

320

C1001N/H/C1251N/H

1000 1250 800


400

500

630
6.3

800
8
8
8

1000
10
10
10
10

1250 320
12.5
12.5
12.5
12.5

6.3

8
8
8

10
10
10
10

12.5
12.5
12.5
12.5

8
8

10
10
10

12.5
12.5
12.5

8
8

10
10
10

1000
400

500

630
12

800
12
12
12

12

12
12
12

400

1250
500

630
15

800
15
15
15

1000
15
15
15
15

1250
15
15
15
15

15

15
15
15

15
15
15
15

15
15
15
15

12
12

15
15

15
15
15

15
15
15

12.5
12.5
12.5

12
12

15
15

15
15
15

15

10
10

12.5
12.5

12

15

15
15

15
15

10
10

12.5
12.5

12

15

15
15

15
15

15

Nota :
b C801N/H with trip unit STR45AE : no distrimination with the dowstream devices give, in this table
b upstream values CM N/H are to be read with distrimination:
v CM (trip unit STCM1)
v Masterpact L (trip unit STR38S - 68U).

60

Schneider Electric

Protection discrimination
Upstream: C801 to C1251, CM
Downstream: C801 to C1251, CM,
Masterpact

Complementary
technical information

Upstream

Downstream
C801N
Trip unit STR25DE

C801H
Trip unit STR25DE

C801L

C1001N
Trip unit STR25DE

C1001H
Trip unit STR25DE

C1001L

C1251N
Trip unit STR25DE

C1251H
Trip unit STR25DE

CM

Masterpact
N1/H1/H2
STR28D

Masterpact L
STR28D

Schneider Electric

C1001N/H/C1251N/H

C801L

C1001L

CM N/H

Trip unit STR45AE

Trip unit

Trip unit

Trip unit STCM2-STCM3

STR35SE/GE/ME/55UE

STR35SE/GE/ME/55UE

Rating (A)

800

1000 1250 800

Setting Ir
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
1250
1600
2000
2500
3200
M08
M10
M12
M16
M20
M25
M32
M40
M50
M63
M08
M10
M12
M16
M20
M25

400 500 630 800


15
15
15
15
15
15

1000
15
15
15
15

1000

1250 1600 2000 2500 3200

1250 320 400 500 630 800 400 500 630 800 1000 1250
15
45
15
45
15
45
15
45
15
15
45
15
45
15
45
15
45
15
15
80
15
80
15
80
15
80
15
15
45
15
45
15
45
15

1600
45
45
45
45
45
45
45
45
45
45
80
80
80
80
80
45
45
45
45

15

15
15

15
15
15

15
15
15
15

15

15
15

15
15
15

15
15
15
15

15

15
15

15
15
15

15

15
15

15
15
15

15
15
15
15

45
45
45

45
45
45
45

15

15
15

15
15
15

15
15
15
15

80
80
80

80
80
80
80

15

15
15

15
15
15

45
45

45
45
45

15

15
15

15
15
15

45
45

45
45
45

2000
45
45
45
45
45
45
45
45
45
45
80
80
80
80
80
45
45
45
45
45
45
45
45
45
45
80
80
80
80
80
45
45
45
45

2500
45
45
45
45
45
45
45
45
45
45
80
80
80
80
80
45
45
45
45
45
45
45
45
45
45
80
80
80
80
80
45
45
45
45
45
45
45
45
45
45
35
35

3200
45
45
45
45
45
45
45
45
45
45
80
80
80
80
80
45
45
45
45
45
45
45
45
45
45
80
80
80
80
80
45
45
45
45
45
45
45
45
45
45
35
35
35

35

35
35

35
35
35

40
40
40

35
35
35
35

35
35
35
35
35

45
45
45
45
35

40

40
40

61

Protection discrimination
Upstream: Masterpact NT
Downstream: Multi 9, NS100 to 250

Complementary
technical information

Upstream Masterpact NT H1
Trip unit
Micrologic 2.0
Isd: 10 Ir
NT06 NT08 NT10
Downstream
Rating (A) 630
800
1000
Setting Ir 630
800
1000
DPN, DPN N, XC40, C60
T
T
T
NC100H, C120, NC125H, NG125 T
T
T
NS100N
16
T
T
T
TM-D
25
T
T
T
32
T
T
T
40
T
T
T
50
T
T
T
63
T
T
T
80
T
T
T
100
T
T
T
NS100H
16
T
T
T
TM-D
25
T
T
T
32
T
T
T
40
T
T
T
50
T
T
T
63
T
T
T
80
T
T
T
100
T
T
T
NS100L
16
T
T
T
TM-D
25
T
T
T
32
T
T
T
40
T
T
T
50
T
T
T
63
T
T
T
80
T
T
T
100
T
T
T
y 63
NS160N/NE
T
T
T
TM-D
80
T
T
T
100
T
T
T
125
T
T
T
160
T
T
T
y 63
NS160H
T
T
T
TM-D
80
T
T
T
100
T
T
T
125
T
T
T
160
T
T
T
y 63
NS160L
T
T
T
TM-D
80
T
T
T
100
T
T
T
125
T
T
T
160
T
T
T
y 100
NS250N
T
T
T
TM-D
125
T
T
T
160
T
T
T
200
T
T
T
250
T
T
T
y 100
NS250H/L
T
T
T
TM-D
125
T
T
T
160
T
T
T
200
T
T
T
250
T
T
T
NS100N
40
T
T
T
STR22SE
100
T
T
T
NS100H/L
40
T
T
T
STR22SE
100
T
T
T
NS160N
40
T
T
T
STR22SE
100
T
T
T
160
T
T
T
NS160H/L
40
T
T
T
STR22SE
80
T
T
T
100
T
T
T
160
T
T
T
y 100
NS250N
T
T
T
STR22SE
160
T
T
T
250
T
T
T
y 100
NS250H/L
T
T
T
STR22SE
160
T
T
T
250
T
T
T

62

NT12
1250
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT16
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Masterpact NT H1
Micrologic 5.0 - 6.0 - 7.0
Inst: 15 In
NT06 NT08 NT10
630
800
1000
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT12
1250
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT16
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Masterpact NT H1
Micrologic 5.0 - 6.0 - 7.0
Inst: OFF
NT06 NT08 NT10
630
800
1000
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT12
1250
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT16
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Complementary
technical information

Upstream Masterpact NT L1
Trip unit
Micrologic 2.0
Isd: 10 Ir
NT06 NT08 NT10
Downstream
Rating (A) 630
800
1000
Setting Ir 630
800
1000
DPN, DPN N, XC40, C60
T
T
T
NC100H, NC125H, C120, NG125 T
T
T
NS100N
16
T
T
T
TM-D
25
14
T
T
32
11
17
T
40
11
17
T
50
11
17
T
63
11
17
T
80
11
17
T
100
11
17
T
NS100H
16
T
17
28
TM-D
25
11
17
28
32
11
17
28
40
11
17
28
50
11
17
28
63
11
17
28
80
11
17
28
100
11
17
28
NS100L
16
T
17
28
TM-D
25
14
17
28
32
11
17
28
40
11
17
28
50
11
17
28
63
11
17
28
80
11
17
28
100
11
17
28
y 63
NS160N/NE
9
13
22
TM-D
80
9
13
22
100
9
13
22
125
9
13
22
160
9
13
22
y 63
NS160H
9
13
22
TM-D
80
9
13
22
100
9
13
22
125
9
13
22
160
9
13
22
y 63
NS160L
9
13
22
TM-D
80
9
13
22
100
9
13
22
125
9
13
22
160
9
13
22
y 100
NS250N
8
11
19
TM-D
125
8
11
19
160
8
11
19
200
8
11
19
250
8
11
19
y 100
NS250H/L
8
11
19
TM-D
125
8
11
19
160
8
11
19
200
8
11
19
250
8
11
19
NS100N
40
11
17
T
STR22SE
100
11
17
T
NS100H/L
40
11
17
28
STR22SE
100
11
17
28
NS160N
40
9
13
22
STR22SE
100
9
13
22
160
9
13
22
NS160H/L
40
9
13
22
STR22SE
80
9
13
22
100
9
13
22
160
9
13
22
y 100
NS250N
8
11
19
STR22SE
160
8
11
19
250
8
11
19
y 100
NS250H/L
8
11
19
STR22SE
160
8
11
19
250
8
11
19
Schneider Electric

Protection discrimination
Upstream: Masterpact NT
Downstream: Multi 9, NS100 to 250
Masterpact NT L1
Micrologic 5.0 - 6.0 - 7.0
Inst: 15 In
NT06 NT08 NT10
630
800
1000
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Masterpact NT L1
Micrologic 5.0 - 6.0 - 7.0
Inst: OFF
NT06 NT08 NT10
630
800
1000
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

63

Protection discrimination
Upstream: Masterpact NT
Downstream: NS400 to 630, NSC100N,
NS125E, NSA160, NB225 to 600

Complementary
technical information

Upstream
Trip unit

Downstream Rating (A)


Setting Ir
NS400N
160
STR23SE
200
STR53UE
250
320
400
NS400H
160
STR23SE
200
STR53UE
250
320
400
NS400L
160
STR23SE
200
STR53UE
250
320
400
NS630N
250
STR23SE
320
STR53UE
400
500
630
NS630H
250
STR23SE
320
STR53UE
400
500
630
NS630L
250
STR23SE
320
STR53UE
400
500
630

NSC100N

y 25
32
40
50
63
70
80
100
y 25
NS125E
Trip unit TM-D 40
63
80
100
125
y 25
NSA160N
32
40
50
63
80
100
125
160
NB225N
100
125
150
175
200
225
NS400NB
250
300
350
400
NB600N
500
600

64

Masterpact NT H1
Micrologic 2.0
Isd: 10 Ir
NT06 NT08 NT10
630
800
1000
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT12
1250
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT16
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Masterpact NT H1
Micrologic 5.0 - 6.0 - 7.0
Inst: 15 In
NT06 NT08 NT10
630
800
1000
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT12
1250
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT16
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Masterpact NT H1
Micrologic 5.0 - 6.0 - 7.0
Inst: OFF
NT06 NT08 NT10
630
800
1000
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT12
1250
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

NT16
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: Masterpact NT
Downstream: NS400 to 630, NSC100N,
NS125E, NSA160, NB225 to 600

Complementary
technical information

Upstream
Trip unit

Downstream Rating (A)


Setting Ir
NS400N
160
STR23SE
200
STR53UE
250
320
400
NS400H
160
STR23SE
200
STR53UE
250
320
400
NS400L
160
STR23SE
200
STR53UE
250
320
400
NS630N
250
STR23SE
320
STR53UE
400
500
630
NS630H
250
STR23SE
320
STR53UE
400
500
630
NS630L
250
STR23SE
320
STR53UE
400
500
630

NSC100N

y 25
32
40
50
63
70
80
100
y 25
NS125E
Trip unit TM-D 40
63
80
100
125
y 25
NSA160N
32
40
50
63
80
100
125
160
NB225N
100
125
150
175
200
225
NS400NB
250
300
350
400
NB600N
500
600

Schneider Electric

Masterpact NT L1
Micrologic 2.0
Isd: 10 Ir
NT06 NT08 NT10
630
800
1000
630
800
1000
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
6.3
8
10
8
10
10
6.3
8
10
6.3
8
10
6.3
8
10
8
10
10
6.3
8
10
6.3
8
10
6.3
8
10
8
10
10

Masterpact NT L1
Micrologic 5.0 - 6.0 - 7.0
Inst: 15 In
NT06 NT08 NT10
630
800
1000
630
800
1000
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
18
8.5
15
23
8.5
15
23
8.5
15
23
8.5
15
23
8.5
15
23
9.4
12
12
9.4
12
12
9.4
12
12
12
12
12
9.4
12
12
9.4
12
12
9.4
12
12
12
12
12
9.4
12
12
9.4
12
12
9.4
12
12
12
12
12

Masterpact NT L1
Micrologic 5.0 - 6.0 - 7.0
Inst: OFF
NT06 NT08 NT10
630
800
1000
630
800
1000
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

12
12
12
12
12
12
12
12
9
9
9
9
9
9
11
11
11
11
11
11
11
11
11
8
8
8
8
8
8
6.3
6.3
6.3
6.3

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
8.5
8.5
8.5
8.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18

T
T
T
T
T
T
T
T
13
13
13
13
13
13
T
T
T
T
T
T
T
T
T
11
11
11
11
11
11
8
8
8
8
8
8

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
19
19
19
19
19
19
10
10
10
10
10
10

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
15
15
15
15
12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12

65

Protection discrimination
Upstream: Masterpact NT
Downstream: NS630b to NS1600, C801
to C1251, CM, Masterpact NT

Complementary
technical information

Upstream

Masterpact NT H1

Masterpact NT H1

Masterpact NT H1

Trip unit

Micrologic 2.0

Micrologic 5.0 - 6.0 -7.0

Micrologic 5.0 - 6.0 -7.0

Isd: 10 Ir
Downstream

Rating (A)

Setting Ir
250
320
400
500
630
NS800N/H/L
320
400
500
630
800
NS1000N/H/L 400
500
630
800
1000
NS1250N/H
500
630
800
1000
1250
NS1600N/H
640
800
960
1280
1600
C801N/H/L
320
400
500
630
800
C1001N/H/L
400
500
630
800
1000
C1251N/H
500
630
800
1000
1250
CM
1250
N/H
1600
2000
2500
3200
Masterpact NT NT06
H1
NT08
NT10
NT12
NT16
Masterpact NT NT06
L1
NT08
NT10
NS630bN/H/L

66

Inst: 15 In

Inst: OFF

NT06

NT08

NT10

NT12

NT16

NT06

NT08

NT10

NT12

NT16

NT06

NT08

NT10

NT12

NT16

630

800

1000

1250

1600

630

800

1000

1250

1600

630

800

1000

1250

1600

630
6.3
6.3
6.3

800
8
8
8
8

1000
10
10
10
10
10
10
10
10
10

1250
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

630
9.4
9.4
9.4

800
12
12
12
12

1000
15
15
15
15
15
15
15
15
15

1250
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

1600
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

630
T
T
T

800
T
T
T
T

1000
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

8
8
8

10
10
10

12.5
12.5
12.5

12
12
12

15
15
15

18.7
18.7
18.7

16
16
16

8
8
8

10
10
10
10
10
10
10

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16

T
T
T

T
T
T

T
T
T

24
24
24

12
12
12

15
15
15
15
15
15
15

18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

24
24
24
24
24
24
24
24
24
24
24
24
24
24

T
T
T

T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

10

12.5
12.5

16
16
16

15

18.7
18.7

24
24
24

T
T

T
T
T

10

12.5
12.5

16
16
16

15

18.7
18.7

24
24
24

T
T

T
T
T

Schneider Electric

Protection discrimination
Upstream: Masterpact NT
Downstream: NS630b to NS1600,
C801 to C1251, CM, Masterpact NT

Complementary
technical information

Upstream

Masterpact NT L1

Masterpact NT L1

Trip unit

Micrologic 2.0

Micrologic 5.0 - 6.0 - 7.0 Micrologic 5.0 - 6.0 - 7.0

Isd: 10 Ir
Downstream

Rating (A)

Setting Ir
250
320
400
500
630
NS800N/H/L
320
400
500
630
800
NS1000N/H/L 400
500
630
800
1000
NS1250N/H
500
630
800
1000
1250
NS1600N/H
640
800
960
1280
1600
C801N/H/L
320
400
500
630
800
C1001N/H/L
400
500
630
800
1000
C1251N/H
500
630
800
1000
1250
CM
1250
N/H
1600
2000
2500
3200
Masterpact NT NT06
H1
NT08
NT10
NT12
NT16
Masterpact NT NT06
L1
NT08
NT10
NS630bN/H/L

Schneider Electric

Inst: 15 In

Masterpact NT L1
Inst: OFF

NT06

NT08

NT10

NT06

NT08

NT10

NT06

NT08

NT10

630

800

1000

630

800

1000

630

800

1000

630
6.3
6.3
6.3

800
8
8
8
8

1000
10
10
10
10
10
10
10
10
10

630
9.4
9.4
9.4

800
10
10
10
10

1000
10
10
10
10
10
10
10
10
10

630
10
10
10

800
10
10
10
10

1000
10
10
10
10
10
10
10
10
10

8
8
8

10
10
10

10
10
10

8
8
8

10
10
10
10

10
10
10

10
10
10

10
10
10

10
10
10
10

10
10
10

10
10
10

10
10
10
10

10
10
10

10
10
10

10
10
10

10

10

10

10

10

10

67

Protection discrimination
Upstream: Masterpact NW
Downstream: Multi 9, NS100 to 630,
NSC100N, NSA160, NB225 to 600

Complementary
technical information

Upstream

Masterpact NW N1 - H1 - H2

Masterpact NW N1 - H1 - H2

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

Downstream
DPN, DPN N
C60
XC40
NC100H
NC125H
NC125N/H/L
C120N/H
NS100N
NS100H
NS100L
NS160N/NE
NS160H
NS160L
NS250N
NS250H/L
NS400N
STR23SE
STR53UE

NS400H
STR23SE
STR53UE

NS400L
STR23SE
STR53UE

NS630N
STR23SE
STR53UE

NS630H
STR23SE
STR53UE

NS630L
STR23SE
STR53UE

NSC100N
NS125E
NSA160N
NB225N
NB400N
NB600N

68

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300 800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: Multi 9, NS100 to 630,
NSC100N, NSA160, NB225 to 600

Complementary
technical information

Upstream
Trip unit

Masterpact NW N1 - H1 - H2
Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF
NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

Downstream
DPN, DPN N
C60
XC40
NC100H
NC125H
NG125N/H/L
C120H/L
NS100N
NS100H
NS100L
NS160N/NE
NS160H
NS160L
NS250N
NS250H/L
NS400N
STR23SE
STR53UE

NS400H
STR23SE
STR53UE

NS400L
STR23SE
STR53UE

NS630N
STR23SE
STR53UE

NS630H
STR23SE
STR53UE

NS630L
STR23SE
STR53UE

NSC100N
NS125E
NSA160N
NB225N
NB400N
NB600N

Schneider Electric

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

69

Protection discrimination
Upstream: Masterpact NW
Downstream: Multi 9, NS100 to 630,
NSC100, NSA160, NB225 to 600

Complementary
technical information

Downstream
DPN, DPN N
C60
XC40
NC100H
NC125H
NG125N/H/L
C1200N/H
NS100N
NS100H
NS100L
NS160N/NE
NS160H
NS160L
NS250N
NS250H/L
NS400N
STR23SE
STR53UE

NS400H
STR23SE
STR53UE

NS400L
STR23SE
STR53UE

NS630N
STR23SE
STR53UE

NS630H
STR23SE
STR53UE

NS630L
STR23SE
STR53UE

NSC100N
NS125E
NSA160N
NB225N
NB400N
NB600N

70

Upstream Masterpact NW H3

Masterpact NW H3

Masterpact NW H3

Trip unit

Micrologic 2.0

Micrologic 5.0 - 6.0 - 7.0

Micrologic 5.0 - 6.0 - 7.0

Isd: 10 Ir

Inst: 15 In

Inst: OFF

NW20

NW25

NW32

NW40

NW20

NW25

NW32

NW40

NW20

NW25

NW32

NW40

Rating (A)

2000

2500

3200

4000

2000

2500

3200

4000

2000

2500

3200

4000

Setting Ir

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: Multi 9, NS100 to 630,
NSC100, NSA160, NB225 to 600

Complementary
technical information

Upstream Masterpact NW L1

Masterpact NW L1

Masterpact NW L1

Trip unit

Micrologic 5.0 - 6.0 - 7.0

Micrologic 5.0 - 6.0 - 7.0

Micrologic 2.0
Isd: 10 Ir

Downstream
DPN, DPN N
C60
XC40
NC100H
NC125H
NG125N/H/L
C120N/H
NS100N
NS100H
NS100L
NS160N/NE
NS160H
NS160L
NS250N
NS250H/L
NS400N
STR23SE
STR53UE

NS400H
STR23SE
STR53UE

NS400L
STR23SE
STR53UE

NS630N
STR23SE
STR53UE

NS630H
STR23SE
STR53UE

NS630L
STR23SE
STR53UE

Inst: 15 In

Inst: OFF

NW08

NW10

NW12

NW16

NW20

NW08

NW10

NW12

NW16

NW20

NW08

NW10

NW12

NW16

NW20

Rating (A)

800

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

Setting Ir

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

NSC100N
NS125E
NSA160N
NB225N
NB400N
NB600N

Schneider Electric

T
T
T
T
T
T
T
T

T
T
T
T
T
T

71

Protection discrimination
Upstream: Masterpact NW
Downstream: NS630b to NS3200

Complementary
technical information

Downstream
NS630bN

Upstream

Masterpact NW N1 - H1 - H2

Masterpact NW N1 - H1 - H2

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0-6.0-7.0 - Inst: 15 In

Rating (A)

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63
800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
250
320
400
500
630
NS630bH
250
320
400
500
630
NS630bL
250
320
400
500
630
NS800N
320
400
500
630
800
NS800H
320
400
500
630
800
NS800L
320
400
500
630
800
NS1000N
400
500
630
800
1000
NS1000H
400
500
630
800
1000
NS1000L
400
500
630
800
1000
NS1250N
500
630
800
1000
1250
NS1250H
500
630
800
1000
1250
NS1600N
640
800
960
1280
1600
NS1600H
640
800
960
1280
1600
NS1600b/3200 1250
N/H
1600
2000
2500
3200

72

800
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

1000
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1250
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

8
8
8

10
10
10
10

8
8
8

10
10
10
10

8
8

10
10
10

8
8

10
10
10

12.5
12.5
12.5
12.5

8
8

10
10
10

12.5
12.5
12.5
12.5

10
10

12.5
12.5
12.5

10
10

12.5 16
12.5 16
12.5 16
16

10

12.5 16
12.5 16
16

10

12.5 16
12.5 16
16

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

5000
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50

6300
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63

800
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

1000
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

1250
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

1600
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

12
12
12

15
15
15
15

12
12
12

15
15
15
15

12
12

15
15
15

12
12

15
15
15

18.7
18.7
18.7
18.7

12
12

15
15
15

18.7
18.7
18.7
18.7

12

15
15

18.7
18.7
18.7

12

15
15

18.7 24
18.7 24
18.7 24
24

15

18.7 24
18.7 24
24

15

18.7 24
18.7 24
24

2000
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

2500
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
40
40
40
40
40
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
40
40
40
40
40
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
40
40
40
40
40
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

3200
48
48
48
48
48
48
48
48
48
48
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48

4000
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
60
60
60
60

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
75

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
94.5
94.5
94.5
94.5
94.5

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: NS630b to NS3200

Complementary
technical information

Upstream

Masterpact NW N1 - H1 - H2

Trip unit

Micrologic 5.0-6.0-7.0 - Inst: OFF

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63
Rating (A) 800
1000 1250 1600 2000 2500 3200 4000 5000 6300
Downstream
NS630bN

NS630bH

NS630bL

NS800N

NS800H

NS800L

NS1000N

NS1000H

NS1000L

NS1250N

NS1250H

NS1600N

NS1600H

NS1600b/3200
N/H

Schneider Electric

Setting Ir
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
640
800
960
1280
1600
640
800
960
1280
1600
1250
1600
2000
2500
3200

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

73

Protection discrimination
Upstream: Masterpact NW
Downstream: NS630b to NS3200

Complementary
technical information

Upstream

Masterpact NW H3

Masterpact NW H3

Masterpact NW H3

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

NW20
Rating (A) 2000
Downstream Setting Ir
NS630bN
250
320
400
500
630
NS630bH
250
320
400
500
630
NS630bL
250
320
400
500
630
NS800N
320
400
500
630
800
NS800H
320
400
500
630
800
NS800L
320
400
500
630
800
NS1000N
400
500
630
800
1000
NS1000H
400
500
630
800
1000
NS1000L
400
500
630
800
1000
NS1250N
500
630
800
1000
1250
NS1250H
500
630
800
1000
1250
NS1600N
640
800
960
1280
1600
NS1600H
640
800
960
1280
1600
NS1600b/3200 1250
N/H
1600
2000
2500
3200

74

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

NW25
2500

NW32
3200

NW40
4000

NW20
2000

NW25
2500

NW32
3200

NW40
4000

NW20
2000

NW25
2500

NW32
3200

NW40
4000

2500
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2000
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

2500
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
40
40
40
40
40
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
40
40
40
40
40
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
40
40
40
40
40
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

3200
48
48
48
48
48
48
48
48
48
48
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48

4000
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
60
60
60
60
60
60
60
60
60

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65

30
30
30
30
30

T
T
T
T
65

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: NS630b to NS3200

Complementary
technical information

Upstream

Masterpact NW L1

Masterpact NW L1

Masterpact NW L1

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In

Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF

Rating (A)

NW08
800

NW10
1000

NW12
1250

NW16
1600

NW20
2000

NW08
800

NW10
1000

NW12
1250

NW16
1600

NW20
2000

NW08
800

NW10
1000

NW12
1250

NW16
1600

NW20
2000

800
8
8
8
8

1000
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1250
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

800
12
12
12
12

1000
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

1250
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

1600
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

2000
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

800
37
37
37
37

1000
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37

1250
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37

1600
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37

2000
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
37
37
37
37
37
37
37
37
37
37
37
37
37
37

Downstream Setting Ir
NS630bN
250
320
400
500
630
NS630bH
250
320
400
500
630
NS630bL
250
320
400
500
630
NS800N
320
400
500
630
800
NS800H
320
400
500
630
800
NS800L
320
400
500
630
800
NS1000N
400
500
630
800
1000
NS1000H
400
500
630
800
1000
NS1000L
400
500
630
800
1000
NS1250N
500
630
800
1000
1250
NS1250H
500
630
800
1000
1250
NS1600N
640
800
960
1280
1600
NS1600H
640
800
960
1280
1600
NS1600b/3200 1250
N/H
1600
2000
2500
3200
Schneider Electric

8
8
8
8
8
8
8
8
8
8
8

8
8
8

10
10
10
10

8
8
8

10
10
10
10

8
8

10
10
10

8
8

10
10
10

12.5
12.5
12.5
12.5

8
8

10
10
10

12.5
12.5
12.5
12.5

10
10

12.5
12.5
12.5

10
10

12.5
12.5
12.5

16
16
16
16

10

12.5
12.5

16
16
16

10

12.5
12.5

16
16
16

20
20
20
20
20

12
12
12
12
12
12
12
12
12
12
12

12
12
12

15
15
15
15

12
12
12

15
15
15
15

12
12

15
15
15

12
12

15
15
15

18.7
18.7
18.7
18.7

12
12

15
15
15

18.7
18.7
18.7
18.7

12

15
15

18.7
18.7
18.7

12

15
15

18.7
18.7
18.7

24
24
24
24

15

18.7
18.7

24
24
24

15

18.7
18.7

24
24
24

30
30
30
30
30

37
37
37
37
T
T
T
T
37
37
37

37
37
37

37
37
37
37

T
T
T

T
T
T
T

37
37

37
37
37

37
37

37
37
37

37
37
37
37

T
T

T
T
T

T
T
T
T

37

37
37

37
37
37

37

37
37

37
37
37

37
37
37
37

37

37
37

37
37
37

37

37
37

37
37
37

37
37
37
37
37

75

Protection discrimination
Upstream: Masterpact NW
Downstream: C801 to C1251, CM

Complementary
technical information

Upstream

Masterpact NW N1 - H1 - H2

Masterpact NW N1 - H1 - H2

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0 - 6.0 - 7.0 - Inst: 15 In

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

Downstream
C801N

C801H

C801L

C1001N

C1001H

C1001L

C1251N

C1251H

CM
N/H

76

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300 800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
1250
1600
2000
2500
3200

800
8
8
8

1000
10
10
10
10

1000
15
15
15
15

8
8
8

10
10
10
10

8
8
8

10
10
10
10
10
10
10

1250
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

10
10
10

12.5
12.5
12.5
12.5

10
10
10

12.5
12.5
12.5
12.5
12.5
12.5
12.5

1600
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

12.5 16
12.5 16
12.5 16
16

2000
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

5000
T
T
T
T
T
50
50
50
50
50
70
70
70
70
70
T
T
T
T
T
50
50
50
50
50
70
70
70
70
70
T
T
T
T
T
50
50
50
50
50

6300
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63

800
12.5
12.5
12.5

12.5 15
12.5 15
12.5 15
15
12.5 15
12.5 15
12.5 15
15
15
15
15

1250
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

15
15
15

18.7
18.7
18.7
18.7

15
15
15

18.7
18.7
18.7
18.7
18.7
18.7
18.7

1600
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

18.7 24
18.7 24
18.7 24
24

2000
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

2500
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

3200
48
48
48
48
48
48
48
48
48
48
60
60
60
60
60
48
48
48
48
48
48
48
48
48
48
60
60
60
60
60
48
48
48
48
48
48
48
48
48
48

4000
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: C801 to C1251, CM

Complementary
technical information

Upstream
Trip unit

Masterpact NW N1 - H1 - H2
Micrologic 5.0 - 6.0 - 7.0 - Inst: OFF
NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

Downstream
C801N

C801H

C801L

C1001N

C1001H

C1001L

C1251N

C1251H

CM
N/H

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
1250
1600
2000
2500
3200

800
T
T
T

1000
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

Schneider Electric

T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T
T
T
T

T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

77

Protection discrimination
Upstream: Masterpact NW
Downstream: C801 to C1251, CM

Complementary
technical information

Downstream
C801N

C801H

C801L

C1001N

C1001H

C1001L

C1251N

C1251H

CM
N/H

78

Upstream

Masterpact NW H3

Masterpact NW H3

Masterpact NW H3

Trip unit

Micrologic 2.0

Micrologic 5.0 - 6.0 - 7.0

Micrologic 5.0 - 6.0 - 7.0

Isd: 10 Ir

Inst: 15 In

Inst: OFF

NW20

NW25

NW32

NW40

NW20

NW25

NW32

NW40

NW20

NW25

NW32

NW40

Rating (A)

2000

2500

3200

4000

2000

2500

3200

4000

2000

2500

3200

4000

Setting Ir
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
1250
1600
2000
2500
3200

2000
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40

20
20
20
20
20

25
25
25
25
25

32
32
32
32
32

40
40
40
40
40

20
20
20
20
20

25
25
25
25
25

32
32
32
32
32

40
40
40
40
40

2000
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

2500
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

3200
48
48
48
48
48
48
48
48
48
48
60
60
60
60
60
48
48
48
48
48
48
48
48
48
48
60
60
60
60
60
48
48
48
48
48

4000
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: C801 to C1251, CM

Complementary
technical information

Upstream

Masterpact NW L1

Masterpact NW L1

Masterpact NW L1

Trip unit

Micrologic 2.0

Micrologic 5.0 - 6.0 - 7.0

Micrologic 5.0 - 6.0 - 7.0

Isd: 10 Ir
Downstream
C801N

C801H

C801L

C1001N

C1001H

C1001L

C1251N

C1251H

CM
N/H

Inst: 15 In

Inst: OFF

NW08

NW10

NW12

NW16

NW20

NW08

NW10

NW12

NW16

NW20

NW08

NW10

NW12

NW16

NW20

Rating (A)

800

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

Setting Ir
320
400
500
630
800
320
400
500
630
800
320
400
500
630
800
400
500
630
800
1000
400
500
630
800
1000
400
500
630
800
1000
500
630
800
1000
1250
500
630
800
1000
1250
1250
1600
2000
2500
3200

800
8
8
8

1000
10
10
10
10

2000
20
20
20
20
20
20
20
20
20
20

1000
15
15
15
15
15
15
15
15

50
50
50
50

15
15
15
15

2000
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

50
50
50

12
12
12

1600
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

1000
T
T
T
T

12
12
12

1250
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

800
T
T
T

10
10
10
10

1600
16
16
16
16
16
16
16
16
16
16

800
12
12
12

8
8
8

1250
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

90
90
90

90
90
90
90

1250
T
T
T
T
T
50
50
50
50
50
90
90
90
90
90
T
T
T
T

1600
T
T
T
T
T
50
50
50
50
50
90
90
90
90
90
T
T
T
T
T
50
50
50
50
50
90
90
90
90
90
50
50
50
50

2000
T
T
T
T
T
50
50
50
50
50
90
90
90
90
90
T
T
T
T
T
50
50
50
50
50
90
90
90
90
90
50
50
50
50
50

Schneider Electric

10
10
10

12.5
12.5
12.5
12.5

12.5
12.5
12.5

16
16
16
16
16

16
16
16
16

20
20
20
20
20

20
20
20
20
20

15
15
15

15
15
15

18.7
18.7
18.7
18.7

15
15
15

18.7
18.7
18.7
18.7
18.7
18.7
18.7

T
T
T

50
50
50

50
50
50
50

90
90
90

90
90
90
90
50
50
50

79

Protection discrimination
Upstream: Masterpact NW
Downstream: Masterpact NT, NW,
Masterpact M

Complementary
technical information

Upstream

Masterpact NW N1 - H1 - H2

Masterpact NW N1 - H1 - H2

Trip unit

Micrologic 2.0 - Isd: 10 Ir

Micrologic 5.0-6.0-7.0 - Inst: 15 In

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300 800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20
M08
M10
M12
M16
M20
M25
M32
M40
M50
M63
M08
M10
M12
M16
M20
M25
M32
M40
M50
M63
M08
M10
M12
M16
M20
M25

800

1000 1250 1600


10
12
16
12
16
16

2000
20
20
20
20

1000 1250 1600


15
18.7 24
18.7 24
24

2000
30
30
30
30

10

16
16
16
16
16

20
20
20
20
20
20

15

18.7 24
18.7 24
24
18.7 24
24

35
35
35
30
30
30

12

16
16

12

NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

Downstream
Masterpact NT
H1

Masterpact NT
L1
Masterpact NW
N1/H1

Masterpact NW
H2/H3

Masterpact NW
L1

Masterpact
N1/H1

Masterpact
H2

Masterpact
L1

80

2500
25
25
25
25
25
26
26
26
25
25
25
25

3200
32
32
32
32
32
45
45
45
32
32
32
32
32

4000
40
40
40
40
40
T
T
T
40
40
40
40
40
40

5000
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50

6300 800
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63

20
20
20

25
25
25
25

32
32
32
32
32

40
40
40
40
40
40

50
50
50
50
50
50
50

63
63
63
63
63
63
63
63

18.7 24
24

16
16

20
20
20

25
25
25
25

12

16
16

20
20
20

25
25
25
25

32
32
32
32
32
32
32
32
32
32

40
40
40
40
40
40
40
40
40
40
40

50
50
50
50
50
50
50
50
50
50
50
50

63
63
63
63
63
63
63
63
63
63
63
63
63

12

16
16

20
20
20

25
25
25
25

32
32
32
32
32

40
40
40
40
40
40

50
50
50
50
50
50
50

63
63
63
63
63
63
63
63

12
12
12

2500
37.5
37.5
37.5
37.5
37.5
65
65
65
37.5
37.5
37.5
37.5

3200
T
T
T
T
T
T
T
T
48
48
48
48
48

4000
T
T
T
T
T
T
T
T
60
60
60
60
60
60

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

30
30
30

37.5
37.5
37.5
37.5

48
48
48
48
48

60
60
60
60
60
60

75
75
75
75
75
75
75

82
82
82
82
82
82
82
82

18.7 24
24

30
30
30

37.5
37.5
37.5
37.5

18.7 24
24

30
30
30

37.5
37.5
37.5
37.5

48
48
48
48
48
48
48
48
48
48

60
60
60
60
60
60
60
60
60
60
60

75
75
75
75
75
T
T
T
T
T
T
T

94.5
94.5
94.5
94.5
94.5
T
T
T
T
T
T
T
T

18.7 24
24

30
30
30

37.5
37.5
37.5
37.5

48
48
48
48
48

60
60
60
60
60
60

75
75
75
75
75
75
75

85
85
85
85
85
85
85
85

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: Masterpact NT, NW,
Masterpact M

Complementary
technical information

Upstream
Trip unit

Masterpact NW N1 - H1 - H2
Micrologic 5.0-6.0-7.0 - Inst: OFF
NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63

Downstream
Masterpact NT
H1

Masterpact NT
L1
Masterpact NW
N1/H1

Masterpact NW
H2/H3

Masterpact NW
L1

Masterpact
N1/H1

Masterpact
H2

Masterpact
L1

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20
M08
M10
M12
M16
M20
M25
M32
M40
M50
M08
M10
M12
M16
M20
M25
M32
M40
M50
M63
M08
M10
M12
M16
M20
M25

800

1000 1250 1600


T
T
T
T
T
T

2000
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

85

85
85

Schneider Electric

2500
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

85
85
85

85
85
85
85

85
85
85
85
85

85
85
85
85
85
85

T
T
T
T
100
100
100

T
T
T
T
100
100
100
100

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

85

85
85

85
85
85

85
85
85
85

85
85
85
85
85

85
85
85
85
85
85

85
85
85
85
85
85
85

85
85
85
85
85
85
85
85

T
T
T

81

Protection discrimination
Upstream: Masterpact NW
Downstream: Masterpact NT, NW,
Masterpact M

Complementary
technical information

Downstream

Upstream

Masterpact NW H3

Masterpact NW H3

Masterpact NW H3

Trip unit

Micrologic 2.0

Micrologic 5.0 - 6.0 - 7.0

Micrologic 5.0 - 6.0 - 7.0

Isd: 10 Ir

Inst: 15 In

Rating (A)

Setting Ir
Masterpact NT NT06
H1
NT08
NT10
NT12
NT16
Masterpact NT NT06
L1
NT08
NT10
Masterpact NW NW08
N1/H1
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
Masterpact NW NW08
H2/H3
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
Masterpact NW NW08
L1
NW10
NW12
NW16
NW20
Masterpact
M08
N1/H1
M10
M12
M16
M20
M25
M32
M40
M50
M63
Masterpact
M08
H2
M10
M12
M16
M20
M25
M32
M40
M50
M63
Masterpact
M08
L1
M10
M12
M16
M20
M25

82

Inst: OFF

NW20

NW25

NW32

NW40

NW20

NW25

NW32

NW40

NW20

NW25

NW32

NW40

2000

2500

3200

4000

2000

2500

3200

4000

2000

2500

3200

4000

2000
20
20
20
20

2500
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2000
30
30
30
30

2500
37.5
37.5
37.5
37.5
37.5
65
65
65
37.5
37.5
37.5
37.5

3200
T
T
T
T
T
110
110
110
48
48
48
48
48

4000
T
T
T
T
T
T
T
T
60
60
60
60
60
60

2000
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T

20
20
20

25
25
25
25

32
32
32
32
32

40
40
40
40
40
40

30
30
30

37.5
37.5
37.5
37.5

48
48
48
48
48

60
60
60
60
60
60

65
65
65

65
65
65
65

65
65
65
65
65

65
65
65
65
65
65

20
20
20

25
25
25
25

32
32
32
32
32
32
32
32
32
32

45
45
45
45
45
40
40
40
40
40
40

30
30
30

37.5
37.5
37.5
37.5

48
48
48
48
48
48
48
48
48
48

60
60
60
60
60
60
60
60
60
60
60

100
100
100

100
100
100
100

100
100
100
100
100
T
T
T
T
T

100
100
100
100
100
T
T
T
T
T
T

32
32
32
32
32

40
40
40
40
40
40

48
48
48
48
48

60
60
60
60
60
60

65
65
65
65
65

65
65
65
65
65
65

20
20
20
20
20
20

25
25
25
25

25
25
25
25

35
35
35
30
30
30

37.5
37.5
37.5
37.5

37.5
37.5
37.5
37.5

T
T
T
T
T
T

T
T
T
T

65
65
65
65

Schneider Electric

Protection discrimination
Upstream: Masterpact NW
Downstream: Masterpact NT, NW,
Masterpact M

Complementary
technical information

Upstream

Masterpact NW L1

Masterpact NW L1

Masterpact NW L1

Trip unit

Micrologic 2.0

Micrologic 5.0 - 6.0 - 7.0

Micrologic 5.0 - 6.0 - 7.0

Isd: 10 Ir
Downstream

Rating (A)

Setting Ir
Masterpact NT NT06
H1
NT08
NT10
NT12
NT16
Masterpact NT NT06
L1
NT08
NT10
Masterpact NW NW08
N1/H1
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
Masterpact NW NW08
H2/H3
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
Masterpact NW NW08
L1
NW10
NW12
NW16
NW20
Masterpact
M08
N1/H1
M10
M12
M16
M20
M25
M32
M40
M50
M63
Masterpact
M08
H2
M10
M12
M16
M20
M25
M32
M40
M50
M63
Masterpact
M08
L1
M10
M12
M16
M20
M25

Schneider Electric

Inst: 15 In

Inst: OFF

NW08

NW10

NW12

NW16

NW20

NW08

NW10

NW12

NW16

NW20

NW08

NW10

NW12

NW16

NW20

800

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000
10

1250
12.5
12.5

1600
16
16
16

2000
20
20
20
20

800

1000
15

1250
18.7
18.7

1600
24
24
24

2000
30
30
30
30

800

1000
37

1250
37
37

1600
37
37
37

2000
37
37
37
37

10

12.5
12.5

16
16
16
16
16

20
20
20
20
20
20

15

18.7
18.7

24
24
24
24
24

30
30
30
30
30
30

T
T

T
T
T
37
37

T
T
T
37
37
37

12.5

16
16

20
20
20

18.7

24
24

30
30
30

37

37
37

37
37
37

12.5

16
16

20
20
20

18.7

24
24

30
30
30

37

37
37

37
37
37

12.5

16
16

20
20
20

18.7

24
24

30
30
30

37

37
37

37
37
37

12.5

16
16

20
20
20

18.7

24
24

30
30
30

37

37
37

37
37
37

12.5

16
16

20
20
20

18.7

24
24

30
30
30

37

37
37

37
37
37

12.5

18.7

37

83

Protection discrimination
Upstream: Masterpact M
Downstream: Multi 9, NS100 to 630,
NSC100N, NSA160, NB225 to 600

Complementary
technical information

Upstream
Downstream
DPN, DPN N
XC40
C60
NC100
NC125
NG125N/H/L
C120N/H
NS100N/H/L
NS160N/H/L
NS250N/H/L
NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

NSC100N
NS125E
NSA160N
NB225N
NB400N
NB600N

84

Masterpact N1 - H1 - H2

Masterpact N1 - H1 - H2

Trip unit STR28D

Trip unit STR38S - 58U - Inst: ON - position maxi

Rating (A)

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63

Setting Ir

800
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70
T
T
T
T
T
45
45
45
45
45
45
45
45
45
45

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
70
70
70
70
70

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

Schneider Electric

Protection discrimination
Upstream: Masterpact M
Downstream: Multi 9, NS100 to 630,
NSC100N, NSA160, NB225 to 600
Upstream
Downstream
DPN, DPN N
XC40
C60
NC100
NC125
NG125
C120
NS100N/H/L
NS160N/H/L
NS250N/H/L
NS400N

NS400H

NS400L

NS630N

NS630H

NS630L

Masterpact N1 - H1 - H2

Masterpact N1 - H1

Trip unit STR68U - Inst: ON - position maxi

Trip unit STR38S - 58U - Inst: OFF

Rating (A)

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63

Setting Ir

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

160
200
250
320
400
160
200
250
320
400
160
200
250
320
400
250
320
400
500
630
250
320
400
500
630
250
320
400
500
630

NSC100N
NS125E
NSA160N
NB225N
NB400N
NB600N

Schneider Electric

85

Complementary
technical information

Upstream

Masterpact N1 - H1
Trip unit STR68U - Inst: OFF
Downstream Rating (A) M08 M10 M12 M16 M20 M25
Setting Ir 800 1000 1250 1600 2000 2500
DPN, DPN N
T
T
T
T
T
T
XC40
T
T
T
T
T
T
C60
T
T
T
T
T
T
NC100/125
T
T
T
T
T
T
NG125
T
T
T
T
T
T
C120
T
T
T
T
T
T
y 32
NS100N
T
T
T
T
T
T
Trip unit TM-D 40
T
T
T
T
T
T
50
T
T
T
T
T
T
63
T
T
T
T
T
T
80
T
T
T
T
T
T
100
T
T
T
T
T
T
y 32
NS100H/L
T
T
T
T
T
T
Trip unit TM-D 40
T
T
T
T
T
T
50
T
T
T
T
T
T
63
T
T
T
T
T
T
80
T
T
T
T
T
T
100
T
T
T
T
T
T
y 63
NS160N
T
T
T
T
T
T
Trip unit TM-D 80
T
T
T
T
T
T
100
T
T
T
T
T
T
125
T
T
T
T
T
T
160
T
T
T
T
T
T
y 63
NS160H/L
T
T
T
T
T
T
Trip unit TM-D 80
T
T
T
T
T
T
100
T
T
T
T
T
T
125
T
T
T
T
T
T
160
T
T
T
T
T
T
y 100
NS250N
T
T
T
T
T
T
Trip unit TM-D 125
T
T
T
T
T
T
160
T
T
T
T
T
T
200
T
T
T
T
T
T
250
T
T
T
T
T
T
NS250H/L
T
T
T
T
T
T
y 100
Trip unit TM-D 125
T
T
T
T
T
T
160
T
T
T
T
T
T
200
T
T
T
T
T
T
250
T
T
T
T
T
T
NS100N
40
T
T
T
T
T
T
Trip unit STR22SE 100
T
T
T
T
T
T
NS100H/L
40
T
T
T
T
T
T
Trip unit STR22SE 100
T
T
T
T
T
T
NS160N
40
T
T
T
T
T
T
Trip unit STR22SE 100
T
T
T
T
T
T
160
T
T
T
T
T
T
NS160H/L
40
T
T
T
T
T
T
Trip unit STR22SE 100
T
T
T
T
T
T
160
T
T
T
T
T
T
y 100
NS250N
T
T
T
T
T
T
Trip unit STR22SE 160
T
T
T
T
T
T
250
T
T
T
T
T
T
y 100
NS250H/L
T
T
T
T
T
T
Trip unit STR22SE 160
T
T
T
T
T
T
250
T
T
T
T
T
T
NS400N/H/L
160
T
T
T
T
T
T
200
T
T
T
T
T
T
250
T
T
T
T
T
T
320
T
T
T
T
T
T
400
T
T
T
T
T
T
NS630N/H/L
250
T
T
T
T
T
T
320
T
T
T
T
T
T
400
T
T
T
T
T
T
500
T
T
T
T
T
T
630
T
T
T
T
T
T

Masterpact L
Trip unit STR38S - 58U
M32 M40 M50 M63 M08 M10 M12 M16 M20
3200 4000 5000 6300 800 1000 1250 1600 2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
7
9
9
T
T
T
T
T
T
7
9
9
T
T
T
T
T
T
7
9
9
T
T
T
T
T
T
7
9
9
T
T
T
T
T
T
7
9
9
T
T
T
T
T
T
7
9
9
T
T
T
T
T
T
7
9
9
35
35
T
T
T
T
7
9
9
35
35
T
T
T
T
7
9
9
35
35
T
T
T
T
7
9
9
35
35
T
T
T
T
7
9
9
35
35
T
T
T
T
7
9
9
35
35
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
30
30
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
7
9
9
25
25
T
T
T
T
8
10
10
T
T
T
T
T
T
8
10
10
T
T
T
T
T
T
8
10
10
35
35
T
T
T
T
8
10
10
35
35
T
T
T
T
8
10
10
30
30
T
T
T
T
8
10
10
30
30
T
T
T
T
8
10
10
30
30
T
T
T
T
8
10
10
30
30
T
T
T
T
8
10
10
30
30
T
T
T
T
8
10
10
30
30
T
T
T
T
8
10
10
25
25
T
T
T
T
8
10
10
25
25
T
T
T
T
8
10
10
25
25
T
T
T
T
8
10
10
25
25
T
T
T
T
8
10
10
25
25
T
T
T
T
8
10
10
25
25
T
T
T
T
8
10
10
12
12
T
T
T
T
8
10
10
12
12
T
T
T
T
8
10
10
12
12
T
T
T
T
8
10
10
12
12
T
T
T
T
8
10
10
12
12
T
T
T
T
10
10
10
10
T
T
T
T
10
10
10
10
T
T
T
T
10
10
10
10
T
T
T
T
10
10
10
10
T
T
T
T
10
10
10
10

Masterpact L
Trip unit STR68U
M25 M08 M10 M12 M16
2500 800 1000 1250 1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
T
T
25
25
25
T
T
25
25
25
T
T
25
25
25
T
T
25
25
25
T
T
25
25
25
T
60
25
25
25
50
60
25
25
25
50
60
25
25
25
50
60
25
25
25
50
60
25
25
25
50
60
25
25
25
50
T
18
18
18
T
T
18
18
18
T
T
18
18
18
T
T
18
18
18
T
T
18
18
18
T
50
18
18
18
40
50
18
18
18
40
50
18
18
18
40
50
18
18
18
40
50
18
18
18
40
T
16
16
16
T
T
16
16
16
T
T
16
16
16
T
T
16
16
16
T
T
16
16
16
T
36
16
16
16
36
36
16
16
16
36
36
16
16
16
36
36
16
16
16
36
36
16
16
16
36
T
25
25
25
T
T
25
25
25
T
60
25
25
25
50
60
25
25
25
50
T
18
18
18
T
T
18
18
18
T
T
18
18
18
T
50
18
18
18
40
50
18
18
18
40
50
18
18
18
40
T
16
16
16
T
T
16
16
16
T
T
16
16
16
T
36
16
16
16
36
36
16
16
16
36
36
16
16
16
36
18
8
10
10
12
18
8
10
10
12
18
8
10
10
12
18
8
10
10
12
18
8
10
10
12
12
8
10
10
12
12
8
10
10
12
12
8
10
10
12
12
8
10
10
12
12
8
10
10
12

M20
2000
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
36
36
36
36
36
T
T
50
50
T
T
T
40
40
40
T
T
T
36
36
36
12
12
12
12
12
12
12
12
12
12

M25
2500
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
T
T
T
T
T
40
40
40
40
40
T
T
T
T
T
36
36
36
36
36
T
T
50
50
T
T
T
40
40
40
T
T
T
36
36
36
12
12
12
12
12
12
12
12
12
12

NSC100N
NS125E
NSA160N

T
T
T
T
T
T
T

T
T
T
T
T
18
12

T
T
T
T
T
12
12

T
T
T
T
T
12
12

NB225N
NB400N
NB600N

86

y 50
u 50

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
7
T
10
7
8

T
9
T
15
9
10
10

T
9
T
15
9
10
10

T
T
T
T
25
12
10

T
T
T
T
25
12
10

T
T
T
T
16
8

T
T
T
T
16
10
10

T
T
T
T
16
10
10

T
T
T
T
T
12
12

Schneider Electric

Protection discrimination
Upstream: Masterpact M
Downstream: NS630b to NS3200

Complementary
technical information

Upstream

Masterpact N1 - H1 - H2

Masterpact N1 - H1 - H2

Trip unit

STR28D

STR38S/58U - Inst: ON - position maxi

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63
Downstream
NS630bN

Rating (A)
250
320
400
500
630
NS630bH
250
320
400
500
630
NS630bL
250
320
400
500
630
NS800N
320
400
500
630
800
NS800H
320
400
500
630
800
NS800L
320
400
500
630
800
NS1000N
400
500
630
800
1000
NS1000H
400
500
630
800
1000
NS1000L
400
500
630
800
1000
NS1250N
500
630
800
1000
1250
NS1250H
500
630
800
1000
1250
NS1600N
640
800
960
1280
1600
NS1600H
640
800
960
1280
1600
NS1600b/3200 1250
N/H
1600
2000
2500
3200

Schneider Electric

800
8
8
8
8
8
8
8
8
8
8
8
8

1000
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1250
12
12
12
12
12
12
12
12
12
12
16
16
16
16
16
12
12
12
12
12
12
12
12
12
12
16
16
16
16
16
12
12
12
12
12
12
12
12
12
12
12
12

1600
16
16
16
16
16
16
16
16
16
16
30
30
30
30
30
16
16
16
16
16
16
16
16
16
16
30
30
30
30
30
16
16
16
16
16
16
16
16
16
16
18
18
18
18
18
16
16
16
16
16
16
16
16

2000
20
20
20
20
20
20
20
20
20
20
45
45
45
45
45
20
20
20
20
20
20
20
20
20
20
45
45
45
45
45
20
20
20
20
20
20
20
20
20
20
31
31
31
31
31
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

2500
25
25
25
25
25
25
25
25
25
25
90
90
90
90
90
25
25
25
25
25
25
25
25
25
25
90
90
90
90
90
25
25
25
25
25
25
25
25
25
25
54
54
54
54
54
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
T
T
T
T
T
32
32
32
32
32
32
32
32
32
32
T
T
T
T
T
32
32
32
32
32
32
32
32
32
32
T
T
T
T
T
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

5000
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
50
50
50
50
50

6300 800
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
63
63
63
63
63

1000
28
28
28
28
28
28
28
28
28
28
70
70
70
70
70
28
28
28
28
28
28
28
28
70
70
70
70

1250
28
28
28
28
28
28
28
28
28
28
70
70
70
70
70
28
28
28
28
28
28
28
28
28
28
70
70
70
70
70
28
28
28
28
28
28
28
28
70
70
70
70

1600
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2000
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

2500
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

3200
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

4000
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

5000
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50

6300
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63

87

Protection discrimination
Upstream: Masterpact M
Downstream: NS630b to NS3200

Complementary
technical information

Downstream
NS630bN

Upstream
Trip unit

Masterpact N1 - H1 - H2
STR68U - Inst: ON - position maxi

Rating (A)

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63
800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
250
320
400
500
630
NS630bH
250
320
400
500
630
NS630bL
250
320
400
500
630
NS800N
320
400
500
630
800
NS800H
320
400
500
630
800
NS800L
320
400
500
630
800
NS1000N
400
500
630
800
1000
NS1000H
400
500
630
800
1000
NS1000L
400
500
630
800
1000
NS1250N
500
630
800
1000
1250
NS1250H
500
630
800
1000
1250
NS1600N
640
800
960
1280
1600
NS1600H
640
800
960
1280
1600
NS1600b/3200 1250
N/H
1600
2000
2500
3200

88

800

1000
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T

1250
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
T
T
T
T

1600
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
40
40
40
40
40
40
40
40

2000
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
65
65
65
65
40

2500
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
65
65
65
65
65
40
40

Masterpact N1 - H1
STR38S/58U - Inst: OFF

3200
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
65
65
65
65
65
40
40
40

4000
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
65
65
65
65
65
40
40
40
40

5000
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
65
65
65
65
65
50
50
50
50
50

6300
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
65
65
65
65
65
63
63
63
63
63

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T
T
T
T

T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: Masterpact M
Downstream: NS630b to NS3200

Complementary
technical information

Upstream
Trip unit

Masterpact N1 - H1
STR68U - Inst: OFF

Masterpact L
STR38S/58U

Masterpact L
STR68U

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25
Rating (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500
Downstream
NS630bN

Setting Ir
250
320
400
500
630
NS630bH
250
320
400
500
630
NS630bL
250
320
400
500
630
NS800N
320
400
500
630
800
NS800H
320
400
500
630
800
NS800L
320
400
500
630
800
NS1000N
400
500
630
800
1000
NS1000H
400
500
630
800
1000
NS1000L
400
500
630
800
1000
NS1250N
500
630
800
1000
1250
NS1250H
500
630
800
1000
1250
NS1600N
640
800
960
1280
1600
NS1600H
640
800
960
1280
1600
NS1600b/3200 1250
N/H
1600
2000
2500
3200

Schneider Electric

800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T
T
T
T

T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300 800 1000


T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
10
T
T
10
T
10
T
10
T
10
T
T
10
T
10
T
10
T
10
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1250
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1600
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
12

12
12
12

2000
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
15

2500 800 1000


15
10
15
10
15
10
15
10
15
10
15
10
15
10
15
10
15
10
15
10
25
10
25
10
25
10
25
10
25
10
15
10
15
10
15
10
15
10
15
15
10
15
10
15
10
15
10
15
25
10
25
10
25
10
25
10
25
15
15
15
15
15
15
15
15
15
15
25
25
25
25
25
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

1250
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1600
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
12

12
12
12

2000
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
15

2500
15
15
15
15
15
15
15
15
15
15
25
25
25
25
25
15
15
15
15
15
15
15
15
15
15
25
25
25
25
25
15
15
15
15
15
15
15
15
15
15
25
25
25
25
25
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

89

Protection discrimination
Upstream: Masterpact M
Downstream: Masterpact NT, NW

Complementary
technical information

Upstream Masterpact N1 - H1 - H2

Masterpact N1 - H1 - H2

Trip unit

STR38S/58U - Inst: ON - position maxi

STR28D

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63
Downstream
Masterpact NT
N1/H1

Masterpact NT
L1
Masterpact NW
N1/H1/H2/H3

Masterpact NW
L1

Rating (A) 800

1000 1250 1600 2000 2500 3200 4000 5000 6300 800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20

1000 1250 1600


10
12
16
12
16
16

2000
20
20
20
20

1000 1250 1600


28
28
40
28
40
40

2000
40
40
40
40

10

16
16
16
12.5 16
16

20
20
20
20
20
20

70

120
120
120
40
40

120
120
120
40
40
40

12.5 16
16

20
20
20

70
70

70
70
70

800

12
12

2500
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40
40
40
40
40

5000
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50

6300 800
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63

25
25
25
25

32
32
32
32
32

40
40
40
40
40

50
50
50
50
50

63
63
63
63
63

70
70
28

30

Upstream Masterpact N1 - H1 - H2

Masterpact N1 - H1

Trip unit

STR38S/58 - Inst: OFF

STR68U - Inst: ON - position maxi

2500
40
40
40
40
40
120
120
120
40
40
40
40

3200
40
40
40
40
40
120
120
120
40
40
40
40
40

4000
40
40
40
40
40
120
120
120
40
40
40
40
40
40

5000
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50

6300
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63

70
70
70
70

70
70
70
70
70

70
70
70
70
70

T
T
T
T
T

T
T
T
T
T

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63
Downstream
Masterpact NT
N1/H1

Masterpact NT
L1
Masterpact NW
N1/H1/H2/H3

Masterpact NW
L1

90

Rating (A) 800

1000 1250 1600 2000 2500 3200 4000 5000 6300 800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir 800
NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20

1000 1250 1600


40
40
40
40
40
40

2000
T
T
T
T

1000 1250 1600


T
T
T
T
T
T

2000
T
T
T
T

T
T
T
40
40

T
T
T
65
65
65

T
T
T
T
T

T
T
T
T
T
T

40
40

95
95
95

T
T

T
T
T

T
T
40

40

2500
T
T
T
T
T
T
T
T
65
65
65
65

3200
T
T
T
T
T
T
T
T
65
65
65
65
65

4000
T
T
T
T
T
T
T
T
65
65
65
65
65
65

5000
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65

6300 800
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
65

95
95
95
95

95
95
95
95
95

95
95
95
95
95

95
95
95
95
95

95
95
95
95
95

T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

Schneider Electric

Protection discrimination
Upstream: Masterpact M
Downstream: Masterpact NT, NW

Complementary
technical information

Upstream Masterpact N1 - H1

Masterpact L

Masterpact L

Trip unit

STR38S/58U

STR68U

STR68U - Inst: OFF

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25
Rating (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500
Downstream
Setting Ir
Masterpact NT NT06
N1/H1
NT08
NT10
NT12
NT16
Masterpact NT NT06
L1
NT08
NT10
Masterpact NW NW08
N1/H1/H2/H3
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
Masterpact NW NW08
L1
NW10
NW12
NW16
NW20

Schneider Electric

800 1000 1250 1600


T
T
T
T
T
T

T
T
T

2000
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300 800 1000


T
10
T
T
T
T
T
10
T
T
T
T
T
T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

1250 1600 2000


10
12
12
10
12
12
12
12
12
10
10

15
15
15

15
15
15

2500 800 1000


15
10
15
15
15
15
25
10
25
25

1250 1600 2000


10
12
12
10
12
12
12
12
12
10
10

15
15
15

15
15
15

2500
15
15
15
15
15
25
25
25

91

Complementary
technical information

Upstream
Downstream

Rating (A)

Masterpact N1 - H1 - H2

Masterpact N1 - H1 - H2

Trip unit STR28D (1)

Trip unit STR38S - 58U - Inst: ON - position maxi

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63

Setting Ir
800 1000 1250 1600 2000
320
10
12
16
20
400
10
12
16
20
500
10
12
16
20
630
10
12
16
20
800
12
16
20
C801H
320
10
12
16
20
Trip unit
400
10
12
16
20
STR25DE,
500
10
12
16
20
35SE/GE, 55UE 630
10
12
16
20
800
12
16
20
C801L
320
10
12
16
20
Trip unit
400
10
12
16
20
STR25DE,
500
10
12
16
20
35SE/GE, 55UE 630
10
12
16
20
800
12
16
20
C1001N
400
12
16
20
Trip unit
500
12
16
20
STR25DE,
630
12
16
20
35SE/GE, 55UE 800
12
16
20
1000
16
20
C1001H
400
12
16
20
Trip unit
500
12
16
20
STR25DE,
630
12
16
20
35SE/GE, 55UE 800
12
16
20
1000
16
20
C1001L
400
12
16
20
Trip unit
500
12
16
20
STR25DE,
630
12
16
20
35SE/GE, 55UE 800
12
16
20
1000
16
20
C1251N
500
16
20
Trip unit
630
16
20
STR25DE,
800
16
20
35SE/GE, 55UE 1000
16
20
1250
20
C1251H
500
16
20
Trip unit
630
16
20
STR25DE,
800
16
20
35SE/GE, 55UE 1000
16
20
1250
20
CM
1250
15
Trip unit ST
1600
CM1,2,3
2000
2500
3200
Masterpact
M08
12
16
20
N1, H1, H2
M10
16
20
Trip unit
M12
20
STR28D
M16
M20
M25
M32
M40
M50
M63
Masterpact L
M08
Trip unit
M10
STR38S,
M12
58U, 68U
M16
M20
M25
(1) Discrimination with Compact C trip unit STR25DE only.
C801N
Trip unit
STR25DE,
35SE/GE, 55UE

92

Protection discrimination
Upstream: Masterpact M
Downstream: C801 to C1251, CM,
Masterpact

2500
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
20
20

3200
32
32
32
32
32
32
32
32
32
32
35
35
35
35
35
32
32
32
32
32
32
32
32
32
32
35
35
35
35
35
32
32
32
32
32
32
32
32
32
32
25
25
25

4000
40
40
40
40
40
40
40
40
40
40
50
50
50
50
50
40
40
40
40
40
40
40
40
40
40
50
50
50
50
50
40
40
40
40
40
40
40
40
40
40
32
32
32
32

25
25
25
25

32
32
32
32
32

40
40
40
40
40
40

5000
45
45
45
45
45
45
45
45
45
45
90
90
90
90
90
45
45
45
45
45
45
45
45
45
45
90
90
90
90
90
45
45
45
45
45
45
45
45
45
45
40
40
40
40
40
50
50
50
50
50
50
50

6300 800
T
T
T
T
T
65
65
65
65
65
100
100
100
100
100
T
T
T
T
T
65
65
65
65
65
100
100
100
100
100
T
T
T
T
T
65
65
65
65
65
50
50
50
50
50
63
63
63
63
63
63
63
63

1000
30
30
30
30
30
30
30
30
40
40
40
40

1250
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
70
70
70
70

1600
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45

2000
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
45
45
35

2500
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
45
45
35
35

3200
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
45
45
70
70
70
70
70
45
45
45
45
45
45
45
45
45
45
40
40
40

4000
T
T
T
T
T
50
50
50
50
50
80
80
80
80
80
T
T
T
T
T
50
50
50
50
50
80
80
80
80
80
T
T
T
T
T
50
50
50
50
50
40
40
40
40

30

35
35

35
35
35

35
35
35
35

40
40
40
40
40

40
40
40
40
40
40

50

50
50

50
50
50

50
50
50
50

50
50
50
50
50

55
55
55
55
55
55

5000
T
T
T
T
T
60
60
60
60
60
110
110
110
110
110
T
T
T
T
T
60
60
60
60
60
110
110
110
110
110
T
T
T
T
T
60
60
60
60
60
50
50
50
50
50
50
50
50
50
50
50
50

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63

60
63
63
63
63
60

80
80
80
80
80
80

Schneider Electric

Protection discrimination
Upstream: Masterpact M
Downstream: C801 to C1251, CM,
Masterpact

Complementary
technical information

Upstream
Downstream

Schneider Electric

Masterpact N1 - H1

Trip unit STR68U - Inst: ON - position maxi

Trip unit STR38S - 58U - Inst: OFF

Rating (A) M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M60 M63

Setting Ir
320
400
500
630
800
C801H
320
Trip unit
400
STR25DE,
500
35SE/GE, 55UE 630
800
C801L
320
Trip unit
400
STR25DE,
500
35SE/GE, 55UE 630
800
C1001N
400
Trip unit
500
STR25DE,
630
35SE/GE, 55UE 800
1000
C1001H
400
Trip unit
500
STR25DE,
630
35SE/GE, 55UE 800
1000
C1001L
400
Trip unit
500
STR25DE,
630
35SE/GE, 55UE 800
1000
C1251N
500
Trip unit
630
STR25DE,
800
35SE/GE, 55UE 1000
1250
C1251H
500
Trip unit
630
STR25DE,
800
35SE/GE, 55UE 1000
1250
CM
1250
Trip unit ST
1600
CM1,2,3
2000
2500
3200
Masterpact
M08
N1, H1, H2
M10
Trip unit
M12
STR28D
M16
M20
M25
M32
M40
M50
M63
Masterpact L
M08
Trip unit STR38S, M10
58U, 68U
M12
M16
M20
M25
C801N
Trip unit
STR25DE,
35SE/GE, 55UE

Masterpact N1 - H1 - H2

800

1000
T
T
T
T
50
50
50
50
T
T
T
T

1250
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
50
50
50
50
T
T
T
T

1600
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
50
50
50
50

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T

6300 800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

1000
T
T
T
T
T
T
T
T
T
T
T
T

1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

93

Protection discrimination
Upstream: Masterpact M
Downstream: C801 to C1251, CM,
Masterpact

Complementary
technical information

Upstream Masterpact N1 - H1
Trip unit STR68U - Inst: OFF
Downstream

94

Masterpact L (1)
Trip unit STR68U

Rating (A) M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25

Setting Ir 800 1000 1250 1600 2000


320
T
T
T
T
400
T
T
T
T
500
T
T
T
T
630
T
T
T
T
800
T
T
T
C801H
320
T
T
T
T
Trip unit
400
T
T
T
T
STR25DE,
500
T
T
T
T
35SE/GE, 55UE 630
T
T
T
T
800
T
T
T
C801L
320
T
T
T
T
Trip unit
400
T
T
T
T
STR25DE,
500
T
T
T
T
35SE/GE, 55UE 630
T
T
T
T
800
T
T
T
C1001N
400
T
T
T
Trip unit
500
T
T
T
STR25DE,
630
T
T
T
35SE/GE, 55UE 800
T
T
T
1000
T
T
C1001H
400
T
T
T
Trip unit
500
T
T
T
STR25DE,
630
T
T
T
35SE/GE, 55UE 800
T
T
T
1000
T
T
C1001L
400
T
T
T
Trip unit
500
T
T
T
STR25DE,
630
T
T
T
35SE/GE, 55UE 800
T
T
T
1000
T
T
C1251N
500
T
T
Trip unit
630
T
T
STR25DE,
800
T
T
35SE/GE, 55UE 1000
T
T
1250
T
C1251H
500
T
T
Trip unit
630
T
T
STR25DE,
800
T
T
35SE/GE, 55UE 1000
T
T
1250
T
CM
1250
65
Trip unit ST
1600
CM1,2,3
2000
2500
3200
Masterpact
M08
T
T
T
N1, H1, H2
M10
T
T
Trip unit STR28D M12
T
M16
M20
M25
M32
M40
M50
M63
Masterpact L
M08
T
T
T
Trip unit STR38S, M10
T
T
58U, 68U
M12
T
M16
M20
M25
(1) Discrimination with Compact C trip unit STR25DE only.
C801N
Trip unit
STR25DE,
35SE/GE, 55UE

Masterpact L (1)
Trip unit STR38S - 58U

2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65

3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T

6300 800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

1000
8
8
8
8
8
8
8
8
8
8
8
8

1250
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1600
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

10

12
12

2000
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

2500 800
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

12
12
12

15
15
15
15

1000
8
8
8
8
8
8
8
8
8
8
8
8

1250
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

1600
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

10

12
12

2000
12
12
12
12
12
12
2
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12

2500
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

12
12
12

15
15
15
15

Schneider Electric

Protection discrimination
Upstream: Masterpact M
Downstream: Masterpact NT, NW

Complementary
technical information

Upstream

Masterpact N1 - H1 - H2

Masterpact N1 - H1 - H2

Trip unit

STR28D

STR38S/58U - Inst: ON - position maxi

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63
Downstream
Masterpact NT
H1

Masterpact NT
L1
Masterpact NW
N1/H1/H2/H3

Masterpact NW
L1

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300 800

1000 1250 1600 2000 2500 3200 4000 5000 6300

Setting Ir
NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20

800

1000 1250 1600


10
12
16
12
16
16

2000
20
20
20
20

1000 1250 1600


30
30
40
30
40
40

2000
40
40
40
40

10

16
16
16
16
16

20
20
20
20
20
20

70

T
T
T
40
40

T
T
T
40
40
40

16
16

20
20
20

40
40

40
40
40

Upstream

Masterpact N1 - H1 - H2

Masterpact N1 - H1

Trip unit

STR68U - Inst: ON - position maxi

STR38S/58U - Inst: OFF

12
12
12

12

2500
25
25
25
25
25
25
25
25
25
25
25
25

3200
32
32
32
32
32
32
32
32
32
32
32
32
32

4000
40
40
40
40
40
40
40
40
40
40
40
40
40
40

5000
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50

6300 800
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63

25
25
25
25

32
32
32
32
32

40
40
40
40
40

50
50
50
50
50

63
63
63
63
63

100
100
28

30

2500
40
40
40
40
40
T
T
T
40
40
40
40

3200
40
40
40
40
40
T
T
T
40
40
40
40
40

4000
40
40
40
40
40
T
T
T
40
40
40
40
40
40

5000
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50

6300
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63

40
40
40
40

40
40
40
40
40

40
40
40
40
40

60
60
60
60
60

T
T
T
T
T

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M32 M40 M50 M63
Downstream
Masterpact NT
H1

Masterpact NT
L1
Masterpact NW
N1/H1/H2/H3

Masterpact NW
L1

Rating (A)

800

1000 1250 1600 2000 2500 3200 4000 5000 6300 800

1000 1250 1600 2000 2500 3200 4000 5000 6300

rglage Ir
NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
NW08
NW10
NW12
NW16
NW20

800

1000 1250 1600


T
T
T
T
T
T

2000
T
T
T
T

1000 1250 1600


T
T
T
T
T
T

2000
T
T
T
T

T
T
T
65
65

T
T
T
65
65
65

T
T
T
T
T

T
T
T
T
T
T

95
95

T
T
T

T
T

T
T
T

Schneider Electric

T
T
65

95

2500
T
T
T
T
T
T
T
T
65
65
65
65

3200
T
T
T
T
T
T
T
T
65
65
65
65
65

4000
T
T
T
T
T
T
T
T
65
65
65
65
65
65

5000
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65

6300 800
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
65

T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

95

Protection discrimination
Upstream: Masterpact M
Downstream: Masterpact NT, NW

Complementary
technical information

Upstream

Masterpact N1 - H1

Masterpact L

Masterpact L

Trip unit

STR68U - Inst: OFF

STR38S/58U

STR68U

M08 M10 M12 M16 M20 M25 M32 M40 M50 M63 M08 M10 M12 M16 M20 M25 M08 M10 M12 M16 M20 M25
Downstream

Rating (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500

rglage Ir
Masterpact NT NT06
H1
NT08
NT10
NT12
NT16
Masterpact NT NT06
L1
NT08
NT10
Masterpact NW NW08
N1/H1/H2/H3
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW50
NW63
Masterpact NW NW08
L1
NW10
NW12
NW16
NW20

96

800 1000 1250 1600


T
T
T
T
T
T

T
T
T

2000
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T

2500
T
T
T
T
T
T
T
T
T
T
T
T

3200
T
T
T
T
T
T
T
T
T
T
T
T
T

4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T

5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

6300 800 1000


T
10
T
T
T
T
T
10
T
T
T
T
T
T
T
T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

1250 1600 2000


10
12
12
10
12
12
12
12
12
10
10

15
15
15

15
15
15

2500 800 1000


15
10
15
15
15
15
25
10
25
25

1250 1600 2000


10
12
12
10
12
12
12
12
12
10
10

15
15
15

15
15
15

2500
15
15
15
15
15
25
25
25

Schneider Electric

Motor protection discrimination


Upstream: Compact NSC100N
Downstream: GV2, Integral 18, 32

Complementary
technical information

Upstream

NSC100N
18 kA
Trip unit TM-D

Downstream

Trip unit

Rating (A)

16

20

25

or Th. relay
Setting Ir
GV2 M01
integrated
0.1 to 0.16
T
T
T
GV2 M02
integrated
0.16 to 0.25
T
T
T
GV2 M03
integrated
0.25 to 0.40
T
T
T
GV2 M04
integrated
0.40 to 0.63
T
T
T
GV2 M05
integrated
0.63 to 1
T
T
T
GV2 M06
integrated
1 to 1.6
T
T
T
GV2 M07
integrated
1.6 to 2.5
T
T
T
GV2 M08
integrated
2.5 to 4
T
T
T
GV2 M10
integrated
4 to 6.3
0.6
0.6
GV2 M14
integrated
6 to 10
GV2 M16
integrated
9 to 14
GV2 M20
integrated
13 to 18
GV2 M21
integrated
17 to 23
GV2 M22
integrated
20 to 25
GV2 M32
integrated
24 to 32
GV2 P01
integrated
0.1 to 0.16
T
T
T
GV2 P02
integrated
0.16 to 0.25
T
T
T
GV2 P03
integrated
0.25 to 0.40
T
T
T
GV2 P04
integrated
0.40 to 0.63
T
T
T
GV2 P05
integrated
0.63 to 1
T
T
T
GV2 P06
integrated
1 to 1.6
T
T
T
GV2 P07
integrated
1.6 to 2.5
T
T
T
GV2 P08
integrated
2.5 to 4
T
T
T
GV2 P10
integrated
4 to 6.3
0.6
0.6
GV2 P14
integrated
6 to 10
GV2 P16
integrated
9 to 14
GV2 P20
integrated
13 to 18
GV2 P21
integrated
17 to 23
GV2 P22
integrated
20 to 25
GV2 L03
LR2 D13 03
0.25 to 0.40
T
T
T
GV2 L04
LR2 D13 04
0.40 to 0.63
T
T
T
GV2 L05
LR2 D13 05
0.63 to 1
T
T
T
GV2 L06
LR2 D13 06
1 to 1.6
T
T
T
GV2 L07
LR2 D13 07
1.6 to 2.5
T
T
T
GV2 L08
LR2 D13 08
2.5 to 4
T
T
T
GV2 L10
LR2 D13 10
4 to 6.3
0.6
0.6
GV2 L14
LR2 D13 14
7 to 10
GV2 L16
LR2 D13 16
9 to 13
GV2 L20
LR2 D13 21
12 to 18
GV2 L22
LR2 D13 22
17 to 25
Integral 18
LB1-LB03P01
0.1 to 0.16
T
T
T
LD1-LB030
LB1-LB03P02
0.16 to 0.25
T
T
T
LB1-LB03P03
0.25 to 0.40
T
T
T
LB1-LB03P04
0.40 to 0.63
T
T
T
LB1-LB03P05
0.63 to 1
T
T
T
LB1-LB03P06
1 to 1.6
T
T
T
LB1-LB03P07
1.6 to 2.5
T
T
T
LB1-LB03P08
2.5 to 4
T
T
T
LB1-LB03P10
4 to 6
0.6
0.6
LB1-LB03P13
6 to 10
LB1-LB03P17
10 to 16
LB1-LB03P21
12 to 18
Integral 32
LB1-LC03M03
0.25 to 0.40
T
T
T
LD1-LC030
LB1-LC03M04
0.40 to 0.63
T
T
T
LD4-LC130
LB1-LC03M05
0.63 to 1
T
T
T
LD4-LC030
LB1-LC03M06
1 to 1.6
T
T
T
LB1-LC03M07
1.6 to 2.5
T
T
T
LB1-LC03M08
2.5 to 4
T
T
T
LB1-LC03M10
4 to 6
0.6
0.6
LB1-LC03M13
6 to 10
LB1-LC03M17
10 to 16
LB1-LC03M22
16 to 25
LB1-LC03M53
23 to 32
Note. respect the basic overload and short-circuit discrimination rules, see page 16.

Schneider Electric

32

40

50

63

70

80

100

T
T
T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
T
T
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1
1
1

T
T
T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
T
T
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1
1

T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
1
1
1

T
T
T
T
T
T
1
1
1
1

T
T
T
T
T
T
1
1
1
1

T
T
T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
T
T
1
1
1

T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
0.6
0.6

T
T
T
T
T
T
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1
T
T
T
T
T
T
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1
T
T
T
T
T
T
1
1
1

T
T
T
T
T
T
T
T
1
1
1
1
1
1
T
T
T
T
T
T
1
1
1
1
1
T
T
T
T
T
T
T
T
1
1
1
1
T
T
T
T
T
T
1
1
1
1

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

97

Motor protection discrimination


Upstream: NS100 to 630
Downstream: GV2, GV3

Complementary
technical information

Upstream

NS100N/H/L

NS160N/H/L

Trip unit TM-D


Downstream

Trip unit

Rating (A)

16

25

Trip unit TM-D


40

63

or Th. relay
Setting Ir
GV2 M01
integrated
0.1 to 0.16 A
T
T
T
T
GV2 M02
integrated
0.16 to 0.25 A
T
T
T
T
GV2 M03
integrated
0.25 to 0.40 A
T
T
T
T
GV2 M04
integrated
0.40 to 0.63 A
T
T
T
T
GV2 M05
integrated
0.63 to 1 A
T
T
T
T
GV2 M06
integrated
1 to 1.6 A
2
T
T
T
GV2 M07
integrated
1.6 to 2.5 A
0.6
2
T
T
GV2 M08
integrated
2.5 to 4 A
0.2
0.8
4
4
GV2 M10
integrated
4 to 6.3 A
0.3
1
1
GV2 M14
integrated
6 to 10 A
0.5
0.5
GV2 M16
integrated
9 to 14 A
0.5
GV2 M20
integrated
13 to 18 A
0.5
GV2 M21
integrated
17 to 23 A
GV2 M22
integrated
20 to 25 A
GV2 P01
integrated
0.1 to 0.16 A
T
T
T
T
GV2 P02
integrated
0.16 to 0.25 A
T
T
T
T
GV2 P03
integrated
0.25 to 0.40 A
T
T
T
T
GV2 P04
integrated
0.40 to 0.63 A
T
T
T
T
GV2 P05
integrated
0.63 to 1 A
T
T
T
T
GV2 P06
integrated
1 to 1.6 A
2
T
T
T
GV2 P07
integrated
1.6 to 2.5 A
0.6
2
T
T
GV2 P08
integrated
2.5 to 4 A
0.2
0.8
4
4
GV2 P10
integrated
4 to 6.3 A
0.3
1
1
GV2 P14
integrated
6 to 10 A
0.5
0.5
GV2 P16
integrated
9 to 14 A
0.5
GV2 P20
integrated
13 to 18 A
0.5
GV2 P21
integrated
17 to 23 A
GV2 P22
integrated
20 to 25 A
GV2 L03
LR2 D13 03
0.25/0.4
T
T
T
T
GV2 L04
LR2 D13 04
0.4/0.63
T
T
T
T
GV2 L05
LR2 D13 05
0.63/1
T
T
T
T
GV2 L06
LR2 D13 06
1/1.6
2
T
T
T
GV2 L07
LR2 D13 07
1.6/2.5
0.6
2
T
T
GV2 L08
LR2 D13 08
2.5/4
0.2
0.8
4
4
GV2 L10
LR2 D13 10
4/6
0.3
1
1
GV2 L14
LR2 D13 14
7/10
0.5
0.5
GV2 L16
LR2 D13 16
9/13
0.5
GV2 L20
LR2 D13 21
12/18
0.5
GV2 L22
LR2 D33 22
17/25
GV3 M06
integrated
1 to 1.6 A
0.2
0.3
T
T
GV3 M07
integrated
1.6 to 2.5 A
0.2
0.3
1
1
GV3 M08
integrated
2.5 to 4 A
0.2
0.3
0.5
0.5
GV3 M10
integrated
4 to 6 A
0.2
0.3
0.5
0.5
GV3 M14
integrated
6 to 10 A
0.5
0.5
GV3 M20
integrated
10 to 16 A
0.5
GV3 M25
integrated
16 to 25 A
GV3 M40
integrated
25 to 40 A
GV3 M63
integrated
40 to 63 A
GV3 M80
integrated
63 to 80 A
Note. respect the basic overload and short-circuit discrimination rules, see page 16.

98

80

100

40

63

80

100

125

160

T
T
T
T
T
T
T
4
1
0.7
0.7
0.7
0.7
0.7
T
T
T
T
T
T
T
4
1
0.7
0.7
0.7
0.7
0.7
T
T
T
T
T
4
0.7
0.7
0.7
0.7
0.7
T
0.7
0.7
0.7
0.7
0.7
0.7

T
T
T
T
T
T
T
10
2
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
10
2
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
10
2
0.8
0.8
0.8
0.8
T
T
0.8
0.8
0.8
0.8
0.8

T
T
T
T
T
T
T
4
1
0.5

T
T
T
T
T
T
T
4
1
0.5
0.5
0.5

T
T
T
T
T
T
T
4
1
0.5

T
T
T
T
T
T
T
4
1
0.5
0.5
0.5

T
T
T
T
T
4
1
0.5

T
T
T
T
T
4
1
0.5
0.5
0.5

T
1
0.5
0.5
0.5

T
1
0.5
0.5
0.5
0.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2
1.5
1

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
3
2
2

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
3
2
2
1.25

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
3
2
2
1.25

Schneider Electric

Motor protection discrimination


Upstream: NS100 to 630
Downstream: GV2, GV3

Complementary
technical information

Upstream

Downstream Trip unit

Rating (A)

NS250N/H/L

NS100N/H/L

NS160N/H/L

NS250N/H/L

NS400N/H/L

Trip unit TM-D

STR22SE (1)

STR22SE (1)

STR22SE (1)

STR23SE

STR23SE

/53UE (1)

/53UE (1)

40

63

80

100 125 160 200 250 40

or Th. relay Setting Ir


GV2 M01
integrated
0.1 to 0.16 A
T
T
T
T
T
T
T
GV2 M02
integrated
0.16 to 0.25 A
T
T
T
T
T
T
T
GV2 M03
integrated
0.25 to 0.40 A
T
T
T
T
T
T
T
GV2 M04
integrated
0.40 to 0.63 A
T
T
T
T
T
T
T
GV2 M05
integrated
0.63 to 1 A
T
T
T
T
T
T
T
GV2 M06
integrated
1 to 1.6 A
T
T
T
T
T
T
T
GV2 M07
integrated
1.6 to 2.5 A
T
T
T
T
T
T
T
GV2 M08
integrated
2.5 to 4 A
4
4
T
T
T
T
T
GV2 M10
integrated
4 to 6.3 A
1
1
T
T
T
T
T
GV2 M14
integrated
6 to 10 A
0.5 0.5 T
T
T
T
T
GV2 M16
integrated
9 to 14 A
0.5 T
T
T
T
T
GV2 M20
integrated
13 to 18 A
0.5 T
T
T
T
T
GV2 M21
integrated
17 to 23 A
T
T
T
T
T
GV2 M22
integrated
20 to 25 A
T
T
T
T
T
GV2 P01
integrated
0.1 to 0.16 A
T
T
T
T
T
T
T
GV2 P02
integrated
0.16 to 0.25 A
T
T
T
T
T
T
T
GV2 P03
integrated
0.25 to 0.40 A
T
T
T
T
T
T
T
GV2 P04
integrated
0.40 to 0.63 A
T
T
T
T
T
T
T
GV2 P05
integrated
0.63 to 1 A
T
T
T
T
T
T
T
GV2 P06
integrated
1 to 1.6 A
T
T
T
T
T
T
T
GV2 P07
integrated
1.6 to 2.5 A
T
T
T
T
T
T
T
GV2 P08
integrated
2.5 to 4 A
4
4
T
T
T
T
T
GV2 P10
integrated
4 to 6.3 A
1
1
T
T
T
T
T
GV2 P14
integrated
6 to 10 A
0.5 0.5 T
T
T
T
T
GV2 P16
integrated
9 to 14 A
0.5 T
T
T
T
T
GV2 P20
integrated
13 to 18 A
0.5 T
T
T
T
T
GV2 P21
integrated
17 to 23 A
T
T
T
T
T
GV2 P22
integrated
20 to 25 A
T
T
T
T
T
GV2 L03
LR2 D13 03 0.25/0.4
T
T
T
T
T
T
T
GV2 L04
LR2 D13 04 0.4/0.63
T
T
T
T
T
T
T
GV2 L05
LR2 D13 05 0.63/1
T
T
T
T
T
T
T
GV2 L06
LR2 D13 06 1/1.6
T
T
T
T
T
T
T
GV2 L07
LR2 D13 07 1.6/2.5
T
T
T
T
T
T
T
GV2 L08
LR2 D13 08 2.5/4
4
4
T
T
T
T
T
GV2 L10
LR2 D13 10 4/6
1
1
T
T
T
T
T
GV2 L14
LR2 D13 14 7/10
0.5 0.5 T
T
T
T
T
GV2 L16
LR2 D13 16 9/13
0.5 T
T
T
T
T
GV2 L20
LR2 D13 21 12/18
0.5 T
T
T
T
T
GV2 L22
LR2 D33 22 17/25
T
T
T
T
T
GV3 M06
integrated
1 to 1.6 A
T
T
T
T
T
T
T
GV3 M07
integrated
1.6 to 2.5 A
1
1
T
T
T
T
T
GV3 M08
integrated
2.5 to 4 A
0.5 0.5 T
T
T
T
T
GV3 M10
integrated
4 to 6 A
0.5 0.5 T
T
T
T
T
GV3 M14
integrated
6 to 10 A
0.5 0.5 2
3
3
T
T
GV3 M20
integrated
10 to 16 A
0.5 1.5 2
2
T
T
GV3 M25
integrated
16 to 25 A
1
2
2
T
T
GV3 M40
integrated
25 to 40 A
1.25 T
T
GV3 M63
integrated
40 to 63 A
T
GV3 M80
integrated
63 to 80 A
(1) Note. respect the basic overload and short-circuit discrimination rules, see page 16.

Schneider Electric

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
1
1
0.8
0.5
0.5

T
T
T
T
T
1
1
0.8
0.5
0.5

T
T
T
1
1
0.8
0.5
0.5

T
1
0.5
0.5
0.5

NS630N/H/L

100

80

160

160

250

160 to 400 250 to 630

T
T
T
T
T
T
4
3
2
1.2
1.2
1.2
1.2
1.2
T
T
T
T
T
T
4
3
2
1.2
1.2
1.2
1.2
1.2
T
T
T
T
4
3
2
1.2
1.2
1.2
1.2
T
T
5
2
1.2
1.2
1.2

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.9
0.9
0.9

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

99

Motor protection discrimination


Upstream: NS100 to 630
Downstream: Integral 18, 32, 63

Complementary
technical information

Upstream

NS100N/H/L

NS160N/H/L

Trip unit TM-D


Downstream

Trip unit

Rating (A)

16

25

Trip unit TM-D


40

63

or Th. relay
Setting Ir
Integral 18
LB1-LB03P01
0.1 to 0.16 A
T
T
T
T
LD1-LB030
LB1-LB03P02
0.16 to 0.25 A
T
T
T
T
LB1-LB03P03
0.25 to 0.40 A
T
T
T
T
LB1-LB03P04
0.40 to 0.63 A
T
T
T
T
LB1-LB03P05
0.63 to 1 A
T
T
T
T
LB1-LB03P06
1 to 1.6 A
0.2
T
T
T
LB1-LB03P07
1.6 to 2.5 A
0.2
0.3
1.5
1.5
LB1-LB03P08
2.5 to 4 A
0.2
0.3
0.5
0.5
LB1-LB03P10
4 to 6 A
0.3
0.5
0.5
LB1-LB03P13
6 to 10 A
0.5
0.5
LB1-LB03P17
10 to 16 A
0.5
LB1-LB03P21
12 to 18 A
0.5
Integral 32
LB1-LC03M03
0.25 to 0.40 A
T
T
T
T
LD1-LC030
LB1-LC03M04
0.40 to 0.63 A
T
T
T
T
LD4-LC130
LB1-LC03M05
0.63 to 1 A
T
T
T
T
LD4-LC030
LB1-LC03M06
1 to 1.6 A
0.2
T
T
T
LB1-LC03M07
1.6 to 2.5 A
0.2
0.3
1.5
1.5
LB1-LC03M08
2.5 to 4 A
0.2
0.3
0.5
0.5
LB1-LC03M10
4 to 6 A
0.3
0.5
0.5
LB1-LC03M13
6 to 10 A
0.5
0.5
LB1-LC03M17
10 to 16 A
0.5
LB1-LC03M22
16 to 25 A
0.5
LB1-LC03M53
23 to 32 A
Integral 63
LB1-LD03M16
10 13 A
0.5
0.5
LD1-LD030
LB1-LD03M21
13 18 A
0.5
LD4-LD130
LB1-LD03M22
18 to 25 A
LD4-LD030
LB1-LD03M53
23 to 32 A
LB1-LD03M55
28 to 40 A
LB1-LD03M57
35 to 50 A
LB1-LD03M61
45 to 63 A
Note. respect the basic overload and short-circuit discrimination rules, see page 16.

100

80

100

40

63

80

100

125

160

T
T
T
T
T
T
4
0.7
0.7
0.7
0.7
0.7
T
T
T
T
1
0.7
0.7
0.7
0.7
0.7

T
T
T
T
T
T
T
2
1
0.8
0.8
0.8
T
T
T
T
T
1
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
T
T
T
1.5
0.5
0.5
0.5

T
T
T
T
T
T
1.5
0.5
0.5
0.5
0.5
0.5
T
T
T
T
1.5
0.5
0.5
0.5
0.5
0.5

T
T
T
T
T
T
T
T
T
T
4
3
T
T
T
T
T
T
T
T
4
3

0.5
0.5

1
1
1

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1.25
1.25
1.25
1.25

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1.25
1.25
1.25
1.25
1.25

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1.25
1.25
1.25
1.25
1.25
1.25

0.65
0.65
0.65

T
T
T
T
1.5
0.5
0.5
0.5

0.5

Schneider Electric

Motor protection discrimination


Upstream: NS100 to 630
Downstream: Integral 18, 32, 63

Complementary
technical information

Upstream

Downstream Trip unit

Rating (A)

NS250N/H/L

NS100N/H/L

NS160N/H/L

NS250N/H/L

NS400N/H/L

NS630N/H/L

Trip unit TM-D

STR22SE (1)

STR22SE (1)

STR22SE (1)

STR23SE/

STR23SE/

53UE (1)

53UE (1)

40

63

80

100 125 160 200 250 40

or Th. relay Setting Ir


Integral 18 LB1-LB03P01 0.1 to 0.16 A
T
T
T
T
T
T
T
LD1-LB030 LB1-LB03P02 0.16 to 0.25 A
T
T
T
T
T
T
T
LB1-LB03P03 0.25 to 0.40 A
T
T
T
T
T
T
T
LB1-LB03P04 0.40 to 0.63 A
T
T
T
T
T
T
T
LB1-LB03P05 0.63 to 1 A
T
T
T
T
T
T
T
LB1-LB03P06 1 to 1.6 A
T
T
T
T
T
T
T
LB1-LB03P07 1.6 to 2.5 A
1.5 1.5 T
T
T
T
T
LB1-LB03P08 2.5 to 4 A
0.5 0.5 T
T
T
T
T
LB1-LB03P10 4 to 6 A
0.5 0.5 T
T
T
T
T
LB1-LB03P13 6 to 10 A
0.5 0.5 T
T
T
T
T
LB1-LB03P17 10 to 16 A
0.5 4
T
T
T
T
LB1-LB03P21 12 to 18 A
0.5 3
T
T
T
T
Integral 32 LB1-LC03M03 0.25 to 0.40 A
T
T
T
T
T
T
T
LD1-LC030 LB1-LC03M04 0.40 to 0.63 A
T
T
T
T
T
T
T
LD4-LC130 LB1-LC03M05 0.63 to 1 A
T
T
T
T
T
T
T
LD4-LC030 LB1-LC03M06 1 to 1.6 A
T
T
T
T
T
T
T
LB1-LC03M07 1.6 to 2.5 A
1.5 1.5 T
T
T
T
T
LB1-LC03M08 2.5 to 4 A
0.5 0.5 T
T
T
T
T
LB1-LC03M10 4 to 6 A
0.5 0.5 T
T
T
T
T
LB1-LC03M13 6 to 10 A
0.5 0.5 T
T
T
T
T
LB1-LC03M17 10 to 16 A
0.5 1
T
T
T
T
LB1-LC03M22 16 to 25 A
0.5 0.8 T
T
T
T
LB1-LC03M53 23 to 32 A
T
T
T
T
Integral 63 LB1-LD03M16 13 to 13 A
0.5 0.5 1
1.25 1.25 T
T
LD1-LD030 LB1-LD03M21 13 to 18 A
0.5 1
1.25 1.25 T
T
LD4-LD130 LB1-LD03M22 18 to 25 A
1
1.25 1.25 T
T
LD4-LD030 LB1-LD03M53 23 to 32 A
1.25 1.25 T
T
LB1-LD03M55 28 to 40 A
1.25 T
T
LB1-LD03M57 35 to 50 A
T
T
LB1-LD03M61 45 to 63 A
T
(1) Note: respect the basic overload and short-circuit discrimination rules, see page 16.

Schneider Electric

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
2
0.5
0.5
0.5

T
T
T
T
0.5
0.5
0.5
0.5

0.5

100

80

160

160

250

160 to 400 250 to 630

T
T
T
T
T
T
T
3
1.2
1.2
1.2
1.2
T
T
T
T
T
3
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.9
0.9
0.9

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
35
35
35
35

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
35
35
35
35

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

101

Motor protection discrimination


Upstream: NS100 to 630
Downstream: C60LMA, NC100LMA,
NS80HMA

Complementary
technical information

Upstream

NS100N/H/L

NS160N/H/L

Trip unit TM-D


Downstream
C60LMA 1.6
C60LMA 2.5
C60LMA 4
C60LMA 6.3
C60LMA 10
C60LMA 10
C60LMA 12.5
C60LMA 16
C60LMA 25
C60LMA 40
C60LMA 40
NC100LMA 1.6
NC100LMA 2.5
NC100LMA 4
NC100LMA 6.3
NC100LMA 10
NC100LMA 10
NC100LMA 12.5
NC100LMA 16
NC100LMA 25
NC100LMA 40
NC100LMA 40
NC100LMA 63
NC100LMA 63
NS80HMA 2.5
NS80HMA 2.5
NS80HMA 6.3
NS80HMA 6.3
NS80HMA 12.5
NS80HMA 12.5
NS80HMA 12.5
NS80HMA 25
NS80HMA 25
NS80HMA 50
NS80HMA 50
NS80HMA 50
NS80HMA 80

102

Trip unit

Rating (A)

or Th. relay
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 12
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D13 22
LR2 D33 53
LR2 D33 55
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 12
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D13 22
LR2 D33 53
LR2 D33 55
LR2 D33 57
LR2 D33 59
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 12
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D33 22
LR2 D33 53
LR2 D33 55
LR2 D33 57
LR2 D33 59

Setting Ir
1/1.6
1.6/2.5
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
23/32
30/40
37/50
48/65

Trip unit TM-D

16

25

40

63

80

100

40

63

80

100

125

160

0.2
0.2
0.2

T
0.3
0.3
0.3
0.3

T
T
0.5
0.5
0.5
0.5
0.5

T
T
0.5
0.5
0.5
0.5
0.5
0.5

T
T
3
0.7
0.7
0.7
0.7
0.7
0.7

T
T
T
5
2
0.8
0.8
0.8
0.8
0.8

T
T
0.5
0.5
0.5
0.5
0.5

T
T
0.5
0.5
0.5
0.5
0.5
0.5

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T

0.2
0.2
0.2

T
0.3
0.3
0.3
0.3

T
T
0.5
0.5
0.5
0.5
0.5

T
T
0.5
0.5
0.5
0.5
0.5
0.5

T
T
10
0.7
0.7
0.7
0.7
0.7
0.7

T
T
T
10
2
0.8
0.8
0.8
0.8
0.8

T
T
0.5
0.5
0.5
0.5
0.5

T
T
0.5
0.5
0.5
0.5
0.5
0.5

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
0.2

T
T
0.3
0.3
0.3

T
T
0.5
0.5
0.5
0.5
0.5

T
T
0.5
0.5
0.5
0.5
0.5
0.5

T
T
0.7
0.7
0.7
0.7
0.7
0.7
0.7

T
T
10
2
0.8
0.8
0.8
0.8
0.8
0.8

T
T
0.5
0.5
0.5
0.5
0.5

T
T
0.5
0.5
0.5
0.5
0.5
0.5

T
T
T
T
T
T
T
1
1

T
T
T
T
T
T
T
T
1.2
1.2

T
T
T
T
T
T
T
T
1.2
1.2
1.2

T
T
T
T
T
T
T
T
1.2
1.2
1.2
1.2

Schneider Electric

Motor protection discrimination


Upstream: NS100 to 630
Downstream: C60LMA, NC100LMA,
NS80HMA

Complementary
technical information

Upstream

Downstream

Trip unit

Rating (A)

NS250N/H/L

NS100N/H/L NS160N/H/L NS250N/H/L NS400N/H/L NS630N/H/L

Trip unit TM-D

STR22SE

40

63

80

100 125 160 200 250 40

or Th. relay Setting Ir


C60LMA 1.6
LR2 D13 06 1/1.6
T
T
T
T
T
T
C60LMA 2.5
LR2 D13 07 1.6/2.5
T
T
T
T
T
T
C60LMA 4
LR2 D13 08 2.5/4
0.5 0.5 T
T
T
T
C60LMA 6.3
LR2 D13 10 4/6
0.5 0.5 T
T
T
T
C60LMA 10
LR2 D13 12 5.5/8
0.5 0.5 T
T
T
T
C60LMA 10
LR2 D13 14 7/10
0.5 0.5 T
T
T
T
C60LMA 12.5
LR2 D13 16 9/13
0.5 0.5 T
T
T
T
C60LMA 16
LR2 D13 21 12/18
0.5 T
T
T
T
C60LMA 25
LR2 D13 22 17/25
T
T
T
T
C60LMA 40
LR2 D33 53 23/32
T
T
T
C60LMA 40
LR2 D33 55 30/40
T
T
NC100LMA 1.6
LR2 D13 06 1/1.6
T
T
T
T
T
T
NC100LMA 2.5
LR2 D13 07 1.6/2.5
T
T
T
T
T
T
NC100LMA 4
LR2 D13 08 2.5/4
0.5 0.5 T
T
T
T
NC100LMA 6.3
LR2 D13 10 4/6
0.5 0.5 T
T
T
T
NC100LMA 10
LR2 D13 12 5.5/8
0.5 0.5 T
T
T
T
NC100LMA 10
LR2 D13 14 7/10
0.5 0.5 T
T
T
T
NC100LMA 12.5
LR2 D13 16 9/13
0.5 0.5 T
T
T
T
NC100LMA 16
LR2 D13 21 12/18
0.5 T
T
T
T
NC100LMA 25
LR2 D13 22 17/25
T
T
T
T
NC100LMA 40
LR2 D33 53 23/32
T
T
T
NC100LMA 40
LR2 D33 55 30/40
T
T
NC100LMA 63
LR2 D33 57 37/50
T
NC100LMA 63
LR2 D33 59 48/65
NS80HMA 2.5
LR2 D13 06 1/1.6
T
T
T
T
T
T
NS80HMA 2.5
LR2 D13 07 1.6/2.5
T
T
T
T
T
T
NS80HMA 6.3
LR2 D13 08 2.5/4
0.5 0.5 T
T
T
T
NS80HMA 6.3
LR2 D13 10 4/6
0.5 0.5 T
T
T
T
NS80HMA 12.5
LR2 D13 12 5.5/8
0.5 0.5 T
T
T
T
NS80HMA 12.5
LR2 D13 14 7/10
0.5 0.5 T
T
T
T
NS80HMA 12.5
LR2 D13 16 9/13
0.5 0.5 T
T
T
T
NS80HMA 25
LR2 D13 21 12/18
0.5 1
T
T
T
NS80HMA 25
LR2 D33 22 17/25
1
1.2 1.2 T
NS80HMA 50
LR2 D33 53 23/32
1.2 1.2 T
NS80HMA 50
LR2 D33 55 30/40
1.2 T
NS80HMA 50
LR2 D33 57 37/50
T
NS80HMA 80
LR2 D33 59 48/65
(1) Note. respect the basic overload and short-circuit discrimination rules, see page 16.

Schneider Electric

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

STR22SE (1)

STR22SE (1)

STR23SE/

STR23SE/

53UE

53UE

100 80

160 160 250 160 to 400 250 to 630

T
1
0.5
0.5
0.5
0.5
0.5

T
T
T
5
2
1.2
1.2
1.2
1.2
1.2

T
T
T
T
T
T
T
T
T
T

T
1
0.5
0.5
0.5
0.5
0.5

T
T
15
2
1.2
1.2
1.2
1.2
1.2
1.2

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
1
0.5
0.5
0.5
0.5
0.5

T
T
T
5
2
1.2
1.2
1.2
1.2
1.2

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

103

Motor protection discrimination


Upstream: NS100 to 630,
NS630b to NS1600
Downstream: NS100 to 630

Complementary
technical information

Upstream
Downstream
NS100N/H/LMA 2.5
NS100N/H/LMA 2.5
NS100N/H/LMA 6.3
NS100N/H/LMA 6.3
NS100N/H/LMA 12.5
NS100N/H/LMA 12.5
NS100N/H/LMA 12.5
NS100N/H/LMA 25
NS100N/H/LMA 25
NS100N/H/LMA 50
NS100N/H/LMA 50
NS100N/H/LMA 50
NS100N/H/LMA 100
NS100N/H/LMA 100
NS100N/H/LMA 100
NS160N/H/LMA 150
NS250N/H/LMA 220
NS400N/H/LMA 320
NS630N/H/LMA 500
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS160N/H/L
NS250N/H/L
NS400N/H/L

Downstream

Trip unit

Rating (A)

or Th. relay
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 12
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D33 22
LR2 D33 53
LR2 D33 55
LR2 D33 57
LR2 D33 59
LR2 D33 63

Setting Ir
1/1.6
1.6/2.5
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80

STR22ME40
STR22ME50
STR22ME80
STR22ME100
STR22ME150
STR22ME220
STR43ME320

24/40
30/50
48/80
60/100
90/150
131/220
190/320

Trip unit

NS100N/H/L

NS160N/H/L

NS250N/H/L

Trip unit TM-D

Trip unit TM-D

Trip unit TM-D

16

25

32

40

50

63

80

100

80

100

125

160

200

250

0.19
0.19
0.19

3
3
3
3
3

T
4
4
4
4
4

T
5
5
5
5
5
5

T
5
5
5
5
5
5

T
5
5
5
5
5
5
5

T
T
6.4
6.4
6.4
6.4
6.4
6.4
6.4

T
T
8
8
8
8
8
8
8
8

T
T
T
T
10
10
10
10
10

T
T
T
T
12.5
12.5
12.5
12.5
12.5
12.5

T
T
T
T
12.5
12.5
12.5
12.5
12.5
12.5
12.5

T
T
T
T
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

T
T
T
T
20
20
20
20
20
20
20
20
20

T
T
T
T
25
25
25
25
25
25
25
25
25
25

12.5

12.5
12.5

36
36

36
36
36

Upstream NS100N/H/L NS160N/H/L

NS400N/H/L

NS630bN/H

NS630bL

NS1000N/H

NS250N/H/L

NS630N/H/L

NS800N/H

NS800bL

NS1250/1600N/H

STR22SE (1) STR22SE (1)

STR23SE (1)

Micrologic

Micrologic

Micrologic

STR53SE

2.0 - 5.0

2.0 - 5.0

2.0 - 5.0

400

630

630

800

630

800

1000

1250

1600

1000

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18

T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
T

T
T
T
T
T
T
18

Rating (A) 40

100

80

160

250

or Thermal th. Setting Ir


NS100N/H/LMA 2,5 LR2 D13 06 1/1,6
0,45 T
T
T
T
T
NS100N/H/LMA 2,5 LR2 D13 07 1,6/2,5
0,45 T
T
T
T
T
NS100N/H/LMA 6,3 LR2 D13 08 2,5/4
0,45 1,1
T
T
T
T
NS100N/H/LMA 6,3 LR2 D13 10 4/6
0,45 1,1
T
T
T
T
NS100N/H/LMA 12,5 LR2 D13 12 5,5/8
0,45 1,1
0,9
T
T
T
NS100N/H/LMA 12,5 LR2 D13 14 07/10
0,45 1,1
0,9
T
T
T
NS100N/H/LMA 12,5 LR2 D13 16 9/13
0,45 1,1
0,9
T
T
T
NS100N/H/LMA 25
LR2 D13 21 12/18
1,1
0,9
1,75 36
T
NS100N/H/LMA 25
LR2 D33 22 17/25
1,1
0,9
1,75 36
T
NS100N/H/LMA 50
LR2 D33 53 23/32
1,1
1,75 36
T
NS100N/H/LMA 50
LR2 D33 55 30/40
1,75 36
T
NS100N/H/LMA 50
LR2 D33 57 37/50
1,75 36
T
NS100N/H/LMA 100 LR2 D33 59 48/65
36
T
NS100N/H/LMA 100 LR2 D33 63 63/80
36
T
NS100N/H/LMA 100
T
NS160N/H/LMA 150
NS250N/H/LMA 220
NS400N/H/LMA 320
NS630N/H/LMA 500
NS100N/H/L
STR22ME40 24/40
1,75 3,6
T
NS100N/H/L
STR22ME50 30/50
1,75 3,6
T
NS100N/H/L
STR22ME80 48/80
3,6
T
NS100N/H/L
STR22ME100 60/100
T
NS160N/H/L
STR22ME150 90/150
NS250N/H/L
STR22ME220 131/220
NS400N/H/L
STR43ME320 190/320
(1) Note. respect the basic overload and short-circuit discrimination rules, see page 16.

104

NS1000L
Micrologic
2.0 - 5.0

Schneider Electric

Motor protection discrimination


Upstream: NS1600, Masterpact NT, NW
Downstream: NS630, NS630b, NS800,
NS1000, NS1250

Complementary
technical information

Upstream
Downstream
NS630N/H/L
NS630bN/H/L
NS800N/H/L
NS1000N/H/L
NS1250N/H/L

STR43ME
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0

Schneider Electric

200...500
250...630
320...800
400...1000
500...1250

NS1600N/H

NT16H1

NW16N1/H1

NW20H1/H2/H3 NW25H1/H2/H3 NW32H1/H2/H3 NW40H1/H2/H3

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

2.0 - 5.0
T

2.0 - 5.0
T

2.0 - 5.0
T

2.0 - 5.0
T
T

2.0 - 5.0
T
T
T

2.0 - 5.0
T
T
T
T

2.0 - 5.0
T
T
T
T

105

Cascading and enhanced discrimination


Upstream: Compact NS100 to NS1600
Downstream: circuit breaker Multi 9 /
Integral /GV2 / Compact NS100 to 630

Complementary
technical information

With traditional circuit breakers, cascading between two devices generally results
in the look of discrimination.
With Compact NS circuit breakers, the discrimination characteristics in the tables
remain applicable and are in some cases even enhanced. Protection discrimination
is ensured for short-circuit currents greater than the rated breaking capacity of the
circuit breaker and even, in some cases, for its enhanced breaking capacity. In the
later case, protection discrimination is total, i.e. only the downstream device
trips for any and all possible faults at its point in the installation.
Example
Consider a combination between:
b a Compact NS250N with trip unit TM250D
b a Compact NS100N with trip unit TM100D.
The discrimination tables indicate total discrimination. Protection discrimination is
therefore ensured up to the breaking capacity of the NS100N, i.e. 25 kA.
The cascading tables indicate an enhanced breaking capacity of 36 kA.
The enhanced discrimination tables indicate that in a cascading configuration,
discrimination is ensured up to 36 kA, i.e. for any and all possible faults at that
point in the installation.

Enhanced discrimination tables - 380/415 V


For each combination of two circuit breakers, the tables indicate the:

15/25

downstream device breaking


capacity enhanced by
cascading (in kA)
selectivity limit enhanced
by cascading
(in kA)

In a table, a box containing two equal values indicates that discrimination is


provided up to the reinforced breaking capacity of the downstream device.
These tables apply only to cases with combined discrimination and cascading
between two devices. For all other cases, refer to the normal cascading and
discrimination tables.

Technical principle

E43820

Enhanced discrimination is the result of the exclusive Compact NS Roto-active


breaking technique which operates as follows:
b due to the short-circuit current (electrodynamic forces), the contacts in both
devices simultaneously separate. The result is major limitation of the short-circuit
current
b the dissipated energy provokes the reflex tripping of the downstream device, but
is insufficient to trip the upstream device.

NS160N
TM160D

NS400H
STR23SE
discrimination
limit in kA

30 / 30

70 / 70

C60N
63 A

NS160N
TM160D

cascading
limit in kA

106

Schneider Electric

Cascading and enhanced


discrimination
Upstream: NSC100N, NSA160
Downstream: Multi 9

Complementary
technical information

Upstream: Compact NSC100 TM-D


Downstream: Multi 9
Upstream

NSC100N

Breaking capacity

18 kA

Trip unit

TM-D

Downstream
C60a
5 kA

C60N

10 kA

Rating
y 16
20
25
32
40
y 16
20
25
32
40
50
63

63
18/18
18/18
18/18
6/18
18/18
18/18
18/18
6/18

70
18/18
18/18
18/18
6/18
6/18
18/18
18/18
18/18
6/18
6/18

80
18/18
18/18
18/18
6/18
6/18
18/18
18/18
18/18
6/18
6/18
6/18

100
18/18
18/18
18/18
8/18
8/18
18/18
18/18
18/18
8/18
8/18
6/18
6/18

Upstream: Compact NSA160 TM-D


Downstream: Multi 9
Upstream

NSA160E

Breaking capacity

16 kA

30 kA

Trip unit

TM-D

TM-D

Downstream
C60a
5 kA

Rating
63
80
100
125
15/15
15/15
15/15
15/15
y 16
20
15/15
15/15
15/15
15/15
25
15/15
15/15
15/15
15/15
32
6/15
6/15
8/15
8/15
40
6/15
6/15
8/15
8/15
y 16
C60N
10 kA
15/15
15/15
15/15
15/15
20
15/15
15/15
15/15
15/15
25
15/15
15/15
15/15
15/15
32
6/15
6/15
8/15
8/15
40
6/15
8/15
8/15
50
6/15
6/15
6/15
63
6/15
6/15
y 16
C60H
15 kA
20
25
32
40
50
63
y 16
C60L
25 kA
20
25
20 kA
32
40
15 kA
50
63
y 16
NC100L
22 kA
20 - 25
32 - 40
50 - 63
Note. respect the basic overload and short-circuit discrimination rules, see page 16.

Schneider Electric

NSA160N

160
15/15
15/15
15/15
8/15
8/15
15/15
15/15
15/15
8/15
8/15
6/15
6/15

63
15/15
15/15
15/15
6/15
6/15
15/25
15/25
15/25
6/25

80
15/15
15/15
15/15
6/15
6/15
15/25
15/25
15/25
6/25
6/25
6/25

15/30
15/30
15/30
6/30

15/30
15/30
15/30
6/30
6/30
6/30

15/30
15/30
15/30
6/30

15/30
15/30
15/30
6/30
6/30
6/30

30/30
15/30

30/30
15/30
8/30

100
15/15
15/15
15/15
8/15
8/15
15/25
15/25
15/25
8/25
8/25
6/25
6/25
30/30
30/30
30/30
8/30
8/30
6/30
6/30
30/30
30/30
30/30
8/30
8/30
6/30
6/30
30/30
30/30
30/30
30/30

125
15/15
15/15
15/15
8/15
8/15
15/25
15/25
15/25
8/25
8/25
6/25
6/25
30/30
30/30
30/30
8/30
8/30
6/30
6/30
30/30
30/30
30/30
8/30
8/30
6/30
6/30
30/30
30/30
30/30
30/30

160
15/15
15/15
15/15
8/15
8/15
15/25
15/25
15/25
8/25
8/25
6/25
6/25
30/30
30/30
30/30
8/30
8/30
6/30
6/30
30/30
30/30
30/30
8/30
8/30
6/30
6/30
30/30
30/30
30/30
30/30

107

Complementary
technical information

Cascading and enhanced discrimination


Upstream: NS160 to NS250
Trip unit TM-D
Downstream: Multi 9

Upstream

NS160N

NS160H

NS160L

NS250N

NS250H

Breaking capacity

36 kA

70 kA

150 kA

36 kA

70 kA

150 kA

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

TM-D

160/200/250
15/15
15/15
15/15
15/15
15/15
25/25
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36

160/200/250
20/20
20/20
20/20
20/20
20/20
30/30
30/30
30/30
30/30
30/30
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
30/30
30/30
30/30
30/30
30/30
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70

160/200/250
20/20
20/20
20/20
20/20
20/20
30/30
30/30
30/30
30/30
30/30
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
30/30
30/30
30/30
30/30
30/30
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150

Downstream
C60a
5 kA

Rating
80
100/125/160 80
100/125/160
y 16
15/15
15/15
20/20
20/20
20
15/15
15/15
20/20
20/20
25
15/15
15/15
20/20
20/20
32
15/15
15/15
20/20
20/20
40
15/15
15/15
20/20
20/20
y 16
C60N
10 kA
25/25
25/25
30/30
30/30
20
25/25
25/25
30/30
30/30
25
25/25
25/25
30/30
30/30
32
15/25
25/25
15/30
30/30
40
15/25
25/25
15/30
30/30
50
15/25
25/25
15/30
30/30
63
25/25
30/30
y 16
C60H
15 kA
30/30
30/30
40/40
40/40
20
30/30
30/30
40/40
40/40
25
30/30
30/30
40/40
40/40
32
15/30
30/30
15/40
40/40
40
15/30
30/30
15/40
40/40
50
15/30
30/30
15/40
40/40
63
30/30
40/40
y 16
C60L
25 kA
30/30
30/30
40/40
40/40
20
30/30
30/30
40/40
40/40
25
30/30
30/30
40/40
40/40
20 kA
32
15/30
30/30
15/40
40/40
40
15/30
30/30
15/40
40/40
15 kA
50
15/30
30/30
15/40
40/40
63
30/30
40/40
NC100H 10 kA
50
63
80
100
NC125H 10 kA
125
y 16
NC100L
22 kA
36/36
36/36
50/50
50/50
20 - 25
36/36
36/36
50/50
50/50
32 - 40
36/36
36/36
50/50
50/50
50 - 63
36/36
50/50
50/50
y 16
NC100LS 36 kA
70/70
70/70
20 - 25
70/70
70/70
32 - 40
70/70
70/70
50 - 63
70/70
70/70
y 16
NC100LH 50 kA
70/70
70/70
20 - 25
70/70
70/70
32 - 40
70/70
70/70
50 - 63
70/70
70/70
C120N/H 10/15 kA y 16
25/25
25/25
25/25
25/25
20 - 25
25/25
25/25
25/25
25/25
32 - 40
25/25
25/25
25/25
25/25
50 - 63
80
100
125
y 16
NG125a
16 kA
25/25
25/25
25/25
25/25
20 - 25
25/25
25/25
25/25
25/25
32 - 40
25/25
25/25
25/25
25/25
50 - 63
80
100
125
y 16
NG125N 25 kA
36/36
36/36
36/36
36/36
20 - 25
36/36
36/36
36/36
36/36
32 - 40
36/36
36/36
36/36
36/36
50 - 63
80
100
125
y 16
NG125H 36 kA
50/50
50/50
20 - 25
50/50
50/50
32 - 40
50/50
50/50
50 - 63
80
y 16
NG125L 50 kA
70/70
70/70
NG125LMA
20 - 25
70/70
70/70
32 - 40
70/70
70/70
50 - 63
80
Note. respect the basic overload and short-circuit discrimination rules, see page 16.

108

80
20/20
20/20
20/20
20/20
20/20
30/30
30/30
30/30
15/30
15/30
15/30
40/40
40/40
40/40
15/40
15/40
15/40
40/40
40/40
40/40
15/40
15/40
15/40

100/125/160
20/20
20/20
20/20
20/20
20/20
30/30
30/30
30/30
30/30
30/30
30/30
30/30
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40

70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
25/25
25/25
25/25

70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
25/25
25/25
25/25

25/25
25/25
25/25

25/25
25/25
25/25

70/70
70/70
70/70

70/70
70/70
70/70

100/100
100/100
100/100

100/100
100/100
100/100

150/150
150/150
150/150

150/150
150/150
150/150

25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36

NS250L

Schneider Electric

Complementary
technical information

Cascading and enhanced discrimination


Upstream: NS160 to NS250
Trip unit STR
Downstream: Multi 9

Upstream

NS160N

NS160H

NS160L

NS250N

NS250H

Breaking capacity

36 kA

70 kA

150 kA

36 kA

70 kA

150 kA

Trip unit

STR22SE

STR22SE

STR22SE

STR22SE

STR22SE

STR22SE

250
15/15
15/15
15/15
15/15
15/15
25/25
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36

25/25
25/25
25/25
25/25
25/25
25/25

250
20/20
20/20
20/20
20/20
20/20
30/30
30/30
30/30
30/30
30/30
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
30/30
30/30
30/30
30/30
30/30
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
25/25
25/25
25/25
25/25
25/25
25/25

250
20/20
20/20
20/20
20/20
20/20
30/30
30/30
30/30
30/30
30/30
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
30/30
30/30
30/30
30/30
30/30
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
25/25
25/25
25/25
25/25
25/25
25/25

Downstream
C60a
5 kA

Rating
80
160
80
160
y 16
15/15
15/15
20/20
20/20
20
15/15
15/15
20/20
20/20
25
15/15
15/15
20/20
20/20
32
15/15
20/20
40
15/15
20/20
y 16
C60N
10 kA
25/25
25/25
30/30
30/30
20
25/25
25/25
30/30
30/30
25
25/25
25/25
30/30
30/30
32
25/25
30/30
40
25/25
30/30
50
25/25
30/30
63
25/25
30/30
y 16
C60H
15 kA
30/30
30/30
40/40
40/40
20
30/30
30/30
40/40
40/40
25
30/30
30/30
40/40
40/40
32
30/30
40/40
40
30/30
40/40
50
30/30
40/40
63
30/30
40/40
y 16
C60L
25 kA
30/30
30/30
40/40
40/40
20
30/30
30/30
40/40
40/40
25
30/30
30/30
40/40
40/40
20 kA
32
30/30
40/40
40
30/30
40/40
15 kA
50
30/30
40/40
63
30/30
40/40
NC100H 10 kA
50
63
80
100
NC125H 10 kA
125
y 16
NC100L
22 kA
36/36
36/36
50/50
50/50
20 - 25
36/36
36/36
50/50
50/50
32 - 40
36/36
50/50
50 - 63
36/36
50/50
y 16
NC100LS 36 kA
70/70
70/70
20 - 25
70/70
70/70
32 - 40
70/70
50 - 63
70/70
y 16
NC100LH 50 kA
70/70
70/70
20 - 25
70/70
70/70
32 - 40
70/70
50 - 63
70/70
C120N/H 10/15 kA y 16
25/25
25/25
25/25
25/25
20 - 25
25/25
25/25
25/25
25/25
32 - 40
25/25
25/25
50 - 63
80
100
125
y 16
NG125a
16 kA
25/25
25/25
25/25
25/25
20 - 25
25/25
25/25
25/25
25/25
32 - 40
25/25
25/25
50 - 63
80
100
125
y 16
NG125N 25 kA
36/36
36/36
36/36
36/36
20 - 25
36/36
36/36
36/36
36/36
32 - 40
36/36
36/36
50 - 63
80
100
125
y 16
NG125H 36 kA
50/50
50/50
20 - 25
50/50
50/50
32 - 40
50/50
50 - 63
80
y 16
NG125L 50 kA
70/70
70/70
NG125LMA
20 - 25
70/70
70/70
32 - 40
70/70
50 - 63
80
Note. respect the basic overload and short-circuit discrimination rules, see page 16.
Schneider Electric

80
20/20
20/20
20/20

30/30
30/30
30/30

40/40
40/40
40/40

40/40
40/40
40/40

70/70
70/70

100/100
100/100

150/150
150/150

25/25
25/25

160
20/20
20/20
20/20
20/20
20/20
30/30
30/30
30/30
30/30
30/30
30/30
30/30
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40

70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
25/25
25/25
25/25

NS250L

25/25
25/25

25/25
25/25
25/25

25/25
25/25
25/25
25/25
25/25
25/25

25/25
25/25
25/25
25/25
25/25
25/25

25/25
25/25
25/25
25/25
25/25
25/25

70/70
70/70

70/70
70/70
70/70

36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36

70/70
70/70
70/70
70/70
70/70
70/70

100/100
100/100

100/100
100/100
100/100

150/150
150/150

150/150
150/150
150/150

50/50
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70

100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150

109

Cascading and enhanced discrimination


Upstream: NS250 to NS630b
Downstream: NSA160N, NSC100N,
NS100 to NS250

Complementary
technical information

Upstream: Compact NS250


Downstream: Compact NS100 to NSA160
Upstream

NS250N

NS250H

NS250L

Breaking capacity

36 kA

70 kA

150 kA

36 kA

Trip unit

TM-D

TM-D

TM-D

STR22SE

Downstream
NSA160N
30 kA
NSC100N
18 kA
NS100N
25 kA
Trip unit TM-D
NS100H
70 kA
Trip unit TM-D
NS100N
25 kA

Rating
160
200
250
160
63 - 160
36/36
36/36
36/36
50/50
16 - 100
36/36
36/36
36/36
50/50
y 25
36/36
36/36
36/36
70/70
40 - 100
36/36
36/36
36/36
36/70
y 25
40 - 100
Trip unit STR22SE 36/36
36/36
36/36
36/70
Trip unit STR22ME 36/36
36/36
36/36
36/70
NS100H
70 kA Trip unit STR22SE
Trip unit STR22ME
Note. respect the basic overload and short-circuit discrimination, see page 16.

200
50/50
50/50
70/70
36/70

250
50/50
50/50
70/70
36/70

36/70
36/70

36/70
36/70

160
50/50
50/50
150/150
36/150
150/150
36/150
36/150
36/150
36/150
36/150

NS250N NS250H NS250L

200
50/50
50/50
150/150
36/150
150/150
36/150
36/150
36/150
36/150
36/150

250
50/50
50/50
150/150
36/150
150/150
36/150
36/150
36/150
36/150
36/150

70 kA

150 kA

250
36/36
36/36
36/36
36/36

250
50/50
50/50
70/70
36/70

36/36
36/36

36/70
36/70

250
50/50
50/50
150/150
36/150
150/150
36/150
36/150
36/150
36/150
36/150

Upstream: Compact NS400 to NS630b


Downstream: Compact NS100 to NS250
Upstream

NS400N NS400 H NS400L NS630N NS630H NS630L NS630bN

NS630bH

Breaking capacity

45 kA

50 kA

70 kA

150 kA

Trip unit

STR23SE or STR53UE

STR23SE or STR53UE

Micrologic 5.0

Micrologic 5.0

Micrologic 5.0

Rating
36/36
36/36
45/45

400
50/50
50/50
70/70

400
36/36
36/36
45/45

630
50/50
50/50
70/70

630
36/36
36/36
50/50

630
50/50
50/50
70/70

45/45

70/70

45/45

70/70

50/50

70/70

45/45

70/70

50/50

70/70

45/45
45/45

70/70
70/70

50/50
50/50

70/70
70/70

45/45
45/45

70/70
70/70

50/50
50/50

70/70
70/70

45/45
45/45

70/70
70/70

50/50
50/50

70/70
70/70

630
50/50
50/50
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

Downstream
NSA160N
30 kA
NSC100N
18 kA
NS100N
25 kA
NS100H
70 kA
NS160N
35 kA
NS160H
70 kA
NS250N
35 kA
NS250H
70 kA
NS100N
25 kA
NS100H

70 kA

NS160N

35 kA

NS160H

70 kA

NS250N

35 kA

NS250H

70 kA

110

63 - 160
16 - 100
all TM-D-G-MA
all TM-D-MA
all TM-D-MA
all TM-D-MA
all TM-D-MA
all TM-D-MA
Trip unit STR22SE
Trip unit STR22ME
Trip unit STR22/SE
Trip unit STR22ME
Trip unit STR22SE
Trip unit STR22ME
Trip unit STR22SE
Trip unit STR22ME
Trip unit STR22SE
Trip unit STR22ME
Trip unit STR22SE
Trip unit STR22ME

70 kA

45/45
45/45

70/70
70/70

45/45
45/45

70/70
70/70

150 kA
400
50/50
50/50
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

45 kA

70 kA

150 kA
630
50/50
50/50
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

NS630bL

630

Schneider Electric

Cascading and enhanced discrimination


Upstream: NS800 to NS1600
Downstream: NSA160N, NSC100N,
NS100 to NS630

Complementary
technical information

Upstream

NS800N

NS800 H

NS800L

NS1000N NS1000H NS1000L

Breaking capacity

50 kA

70 kA

150 kA

50 kA

Trip unit

Micrologic 2.0

Downstream
NSA160N 30 kA
NSC100N 18 kA
NS100N
25 kA
NS100H
70 kA
NS160N
35 kA
NS160H
70 kA
NS250N
35 kA
NS250H
70 kA
NS100N
25 kA

150 kA

Micrologic 2.0

Rating
800
800
800
1000
63 - 160
16 - 100
all TM-D-G-MA
50/50
70/70
150/150
50/50
all TM-D-MA
150/150
all TM-D-MA
50/50
70/70
150/150
50/50
all TM-D-MA
150/150
all TM-D-MA
50/50
70/70
150/150
50/50
all TM-D-MA
150/150
Trip unit STR22SE 50/50
70/70
150/150
50/50
Trip unit STR22ME 50/50
70/70
150/150
50/50
NS100H
70 kA Trip unit STR22SE
150/150
Trip unit STR22ME
150/150
NS160N
35 kA Trip unit STR22SE 50/50
70/70
150/150
50/50
Trip unit STR22ME 50/50
70/70
150/150
50/50
NS160H
70 kA Trip unit STR22SE
150/150
Trip unit STR22ME
150/150
NS250N
35 kA Trip unit STR22SE 50/50
70/70
150/150
50/50
Trip unit STR22ME 50/50
70/70
150/150
50/50
NS250H
70 kA Trip unit STR22SE
150/150
Trip unit STR22ME
150/150
NS400N
45 kA Trip unit STR23SE 50/50
70/70
50/50
Trip unit STR53UE 50/50
70/70
50/50
Trip unit STR43ME 50/50
70/70
50/50
NS630N
45 kA Trip unit STR23SE 50/50
70/70
50/50
Trip unit STR53UE 50/50
70/70
50/50
Trip unit STR43ME 50/50
70/70
50/50
Note. respect the basic overload and short-circuit discrimination rules, see page 16.

Schneider Electric

70 kA

NS1250N NS1250H NS1600N NS1600H


50 kA

70 kA

50 kA

70 kA

Micrologic 2.0

Micrologic 2.0

1000

1000

1250

1250

1600

1600

70/70

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

50/50

70/70

50/50

70/70

50/50

70/70

50/50

70/70

50/50

70/70

50/50

70/70

50/50
50/50

70/70
70/70

50/50
50/50

70/70
70/70

50/50
50/50

70/70
70/70

50/50
50/50

70/70
70/70

50/50
50/50

70/70
70/70

50/50
50/50

70/70
70/70

50/50
50/50
50/50
50/50
50/50
50/50

70/70
70/70
70/70
70/70
70/70
70/70

50/50
50/50
50/50
50/50
50/50
50/50

70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70

70/70
70/70

70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70

111

Cascading and enhanced discrimination


Upstream: Compact NS160 to NS400
Downstream: Integral 18 to Integral 63

Complementary
technical information

Upstream

NS160H

NS160L

NS250H

NS250L

Breaking capacity

70 kA

150 kA

70 kA

150 kA

Trip unit

TM-D

TM-D

TM-D

Downstream Thermal

Rating (A)

80

100/125/160 80

relay
Integral 18
LB1-LB03P01 0.1 to 0.16
70/70
70/70
150/150
LD1-LB030
LB1-LB03P02 0.16 to 0.25
70/70
70/70
150/150
LB1-LB03P03 0.25 to 0.40
70/70
70/70
150/150
LB1-LB03P04 0.40 to 0.63
70/70
70/70
150/150
LB1-LB03P05 0.63 to 1
70/70
70/70
150/150
LB1-LB03P06 1 to 1.6
70/70
70/70
150/150
LB1-LB03P07 1.6 to 2.5
70/70
70/70
150/150
LB1-LB03P08 2.5 to 4
70/70
70/70
150/150
LB1-LB03P10 4 to 6
70/70
70/70
150/150
LB1-LB03P13 6 to 10
70/70
70/70
150/150
LB1-LB03P17 10 to 16
70/70
LB1-LB03P21 12 to 18
70/70
Integral 32
LB1-LC03M03 0.25 to 0.40
70/70
70/70
150/150
LD1-LC030
LB1-LC03M04 0.40 to 0.63
70/70
70/70
150/150
LD4-LC130
LB1-LC03M05 0.63 to 1
70/70
70/70
150/150
LD4-LC030
LB1-LC03M06 1 to 1.6
70/70
70/70
150/150
LB1-LC03M07 1.6 to 2.5
70/70
70/70
150/150
LB1-LC03M08 2.5 to 4
70/70
70/70
150/150
LB1-LC03M10 4 to 6
70/70
70/70
150/150
LB1-LC03M13 6 to 10
70/70
150/150
LB1-LC03M17 10 to 16
70/70
150/150
LB1-LC03M22 16 to 25
70/70
150/150
LB1-LC03M53 23 to 32
70/70
8/150
Integral 63
LB1-LD03M16 10 to 13
LD1-LD030
LB1-LD03M21 11 to 18
LD4-LD130
LB1-LD03M22 18 to 25
LD4-LD030
LB1-LD03M53 23 to 32
LB1-LD03M55 28 to 40
LB1-LD03M57 35 to 50
LB1-LD03M61 45 to 63
Note: respect the basic overload and short-circuit discrimination rules, see page 16.

100/125/160 160
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

TM-D
200/250

160

200/250

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

Upstream

NS160H

NS160L

NS250H

NS250L

NS400H

NS400L

Breaking capacity

70 kA

150 kA

70 kA

150 kA

70 kA

150 kA

Trip unit

STR22SE

STR22SE

STR22SE or STR53UE

STR22SE or STR53UE

160

250

250

400

400

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

70/70
70/70
70/70
70/70
70/70
70/70
70/70

150/150
150/150
150/150
150/150
150/150
150/150
150/150

Downstream Thermal

Rating (A)

80

160

80

relay
Integral 18
LB1-LB03P01 0.1 to 0.16
70/70
70/70
150/150
LD1-LB030
LB1-LB03P02 0.16 to 0.25
70/70
70/70
150/150
LB1-LB03P03 0.25 to 0.40
70/70
70/70
150/150
LB1-LB03P04 0.40 to 0.63
70/70
70/70
150/150
LB1-LB03P05 0.63 to 1
70/70
70/70
150/150
LB1-LB03P06 1 to 1.6
70/70
70/70
150/150
LB1-LB03P07 1.6 to 2.5
70/70
70/70
150/150
LB1-LB03P08 2.5 to 4
70/70
70/70
150/150
LB1-LB03P10 4 to 6
70/70
70/70
150/150
LB1-LB03P13 6 to 10
70/70
70/70
150/150
LB1-LB03P17 10 to 16
70/70
70/70
150/150
LB1-LB03P21 12 to 18
70/70
70/70
150/150
Integral 32
LB1-LC03M03 0.25 to 0.40
70/70
70/70
150/150
LD1-LC030
LB1-LC03M04 0.40 to 0.63
70/70
70/70
150/150
LD4-LC130
LB1-LC03M05 0.63 to 1
70/70
70/70
150/150
LD4-LC030
LB1-LC03M06 1 to 1.6
70/70
70/70
150/150
LB1-LC03M07 1.6 to 2.5
70/70
70/70
150/150
LB1-LC03M08 2.5 to 4
70/70
70/70
150/150
LB1-LC03M10 4 to 6
70/70
70/70
150/150
LB1-LC03M13 6 to 10
70/70
70/70
150/150
LB1-LC03M17 10 to 16
70/70
70/70
150/150
LB1-LC03M22 16 to 25
70/70
70/70
150/150
LB1-LC03M53 23 to 32
70/70
Integral 63
LB1-LD03M16 10 to 13
70/70
LD1-LD030
LB1-LD03M21 11 to 18
LD4-LD130
LB1-LD03M22 18 to 25
LD4-LD030
LB1-LD03M53 23 to 32
LB1-LD03M55 28 to 40
LB1-LD03M57 35 to 50
LB1-LD03M61 45 to 63
Note. respect the basic overload and short-circuit discrimination rules, see page 16.

112

Schneider Electric

Cascading and enhanced discrimination


Upstream: Compact NS160
Downstream: GV2 M

Complementary
technical information

Upstream

NS160N

Breaking capacity

36 kA

70/150 kA

Trip unit

TM-D

TM-D

Downstream Thermal
GV2 M01
GV2 M02
GV2 M03
GV2 M04
GV2 M05
GV2 M06
GV2 M07
GV2 M08
GV2 M10
GV2 M14
GV2 M16
GV2 M20
GV2 M21
GV2 M22
GV2 M32

relay
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated

Rating (A)

16

25

40

63

80

100

125

160

16

25

40

63

80

100

125

160

0.1 to 0.16
0.16 to 0.25
0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
6 to 10
9 to 14
13 to 18
17 to 23
20 to 25
24 to 32

36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

Upstream

NS160N

Breaking capacity

36 kA

Trip unit

STR22SE80

Downstream Thermal
GV2 M01
GV2 M02
GV2 M03
GV2 M04
GV2 M05
GV2 M06
GV2 M07
GV2 M08
GV2 M10
GV2 M14
GV2 M16
GV2 M20
GV2 M21
GV2 M22
GV2 M32

relay
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated

Schneider Electric

NS160H/L

NS160H/L
70/150 kA
STR22SE160

STR22SE80

STR22SE160

Rating (A)

32

40

50

63

80

100

125

160

32

40

50

63

80

100

125

160

0.1 to 0.16
0.16 to 0.25
0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
6 to 10
9 to 14
13 to 18
17 to 23
20 to 25
24 to 32

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50

113

Cascading and enhanced discrimination


Upstream: Compact NS160
Downstream: GV2 P

Complementary
technical information

Upstream

NS160H

NS160L

Breaking capacity

700 kA

150 kA

Trip unit

TM-D

Downstream Thermal
GV2 P01
GV2 P02
GV2 P03
GV2 P04
GV2 P05
GV2 P06
GV2 P07
GV2 P08
GV2 P10
GV2 P14
GV2 P16
GV2 P20
GV2 P21
GV2 P22

relay
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated

80

100

125

160

80

100

125

160

0.1 to 0.16
0.16 to 0.25
0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
6 to 10
9 to 14
13 to 18
17 to 23
20 to 25

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

Upstream

NS160H

Breaking capacity

70 kA

Trip unit

STR22SE80

Downstream Thermal
GV2 P01
GV2 P02
GV2 P03
GV2 P04
GV2 P05
GV2 P06
GV2 P07
GV2 P08
GV2 P10
GV2 P14
GV2 P16
GV2 P20
GV2 P21
GV2 P22

relay
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated

32

40

50

63

80

100

125

160

0.1 to 0.16
0.16 to 0.25
0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
6 to 10
9 to 14
13 to 18
17 to 23
20 to 25

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

NS160L

Breaking capacity

150 kA

Trip unit

STR22SE80

Downstream Thermal

114

STR22SE160

Rating (A)

Upstream

GV2 P01
GV2 P02
GV2 P03
GV2 P04
GV2 P05
GV2 P06
GV2 P07
GV2 P08
GV2 P10
GV2 P14
GV2 P16
GV2 P20
GV2 P21
GV2 P22

TM-D

Rating (A)

Relay
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated
integrated

STR22SE160

Rating (A)

32

40

50

63

80

100

125

160

0.1 to 0.16
0.16 to 0.25
0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
6 to 10
9 to 14
13 to 18
17 to 23
20 to 25

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

Schneider Electric

Cascading and enhanced discrimination


Upstream: Compact NS160
Downstream: GV2 L

Complementary
technical information

Upstream

NS160H

NS160L

Breaking capacity

700 kA

150 kA

Trip unit

TM-D

Downstream Thermal
GV2 L03
GV2 L04
GV2 L05
GV2 L06
GV2 L07
GV2 L08
GV2 L10
GV2 L14
GV2 L16
GV2 L20
GV2 L22

relay
LR2 D13 03
LR2 D13 04
LR2 D13 05
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D13 22

80

100

125

160

80

100

125

160

0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
7 to 10
9 to 13
12 to 18
17 to 25

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

Upstream

NS160H

Breaking capacity

70 kA

Trip unit

STR22SE80

Downstream Thermal
GV2 L03
GV2 L04
GV2 L05
GV2 L06
GV2 L07
GV2 L08
GV2 L10
GV2 L14
GV2 L16
GV2 L20
GV2 L22

relay
LR2 D13 03
LR2 D13 04
LR2 D13 05
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D13 22

STR22SE160

Rating (A)

32

40

50

63

80

100

125

160

0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
7 to 10
9 to 13
12 to 18
17 to 25

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70

Upstream

NS160L

Breaking capacity

150 kA

Trip unit

STR22SE80

Downstream Thermal
GV2 L03
GV2 L04
GV2 L05
GV2 L06
GV2 L07
GV2 L08
GV2 L10
GV2 L14
GV2 L16
GV2 L20
GV2 L22

TM-D

Rating (A)

relay
LR2 D13 03
LR2 D13 04
LR2 D13 05
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D13 22

Schneider Electric

STR22SE160

Rating (A)

32

40

50

63

80

100

125

160

0.25 to 0.40
0.40 to 0.63
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6.3
7 to 10
9 to 13
12 to 18
17 to 25

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150

115

Complementary
technical information

116

Schneider Electric

Complementary
technical information

Protection of motor circuits


Circuit breaker/contactor
coordination
A circuit supplying a motor may include one, two, three or four switchgear or
controlgear devices fulfilling one or more functions.
When a number of devices are used, they must be coordinated to ensure
optimum operation of the motor.
Protection of a motor circuit involves a number of parameters that depend on:
b the application (type of machine driven, operating safety, starting frequency, etc.)
b the level of service continuity imposed by the load or the application
b the applicable standards to ensure protection of life and property.
The necessary electrical functions are of very different natures:
b protection (motor-dedicated for overloads)
b control (generally with high endurance levels)
b isolation

E34300

Protection functions

disconnection
and short-circuit
protection

control

overload or
thermal protection

specific or internal
motor protection

Schneider Electric

Disconnection functions:
Isolate a motor circuit prior to maintenance operations.
Short-circuit protection:
Protect the starter and the cables against major overcurrents (> 10 In).
Control:
Start and stop the motor, and, if applicable:
b gradual acceleration
b speed control.
Overload protection:
Protect the starter and the cables against minor overcurrents (< 10 In).
Additional specific protection:
b limitative fault protection (while the motor is running)
b preventive fault protection (monitoring of motor insulation with motor off).
Overloads (I < 10 In)
An overload may be caused by:
b an electrical problem, for instance on the mains (loss of a phase, voltage outside
tolerances, etc.)
b a mechanical problem, for instance excessive torque due to abnormally high
demands by the process or motor damage (bearing vibrations, etc.).
A further consequence of these two origins is excessively long starting.
Impedant short-circuit (10 < I < 50 In)
Deterioration of motor-winding insulation is the primary cause.
Short-circuit (I > 50 In)
This type of fault is relatively rare. A possible cause may be a connection error
during maintenance.
Overload protection
Thermal relays provide protection against this type of fault. They may be:
b integrated in the short-circuit protective device
b separate.
Short-circuit protection
This type of protection is provided by a circuit breaker.
Protection against insulation faults
This type of protection may be provided by:
b a residual current device (RCD)
b an insulation monitoring device (IMD).

117

Complementary
technical information

Protection of motor circuits


Circuit breaker/contactor
coordination
Applicable standards
A circuit supplying a motor must comply with the general rules set out in IEC
standard 60947-4-1 and in particular with those concerning contactors, motor
starters and their protection as stipulated in IEC 60947-4-1, notably:
b coordination of the components of the motor circuit
b trip class for thermal relays
b contactor utilisation categories
b coordination of insulation.

Coordination of the components of the


motor circuit
Two types of coordination
The standard defines tests at different current levels. The purpose of these tests is
to place the switchgear and controlgear in extreme conditions. Depending on the
state of the components following the tests, the standard defines two types of
coordination.
b type 1
Deterioration of the contactor and the relay is acceptable under two conditions:
v no danger to operating personnel
v no danger to any components other than the contactor and the relay;
b type 2
Only minor welding of the contactor or starter contacts is permissible and the
contacts must be easily separated.
v following type-2 coordination tests, the switchgear and controlgear functions
must be fully operational.
Which type of coordination is needed?
Selection of a type of coordination depends on the operating conditions
encountered.
The goal is to achieve the best balance between the users needs and the cost of
the installation.
b type 1
v qualified maintenance service
v low cost of switchgear and controlgear
v continuity of service is not imperative or may be ensured by simply replacing the
faulty motor drawer;
b type 2
v continuity of service is imperative
v limited maintenance service
v specifications stipulating type 2.

118

Schneider Electric

Protection of motor circuits


Circuit breaker/contactor
coordination

Complementary
technical information

The different test currents


Ic, r and Iq test currents
To qualify for type-2 coordination, the standard requires three fault-current tests to
check that the switchgear and controlgear operates correctly under overload and
short-circuit conditions.
Ic current (overload I < 10 In)
The thermal relay provides protection against this type of fault, up to the Ic value (a
function of Im or Isd) defined by the manufacturer.
IEC standard 60947-4-1 stipulates two tests that must be carried out to guarantee
coordination between the thermal relay and the short-circuit protective device:
b at 0.75 Ic, only the thermal relay reacts
b at 1.25 Ic, the short-circuit protective device reacts.
Following the tests at 0.75 and 1.25 Ic, the trip characteristics of the thermal relay
must be unchanged. Type-2 coordination thus enhances continuity of service. The
contactor may be closed automatically following clearing of the fault.
r current
(Impedant short-circuit 10 < I < 50 In)
The primary cause of this type of fault is the deterioration of insulation. IEC
standard 60947-4-1 defines an intermediate short-circuit current r. This test
current is used to check that the protective device provides protection against
impedant short-circuits.
There must be no modification in the original characteristics of the contactor and
the thermal relay following the test.
The circuit breaker must trip in i 10 ms for a fault current u 15 In.
Operational current Ie (AC3)

r current

of the motor (in A)


Ie y 16
16 < Ie y 63
63 < Ie y 125
125 < Ie y 315
315 < Ie < 630

(in kA)
1
3
5
10
18

Iq current
(short-circuit I > 50 In)
This type of fault is relatively rare. A possible cause may be a connection error
during maintenance.
Short-circuit protection is provided by devices that open quickly.
IEC standard 60947-4-1 defines the Iq current as generally u 50 kA.
The Iq current is used to check the coordination of the switchgear and controlgear
installed on a motor supply circuit.
Following this test under extreme conditions, all the coordinated switchgear and
controlgear must remain operational.

E34301

time

t er i
charac

circuit-breaker
thermal withstand
limit (MA)

s ti

o
cs

ft

he

rm

al r
e

thermal-relay
withstand limit

lay

service continuity >

<imperative tripping of the circuit-breaker


ma

50 ~ k ln

0,75lc

Schneider Electric

c release (MA)

10

1
In

gneti

overload
zone

1,25lc
Ic

inpedant
short-circuit
zone

short-circuit
zone

Iq

119

Protection of motor circuits


Circuit breaker/contactor
coordination

E34302

Complementary
technical information

ts

Trip class of a thermal relay


The four trip class of a thermal relay are 10 A, 10, 20 and 30 (maximum tripping
times at 7.2 Ir).
Classes 10 and 10 A are the most commonly used. Classes 20 and 30 are
reserved for motors with difficult starting conditions.
The diagram and the table opposite can be used to select a thermal relay suited to
the motor starting time.

class 30
30s
class 20
20s
class 10

Class
10 A
10
20
30

10s

1.05 1.20

1.5

7.2

1.05 Ir
t>2h
t>2h
t>2h
t>2h

1.2 Ir
t<2h
t<2h
t<2h
t<2h

1.5 Ir
t < 2 min.
t < 4 min.
t < 8 min.
t < 12 min.

7.2 Ir
2 y t y 10 s
4 y t y 10 s
6 y t y 20 s
9 y t y 30 s

l/lr

Trip class of a thermal relay.

120

Schneider Electric

Protection of motor circuits


Circuit breaker/contactor
coordination
The four utilisation categories of contactors
(AC1 to AC4)
The four utilisation categories of contactors (AC1 to AC4)The utilisation category
determines the operating frequency and endurance of a contactor. The category
depends on the type of load. If the load is a motor; the category also depends on
the service classification.
Main characteristics of the controlled electrical circuits and applications

Category
AC1
AC2

Type of load
no-inductive (cos 0,8)
slip-ring motors (cos 0,65)

AC3

squirrel-cage motors
(cos 0,45 for le y 100A)
(cos 0,35 for le > 100A)
squirrel-cage motors
(cos 0,45 for le y 100A)
(cos 0,35 for le > 100A)

E94969

AC4

Contactor usage
energisation
starting
switching off during running
regenerative braking
inching
starting
switching off during running
starting
switching off during running
regenerative braking
plugging
inching

typical applications
heating, distribution
wire drawing machines

compressors, lifts, mixing


pumps, escalators, fans,
conveyers, air-conditioning
printing machines, wire
drawing machines

AC3 utilisation category

current
Ic
interruption of
power supply

This category covers asynchronous squirrel-cage motors that are switched off
during running. This is the most common situation (85% of all cases).
The control device establishes the starting current and interrupts the rated current
at a voltage equal to approximately one-sixth of the rated value.
Current interruption is carried out with no difficulty.

Id

starting
period

time

E34304

AC3 utilisation category. The contactor interrupts the rated


current of the motor.

AC4 utilisation category

current
Ic

interruption of
power current

Id

starting
period

This category covers asynchronous squirrel-cage or slip-ring motors capable of


operating under regenerative-braking or inching (jogging) conditions.
The control device establishes the starting current and is capable of interrupting
the starting current at a voltage that may be equal to that of the mains.
Such difficult conditions require oversizing of the control and protective devices
with respect to category AC3.

time

AC4 utilisation category. The contactor must be capable of


interrupting the starting current id.

Schneider Electric

121

Protection of motor circuits


Using the circuit breaker /
contactor coordination tables

Complementary
technical information

Subtransient phenomena related to direct


on-line starting of asynchronous motors
Subtransient phenomena occurring when starting squirrel-cage motors:
A squirrel-cage motor draws a high inrush current during starting. This current is
related to the combined influence of two parameters:
b the high inductance of the copper stator winding
b the magnetisation of the iron core of the stator.
In motor: current drawn by the motor at full rated load (in A rms)
Id:
current drawn by the motor during starting (in A ms)
Id:
subtransient current generated by the motor when it is energised.
This very short subtransient phenomenon is expressed as k x Id x r (in A
peak).
td:
motor starting time, from 0.5 to 30 seconds depending on the
application.
td:
duration of the subtransient current, from 0.010 to 0.015 seconds when
the motor is energised.
Irm:
magnetic setting of the circuit breakers.

E41251

t(s)

thermal relay

td
(0.5 to
30s)

short-circuit
protection
(magnetic circuit breaker)

td
(0.010 to
0.015s)

I(A)

Irm

In motor

Id" (2 to 2.5 Id in A peak)


Id (5.8 to 8.6 In in A rms)

Typical upper and lower limits for these subtransient currents:


These values, not covered by standards, also depend on the type of motor
technology used:
b ordinary motors Id=2 Id to 2.1 Id (in A peak),
b high-efficiency motors Id=2.2 Id to 2.5 Id (in A peak).
b variation of Id as a function of Id:
Type of motor

Id

Id

(in A peak)
Id = 2 Id = 11,5 In (A peak)
to Id = 2,1 Id = 18 In (A peak)
High-efficiency motor
5,8 8,6 In motor
Id = 2,2 Id = 12,5 In (A peak)
to Id = 2,5 Id = 21,5 In (A peak)
Example: Upon energisation, a high-efficiency motor with an Id of 7.5 In produces a
subtransient current with a value between (depending on its characteritics):
v minimum = 16.5 In (in A peak),
v maximum = 18.8 In (in A peak).
Ordinary motor

122

(in A rms)
5,8 8,6 In motor

Schneider Electric

Complementary
technical information

Protection of motor circuits


Using the circuit breaker /
contactor coordination tables
Subtransient currents and protection settings:
b as illustrated in the above table, subtransient currents can be very high.
If they approach their upper limits, they can trip short-cicuit protection devices
(nuisance tripping)
b Merlin Gerin and Telemecanique circuit breakers are rated to provide optimum
short-circuit protection for motor starters (type 2 coordination with thermal relay and
contactor)
b combinations made up of Merlin Gerin circuit breakers and Telemecanique
contactors and thermal relays are designed to allow starting of motors generating
high subtransient currents (up to 19 In motor peak)
b the tripping of short-circuit protective devices when starting with a combination
listed in the coordination tables means:
v the limits of certain devices may be reached.
v the use of the starter under type 2 coordination conditions on the given motor
may lead to premature wear of one of the components of the combination.
In event of such a problem, the ratings of the starter and the associated
protective devices must be redesigned.

Using the coordination tables for Merlin Gerin circuit


breaker and Telemecanique contactors:
b ordinary motor:
The starter components can be selected directly from the coordination tables,
whatever the values of the starting current (Id from 5.8 to 8.6 In) and the
subtransient current.
b high-efficiency motors with Id y 7.5 In:
The starter components can be selected directly from the coordination tables,
whatever the values of the starting current and the subtransient current.
b high-efficiency motors with Id > 7.5 In
When Merlin Gerin circuit breakers are used for motor currents in the
neighbourhood of their rated current, they are set to provide minimum shortcircuit protection at 19 In motor (A peak).
There are two possibilities:
b the subtransient starting current is known (indicated by the motor manufacturer)
and is less than 19 In motor (A peak).
In this case, the starter components can be selected directly from the
coordination tables, whatever the value of the starting current (for Id > 7.5 In).
Example: For a 110 kW 380/415 V 3-phase motor, the selected components are:
NS250-MA220 / LC1-F225 / LR9-F5371.
b the subtransient starting current is unknown or greater than 19 In motor
(A peak).
In this case, the value used for the motor power in the coordination tables should
be increased by 20 % to satisfy optimum starting and coordination conditions.
Example: For a 110 kW 380/415 V 3-phase motor, the selected components are
those for a motor power of 110 + 20 % = 132 kW: NS400-MA320 / LC1-F265 /
LR9-F5371.

Reversing starters and coordination:


The starter components can be selected using the tables for direct-on-line starting.
Replace contactors LC1 by LC2.

Start-delta starting and coordination:


b the components should be sized according to the current flowing in the motor
windings.
b the mounting locations and connections of the various components of star-delta
starters should be selected according to the type of coordination required and the
protective devices implemented.

Schneider Electric

123

E34305

Complementary
technical information

Protection of motor circuits


Using the circuit breaker /
contactor coordination tables
Start-delta starting and type 1 coordination

KM3

KM2

KM1

E34306

Solution with thermal-magnetic motor circuit breaker

KM3

KM2

Contactors KM2 and KM3 are sized for the line current divided by e
KM1 can be sized for the line current divided by 3, however, for the sake of
homogeneity, it is often identical to contactors KM2 and KM3.
The starter components are selected from the special star-delta type 1
coordination tables.
Example: Consider the following case:
b 45 kW motor supplied at 380 V
b star-delta starting
b separate thermal relay
b short-circuit current of 20 kA at the starter
b type 1 coordination.
The starter components are selected using the table on page 149:
b circuit breaker: NS100N-MA 100
b contactor: LC3-D50
b thermal relay: LR2-D3357

KM1

Solution with magnetic motor circuit breaker

E34305

Start-delta starting and type 2 coordination

KM3

KM2

KM

E34307

Solution with thermal-magnetic motor circuit breaker

Contactors KM1, KM2 and KM3 are sized for the line current.
The starter components are selected from the direct-on-line type 2
coordination tables.
Example: Consider the following case:
b 55 kW motor supplied at 415 V
b star-delta starting
b thermal protection built into the circuit breaker providing short-circuit protection
b short-circuit current of 45 kA at the starter
b type 2 coordination.
The starter components are selected using the table on page 130:
b circuit breaker: NS160H with STR22ME
b starter: LC1-F115A to be replaced by LC3-F115.

KM2

KM3

KM1

M
Solution with magnetic motor circuit breaker

124

Schneider Electric

Complementary
technical information

Protection of motor circuits


Circuit breaker/contactor
coordination
Starting class and thermal relays
The data in the tables on pages 133 to 158 corresponds to normal motor starting
times. The associated thermal relays are either class 10 or 10 A (tripping time
< 10 s).
b for motors with long starting times, the class 10 or 10 A thermal relays must be
replaced with class 20 thermal relays as indicated in the correspondence table
opposite (for type 1 and type 2 coordination)
b long starting times requiring a class 30 relay:
v apply a derating coefficient (K = 0.8) to the circuit breaker and the contactor.
Example: E.g.NS100H MA 100 for 80 A maximum.LC1F115 for 92 A maximum;
b these tables may also be used for standard thermal protection using
current transformers.
The required thermal relays are:
v LR2-D1305 (0.63 to 1 A) for class 10
v LR2-D1505 (0.63 to 1 A) for class 20 with terminal block LA7-D1064.
The current transformer ratings must be 5 VA per phase. The other characteristics
are identical to those described below.
b coordination tables with the multifunction protective relay LT6-P
v three types of multifunction relays (see the corresponding catalogue for detailed
characteristics) are available. They may be connected:
- directly to the motor power supply line;
- to the secondary winding of the current transformer.
Relay

Rating

Connecting
Direct

LT6-P0M005 FM

0,2 to 1 A
1 to 5 A
5 to 25 A

LT6-P0M025 FM

b
b
b

Using current
transformers
b
b

v the characteristics of the current transformers are the following (as defined by
IEC 44-1 / 44-3):

10

Accuracy class (5 %)
CT intended for motor protection
Multiple of the saturation current

Schneider Electric

125

Complementary
technical information

Protection of motor circuits


Circuit breaker/contactor
coordination
Correspondence table for class 10/10 A and class 20 relays
Thermal relay
Class 10/10 A
LR2-D1305
LR2-D1306
LR2-D1307
LR2-D1308
LR2-D1310
LR2-D1312
LR2-D1314
LR2-D1316
LR2-D1321
LR2-D1322
LR2-D2353
LR2-D2355
LR2-D3322
LR2-D3353
LR2-D3355
LR2-D3357
LR2-D3359
LR2-D3361
LR2-D3363
LR2-D3365
LR9-D5357
LR9-D5363
LR9-D5367
LR9-D5369
LR9-F5357
LR9-F5363
LR9-F5367
LR9-F5369
LR9-F5371
LR9-F7375
LR9-F7379
LR9-F7381
LR2-F7379
LR2-F7381
LR2-F8383
LR2-F8385

Class 20

Setting range
0.63 to 1
1 to 1.6
1.6 to 2.5
2.5 to 4
4 to 6
5.5 to 8
7 to 10
9 to 13
12 to 18
17 to 25
23 to 32
28 to 36
17 to 25
23 to 32
30 to 40
37 to 50
48 to 65
55 to 70
63 to 80
80 to 93
30 to 50
48 to 80
60 to 100
90 to 150
30 to 50
48 to 80
60 to 100
90 to 150
132 to 220
200 to 300
300 to 500
380 to 630
315 to 500
400 to 630
500 to 800
630 to 1000

LR2-D1508
LR2-D1510
LR2-D1512
LR2-D1514
LR2-D1516
LR2-D1521
LR2-D1522
LR2-D2553
LR2-D3522
LR2-D3553
LR2-D3555
LR2-D3557
LR2-D3559
LR2-D3561
LR2-D3563
LR9-D5557
LR9-D5563
LR9-D5567
LR9-D5569
LR9-F5557
LR9-F5563
LR9-F5567
LR9-F5569
LR9-F5571
LR9-F7575
LR9-F7579
LR9-F7581
LR2-F7579
LR2-F7581
LR2-F7583
LR2-F7585

Type 1 coordination tables


Circuit breaker

Direct on-line starting


reverser
page 147

Star-delta
starting
page 150

With short
circuit protection
With short circuit
page 148
and overload protection

page 151

Type 2 coordination tables


Circuit breaker

Direct on-line starting, star-delta or reverser


220/240 V
380/415 V
440 V
500/525 V
p. 128
p. 131
p. 136
p. 141
p. 133
p. 138

Magnetic MA
Magnetic MA +
multifonctional or
thermal relay on CT
Electronic
p. 127

p. 130

p. 135

p. 140

690 V
p. 144

p. 143

b the coordination data for 440 V is valid for 480 V NEMA.

126

Schneider Electric

Type 2 coordination
(IEC 60947-4-1) 220/240 V

E62559

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors

electronic
circuit-breaker

Performance: U = 220/240 V
contactor

Motors

Circuit breakers
NS100-STR22ME
NS160-STR22ME
NS250-STR22ME
NS400-STR43ME
NS630-STR43ME

N
85 kA
85 kA
85 kA
85 kA
85 kA

H
100 kA
100 kA
100 kA
100 kA
100 kA

Starting:
Normal
Long

STR22ME
class 10
-

STR43ME
class 10
class 20

Circuit-breakers

Contactors

P (kW)
1.5
2.2
3
4
5.5
6.3
7.5
10
11
15
18.5
22

I (A) 220 V
6.5
9
12
15
21
24
28
36
39
52
63
75

I (A) 240 V
6
8
11
14
19
22
25
33
36
48
59
70

Ie max (A)
10
10
12.5
20
25
25
40
40
40
80
80
100

Type
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100

Trip unit
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME

Irth (A)
6/10
6/10
7.5/12.5
7.5/20
7.5/25
7.5/25
24/40
24/40
24/40
48/80
48/80
60/100

Irm (A)
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth

30

100

95

100

NS400
NS100

STR43ME
STR22ME

60/120
60/100

13 Irth
13 Irth

37

125

115

150

NS400
NS160

STR43ME
STR22ME

60/120
90/150

13 Irth
13 Irth

45

150

140

150

NS400
NS160

STR43ME
STR22ME

100/200
90/150

13 Irth
13 Irth

55

180

170

185

75
90
110
132
150

250
300
360
430
460

235
280
330
400
450

265
320
400
500
500

NS400
NS250
NS400
NS400
NS400
NS630
NS630
NS630

STR43ME
STR22ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME

100/200
131/220
100/200
160/320
160/320
250/500
250/500
250/500

13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth
13 Irth

Schneider Electric

L
130 kA
130 kA
130 kA
130 kA
130 kA

Type
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
or LC1-F115
LC1-F185
LC1-D115
or LC1-F115
LC1-F185
LC1-D150
or LC1-F150
LC1-F185
LC1-D150
or LC1-F150
LC1-F185
LC1-F185
LC1-F185
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500

127

Type 2 coordination
(IEC 60947-4-1) 220/240 V

E34309

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

magnetic circuit breaker


(MA)

Performance: U = 220/240 V
contactor

Circuit breaker
NS80-MA

thermal relay

N
-

Starting (1): normal

Motors
I (A) 220 V
0.7
0.9
1.2
1.5
2
2.8
3.5
5
6.5
9
12
15
21
24
28

I (A) 240 V
0.6
0.8
1.1
1.4
1.8
2.6
3.2
4.5
6
8
11
14
19
22
25

10

36

33

11

39

36

15

52

48

18.5

63

59

22

75

70

Ie max (A)
1
1
1.6
2.5
2.5
4
4
6
8
10
12.5
18
25
25
32
50
40
50
50
63
80
63
80
80

L
-

LRD2 class 10 A, LR9 class 10

Circuit breakers

P (kW)
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
6.3
7.5

H
100 kA

Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA

Cal. (A)
1.5
1.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50

Irm (A)
13.5
13.5
22.5
32.5
32.5
57
57
82
113
138
163
250
325
325
450

NS80H-MA

50

550

NS80H-MA

50

650

NS80H-MA

80

880

NS80H-MA

80

880

NS80H-MA

80

1040

Contactors (2)

Thermal relays

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D50
LC1-D80
LC1-D50
LC1-D80
LC1-D65
LC1-D80
LC1-D65
LC1-D80
LC1-D80
LC1-D80

Type
LR2-D13 05
LR2-D13 05
LR2-D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D33 22
LR2-D33 22
LR2-D33 53
LR9-D53 57
LR2-D33 55
LR9-D53 57
LR2-D33 57
LR9-D53 57
LR2-D33 59
LR9-D53 63
LR2-D33 59
LR9-D53 63
LR2-D33 63
LR9-D53 63

Irth (1) (A)


0.63/1
0.63/1
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
17/25
23/32
30/50
30/40
30/50
37/50
30/50
48/65
48/80
48/65
48/80
63/80
48/80

(1) For long starting (class 20), see the correspondence table for thermal relays, page 126.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

128

Schneider Electric

Type 2 coordination
(IEC 60947-4-1) 220/240 V

E34309

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

magnetic circuit breaker


(MA)

Performance: U = 220/240 V
contactor

Circuit breakers
NS100-MA
NS160/250-MA
NS400/630-MA

thermal relay

N
85 kA
85 kA
-

Starting (1): normal


Motors
I (A) 220 V
1.2
1.5
2
2.8
3.5
5
6.5
9
12
15
21
24
28

I (A) 240 V
1.1
1.4
1.8
2.6
3.2
4.5
6
8
11
14
19
22
25

70

Ie max (A)
1.6
2.5
2.5
4
4
6
8
10
12.5
18
25
25
32
50
40
50
40
50
63
80
63
80
80

10

36

33

11

39

36

15

52

48

18.5

63

59

22

75

30

100

95

37

125

45
55

Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100MA
NS100-MA
NS100-MA
NS100-MA

Cal. (A)
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50

NS100-MA

50

NS100-MA

50

NS100-MA

100

NS100-MA

100

NS100-MA

100

Irm (A)
22.5
32.5
32.5
57
57
82
113
138
163
250
325
325
450
650
550
650
550
650
700
1100
900
1100
1100

100

NS100-MA

100

1300

115

150

NS160-MA

150

1950

150

140

150

NS160-MA

150

1950

180

170

185
NS250-MA
220
220
NS400-MA
320
75
250
235
265
NS400-MA
320
90
300
270
320
NS400-MA
320
110
360
330
400
NS630-MA
500
132
430
400
500
NS630-MA
500
150
460
450
500
NS630-MA
500
(1) For long starting (class 20), see the correspondence table for thermal relays, page 358.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

L
130 kA
130 kA
130 kA

LR2 class 10 A, LR9 class 10

Circuit breakers

P (kW)
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
6.3
7.5

H
100 kA
100 kA
100 kA

2420
2880
3500
4160
5700
6500
6500

Contactors (2)

Thermal relays

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80

Type
LR2-D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D33 22
LR2-D33 22
LR2-D33 53
LR9-D53 57
LR2-D33 55
LR9-D53 57
LR2-D33 55
LR9-D53 57
LR2-D33 59
LR9-D53 63
LR2-D33 59
LR9-D53 63
LR2-D33 63
LR9-D53 63
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71

Irth (1) (A)


1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
17/25
23/32
30/50
30/40
30/50
30/40
30/50
48/65
48/80
48/65
48/80
63/80
48/80
60/100

LR9-F73 75
LR9-F73 75
LR9-F73 79
LR9-F73 79
LR9-F73 79

200/330
200/330
300/500
300/500
300/500

LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-D150
LC1-F150
LC1-F185
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500

90/150
90/150
132/220

129

Type 2 coordination
(IEC 60947-4-1) 380/415 V

E62559

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors

electronic
circuit-breaker

Performance: U = 380/415 V
Circuit breakers
NS100-STR22ME
NS160-STR22ME
NS250-STR22ME
NS400-STR43ME
NS630-STR43ME
NS630b/1000-Micrologic 5.0

contactor

N
25 kA
35 kA
35 kA
45 kA
45 kA
-

H
70 kA
70 kA
70 kA
70 kA
70 kA
-

L
130 kA
130 kA
130 kA
130 kA
130 kA
130 kA

STR43ME
class 10
class 20

Micrologic 5.0
class 10
class 20

Starting: standard IEC 60947-4-1 , type 2


STR22ME
class 10
-

Normal
Long
Motors

Contactors (1)

Circuit breakers

P(kW)
7.5
10
11
15
18.5
22
30
37
45

I(A) 380V
16
21
23
30
37
44
60
72
85

I(A) 415V
14
19
21
28
35
40
55
66
80

Ie max
20
25
25
40
40
50
80
80
100

265
320
400
500
500
630

Type
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS400
NS160
NS400
NS160
NS400
NS250
NS400
NS250
NS400
NS400
NS400
NS630
NS630
NS630
NS630bL

Trip unit/t.u.
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
Micrologic 5.0

Irth(A)
12/20
15/25
15/25
24/40
24/40
30/50
48/80
48/80
60/100
60/120
90/150
60/120
90/150
100/200
131/220
100/200
131/220
160/200
160/320
160/320
250/500
250/500
250/500
250/630

55

105

100

115

75

138

135

150

90

170

165

185

110

205

200

220

132
160
200
220
250

250
300
370
408
460

240
280
340
385
425

300

565

500

630

NS800L

Micrologic 5.0

320/800

335

620

560

630

NS800L

Micrologic 5.0

320/800

375

670

620

800

NS800L

Micrologic 5.0

320/800

400

710

660

800

NS800L

Micrologic 5.0

320/800

450

800

750

800

NS1000L

Micrologic 5.0

400/1000

Irm(A)
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
Isd = 9Irth (tsd > 0.1)
Ii = 10In
Isd = 9Irth (tsd > 0.1)
Ii = 10In
Isd = 9Irth (tsd > 0.1)
Ii = 11In
Isd = 9Irth (tsd > 0.1)
Ii = 11In
Isd = 9Irth (tsd > 0.1)
Ii = 12In
Isd = 9Irth (tsd > 0.1)
Ii = 10In

Type
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115 or LC1-F115
LC1-F185
LC1-D115 or LC1-F115
LC1-F185
LC1-D150 or LC1-F150
LC1-F185
LC1-F185
LC1-F185
LC1-F225
LC1-F225
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LC1-F800
LC1-F800
LC1-F800

(1) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

130

Schneider Electric

Type 2 coordination
(IEC 60947-4-1) 380/415 V

E34309

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

magnetic circuit breaker


(MA)

Performance: U = 380/415 V
contactor

Circuit breaker
NS80-MA

thermal relay

N
-

Starting (1): normal

Motors

H
70 kA

L
-

LR2 class 10 A, LR9 class 10

Circuit breakers

P (kW)
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15

I (A) 380 V
0.7
0.9
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30

I (A) 415 V
0.6
0.8
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28

Ie max (A)
1
1
1.6
2.5
2.5
4
4
6
8
10
12.5
18
25
25
32

Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA

Cal. (A)
1.5
1.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50

Irm (A)
13.5
13.5
22.5
32.5
32.5
57
57
82
113
138
163
250
325
325
450

18.5

37

34

40

NS80H-MA

50

550

22

43

40

50

NS80H-MA

50

650

30

59

55

63

NS80H-MA

80

880

37

72

66

80

NS80H-MA

80

1040

Contactors (2)

Thermal relays

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D50
LC1-D80
LC1-D50
LC1-D80
LC1-D65
LC1-D80
LC1-D80
LC1-D80

Type
LR2-D13 05
LR2-D13 05
LR2-D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D33 22
LR2-D33 22
LR2-D33 53
LR9-D53 57
LR2-D33 55
LR9-D53 57
LR2-D33 57
LR9-D53 57
LR2-D33 59
LR9-D53 63
LR2-D33 63
LR9-D53 63

Irth (1) (A)


0.63/1
0.63/1
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
17/25
23/32
30/50
30/40
30/50
37/50
30/50
48/65
48/80
63/80
48/80

(1) For long starting (class 20), see the correspondence table for thermal relays, page 358.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

131

Type 2 coordination
(IEC 60947-4-1) 380/415 V

E62560

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

with short circuit


protection

Performance: U = 380/415 V
contactor

Circuit breakers
NS100-MA
NS160/250-MA
NS400/630-MA
NS630b/1000-Micrologic 5.0 (LR OFF)

thermal relay

Starting (1): normal

Motors
I(A) 380V
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30

I(A) 415V
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28

18.5

37

34

22

43

40

30

59

55

37

72

45

85

Ie max
1.6
2.5
2.5
4
4
6
8
10
12.5
18
25
25
32
50
40
50
50

Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA

Cal. (A)
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50

NS100-MA

50

NS100-MA

50

NS100-MA

100

66

63
80
80

NS100-MA

100

Irm(A)
22.5
32.5
32.5
57
57
82
113
138
163
250
325
325
450
650
550
650
650
650
900
1100
1100

L
130 kA
130 kA
130 kA
130 kA

80

100

NS100-MA

100

1300

Contactors (2)

Thermal relays

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80

Type
LR2D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D33 22
LR2-D33 22
LR2-D33 53
LR9-F53 57
LR2-D33 55
LR9-F53 57
LR2-D33 57
LR9-F53 57
LR2-D33 59
LR9-F53 63
LR2-D33 63
LR9-F53 63
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F53 71

Irth (1)
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7 /10
9/13
12/18
17/25
17/25
23/32
30/50
30/40
30/50
37/50
30/50
48/65
48/80
63/80
48/80
60/100

LR9-F73 75
LR9-F73 75
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F7379

200/330
200/330
300/500
300/500
300/500
300/500

LR9-F7381

380/630

LR9-F7381

380/630

LR2-F8385

630/1000

LR2-F8385

630/1000

LR2-F8385

630/1000

LC1-D80
LC1-D80
LC1-D80
LC1-D80

LC1-D115
LC1-F115
55
105
100
115
NS160-MA
150
1500
LC1-D115
LC1-F115
75
140
135
150
NS160-MA
150
1950
LC1-D150
LC1-F150
90
170
160
185
NS250-MA
220
2420
LC1-F185
110
210
200
220
NS250-MA
220
2860
LC1-F225
NS400-MA
320
2880
LC1-F265
132
250
230
265
NS400-MA
320
3500
LC1-F265
160
300
270
320
NS400-MA
320
4160
LC1-F330
200
380
361
400
NS630-MA
500
5700
LC1-F400
220
420
380
500
NS630-MA
500
6500
LC1-F500
250
460
430
500
NS630-MA
500
6500
LC1-F500
500
NS630bL-Micrologic 5.0
630
Isd = 9Irth (tsd > 0.1) LC1-F630
Ii = 10In
300
565
500
630
NS800L-Micrologic 5.0
800
Isd = 9Irth (tsd > 0.1) LC1-F630
Ii = 10In
335
620
560
630
NS800L-Micrologic 5.0
800
Isd = 9Irth (tsd > 0.1) LC1-F630
Ii = 11In
375
670
620
800
NS800L-Micrologic 5.0
800
Isd = 9Irth (tsd > 0.1) LC1-F800
Ii = 11In
400
710
660
800
NS800L-Micrologic 5.0
800
Isd = 9Irth (tsd > 0.1) LC1-F800
Ii = 12In
450
800
750
800
NS1000L-Micrologic 5.0
1000
Isd = 9Irth (tsd > 0.1) LC1-F800
Ii = 10In
(1) For long starting (class 20), see the correspondence table for thermal relays, page 358.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

132

H
70 kA
70 kA
70 kA
-

LRD2 class 10 A, autres class 10

Circuit breakers

P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15

N
25 kA
35 kA
-

90/150
90/150
132/220
132/220

Schneider Electric

E34310

Complementary
technical information

magnetic circuit
breaker (MA)

Type 2 coordination
(IEC 60947-4-1) 380/415 V

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays
Performance: U = 380/415 V

contactor
thermal relay on TC

Motors

Circuit breakers
NS80-MA

N
-

H
70 kA

Starting (1): adjustable class 10 A to 30

Circuit breakers

Contactors (2)

Thermal relays

P (kW)
I (A) 380 V
I (A) 415 V
Ie max (A)
Type
Rating (A)
Irm (A)
Type
Type
0.18
0.7
0.6
1
NS80H-MA 1.5
13.5
LC1-D40
LT6-POM
0.25
0.9
0.8
1
NS80H-MA 1.5
13.5
LC1-D40
LT6-POM
0.37
1.2
1.1
2.5
NS80H-MA 2.5
32.5
LC1-D40
LT6-POM
0.55
1.6
1.5
2.5
NS80H-MA 2.5
32.5
LC1-D40
LT6-POM
0.75
2
1.8
2.5
NS80H-MA 2.5
32.5
LC1-D40
LT6-POM
1.1
2.8
2.6
5
NS80H-MA 6.3
70
LC1-D40
LT6-POM
1.5
3.7
3.4
5
NS80H-MA 6.3
70
LC1-D40
LT6-POM
2.2
5.3
4.8
6.3
NS80.H-MA 6.3
82
LC1-D40
LT6-POM
3
7
6.5
12.5
NS80H-MA 12.5
163
LC1-D40
LT6-POM
4
9
8.2
12.5
NS80H-MA 12.5
163
LC1-D40
LT6-POM
5.5
12
11
12.5
NS80H-MA 12.5
163
LC1-D40
LT6-POM
7.5
16
14
25
NS80H-MA 25
325
LC1-D40
LT6-POM
10
21
19
25
NS80H-MA 25
325
LC1-D40
LT6-POM
11
23
21
25
NS80H-MA 25
325
LC1-D40
LT6-POM
15
30
28
50
NS80H-MA 50
650
LC1-D80
LT6-POM
18.5
37
34
50
NS80H-MA 50
650
LC1-D80
LT6-POM
22
43
40
50
NS80H-MA 50
650
LC1-D80
LT6-POM
30
59
55
80
NS80H-MA 80
1040
LC1-D80
LT6-POM
37
72
66
80
NS80H-MA 80
1040
LC1-D80
LT6-POM
(1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

L
-

Irth (1) (A)


0.2/1
0.2/1
1/5
1/5
1/5
1/5
1/5
5/25
5/25
5/25
5/25
5/25
5/25
5/25
on TC
on TC
on TC
on TC
on TC

133

Type 2 coordination
(IEC 60947-4-1) 380/415 V

E62565

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

with short
circuit breaker
protection

Performance: U = 380/415 V
contactor

Circuit breakers
NS100-MA
NS160/250-MA
NS400/630-MA
NS630b/1000-Micrologic 5.0 (LT OFF)

thermal relay on TC

N
25 kA
35 kA
-

H
70 kA
70 kA
70 kA
-

L
130 kA
130 kA
130 kA
130 kA

Starting (1): adjustable class 10 A to 30

Motors

Contactors (2)

Circuit breakers

Thermal relays

Type
Type
Irth (1)
LC1-D40
LT6-P0M
1/5
LC1-D40
LT6-P0M
1/5
LC1-D40
LT6-P0M
1/5
LC1-D40
LT6-P0M
1/5
LC1-D40
LT6-P0M
1/5
LC1-D40
LT6-P0M
5/25
LC1-D80
LT6-P0M
5/25
LC1-D80
LT6-P0M
5/25
LC1-D80
LT6-P0M
5/25
LC1-D80
LT6-P0M
5/25
LC1-D80
LT6-P0M
5/25
LC1-D80
LT6-P0M
5/25
LC1-D80
LT6-P0M
on TI
LC1-D80
LT6-P0M
on TI
LC1-D80
LT6-P0M
on TI
LC1-D80
LT6-P0M
on TI
LC1-D80
LT6-P0M
on TI
LC1-D115
LT6-P0M
on TI
LC1-F115
55
105
100
115
NS160-MA
150
1500
LC1-D115
LT6-P0M
on TI
LC1-F115
75
140
135
150
NS160-MA
150
1950
LC1-D150
LT6-P0M
on TI
LC1-F150
90
170
160
185
NS250-MA
220
2420
LC1-F185
LT6-P0M
on TI
110
210
200
220
NS250-MA
220
2860
LC1-F225
LT6-P0M
on TI
265
NS400-MA
320
3500
LC1-F265
132
250
230
265
NS400-MA
320
3500
LC1-F265
LT6-P0M
on TI
160
300
270
320
NS400-MA
320
4000
LC1-F330
LT6-P0M
on TI
200
380
361
400
NS630-MA
500
5700
LC1-F400
LT6-P0M
on TI
220
420
380
500
NS630-MA
500
6300
LC1-F500
LT6-P0M
on TI
250
460
430
500
NS630-MA
500
6300
LC1-F500
LT6-P0M
on TI
630
NS630bL-Micrologic 5.0 630
Isd = 9 Irth (tsd > 0.1) LC1-F630
LT6-P0M
on TI
Ii = 10 In
300
565
500
630
NS800L-Micrologic 5.0 800
Isd = 9 Irth (tsd > 0.1) LC1-F630
LT6-P0M
on TI
Ii = 10 In
335
620
560
630
NS800L-Micrologic 5.0 800
Isd = 9Irth (tsd > 0.1) LC1-F630
LT6-P0M
on TI
Ii = 11 In
375
670
620
800
NS800L-Micrologic 5.0 800
Isd = 9Irth (tsd > 0.1) LC1-F800
LT6-P0M
on TI
Ii = 11 In
400
710
660
800
NS800L-Micrologic 5.0 800
Isd = 9Irth (tsd > 0.1) LC1-F800
LT6-P0M
on TI
Ii = 12 In
450
800
750
800
NS1000L-Micrologic 5.0 1000
Isd = 9 Irth (tsd > 0.1) LC1-F800
LT6-P0M
on TI
Ii = 10 In
(1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45

134

I(A) 380V
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30
37
43
59
72
85

I(A) 415V
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28
34
40
55
66
80

Ie max
2.5
2.5
2.5
5
5
6.3
12.5
12.5
12.5
25
25
25
50
50
50
80
80
100

Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA

Rating (A)
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
50
100
100
100

Irm(A)
32.5
32.5
32.5
70
70
82
163
163
163
325
325
325
650
650
650
1100
1100
1300

Schneider Electric

Type 2 coordination
(IEC 60947-4-1) 440 V

E62562

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors

with short circuit


and overload
protection

Performance (1): U = 440V


Circuit breakers
NS100-STR22ME
NS160-STR22ME
NS250-STR22ME
NS400-STR43ME
NS630-STR43ME
NS630b-Micrologic 5.0

contactor

N
25 kA
35 kA
35 kA
42 kA
42 kA
-

H
65 kA
65 kA
65 kA
65 kA
65 kA
-

L
130 kA
130 kA
130 kA
130 kA
130 kA
130 kA

STR22ME
class10

STR43ME
class10
class 20

Micrologic 5.0
class 10
class 20

Starting: standard IEC 60947-4-1, type 2


Normal
Long
Motors

Contactors (2)

Circuit breakers

P(kW)
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55

I(A) 440V
5.8
8
10.5
13.7
19
20
26.5
33
39
51
64
76
90

Ie max
10
10
12.5
20
25
25
40
40
40
80
80
80
100

265
320
400
400
500
630

Type
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS400
NS160
NS400
NS160
NS400
NS250
NS400
NS250
NS400
NS400
NS400
NS630
NS630
NS630
NS630bL

Trip unit t.u.


STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
Micrologic 5.0

Irth(A)
6/10
6/10
7.5/12.5
12/20
15/25
15/25
24/40
24/40
24/40
48/80
48/80
48/80
60/100
60/120
90/150
100/200
90/150
100/200
131/220
100/200
131/220
160/3200
160/320
160/320
250/500
250/500
250/500
250/630

75

125

150

90

146

150

110

178

185

132

215

220

160
200
220
250
300

256
320
353
400
460

335

518

630

NS630bL

Micrologic 5.0

250/630

375

575

630

NS630bL

Micrologic 5.0

250/630

400

611

800

NS800L

Micrologic 5.0

320/800

450

720

800

NS800L

Micrologic 5.0

320/800

Irm(A)
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
Isd = 9 Irth (tsd > 0.1)
Ii = 10 In
Isd = 9 Irth (tsd > 0.1)
Ii = 11In
Isd = 9 Irth (tsd > 0.1)
Ii = 12In
Isd = 9 Irth (tsd > 0.1)
Ii = 10In
Isd = 9 Irth (tsd > 0.1)
Ii = 12In

Type
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115 or LC1-F115
LC1-F185
LC1-D150 or LC1-F150
LC1-F185
LC1-D150 or LC1-F150
LC1-F185
LC1-F185
LC1-F185
LC1-F225
LC1-F225
LC1-F265
LC1-F330
LC1-F400
LC1-F400
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LC1-F800
LC1-F800

(2) Valid for 480 V NEMA.


(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

135

Type 2 coordination
(IEC 60947-4-1) 440 V

E34309

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

magnetic circuit breaker


(MA)

Performance (2): U = 440 V


contactor

Circuit breakers
NS80-MA

thermal relay

Starting (1): normal

Motors

Circuit breakers

P (kW)
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5

I (A) 440 V
0.7
1
1.4
1.7
2.4
3.1
4.5
5.8
8
10.5
13.7
19
20
26.5
33

22

39

30

52

37

63

45

76

Ie max (A)
1
1.6
1.6
2.5
2.5
4
6
6
8
12.5
18
25
25
32
40
50
40
50
63
80
63
80
80

Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA

Rating (A)
1.5
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
50

NS80H-MA

50

NS80H-MA

80

NS80H-MA

80

NS80H-MA

80

Irm (A)
13.5
22.5
22.5
32.5
32.5
57
82
82
113
163
250
325
325
450
550
650
550
650
880
1040
880
1040
1040

N
-

H
65 kA

L
-

LR2 class 10 A, LR9 class 10

Contactors (3)

Thermal relays

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D50
LC1-D80
LC1-D50
LC1-D80
LC1-D65
LC1-D80
LC1-D65
LC1-D80
LC1-D80

Type
LR2-D13 05
LR2-D13 06
LR2-D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 10
LR2-D13 10
LR2-D13 12
LR2-D13 16
LR2-D13 21
LR2-D33 22
LR2-D33 22
LR2-D33 53
LR2-D33 55
LR9-D53 57
LR2-D33 55
LR9-D53 57
LR2-D33 59
LR9-D53 63
LR2-D33 59
LR9-D53 63
LR2-D33 63
LR9-D53 63

Irth (1) (A)


0.63/1
1/1.6
1/1.6
1.6/2.5
1.6/2.5
2.5/4
4/6
4/6
5.5/8
9/13
12/18
17/25
17/25
23/32
30/40
30/50
30/40
30/50
48/65
48/80
48/65
48/80
63/80
48/80

(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

136

Schneider Electric

E62560

Complementary
technical information

Type 2 coordination
(IEC 60947-4-1) 440 V

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

with short circuit


protection

Performance (2): U = 440V


contactor

Circuit breakers
NS100-MA
NS160/250-MA
NS400/630-MA
NS630b/800-Micrologic 5.0 (LT OFF)

thermal relay

Starting (1): normal

Motors

Circuit breakers

P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5

I(A) 440V
1
1.4
1.7
2.4
3.1
4.5
5.8
8
10.5
13.7
19
20
26.5
33

Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA

Rating (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
50

NS100-MA

50

NS100-MA

100

NS100-MA

100

76

Ie max
1.6
1.6
2.5
2.5
4
6
6
8
12.5
18
25
25
32
40
50
40
50
63
80
63
80
80

NS100-MA

100

Irm(A)
22.5
22.5
32.5
32.5
57
82
82
113
163
250
325
325
450
550
650
550
650
900
1100
900
1100
1100

22

39

30

52

37

63

45
55

90

100

NS100-MA

100

1300

75

125

150

NS160-MA

150

1950

90

140

150

NS160-MA

150

1950

110
132

178
210

160
200
220
250
300

256
310
353
400
460

185
220
265
265
320
400
500
500

NS250-MA
NS250-MA
NS400-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA

220
220
320
320
320
500
500
500

2420
2860
3500
3500
4160
5500
6500
6500

630

NS630bL-Micrologic 5.0

630

Isd = 9 Irth (tsd > 0.1)


Ii = 10 In
335
518
630
NS630bL-Micrologic 5.0 630
Isd = 9 Irth (tsd > 0.1)
Ii = 11 In
375
575
630
NS630bL-Micrologic 5.0 630
Isd = 9 Irth (tsd > 0.1)
Ii = 12 In
400
611
630
NS800L-Micrologic 5.0
800
Isd = 9 Irth (tsd > 0.1)
Ii = 10 In
450
720
800
NS800L-Micrologic 5.0
800
Isd = 9 Irth (tsd > 0.1)
Ii = 12 In
(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

N
25 kA
35 kA
-

H
65 kA
65 kA
65 kA
-

L
130 kA
130 kA
130 kA
130 kA

LRD2 class 10 A, LR9 class 10

Contactors (3)

Thermal relays

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80

Type
LR2-D13 06
LR2-D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 10
LR2-D13 10
LR2-D13 12
LR2-D13 16
LR2-D13 21
LR2-D33 22
LR2-D33 22
LR2-D33 53
LR2-D33 55
LR9-F53 57
LR2-D33 55
LR9-D53 57
LR2-D33 59
LR9-D53 63
LR2-D33 59
LR9-D53 63
LR2-D33 63
LR9-D53 63
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F53 71

Irth (1)
1/1.6
1/1.6
1.6/2.5
1.6/2.5
2.5/4
4/6
4/6
5.5/8
9/13
12/18
17/25
17/25
23/32
30/40
30/50
30/40
30/50
48/65
48/80
48/65
48/80
63/80
48/80
60/100

LC1-F630

LR9-F73 75
LR9-F73 75
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR2-F73 79
LR9-F75 80

200/330
200/330
300/500
300/500
300/500
315/500
380/630

LC1-F630

LR9-F75 80

380/630

LC1-F630

LR9-F75 80

380/630

LC1-F800

LR9-F75 80

380/630

LC1-F800

LR2-F75 83

500/800

LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-D150
LC1-F150
LC1-F185
LC1-F225
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500

90/150
90/150
132/220
132/220

137

E34310

Complementary
technical information

Type 2 coordination
(IEC 60947-4-1) 440 V

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

magnetic circuit
breaker (MA)

Performance (2): U = 440 V


contactor

Circuit breakers
NS80 MA

thermal relay on TC

Motors

N
-

H
65 kA

L
-

Starting (1): adjustable class 10 A to 30

Circuit breakers

Contactors (3)

Thermal relays

P (kW)
I (A) 440 V Ie max (A) Type
Rating (A) Irm (A)
Type
Type
Irth (1) (A)
0,25
0,7
1
NS80H-MA
1,5
13,5
LC1-D40
LT6-POM
0,2/1
0,37
1
2,5
NS80H-MA
2,5
32,5
LC1-D40
LT6-POM
1/5
0,55
1,4
2,5
NS80H-MA
2,5
32,5
LC1-D40
LT6-POM
1/5
0,75
1,7
2,5
NS80H-MA
2,5
32,5
LC1-D40
LT6-POM
1/5
1,1
2,4
2,5
NS80H-MA
2,5
32,5
LC1-D40
LT6-POM
1/5
1,5
3,1
4
NS80H-MA
6,3
82
LC1-D40
LT6-POM
1/5
2,2
4,5
5
NS80H-MA
6,3
82
LC1-D40
LT6-POM
1/5
3
5,8
6,3
NS80H-MA
6,3
82
LC1-D40
LT6-POM
5/25
4
8
12,5
NS80H-MA
12,5
163
LC1-D40
LT6-POM
5/25
5,5
10,5
12,5
NS80H-MA
12,5
163
LC1-D40
LT6-POM
5/25
7,5
13,7
25
NS80H-MA
25
325
LC1-D40
LT6-POM
5/25
10
19
25
NS80H-MA
25
325
LC1-D40
LT6-POM
5/25
11
20
25
NS80H-MA
25
325
LC1-D40
LT6-POM
5/25
15
26,5
50
NS80H-MA
50
550
LC1-D80
LT6-POM
on TC
18,5
33
50
NS80H-MA
50
550
LC1-D80
LT6-POM
on TC
22
39
50
NS80H-MA
50
550
LC1-D80
LT6-POM
on TC
30
52
80
NS80H-MA
80
1040
LC1-D80
LT6-POM
on TC
37
63
80
NS80H-MA
80
1040
LC1-D80
LT6-POM
on TC
45
76
80
NS80H-MA
80
1040
LC1-D80
LT6-POM
on TC
(1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

138

Schneider Electric

Type 2 coordination
(IEC 60947-4-1) 440 V

E62565

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

with short
circuit breaker
protection

Performance (2): U = 440V


contactor

Circuit breakers
NS100-MA
NS160/250-MA
NS400/630-MA
NS630b/1000-Micrologic 5.0 (LR OFF)

thermal relay on TC

N
25 kA
35 kA
-

H
65 kA
65 kA
65 kA
-

L
130 kA
130 kA
130 kA
130 kA

Starting (1): adjustable class 10 A to 30

Motors

Circuit breakers

P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55

I(A) 440V
1
1.4
1.7
2.4
3.1
4.5
5.8
8
10.5
13.7
19
20
26.5
33
39
52
63
76
90

Ie max
2.5
2.5
2.5
2.5
5
5
6.3
12.5
12.5
25
25
25
50
50
50
80
80
80
100

Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA

Rating (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
50
50
100
100
100
100

Irm(A)
32.5
32.5
32.5
32.5
82
82
82
163
163
325
325
325
550
550
550
1100
1100
1100
1300

75

125

150

NS160-MA

150

1950

90

140

150

NS160-MA

150

1950

110
132

178
210

185
220
265
265
320
400
500
500
630

NS250-MA
NS250-MA
NS400-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA
NS630bL-Micrologic 5.0

220
220
320
320
320
500
500
500
630

Contactors (3)

Thermal relays

Type
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-D150
LC1-F150
LC1-F185
LC1-F225
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
LC1-F630

Type
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M

Irth (1)
1/5
1/5
1/5
1/5
1/5
1/5
5/25
5/25
5/25
5/25
5/25
5/25
on TI
on TI
on TI
on TI
on TI
on TI
on TI

LT6-P0M

on TI

LT6-P0M

on TI

2420
LT6-P0M
on TI
2860
LT6-P0M
on TI
3500
160
256
3500
LT6-P0M
on TI
200
310
4000
LT6-P0M
on TI
220
353
5500
LT6-P0M
on TI
250
400
6500
LT6-P0M
on TI
300
460
6500
LT6-P0M
on TI
Isd = 9 Irth (tsd > 0.1)
LT6-P0M
on TI
Ii = 10 In
335
518
630
NS630bL-Micrologic 5.0 630
Isd = 9 Irth (tsd > 0.1)
LC1-F630
LT6-P0M
on TI
Ii = 11 In
375
575
630
NS630bL-Micrologic 5.0 630
Isd = 9Irth (tsd > 0.1)
LC1-F630
LT6-P0M
on TI
Ii = 12 In
400
611
800
NS800L-Micrologic 5.0
800
Isd = 9 Irth (tsd > 0.1)
LC1-F800
LT6-P0M
on TI
Ii = 10 In
450
720
800
NS800L-Micrologic 5.0
800
Isd = 9 Irth (tsd > 0.1)
LC1-F800
LT6-P0M
on TI
Ii = 12 In
(1) Observe the recommendations on page 126 for installations with a class 30 relay and mounting of the thermal relay on the current transformer.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

139

Type 2 coordination
(IEC 60947-4-1) 500/525 V

E62562

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors

with short circuit


and overload
protection

Performance: U = 500/525 V
Circuit breakers
NS100-STR22ME
NS160-STR22ME
NS250-STR22ME
NS400-STR43ME
NS630-STR43ME
NS630b/800-Micrologic 5.0

contactor

H
50/35 kA
50/35 kA
50/35 kA
50/35 kA
50/35 kA
-

L
70/50 kA
70/50 kA
70/50 kA
70/50 kA
70/50 kA
100/100kA

Starting: standard IEC 60947-4-1 , type 2


STR22ME
class 10
-

Normal
Long

Motors

STR43ME
class 10
class 20

Contactors (1)

Circuit breakers

P(kW)
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55

I(A) 500V
6.5
9
12
15
18.4
23
28.5
33
45
55
65
75

I(A) 525V
6.5
9
12
15
18.4
23
28.5
33
45
55
65
75

Ie max
10
12.5
12.5
20
20
25
40
40
50
80
80
100

75

105

105

115

90

130

130

150

110

155

155

185

132

185

185

220

160
200
220
250
315
335

220
280
310
360
445
472

220
280
310
360
445
472

375

527

400
450

Micrologic 5.0
class 10
class 20

265
320
320
500
500
500

Type
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS100
NS400
NS160
NS400
NS160
NS400
NS250
NS400
NS250
NS400
NS400
NS400
NS630
NS630
NS630
NS630bL

Trip unit t.u.


STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR22ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
Micrologic 5.0

Irth(A)
6/10
7.5/12.5
7.5/12.5
12/20
12/20
15/25
24/40
24/40
30/50
48/80
48/80
60/100
60/120
90/150
60/120
90/150
100/200
131/220
100/200
131/220
160/320
160/320
160/320
250/500
250/500
250/500
250/630

527

630

NS630bL

Micrologic 5.0

250/630

540

540

630

NS630bL

Micrologic 5.0

250/630

608

608

800

NS800L

Micrologic 5.0

320/800

Irm(A)
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
Isd = 9 Irth (tsd > 0.1)
Ii = 10 In
Isd = 9 Irth (tsd > 0.1)
Ii = 11 In
Isd = 9 Irth (tsd > 0.1)
Ii = 12 In
Isd = 9 Irth (tsd > 0.1)
Ii = 10 In

Type
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115 or LC1-F115
LC1-F185
LC1-D115 or LC1-F115
LC1-F185
LC1-D150 or LC1-F150
LC1-F185
LC1-F185
LC1-F185
LC1-F265
LC1-F265
LC1-F265
LC1-F400
LC1-F500
LC1-F500
LC1-F500
LC1-F500
LC1-F630
LC1-F630
LC1-F800

(1) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

140

Schneider Electric

Type 2 coordination
(IEC 60947-4-1) 500/525 V

E34309

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

magnetic circuit breaker


(MA)

Performance: U = 500/525 V
contactor

Circuit breakers
NS80-MA

thermal relay

H
35 kA

Starting (1): normal

Motors

L
-

LR2 class 10 A, LR9 class 10

Circuit breakers

P (kW)
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22

I (A) 500 V
0.6
0.9
1.2
1.5
2
2.8
3.8
5
6.5
9
12
15
18.4
23
28.5
33

I (A) 525 V
0.6
0.9
1.2
1.5
2
2.8
3.8
5
6.5
9
12
15
18.4
23
28.5
33

Ie max (A)
1
1
1.6
1.6
2.5
4
4
6
8
10
12.5
16
25
25
32
40
50

Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA

Rating (A)
1.5
1.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50

Irm (A)
13.5
13.5
22.5
22.5
32.5
57
57
82
113
138
163
250
325
325
450
550
650

30

45

45

50

NS80H-MA

50

650

37

55

55

63
80

NS80H-MA

80

880
1040

45

65

65

80

NS80H-MA

80

1040

55

75

75

80

NS80H-MA

80

1040

Contactors (2)

Thermal relays (1)

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D50
LC1-D115
LC1-F115
LC1-D50
LC1-D115
LC1-F115
LC1-D65
LC1-D115
LC1-F115
LC1-D115
LC1-F115
LC1-D115
LC1-F115

Type
LR2-D13 05
LR2-D13 05
LR2-D13 06
LR2-D13 06
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D33 21
LR2-D33 22
LR2-D33 22
LR2-D33 53
LR2-D33 55
LR9-D53 57
LR9-F53 57
LR2-D33 57
LR9-D53 57
LR9-F53 57
LR2-D33 59
LR9-D53 63
LR9-F53 63
LR2-D33 63
LR9-D53 63
LR9-F53 63
LR9-D53 63

Irth (A)
0.63/1
0.63/1
1/1.6
1/1.6
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
17/25
23/32
30/40
30/50
30/50
37/50
30/50
30/50
48/65
48/80
48/80
63/80
48/80
48/80
48/80

(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

141

Type 2 coordination
(IEC 60947-4-1) 500/525 V

E62560

Complementary
technical information

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

with short circuit


protection

Performance: U = 500/525 V
contactor

Circuit breakers
NS100-MA
NS160/250-MA
NS400/630-MA
NS630b/800-Micrologic 5.0 (LT OFF)

thermal relay

Starting (1): normal

Motors
P(KW)
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
30
45
45
50
NS100-MA
50
650
LC1-D80
LC1-D115
LC1-F115
37
55
55
63
NS100-MA
100
900
LC1-D80
80
1100
LC1-D115
LC1-F115
45
65
65
80
NS100-MA
100
1100
LC1-D115
LC1-F115
55
75
75
100
NS100-MA
100
1300
LC1-D115
LC1-F115
75
105
105
115
NS160-MA
150
1500
LC1-D115
LC1-F115
90
130
130
150
NS160-MA
150
1950
LC1-D150
LC1-F150
110
156
156
185
NS250-MA
220
2420
LC1-F185
132
187
187
220
NS250-MA
220
2860
LC1-F265
160
230
220
320
NS400-MA
320
4160
LC1-F400
200
280
280
320
NS400-MA
320
4160
LC1-F400
220
310
310
330
NS630-MA
500
4500
LC1-F500
250
360
360
500
NS630-MA
500
6500
LC1-F500
315
445
445
500
NS630-MA
500
6500
LC1-F500
335
472
472
500
NS630bL-Micrologic 5.0 630
Isd = 9 Irth (tsd > 0.1) LC1-F500
Ii = 10 In
375
527
527
630
NS630bL-Micrologic 5.0 630
Isd = 9 Irth (tsd > 0.1) LC1-F630
Ii = 11 In
400
540
540
630
NS630bL-Micrologic 5.0 630
Isd = 9 Irth (tsd > 0.1) LC1-F630
Ii = 12 In
450
608
608
630
NS800L-Micrologic 5.0 800
Isd = 9 Irth (tsd > 0.1) LC1-F800
Ii = 10 In
(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

142

I(A) 525V
1.2
1.5
2
2.8
3.8
5
6.5
9
12
15
18.4
23
28.5
33

Ie max
1.6
1.6
2.5
4
4
6
8
10
12.5
16
25
25
32
40
50

Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA

Rating (A)
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50

Irm(A)
22.5
22.5
32.5
57
57
82
113
138
163
250
325
325
450
550
650

L
70/50 kA
70/50 kA
70/50 kA
100/100 kA

LRD2 class 10 A, autres class 10

Contactors (2)

Circuit breakers
I(A) 500V
1.2
1.5
2
2.8
3.8
5
6.5
9
12
15
18.4
23
28.5
33

H
50/35 kA
50/35 kA
50/35 kA
-

Thermal relays (1)


Type
LR2-D13 06
LR2-D13 06
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D33 22
LR2-D33 22
LR2-D33 55
LR2-D33 55
LR9-D53 57
LR9-F53 57
LR2-D33 57
LR9-D53 57
LR9-F53 57
LR2-D33 59
LR9-D53 63
LR9-F53 63
LR9-D53 63
LR9-F53 63
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F53 71
LR9-F73 75
LR9-F73 75
LR9-F73 75
LR9-F73 79
LR9-F73 79
LR9-F73 79

Irth
1/1.6
1/1.6
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
17/25
23/32
23/32
30/50
30/50
30/40
30/50
30/50
48/65
48/80
48/80
48/80

LR9-F75 81

380/630

LR9-F75 81

380/630

LR9-F75 81

380/630

60/100
90/150
90/150
132/220
132/220
200/330
200/330
200/330
300/500
300/500
300/500

Schneider Electric

Type 2 coordination
(IEC 60947-4-1) 690 V

Complementary
technical information

E34308

Merlin Gerin circuit breakers,Telemecanique


contactors

thermal-magnetic
motor circuit-breaker

Performance: U = 690 V
Circuit breakers
NS100L-STR22ME
NS400L-STR43ME

contactor

L
75 kA
75 kA

Starting: standard IEC 60947-4-1, type 2


STR22ME
class10
-

Normal
Long

Motors
P(kW)
5.5
7.5
10
15
18.5
22
30
37
45
55
75

Contactors (2)

Circuit breakers
I(A) 690V
6.6
8.9
11.5
17
20.2
24.2
33
40
47
58
76

Ie max
Type
Trip unit t.u.
10
NS100L
STR22ME
10
NS100L
STR22ME
13
NS100L
STR22ME
18
NS100L
STR22ME
25
NS100L
STR22ME
40
NS100L
STR22ME
50
NS100L
STR22ME
50
NS100L
STR22ME
50
NS100L
STR22ME
63
NS100L
STR22ME
80
NS100L
STR22ME
165
NS400L
STR43ME
90
94
165
NS400L
STR43ME
110
113
165
NS400L
STR43ME
132
135
165
NS400L
STR43ME
160
165
165
NS400L
STR43ME
200
203
230
NS400L
STR43ME
220
224
230
NS400L
STR43ME
250
253
280
NS400L
STR43ME
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

STR43ME
class10
class 20

Irth(A)
6/10
6/10
7.5/12.5
12/20
12/20
24/40
30/50
30/50
30/50
48/80
60/100
60/120
60/120
100/200
100/200
100/200
160/320
160/320
160/320

Irm(A)
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth
13Irth

Type
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1F-115
LC1F-115
LC1F-265
LC1F-265
LC1F-265
LC1F-265
LC1F-265
LC1F-330
LC1F-330
LC1F-400

143

E34309

Complementary
technical information

Type 2 coordination
(IEC 60947-4-1) 690 V

Merlin Gerin circuit breakers,Telemecanique


contactors and thermal relays

magnetic circuit breaker


(MA)

Performance: U = 690 V
contactor

Circuit breakers
NS100L-MA
NS400L-MA

thermal relay

Starting (1): normal

Motors

Circuit breakers

P(kW)
I(A) 690V Ie max
Type
Rating (A) Irm(A)
0.75
1.2
1.6
NS100L MA
2.5
22.5
1
1.5
2
NS100L MA
2.5
27.5
1.5
2
2.5
NS100L MA
2.5
32.5
2.2
2.8
4
NS100L MA
6.3
57
3
3.8
4
NS100L MA
6.3
57
4
4.9
6
NS100L MA
6.3
82
5.5
6.6
8
NS100L MA
12.5
113
7.5
8.9
10
NS100L MA
12.5
138
10
11.5
13
NS100L MA
25
175
15
17
18
NS100L MA
25
250
18.5
20.2
25
NS100L MA
25
325
22
24.2
25
NS100L MA
25
325
30
33
50
NS100L MA
50
650
37
40
50
NS100L MA
50
650
45
47
50
NS100L MA
50
650
55
58
80
NS100L MA
100
1100
75
76
80
NS100L MA
100
1100
90
94
100
NS400L MA
320
2880
110
113
150
NS400L MA
320
2880
132
135
150
NS400L MA
320
2880
160
165
165
NS400L MA
320
2880
200
203
230
NS400L MA
320
2880
220
224
230
NS400L MA
320
2880
250
253
280
NS400L MA
320
3520
(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

144

L
75 kA
75 kA

LRD2 class 10 A autres class 10

Contactors (2)

Thermal relays

Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1F-115
LC1F-115
LC1F-265
LC1F-265
LC1F-265
LC1F-265
LC1F-330
LC1F-330
LC1F-400

Type
LR2-D13 06
LR2-D13 06
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D13 22
LR2-D13 22
LR9-D53 57
LR9-D53 57
LR9-D53 57
LR9-F53 63
LR9-F53 63
LR9-F53 67
LR9-F53 69
LR9-F53 69
LR9-F53 71
LR9-F73 75
LR9-F73 75
LR9-F73 75

Irth (1)
1/1.6
1.25/2
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
12/18
17/25
17/25
30/50
30/50
30/50
48/80
48/80
60/100
90/150
90/150
132/220
200/330
200/330
200/330

Schneider Electric

Type 1 coordination
(IEC 60947-4-1)

E34309

Complementary
technical information

magnetic circuit breaker


(MA)

Merlin Gerin NS80 circuit breakers,


Telemecanique contactors and thermal relays

contactor

Direct-on-line starting

thermal relay

Reserver
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker
alone.
Starting (1): normal
LR2 class 10 A, LR9 class 10

Motors
220/230 V
P

(kW) (A)

Circuit breakers
380 V

440 V (2)

415 V

500/525 V

(kW)
0.37
0.55
0.75

(A)
1.2
1.6
2

(kW)
0.37
0.55
0.75

(A)
1.1
1.5
1.8

(kW)
0.37
0.55
0.75
1.1

(A)
1
1.4
1.7
2.4

(kW)
0.55
0.75

(A)
1.2
1.5

(kW)
0.75
1

(A)
1.2
1.5

2.8
3.7
5
6.6
8.5

1.1
1.5
2.2
3
4

2.5
3.5
4.8
6.5
8.2

1.1
1.5

2
2.6

1.5
2.2
3
4

3.1
4.5
5.8
7.9

3
4
5.5

5
6.5
9

1.5
2.2
3
4
5.5

2
2.8
3.8
4.9
6.6

7.5

8.9

10

11.5

15
18.5

17
21.3

0.37

1.8

0.55

2.8

1.1
1.5
2.2

4.4
6.1
8.7

1.1
1.5
2.2
3
4

3
4

11.5
14.5

5.5
7.5

11.5
15.5

5.5
7.5
9

11
14
17

5.5
7.5
9

10.4
13.7
16.9

7.5
9
10

12
14
15

5.5

20

11

22

11

21

11

20.1

11

18.4

7.5

28

15

30

15

28

15

26.5

11

39

18.5
22

37
44

22
25

40
47

22

39

15

52

30

51.5

18.5

64

30

59

30
37

55
66

37

22

75

37

72

45

80

45

18.5
22

28.5
33

30

34.6

30

45

33

39

37

42

64

37

55
45

49

76

55

80

Type

Rating Type

NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA

(A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
12.5
25
25
25
25
25
50
50
50
50
50
50
50
80
80
80
80
80

55
60
75
80
(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

Contactors (3)

Thermal relays (1)

660/690 V

LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D12
LC1-D18
LC1-D18
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D50
LC1-D50
LC1-D65
LC1-D65
LC1-D65
LC1-D80
LC1-D80
LC1-D115
LC1-F115

Type
LR2-D13 06
LR2-D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D13 21
LR2-D13 16
LR2-D13 22
LR2-D13 21
LR2-D13 22
LR2-D33 53
LR2-D33 55
LR2-D33 57
LR2-D33 57
LR2-D33 59
LR2-D33 57
LR2-D33 59
LR2-D33 61
LR2-D33 57
LR2-D33 63
LR9-D53 63
LR9-F53 63

Irth
(A)
1/1.6
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
7/10
9/13
12/18
12/18
9/13
17/25
12/18
17/25
23/32
30/40
37/50
37/50
48/65
37/50
48/65
55/70
37/50
63/80
48/80

145

Type 1 coordination
(IEC 60947-4-1)

Complementary
technical information

E34309

Merlin Gerin NS100 circuit breakers,


Telemecanique contactors and thermal relays

magnetic circuit breaker


(MA)

Direct-on-line starting

contactor

Reserver

thermal relay

"Iq" breaking performance: equal to the breaking capacity of the circuit breaker
alone
Starting (1): normal
LR2 class 10 A, LR9 class 10

Motors

Circuit breakers

220/230 V 380 V
P

(kW) (A)

0.37 1.8
0.55 2.8

440 V (2)

415 V

(kW)
0.37
0.55
0.75

(A)
1.2
1.6
2

(kW)
0.37
0.55
0.75

(A)
1.1
1.5
1.8

(kW)
0.37
0.55
0.75
1.1

(A)
1
1.4
1.7
2.4

(kW) (A)
0.55 1.2
0.75 1.5

1.1
1.5
2.2
3
4

2.8
3.7
5
6.6
8.5

1.1
1.5
2.2
3
4

2.5
3.5
4.8
6.5
8.2

1.5
2.2
3
4

3.1
4.5
5.8
7.9

1.1
1.5
2.2

4.4
6.1
8.7

3
4

11.5 5.5
14.5 7.5

11.5 5.5
15.5 7.5
9

11
14
17

5.5
7.5
9

10.4
13.7
16.9

5.5

20

11

22

11

21

11

20.1

7.5

28

15

30

15

28

15

26.5

11

39

18.5 37

22

40

22

39

22

25

47

15
52
18.5 64

500/525 V

30

44

59

30

55

51.5
64
37

45

75

37

72

25

85

45

85

30

100

37
45

55

72
80

100

45

55

76

96

55

Thermal relays (1)

Type

Rating

Type

Type

(A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
12.5
25
25
25
25
25
50
50
50

LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D12
LC1-D18
LC1-D18
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D40

NS100N/H/L-MA

50

LC1-D40

33

39

NS100N/H/L-MA

50

LC1-D50

37

42

NS100N/H/L-MA

50

LC1-D65

NS100N/H/L-MA

100

LC1-D65

NS100N/H/L-MA

100

LC1-D80

NS100N/H/L-MA

100

LC1-D80

NS100N/H/L-MA

100

LC1-D95
LC1-D115
LC1-F115
LC1-D115
LC1-F115

55
45

22

(kW) (A)
0.75 1.2
1
1.5

NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
1.1 2
1.5 2
NS100N/H/L-MA
1.5 2.6 2.2 2.8 NS100N/H/L-MA
3
3.8 NS100N/H/L-MA
3
5
4
4.9 NS100N/H/L-MA
4
6.5 5.5 6.6 NS100N/H/L-MA
5.5 9
NS100N/H/L-MA
7.5 8.9 NS100N/H/L-MA
7.5 12
NS100N/H/L-MA
9
14
NS100N/H/L-MA
10
15
NS100N/H/L-MA
10
11.5 NS100N/H/L-MA
11
18.4
NS100N/H/L-MA
15
17
NS100N/H/L-MA
18.5 21.3 NS100N/H/L-MA
18.5 28.5
NS100N/H/L-MA
22
33
30
34.6 NS100N/H/L-MA

30

30
37

Contactors (3)

660/690 V

49

80

55

60

NS100N/H/L-MA

100

75

80

NS100N/H/L-MA

100

Irth

LR2-D13 06
LR2-D13 06
LR2-D13 07
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 14
LR2-D13 16
LR2-D13 21
LR2-D13 21
LR2-D13 16
LR2-D13 22
LR2-D13 21
LR2-D13 22
LR2-D33 53
LR2-D33 55
LR9-D53 57
LR2-D33 57
LR9-D53 57
LR2-D33 57
LR9-D53 57
LR2-D33 57
LR9-D53 57
LR2-D33 59
LR9-D53 63
LR2-D33 57
LR9-D53 63
LR2-D33 63
LR9-D53 63
LR2-D33 65
LR9-D53 67
LR9-D53 63
LR9-F53 63
LR9-D53 67
LR9-F53 67

(A)
1/1.6
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
7/10
9/13
12/18
12/18
9/13
17/25
12/18
17/25
23/32
30/40
30/50
37/50
30/50
37/50
30/50
37/50
30/50
48/65
48/80
37/50
48/80
63/80
48/80
80/93
60/100
48/80
60/100

(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

146

Schneider Electric

Type 1 coordination
(IEC 60947-4-1)

E62560

Complementary
technical information

Merlin Gerin NS160 to NS1250 and C1251


circuit breakers,Telemecanique contactors
and thermal relays

with short circuit


protection

contactor

Direct-on-line starting

thermal relay

Reserver
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker
alone.
Starting (1): normal class 10
Motors

Circuit breakers
440 V (2)

500/525 V

660/690 V

(kW)
75

(A)
135

(kW)
75

(A)
124

160

110

200

90
110
132

156
180
215

(A)
110
130
156

(kW)
90
110

90

(kW)
75
90
110

220/230 V

380 V

(A)
125
150
180

(kW)
55
75
90

(A)
105
140
170

110

210

(kW)
37
45
55

415 V

75

250

132

250

132

230

90

312

160

300

160

270

110

360

200

380

220

380

150

480

220

420

250

480

160

220

250
430

360

190

160

228

200

281

220

310

401
315
335

445
460

(3)

(1)

Rating Type

Type

(A)
100 NS160N/H/L MA
120
NS 250N/H/L MA

(A)
150
220

LC1D-150
LC1F-150
LC1F-185

(A)
LR9-D53 69 90/150
LR9-F53 69 100/160
LR9-F53 71 132/220

NS 250N/H/L MA

220

LC1F-225

LR9-F53 71

132/220

140 NS 250N/H/L MA
175
NS400N/H/L MA

220

LC1F-265

LR9-F53 71

132/220

320

LC1F-265

LR9-F73 75

200/330

220 NS400N/H/L MA
240
NS630N/H/L MA

320

LC1F-330

LR9-F73 75

200/330

500

LC1F-400

LR9-F73 79

300/500

250

270 NS630N/H/L MA

500

LC1F-400

LR9-F73 75

200/330

335

335 NS630N/H/L MA

500

LC1F-500

LR9-F73 79

300/500

500
630
500
630
630
800
1000
630
800
1000
800
800
1000
800
800
1000
630
800
1000
800
1000
1000
1000
1000
1250
1250

LC1F-500

LR9-F73 79

300/500

LC1-F630

LR9-F73 81

380/630

LC1-F630

LR9-F73 81

380/630

LC1-F630

LR9-F73 81

380/630

LC1-F800

LR2-F83 83

500/800

LC1-F800
LC1-BL33

LR2-F83 83

500/800

LC1-BL33

LR2-F83 83

500/800

LC1-BM33 LR2-F83 83

500/800

LC1-BM33 LR2-F83 85

630/1000

LC1-BP33

630/1000

132
160

200
220

Type

NS630N/H/L MA
NS630bN/H/L Micrologic 5.0
300
480
375
400 NS630N/H/L MA
450
480 NS630bN/H/L Micrologic 5.0
160
520
300
570
300
510
335
540
355
500
NS630bN/H/L Micrologic 5.0
375
530
C801N/H STR35ME
400
570
C1001L STR35ME
200
630
335
630
335
580
375
590
450
630
NS630bN/H/L Micrologic 5.0
C801N/H STR35ME
C1001L STR35ME
220
700
375
700
375
650
400
650
NS800N/H/L Micrologic 5.0
C801N/H STR35ME
C1001L STR35ME
400
750
400
690
450
720
NS800N/H/L Micrologic 5.0
C801N/H STR35ME
C1001L STR35ME
500
530 NS630bN/H/L Micrologic 5.0
560
580 C801N/H STR35ME
C1001L STR35ME
250
800
450
800
450
750
500
700
NS800N/H/L Micrologic 5.0
560
760
NS1000N/H/L Micrologic 5.0
C1001N/H STR35ME
500
900
500
830
500
800
600
830
NS1000N/H/L Micrologic 5.0
560
900
C1001N/H STR35ME
300
970
560
1000 560
920
600
960
670
920
NS1250N/H Micrologic 5.0
600
1100 600
1000 670
1080 750
1020
C1251N/H STR35ME
(1) For long starting (class 20), see the correspondence table for thermal relays on page 126.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 by LC3.

Schneider Electric

250

256

132

Contactors Thermal relay

LR2-F83 85

Irth

147

Type 1 coordination
(IEC 60947-4-1)

E62562

Complementary
technical information

Merlin Gerin NS160 to NS1250 and C1251


circuit breakers,Telemecanique contactors

with short circuit


and overload
protection

Direct-on-line starting
contactor

Reserver
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker
alone.
Starting:
STR22ME
class 10
-

Normal
Long

Motors
220/230 V
P

(kW) (A)
7.5
28
11
39
15
18.5
22
25

52
64
75
85

30
37
45
55

100
125
150
180

440 V (1)

415 V
I

(A)
30
37
44
59

(kW)
15
22
25
30

(A)
28
40
47
55

(kW)
15
22

(A)
26.5
39

(kW)
18.5
22
30

(A)
28.5
33
45

(kW)

(A)

72
85

37

72

51.5
64
76

34.6
39
42

37
45

30
37
45

30
33
37

37
55

55
80

45

49

55
75

100
135

55
75

96
124

55
75
90
110

60
80
100
120

90

160

110

200

90
110
132

156
180
215

55
75
90

105
140
170

110

210

250
300

132
160

230
270

160

110

360

380

220
250

360
401

480

380
420
480

220

150

200
220
250

250

430
300

480

335

540

220

630

700

300

335

570

630

300

335

510

580

375

256

590

375

700

375

650

400

650

400

750

400

690

450

720

75
90
110

110
130
156

132

190

160
200

228
281

220
315
335
355
375
400

310
445
460
500
530
570

450

132
160

140
175

200
220
250
335

220
240
270
335

375
450

400
480

630

500
560
250

300

800

800

450

750

500

900

500

830

560
1000 560
920
600
1100 600
1000
(1) Valid for 480V NEMA
(2) Reversers: replace LC1 with LC2.

148

970

450

500
560
600
670

800
900
960
1080

500
560
600

700
760
830

670
750

920
1020

Micrologic 5.0
class 10
class 20

Contactors (2)

660/690 V

132
160

200

500/525 V

(kW)
15
18.5
22
30

250
312

520

STR55UE
class 10
class 20

Circuit breakers
380 V

75
90

160

STR43ME
class 10
class 20

530
580

Type

Trip unit

Irth

Type

NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS160N/H/L

STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME

(A)
24/40
24/40
30/50
48/80
48/80
48/80
60/100
60/100
60/100
90/150

LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D65
LC1-D80
LC1-D95
LC1D-115 or LC1F-115
LC1D-115 or LC1F-115
LC1D-150 or LC1F-150

NS 250N/H/L

STR22ME

131/220

LC1F-185

NS 250N/H/L
NS 250N/H/L

STR22ME
STR22ME

131/220
131/220

LC1F-225
LC1F-265

NS400N/H/L
NS400N/H/L

STR43ME
STR43ME

190/320
190/320

LC1F-265
LC1F-330

NS630N/H/L
NS630N/H/L
NS630N/H/L
NS630N/H/L
NS630bN/H/L
NS630bN/H/L
NS800N/H/L
C801N/H
C1001L
NS630bN/H/L
NS800N/H/L
C801N/H
C1001L
NS800N/H/L
C801N/H
C1001L
NS800N/H/L
C801N/H
C1001L
NS630bN/H/L
C801N/H
C1001L
NS1000N/H/L
C1001N/H
NS1000N/H/L
C1001N/H
NS1250N/H/L
C1251N/H

STR43ME
STR43ME
STR43ME
STR43ME
Micrologic 5.0
Micrologic 5.0

300/500
300/500
300/500
300/500
250/630
250/630
320/800
320/800
400/1000
250/630
320/800
320/800
400/1000
320/800
320/800
400/1000
320/800
320/800
400/1000
250/630
320/800
400/1000
400/1000
400/1000
400/1000
400/1000
630/1250
630/1250

LC1F-400
LC1F-500
LC1F-500
LC1-F630

STR55UE
Micrologic 5.0
STR55UE
Micrologic 5.0
STR55UE
Micrologic 5.0
STR55UE
Micrologic 5.0
STR55UE
Micrologic 5.0
STR55UE
Micrologic 5.0
STR55UE
Micrologic 5.0
STR55UE

LC1-F630

LC1-F630

LC1-800

LC1-800
LC1-BL33
LC1-BL33

LC1-BM33
LC1-BM33
LC1-BP33

Schneider Electric

Type 1 coordination
(IEC 60947-4-1)

E34311

Complementary
technical information

Merlin Gerin NS80 and NS100 circuit


breakers,Telemecanique contactors
and thermal relays

magnetic circuit
breaker (MA)

star-delta
starter

Star-delta starting

thermal relay

"Iq" breaking performance: equal to the breaking capacity of the circuit breaker.
Starting: normal

Motors
220/230 V
P

Circuit breakers
380 V

(kW)
0.55
1.1
1.5
2.2
3
4
5.5

(A)
2.8
4.4
6.1
8.7
11.5
14.5
20

(kW)
1.5
2.2
3
4
5.5
7.5

(A)
3.7
5
6.6
8.5
11.5
15.5

7.5
11

28
39

11
15
18.5
22

22
30
37
44

(kW)
1.5
2.2
3
4
5.5
7.5
9
11
15
22
25

(A)
3.5
4.8
6.5
8.2
11
14
17
21
28
40
47

(kW)
1.5
2.2
3
4
5.5
7.5
9
11
15
22

(A)
3.1
4.5
5.8
7.9
10.4
13.7
16.9
20.1
26.5
39

15

52

30

51.5

30
37

55
66

37

64

45
1.5
2.2
3
4
5.5
7.5
9
11
15
22
25

80
3.5
4.8
6.5
8.2
11
14
17
21
28
40
47

45
1.5
2.2
3
4
5.5
7.5
9
11
15
22

76
3.1
4.5
5.8
7.9
10.4
13.7
16.9
20.1
26.5
39

30

51.5

30
37

55
66

37

64

45

80

45

76

55

100

55

96

18.5

64

30
37

59
72

22
0.55
1.1
1.5
2.2
3
4
5.5

75
2.8
4.4
6.1
8.7
11.5
14.5
20

1.5
2.2
3
4
5.5
7.5

3.7
5
6.6
8.5
11.5
15.5

7.5
11

28
39

11
15
18.5
22

22
30
37
44

15

52

18.5

64

30
37

59
72

22
75
25
85
45
85
30
100
(1) Valid for 480 V NEMA.

Schneider Electric

Contactors

Thermal relays

Type

Type

Irth

LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 16
LR2-D13 21
LR2-D13 22
LR2-D33 53
LR2-D33 53
LR2-D33 55
LR2-D33 55
LR2-D33 57
LR2-D33 57
LR2-D13 07
LR2-D13 08
LR2-D13 08
LR2-D13 10
LR2-D13 12
LR2-D13 14
LR2-D13 16
LR2-D13 16
LR2-D13 21
LR2-D13 22
LR2-D33 53
LR2-D33 53
LR2-D33 55
LR2-D33 55
LR2-D33 57
LR2-D33 57
LR2-D33 57
LR2-D33 59

(A)
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
9/13
12/18
17/25
23/32
23/32
30/40
30/40
37/50
37/50
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
9/13
12/18
17/25
23/32
23/32
30/40
30/40
37/50
37/50
37/50
48/65

440 V (1)

415 V

Type

Rating

NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA

(A)
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
50
80
80
80
80
80
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
100
100
100
100
100
100
100
100

LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D12
LC3-D12
LC3-D18
LC3-D18
LC3-D32
LC3-D32
LC3-D32
LC3-D40
LC3-D40
LC3-D50
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D12
LC3-D12
LC3-D18
LC3-D18
LC3-D32
LC3-D32
LC3-D32
LC3-D40
LC3-D40
LC3-D50
LC3-D50
LC3-D50

149

Type 1 coordination
(IEC 60947-4-1)

E62563

Complementary
technical information

Merlin Gerin NS160 to NS1000 and C1001


circuit breakers,Telemecanique contactors
and thermal relays

circuit breaker
with short circuit
protection

Star-delta starting

star-delta
starter

"Iq" breaking performance: equal to the breaking capacity of the circuit breaker
alone.
Starting: normal

thermal relay

Motors
220/230 V

Circuit breakers
380 V

(kW)

(A)

(kW)
55
75
75

(A)
105
140
140

(kW)

(A)

(kW)

(A)

75

135

75

90

170

90

160

37
45

55

125
150

180
110

210

110

Type

Rating

124

NS160N/H/L MA
NS160N/H/L MA
NS160N/H/L MA

(A)
150
150
150

90

156

NS 250N/H/L MA

220

110

180

NS 250N/H/L MA

220

NS 250N/H/L MA

220

NS 250N/H/L MA

220

NS400N/H/L MA

320

NS400N/H/L MA
NS630N/H/L MA
NS630N/H/L MA
NS630N/H/L MA
NS630N/H/L MA
NS630bN/H/L Micrologic 5.0
NS630bN/H/L Micrologic 5.0
NS800N/H/L Micrologic 5.0
C801N/H STR35ME
C1001L STR35ME
NS630bN/H/L Micrologic 5.0
NS800N/H/L Micrologic 5.0
C801N/H STR35ME
C1001L STR35ME
NS630bN/H/L Micrologic 5.0
NS800N/H/L Micrologic 5.0
NS800N/H/L Micrologic 5.0
NS1000N/H/L Micrologic 5.0

320
500
500
500
500
630
630
800
800
1000
630
800
800
1000
630
800
800
1000

200
132

75

250

132

250

132

230

90
110

312
360

270
380

480

300
380
420
480

160
220

150

160
200
220
250

250

430

160

520

300

570

Contactors

Thermal relays

Type

Type

440 V (1)

415 V

215

160
220
250

256
360
401

300

480

300

510

335

540

335

580

375

590

375

620

400

627

400

665

450

706

Irth
(A)
48/65
63/80
60/100

LC3-D80
LC3-D80
LC3-D115
LC3-F115
LC3-D115
LC3-F115
LC3-D115
LC3-F115
LC3-D115
LC3-F115
LC3-D150
LC3-F150
LC3-D150
LC3-F150
LC3F-185
LC3-F265
LC3-F265
LC3-F330
LC3-F330

LR2-D33 59
LR2-D33 63
LR9-D53 67
LR9-F53 67
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F73 75
LR9-F73 75
LR9-F73 75
LR9-F73 75

LC3-F400

LR9-F73 75

200/330

LC3-F400

LR9-F73 79

300/500

LC3-F400

LR9-F73 79

300/500

LC3-F500

LR9-F73 79

300/500

60/100
90/150
90/150
90/150
90/150
132/220
200/330
200/330
200/330
200/330

(1) Valid for 480V NEMA.

150

Schneider Electric

Type 1 coordination
(IEC 60947-4-1)

E 62564

Complementary
technical information

Merlin Gerin NS100 to NS1000 and C1001


circuit breakers, Contactors Telemecanique

circuit breaker
with short circuit and
overlaod protection

Star-delta starting
star-delta
starter

"Iq" breaking performance: equal to the breaking capacity of the circuit breaker
alone.
Starting: normal

Motors
220/230 V
P

Circuit breakers
380 V

(kW)
7.5
11

(A)
28
39

(kW)
15
18.5
22

(A)
30
37
44

(kW)
15
22
25

(A)
28
40
47

(kW)
15
22

(A)
26.5
39

15

52

30

51.5

30
37

55
66

37

64

45

80

45

76

55

100

55

96

75

135

75

124

90
110

160
200

90
110
132

156
180
215

160
220
250

256
360
401

300
335

480
540

18.5

64

22
25
30

75
85
100

30
37

59
72

45

85

55
75
75
90
110

105
140
140
170
210
250
300
380
420
480

132
160
220

230
270
380

250

430

570

300

510

37
45

125
150

55

180

75
90
110

250
312
360

150

480

132
160
200
220
250

160

520

300

335

Contactors

440 V (1)

415 V

580

375

590

375

620

400

627

400

665

450

706

Type
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS100N/H/L
NS160N/H/L
NS160N/H/L
NS160N/H/L
NS 250N/H/L
NS 250N/H/L
NS 250N/H/L
NS400N/H/L
NS400N/H/L
NS630N/H/L
NS630N/H/L
NS630N/H/L
NS630N/H/L
NS630bN/H/L
NS800N/H/L
C801N/H
C1001L
NS630bN/H/L
NS800N/H/L
C801N/H
C1001L
NS630bN/H/L
NS800N/H/L
NS800N/H/L
NS1000N/H/L

Trip unit
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR22ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
STR43ME
Micrologic 5.0
STR55UE
Micrologic 5.0
STR55UE
Micrologic 5.0
Micrologic 5.0

Irth
(A)
24/40
30/50
30/50
48/80
48/80
48/80
48/80
60/100
60/100
60/100
90/150
90/150
90/150
131/220
131/220
131/220
190/320
190/320
300/500
300/500
300/500
300/500
250/630
320/800
320/800
400/1000
250/630
320/800
320/800
400/1000
250/630
320/800
320/800

Type
LC3-D18
LC3-D18
LC3-D32
LC3-D32
LC3-D32
LC3-D40
LC3-D40
LC3-D50
LC3-D50
LC3-D50
LC3-D80
LC3-D80
LC3-D115 or LC3-F115
LC3-D115 or LC3-F115
LC3-D115 or LC3-F115
LC3-D150 or LC3-F150
LC3-D150 or LC3-F150
LC3F-185
LC3-F265
LC3-F265
LC3-F330
LC3-F330
LC3-F400

LC3-F400

LC3-F400
LC3-F500

(1) Valid for 480V NEMA.

Schneider Electric

151

Use of LV switches

E94516

Complementary
technical information

Functions performed by switch

source coupling
switch-disconnector

main power
distribution
board-tertiary

main power distribution


board-industrial

15 -40 kA

y 1000 A

sub-distribution
board-modular
products

y 160 A

enclosure
for local
isolation

industrial
distribution
switchboard

15 - 25 kA

y 400 A

enclosure
for local
isolation

final
distribution
board
y 10 kA

20 -80 kA

y 1600 A

y 63 A

y 160 A : 15 - 25 kA
y 400 A : 20 - 80 kA

control and
command
enclosure
y 25 kA

y 10 kA

y 63 A

control and
command
switchboard

y 40 A

y 5 kA

y 630 A

heating, lighting, etc.

NB. Adjacent to or built into the machine

building utilities

152

final
distribution
-building

continuous processes

manufacturing processes
individual machines

Schneider Electric

Complementary
technical information

Use of LV switches

Functions and positions of LV switches


The switch is therefore essentially a control device, (generally manual, possibly
electrical on opening - termed a free tripping switch) capable of breaking and
closing a normal service circuit. It does not use any electricity to remain open or
closed (2 stable positions).
For safety reasons, in the majority of cases is suitable for isolation.
It must always be used in association with a device which protects against
overloads and short-circuits.
6 applications have thus been identified:
b coupling and insolating switch in a power switchboard
b insolating switch in an industrial switchboard and automation cabinets
b insolating switch in a modular switchboard
b insolating switch in proximity units
b insolating switch in small commercial distribution units
b automation unit switch.

E36281

Suitable for isolation


Switch-disconnector
MERLIN GERIN
interpact
INS160
Ui 750V
Uimp 8kV
Lth 100A 60C
Ue(V)
DC23A
AC22A250
690
AC23A 500
AC23A 690
DC23A 250

Ie

100A
100A
100A
63A
100A

IEC 947.3

IEC 947.3
UTE VDE BS CEI UNE
UTE VDE BS CEI UNE

Isolation permits a circuit or a device to be disconnected from the rest of the


electrical installation, in order to guarantee the safety of those who have to achieve
repairs or maintenance.
Normally, all circuits in an electrical installation must be capable of being isolated.
In practice, to ensure optimal continuity of service, an isolating device is installed at
the start of every circuit distribution.
Certain switches allow this function to be achieved in addition to their circuit control
function.
Therefore a switch-disconnector must display the symbol (illustrated opposite),
visibly on the front face of the installed device.

Isolating function
Installation standards stipulate the requirements which must be respected in order
for a device to carry out its isolating function.
It must:
b be with equipped with omnipolar isolation, that is to say that the live conductors,
including the neutral (with the exception of the PEN conductor which must never be
isolated) must be isolated simultaneously
b be lockable in the open position so as to prevent any risk of unvolontary
reclosing ; this is imperative for industrial devices
b conform to a standard which guarantees its suitability for isolation
b It must also meet overvoltage withstand requirements. However, if the isolation is
explicitly recognized by a manufacturing standard, for example IEC 60947-1/3 for
industrial switch-disconnectors, a device which complies with this isolation
standard is judged to comply fully with the conditions required by installation
standards.
The manufacturing standard guarantees its use for isolation suitability for the user.

Schneider Electric

153

Complementary
technical information

Use of LV switches (cont.)

Switch standards and characteristics


Switch standards
Standards define:
b the frequency of operation cycles (with a maximum of 120 per hour)
b mechanical and electrical endurance
b operating breaking and making capacity
v normal
v occasional (closing on short-circuit for example)
b utilization categories.
The IEC standards 60947-3 (1) and 60669-1 (2) thus define the principal values
which are given below.

Utilization category
Depending on the rated operating current and the A or B mechanical endurance,
standards define the utilization categories shown in the table below.
Example:
A switch with a rating of 125 A, from the AC23 category must be able to:
b make a 10 In (1250 A) current with a cos of 0.35
b break a 8 In (1000 A) current with a cos of 0.35.
Its other characteristics are:
b to withstand a 12 In - 1 s short-circuit current, which defines the Icw = 1500 A
r.m.s. thermal withstand during 1 s
b Icm (peak A) short-circuit making capacity which corresponds to the
electrodynamic loads.

Utilization category
Frequent
operations
AC-21A

Characteristic
applications

Non frequent
operations
AC-21B

Resistive loads including


moderate overloads (cos = 0,95)
AC-22A
AC-22B
Mixed resistive and inductive loads including
moderate overloads (cos = 0,65)
AC-23A
AC-23B
Motors with cage winding or orther loads
which are very inductive (cos = 0,45 or 0,35)
(1) The industrial type of switch is defined by the IEC standard 60947-3.
(2) The domestic type of switch is defined by the IEC standard 60669-1.

Choice of switch criteria


Network characteristics
Nominal voltage, nominal frequency and nominal current are determined in the
same way as they are for a circuit breaker:
b nominal voltage = network nominal voltage
b frequency = network frequency
b nominal current = rated current with a value which is just above the downstream
load current. It is to be noted that the rated current is defined for a given ambient
temperature and that a derating may possibly have to be taken into account.

Localization and application


This determines the type and characteristics or major functions that the switch
should include. There are 3 levels of functions (see the table opposite):
b basic functions
practically common to all types of switch: isolation, control, notice.
b functions with complementary characteristics.
They are the direct translation of the users needs and the environment in which
the switch is located.

154

Schneider Electric

Complementary
technical information

Use of LV switches (cont.)

These are:
v industrial type performances
v Isc level
v type of locking
v type of control
v utilization category
v mounting system.
b specific functions
They are linked to the operation and installation restrictions, which are:
v earth leakage protection
v electrical controls
v remote opening
v withdrawable capacity.

Circuit-breaker or fuse / switch coordination


Coordination
E36280

As a switch only has a limited breaking capacity and short-circuit withstand, it must
be protected by a short-circuit protection device (SCPD) placed upstream.
Tables show the SCPD (circuit-breaker or fuse) ensuring proper coordination with
the switches in the event of a downstream short-circuit.
Warning: switches must be also protected against overloads. It's generally
admitted that the protection against the overloads and short-circuit, is ensured by
each downstream circuit-breakers as these circuit-breakers and these switches are
located in the same switchboard, designed according to the electrical standards.

two-pole
NC100H

Modular switch
Isc 20 kA
C60H
30 A

Schneider Electric

C60H
30 A

C60H
30 A

Example 1:
An enclosure feeder, with an Isc on the busbar of 20 kA, supplies loads with
operational currents of 30 A, 20 A and 10 A respectiveldy in single-phase. The
installation earthing system is the TT one. The feeder supplying this enclosure is
placed in the usptream switchboard and protected by a two-pole NC100H circuitbreaker. Which residual current switch should you choose for the enclosure
incomer?
As the feeders are placed in the same enclosure as the switch, cordination can be
achieved with each enclosure feeder. Choice will thus be made of an ID residual
current switch or rating 63 A and of C60H type circuit-breakes for the feeders: the
table above shows that the C60H withstands 20 kA in this case.
Note that C60N type circuit-breakers would have been sufficient without the switch:
in actual fact, the breaking capacity of the C60N downstream form a NC100H is
increased to 100 kA.

155

Complementary
technical information

Use of LV switches (cont.)


Switch-disconnectors protection

E31431

Compact NA switch-disconnectors

NSA125NA

NSA160NA

NS160N / 125
36
75
NS160H / 125
70
154
NS160L / 125
150
330
NSA160N / 125
30
63

NS160N / 160
36
75
NS160H / 160
70
154
NS160L / 160
150
330
NSA160N / 160
30
63

125
55
121
100
100
220
160
100
220
100 & 63M100
80
176
160 & 100M160
80
176

160
33
69
125
100
220
160
100
220
125 & 100M125
80
176
160 & 100M160
80
176

Upstream protection
push
to
trip

STR
90 %Ir
105

Im

.9

3
.95

8
2

.98
.63

alarm

Ir
.85
.8
.7

1.5

10
xIr

xIn

push
to
trip

22 DE

50/60H

Ir Im

test

By Compact NS
Type / maximum rating (A)
Isc max. (380/415 V)
Making capacity (380/415 V)
Type / calibre max. (A)
Isc max. (380/415 V)
Making capacity (380/415 V)
Type / maximum rating (A)
Isc max. (380/415 V)
Making capacity (380/415 V)
Type / maximum rating (A)
Isc max. (380/415 V)
Making capacity (380/415 V)
Type / maximum rating (A)
Isc max. (380/415 V)
Making capacity (380/415 V)
By fuse
Type aM (1) maximum rating (A)
Isc max. (500 V)
Making capacity (500 V)
Type gl (2) maximum rating (A)
Isc max. (500 V)
Making capacity (500 V)
Type gl (1) maximum rating (A)
Isc max. (500 V)
Making capacity (500 V)
Type BS (2) maximum rating (A)
Isc max. (500 V)
Making capacity (500 V)
Type BS (1) maximum rating (A)
Isc max. (500 V)
Making capacity (500 V)

kA ms
kA peak
kA ms
kA peak
kA ms
kA peak
kA ms
kA peak
kA eff.
kA peak

kA ms
kA peak
kA ms
kA peak
kA ms
kA peak
kA ms
kA peak
kA ms
kA peak

(1) Protection by external thermal relay obligatory


(2) Without external thermal relay

156

Schneider Electric

Complementary
technical information

Use of LV switches (cont.)


Switch-disconnectors protection
(cont.)
Compact NA switch-disconnectors
Upstream protection
Compact NS
By 380/415 V circuit breaker

By 440/480 V
circuit breaker (1)

By 500 V circuit breaker

By 525 V circuit breaker

By 690 V circuit breaker

By fuse
By 500 V fuse

type / maximum rating (A)


Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type aM (2) / maximum rating (A)
Isc max.
making capacity
type gG (3) / maximum rating (A)
Isc max.
making capacity
type gG (2) / maximum rating (A)
Isc max.
making capacity
type BS (3) / maximum rating (A)
Isc max.
making capacity
type BS (2) / maximum rating (A)
Isc max.
making capacity

kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
100
kA rms
kA peak
80
kA rms
kA peak
100
kA rms
kA peak
80 et 63M80
kA rms
kA peak
160 et 100M160
kA rms
kA peak

(1) Suitable for NEMA 480 V voltage.


(2) Protection by external thermal relay obligatory.
(3) Without external thermal relay.

158

Schneider Electric

Complementary
technical information

Use of LV switches (cont.)


Switch-disconnectors protection
(cont.)

NS100NA

NS160NA

NS250NA

NS400NA

NS630NA

NS100N/100
25
53
NS100H/100
70
154
NS100L/100
150
330
NS100N/100
25
53
NS100H/100
65
143
NS100L/100
130
286
NS100N/100
18
36
NS100H/100
50
105
NS100L/100
100
220
NS100N/100
18
36
NS100H/100
35
74
NS100L/100
100
220
NS100N/100
8
14
NS100H/100
10
17
NS100L/100
75
165

NS160N/160
35
74
NS160H/160
70
154
NS160L/160
150
330
NS160N/160
35
74
NS160H/160
65
143
NS160L/160
130
286
NS160N/160
30
63
NS160H/160
50
105
NS160L/160
70
154
NS160N/160
22
46
NS160H/160
35
74
NS160L/160
50
105
NS160N/160
8
14
NS160H/160
10
17
NS160L/160
20
40

NS250N/250
35
74
NS250H/250
70
154
NS250L/250
150
330
NS250N/250
35
74
NS250H/250
65
143
NS250L/250
130
286
NS250N/250
30
63
NS250H/250
50
105
NS250L/250
70
154
NS250N/250
22
46
NS250H/250
35
74
NS250L/250
50
105
NS250N/250
8
14
NS250H/250
10
17
NS250L/250
20
40

NS400N/400
45
95
NS400H/400
70
154
NS400L/400
150
330
NS400N/400
42
88
NS400H/400
65
143
NS400L/400
130
286
NS400N/400
30
63
NS400H/400
50
105
NS400L/400
100
220
NS400N/400
22
46
NS400H/400
35
74
NS400L/400
100
220
NS400N/400
10
17
NS400H/400
20
40
NS400L/400
75
165

NS630N/630
45
95
NS630H/630
70
154
NS630L/630
150
330
NS630N/630
42
88
NS630H/630
65
143
NS630L/630
130
286
NS630N/630
30
63
NS630H/630
50
105
NS630L/630
70
154
NS630N/630
22
46
NS630H/630
35
74
NS630L/630
50
105
NS630N/630
10
17
NS630H/630
20
40
NS630L/630
35
74

160
100
220
125
100
220
160
100
220
125 et 100M125
80
176
160 et 100M160
80
176

250
100
220
200
100
220
250
100
220
160 et 100M160
80
176
250 et 200M250
80
176

400
100
220
315
100
220
400
100
220
315 et 200M315
80
176
355 et 315M355
80
176

630
100
220
500
100
220
630
100
220
500
80
176
450 et 400M450
80
176

Schneider Electric

100
220
100
220
100
220
80
176
80
176

159

Complementary
technical information

Use of LV switches (cont.)


Switch-disconnectors protection
(cont.)
Compact NA switch-disconnectors
Upstream protection
Compact NS
By 380/415 V circuit breaker

By 440/480 V
circuit breaker (1)

By 500/525 V circuit breaker

By 690 V circuit breaker

Masterpact NT H1
By 220/690 V circuit breaker

Masterpact NT L1
By 220/525 V circuit breaker

By 690 V circuit breaker

type / maximum rating (A)


Isc max.
making capacity
type / cal maxi (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A))
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity

Masterpact NW N1-H1-H2-H3
By 220/440-480 V
type / maximum rating (A)
circuit breaker (1)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
By 500/525 V circuit breaker type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
By 690 V circuit breaker
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity

(1) Suitable for NEMA 480 V voltage.


(2) Maximum setting position 15.
(3) DIN on: b maximum setting position 15 (In y 2000).
b maximum setting position 12 (In = 2500).
b maximum setting position 8 (In = 3200).

160

Masterpact NW L1
By 220/690 V circuit breaker

type / maximum rating (A)


Isc max.
making capacity

kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak

kA rms DIN off / DIN on (2)


kA peak DIN off / DIN on (2)

kA rms
kA peak
kA rms
kA peak

kA rms DIN off / DIN on (3)


kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)

kA rms
kA peak

Schneider Electric

Complementary
technical information

Use of LV switches (cont.)


Switch-disconnectors protection
(cont.)

NS630bNA

NS800NA

NS1000NA

NS1250NA

NS1600NA

NS630bN/630
50
105
NS630bH/630
70
154
NS630bL/630
150
330
NS630bN/630
50
105
NS1600H-bH/1600
65
143
NS630bL/630
130
286
NS630bN/630
40
84
NS630bH/630
50
105
NS630bL/630
100
220
NS630bN/630
30
63
NS630bH/630
42
88
NS630bL/630
25
53

NS800N/800
50
105
NS800H/800
70
154
NS800L/800
150
330
NS800N/800
50
105
NS1600H-bH/1600
65
143
NS800L/800
130
286
NS800N/800
40
84
NS800H/800
50
105
NS800L/800
100
220
NS800N/800
30
63
NS800H/800
42
88
NS800L/800
25
53

NS1000N/1000
50
105
NS1000H/1000
70
154
NS1000L/1000
150
330
NS1000N/1000
50
105
NS2000H/2000
65
143
NS1000L/1000
130
286
NS1000N/1000
40
84
NS1000H/1000
50
105
NS1000L/1000
100
220
NS1000N/1000
30
63
NS1000H/1000
42
88
NS1000L/1000
25
53

NS1250N/1250
50
105
NS1250H/1250
70
154

NS1600N-bN/1600
50
105
NS1600H-bH/1600
70
154

NS1250N/1250
50
105
NS2500H/2500
65
143

NS1600N-bN/1600
50
105
NS3200H/3200
65
143

NS1250N/1250
40
84
NS1250H/1250
50
105

NS1600N-bN/1600
40
84
NS1600H-bH/1600
50
105

NS1250N/1250
30
63
NS1250H/1250
42
88

NS1600N-bN/1600
30
63
NS1600H-bH/1600
42
88

NT06H1/630
25 / 42
53 / 88

NT08H1/800
25 / 42
53 / 88

NT10H1/1000
25 / 42
53 / 88

NT12H1/1000
25 / 42
53 / 88

NT16H1/160
25 / 42
53 / 88

NT06L1/630
100
220
NT06L1/630
25
53

NT08L1/800
100
220
NT08L1/800
25
53

NT10L1/1000
100
220
NT10L1/1000
25
53

NT12L1/1250
100
220
NT12L1/1250
25
53

NT16L1/160
100
220
NT16L1/160
25
53

NW08N1/630
25 / 42
53 / 88
NW08H1/630
25 / 50
53 / 105
NW08H2/630
25 / 50
53 / 105
NW08N1/630
25 / 40
53 / 84
NW08H1/630
25 / 40
53 / 84
NW08H2/630
25 / 40
53 / 84
NW08N1/630
25 / 30
53 / 63
NW08H1/630
25 / 30
53 / 63
NW08H2/630
25 / 30
53 / 63

NW08N1/800
25 / 42
53 / 88
NW08H1/800
25 / 50
53 / 105
NW08H2/800
25 / 50
53 / 105
NW08N1/800
25 / 40
53 / 84
NW08H1/800
25 / 40
53 / 84
NW08H2/800
25 / 40
53 / 84
NW08N1/800
25 / 30
53 / 63
NW08H1/800
25 / 30
53 / 63
NW08H2/800
25 / 30
53 / 63

NW10N1/1000
25 / 42
53 / 88
NW10H1/1000
25 / 50
53 / 105
NW10H2/1000
25 / 50
53 / 105
NW10N1/1000
25 / 40
53 / 84
NW10H1/1000
25 / 40
53 / 84
NW10H2/1000
25 / 40
53 / 84
NW10N1/1000
25 / 30
53 / 63
NW10H1/1000
25 / 30
53 / 63
NW10H2/1000
25 / 30
53 / 63

NW12N1/1250
25 / 42
53 / 88
NW12H1/1250
25 / 50
53 / 105
NW12H2/1250
25 / 50
53 / 105
NW12N1/1250
25 / 40
53 / 84
NW12H1/1250
25 / 40
53 / 84
NW12H2/1250
25 / 40
53 / 84
NW12N1/1250
25 / 30
53 / 63
NW12H1/1250
25 / 30
53 / 63
NW12H2/1250
25 / 30
53 / 63

NW16N1/160
25 / 4
53 / 88
NW16H1/1600
25 / 50
53 / 105
NW16H2/1600
25 / 50
53 / 105
NW16N1/160
25 / 40
53 / 84
NW16H1/1600
25 / 40
53 / 8
NW16H2/160
25 / 40
53 / 84
NW16N1/160
25 / 3
53 / 6
NW16H1/160
25 / 30
53 / 6
NW16H2/160
25 / 30
53 / 6

NW08L1/630
25
53

NW08L1/800
25
53

NW10L1/1000
25
53

NW12L1/1250
25
53

NW16L1/160
25
53

Schneider Electric

161

Complementary
technical information

Use of LV switches (cont.)


Switch-disconnectors protection
(cont.)
Compact NA switch-disconnectors
Upstream protection
Compact NS
By 380/415 V circuit breaker

By 440/480 V
circuit breaker (1)

By 500/525 V circuit breaker

By 690 V circuit breaker

Masterpact NT H1
By 220/690 V circuit breaker

Masterpact NT L1
By 220/525 V circuit breaker

By 690 V circuit breaker

type / maximum rating (A)


Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity

Masterpact NW N1-H1-H2-H3
By 220/440-480 V
type / maximum rating (A)
circuit breaker (1)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
By 500/525V circuit breaker
type / maximum rating (A)
Icc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
By 690V circuit breaker
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity
type / maximum rating (A)
Isc max.
making capacity

(1) Suitable for NEMA 480 V voltage.


(2) Maximum setting position 15.
(3) DIN on: b maximum setting position 15 (In y 2000)
b maximum setting position 12 (In = 2500)
b maximum setting position 8 (In = 3200).

162

Masterpact NW L1
By 220/690V circuit breaker

type / maximum rating (A)


Isc max.
making capacity

kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak

kA rms DIN off / DIN on (2)


kA peak DIN off / DIN on (2)

kA rms
kA peak
kA rms
kA peak

kA rms DIN off / DIN on (3)


kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)
kA rms DIN off / DIN on (3)
kA peak DIN off / DIN on (3)

kA rms
kA peak

Schneider Electric

Complementary
technical information

Use of LV switches (cont.)


Switch-disconnectors protection
(cont.)

NS1600bNA

NS2000NA

NS2500NA

NS3200NA

NS1600N/bN/1600
50 / 70
105 / 154
NS1600H/bH/1600
70 / 85
154 / 187
NS1600N/bN/1600
50 / 65
105 / 143
NS1600H/bH/1600
65 / 85
143 / 187
NS1600N/bN/1600
40 / 65
84 / 143
NS1600H/BH/1600
50 / 65
105 / 143
NS1600N/bN/1600
30 / 65
63 / 143
NS1600H/bH/1600
42 / 65
88 / 143

NS2000N/2000
70
154
NS2000H/2000
85
187
NS2000N/2000
65
143
NS2000H/2000
85
187
NS2000N/2000
65
143
NS2000H/2000
65
143
NS2000N/2000
65
143
NS2000H/2000
65
143

NS2500N/2500
70
154
NS2500H/2500
85
187
NS2500N/2500
65
143
NS2500H/2500
85
187
NS2500N/2500
65
143
NS2500H/2500
65
143
NS2500N/2500
65
143
NS2500H/2500
65
143

NS3200N/3200
70
154
NS3200H/320
85
187
NS3200N/3200
65
143
NS3200H/3200
85
187
NS3200N/3200
65
143
NS3200H/3200
65
143
NS3200N/3200
65
143
NS3200H/3200
65
143

NW20H1/2000
65
143
NW20H2/2000
70
154
NW20H3/2000
70
154

NW25H1/2500
65
143
NW25H2/2500
70
154
NW25H3/2500
70
154

NW32H1/3200
65
143
NW32H2/3200
70
154
NW32H3/3200
70
154

NW20H1/2000
65
143
NW20H2/2000
65
143
NW20H3/2000
65
143

NW25H1/2500
65
143
NW25H2/2500
65
143
NW25H3/2500
65
143

NW32H1/3200
65
143
NW32H2/3200
65
143
NW32H3/3200
65
143

NW20H1/2000
65
143
NW20H2/2000
65
143
NW20H3/2000
65
143

NW25H1/2500
65
143
NW25H2/2500
65
143
NW25H3/2500
65
143

NW32H1/3200
65
143
NW32H2/3200
65
143
NW32H3/3200
65
143

NT16H1/1600
30 / 42
63 / 88
NT16L1/1600
100
220
NT16L1/1600
25
50
NW16N1/1600
50 / 88
50 / 88
NW16H1/1600
65
143
NW16H2/1600
70
154

NW16N1/1600
50 / 88
50 / 88
NW16H1/1600
65
143
NW16H2/1600
70
154

NW16N1/1600
42
88
NW16H1/1600
65
143
NW16H2/1600
65
143

NW16L1/1600
100
220

Schneider Electric

NW20L1/2000
100
220

163

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

When chosing a circuit breaker to protect a busbar trunking system, it is necessary


to take into account:
b the usual rules concerning the circuit breaker current settings:
Ib y Ir y Inc where
Ib = maximum load current
Ir = circuit breaker current setting
Inc = current rating of the busbar trunking
b the electrodynamic withstand of the busbar trunking: the peak current limited by
the circuit breaker must be less than the electrodynamic withstand capacity (or
rated peak current) of the busbar trunking.
Coordination tables
The tables for coordinating Merlin Gerin

Traditional circuit breaker selection method


The circuit breaker used to protect a distribution circuit is chosen according to two
fundamental criteria:
b the maximum load current Ib flowing in the supply circuit
b the prospective short-circuit current Isc at a point where the circuit breaker is to
be installed.
The circuit breaker is choosen such that:
v In circuit breaker u Ib
v breaking capacity of the circuit breaker u Isc.

E40700

Installation example

CB1
Ib = 360 A

Icc = 65 kA

CB2
Ib = 140 A

Icc = 65 kA

E40701

Application for Compact NS range

CB1 = NS400H
(P of C = 70 kA)

CB2 = NS160H
(P of C = 70 kA)

Schneider Electric

167

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Example
Consider two 630 kVA/400 V transformer (Usc 4 %) supplying a main LV
switchboard for which the prospective short-circuit current on the busbars is 44 kA.
From the switchboard, a 30-metre long Canalis KVA63 transmission electrical
busbar trunking system (630A) supplies a Canalis KSA63 trunking system (630A)
for distribution with high-density tap-offs.
A tap-off on the KSA63 trunking supplies a Canalis KSA16 trunking system.
The short-circuit level are respectively:
b 44 kA downstream of circuit-breaker CB1 and at the upstream connection of the
KVA63 trunking
b 33 kA at the junction between the KVA63 transmission trunking and the KSA63
trunking for high-density tap-offs.
What circuit breakers should be chosen for CB1 and CB2 to protect the
installation against short-circuits?
Prospective Isc
Circuit breakers

E59246

Isc protection level


for KVA63 trunking
Isc protection level
for KVA63 trunking
Isc protection level
for KSA16 trunking

CB1
44 kA
NS630N (45 kA breaking
capacity)
45 kA

CB2
33 kA
NS160N (35 kA breaking
capacity)

45 kA
35 kA

630 kVA
400 V

630 kVA
400 V

prospective Isc
44 kA
LV main
swichboard

D1 disconnector ?
prospective Isc
44 kA

prospective Isc
33 kA
canalis KSA 63

a 30-meter KVA63
transmission EBT
system
D2 disconnector ?

canalis KSA 16

168

Schneider Electric

Complementary
technical information

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking
The different types of Telemecanique
busbar trunking

Type of busbar trunking


Busbar trunking for transmission
and distribution with low-density
tap-offs
Busbar trunking for distribution
with high-density tap-offs
Busbar trunking for lighting
distribution and management

Low power

Medium power
KVA 200 to 800 A
KVC 200 to 800 A
(380/415 V - 660/690 V)
KSA 100 to 800 A
(380/415 V - 660/690 V)

KN 40 at 100 A
(tension 380/415 V)
KLE, KBA, KBB
K System
(tension 380/415 V)

High power
KTA 1000 to 4000 A
KTC 1000 to 4000 A
(380/415 V - 660/690 V)
KHF 1000 to 4500 A
(380/415 V - 660/690 V)

Coordination tables between Merlin Gerin


circuit breakers and Telemecanique Canalis
electrical busbar trunking
Voltage: 380 V / 415 V
Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Multi 9
Icc max. in kA ms.

KLE-16/20
16/20
10
15
25

C60N16/20
C60H16/20
C60L16/20
C60N25
C60H25
C60L25
NC100LH25
C60N40
C60H40
C60L40
NC100LH40
C60N63
C60H63
C60L63
NC100LH63
NS100N (1)
NS100H (1)
NS100L (1)
(1) TM-D trip unit, rating 40 or 63 or 100 A and STR22SE rating 40 or 100 A.

Schneider Electric

KBA-25 KBB-25
25

25

10
15
25
50

10
15
25
50

KBA-40

KBB-40

KN-04

40

40

40

10
15
25
50

10
15
25
50

10
15
25
50

25
25
25

KN-06

KN-10

63

100

10
15
15
50
25
25
25

25
25
25

169

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 380 V / 415 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

170

NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
NS630bN
NS630bH
NS630bL
NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NS1250N
NS1250H
NT06H1
NT08H1
NT10H1
NT12H1
NT06L1
NT08L1
NT10L1
NW08N1
NW10N1
NW12N1
NW08H1
NW10H1
NW12H1
NW08H2
NW10H2
NW12H2
NW08L1
NW10L1
NW12L1

KSA-10

KSA-16

KSA-25

KSA-40

KSA-50

KSA-63

KSA-80

100
25
25
25
20
20
20
17
17
17

160
25
70
90
36
70
70
36
55
55
30
30
30

250

400

500

630

800

45
70
150
26
26
70

45
70
150
32
32
120
32
32
120

26
26
26
26
70
70
70
26
26
26
26
26
26
26
26
26
26
26
26

32
32
32
32
120
120
120
32
32
32
32
32
32
32
32
32
32
32
32

45
70
150
38
38
150
38
38
150
38
38
150
38
38
38
38
38
38
150
150
150
38
38
38
38
38
38
38
38
38
38
38
38

36
70
150
36
70
150
45
45
45
30
30
30
14
14

14

45
70
150
45
70
150

24
24
24
24
55
55
55
24
24
24
24
24
24
24
24
24
24
24
24

Schneider Electric

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 380 V / 415 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
NS630bN
NS630bH
NS630bL
NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NT06H1
NT08H1
NT10H1
NT06L1
NT08L1
NT10L1
NW08N1
NW10N1
NW08H1
NW10H1
NW08H2
NW10H2
NW08L1
NW10L1

KVA-20

KVA-31

KVA-40

KVA-50

KVA-63

KVA-80

200
36
70
100
35
35
35

315
36
70
100
45
70
150
45
70
150

400

500

630

800

45
70
150
45
70
150

45
70
150
45
70
150
26
26
120

45
70
150
45
70
150
29
29
150
29
29
150

18

19
19

26
26

28
28

65
65

29
29
29
85
85
85
29
29
29
29
29
29
29
29

35
35
150
35
35
150
35
35
150
150
150
35
35
35
35
35
35
35
35

Voltage: 380 V / 415 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

Schneider Electric

NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
NS630bN
NS630bH
NS630bL
NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NT06H1
NT08H1
NT10H1
NT06L1
NT08L1
NT10L1
NW08N1
NW10N1
NW08H1
NW10H1
NW08H2
NW10H2
NW08L1
NW10L1

KVC-20

KVC-31

KVC-40

KVC-63

KVC-80

200
36
70
100
35
35
35

315
36
70
100
45
70
150

400

630

800

45
70
150
45
70
150
19
19
40

45
70
150
45
70
150
29
29
150
29
29
150

19

29
29
29
85
85
85
29
29
29
29
29
29
29
29

18

55

60

35
35
150
35
35
150
35
35
150
35
35
150
150
35
35
35
35
35
35
35
35

171

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 380 V / 415 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

172

NS1000N
NS1000H
NS1000L
NS1250N
NS1250H
NS1600N
NS1600H
NT10H1
NT12H1
NT16H1
NT10L1
NW10N1
NW12N1
NW16N1
NW20N1
NW10H1
NW12H1
NW16H1
NW20H1
NW25H1
NW32H1
NW40H1
NW40bH1
NW50H1
NW10H2
NW12H2
NW16H2
NW20H2
NW25H2
NW32H2
NW40H2
NW40bH2
NW50H2
NW25H3
NW32H3
NW40H3
NW10L1
NW12L1
NW16L1
NW20L1

KTA-10

KTA-12

KTA-16

KTA-20

KTA-25

KTA-30

KTA-40

1000
40
40
150
40
40
40
40
40
40
40
150
40
40
40

1200

1600

2000

2500

3000

4000

50
50
50
50
42
42
42
150
42
42
42

42

50
50
50

42
42
42
150
42
42
42
42
65
65
65
65
65

42

40
40
40

60
60
60
60
42
42
42
150
42
42
42
42
60
60
60
60
60

65
65
65
65
65
80

65
65
65
65
65
86

80
80
80
80
80
80

86
86
86
86
86
86

80
80
80

86
86
86

150
150

150

40
40
40

50
50
50

60
60
60
60
60

60

40
40

55
55

80
80
80
80

72
72
72
72
72

72

140
140

65
65
90
90

90
90
90
90
90
90

Schneider Electric

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 380 V / 415 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

Schneider Electric

NS1000N
NS1000H
NS1000L
NS1250N
NS1250H
NS1600N
NS1600H
NT10H1
NT12H1
NT16H1
NT10L1
NW10N1
NW12N1
NW16N1
NW20N1
NW10H1
NW12H1
NW16H1
NW20H1
NW25H1
NW32H1
NW40H1
NW40bH1
NW50H1
NW63H1
NW10H2
NW12H2
NW16H2
NW20H2
NW25H2
NW32H2
NW40H2
NW40bH2
NW50H2
NW63H2
NW25H3
NW32H3
NW40H3
NW10L1
NW12L1
NW16L1
NW20L1

KTC-10

KTC-13

KTC-16

KTC-20

KTC-25

KTC-30

KTC-40

KTC-50

1000
40
40
150
40
40
40
40
40
40
40
150
40
40
40

1350
50
50
150
50
50
50
50

1600

2000

2500

3000

4000

5000

150
42
42
42

42

42

40
40
40

50
50
50

150
42
42
42
42
60
60
60
60
60

65
65
65
65
82

65
65
65
65
82

65
65
90
90
90

95
95

90
90
90
90
90

95
95

40
40
40

50
50
50

60
60
60
60

60
60
60
60
60

60

40
40

55
55
55
55

80
80
80
80

150
42
42
42
42
65
65
65
65
65

73
73
73
73
73

73

140
140

82
82
82
82
82

82
82
82
82
82

82
82
82

82
82
82

150
150

150
150

90
90

173

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 380 V / 415 V


Type of Canalis busbar trunking

KHF

KHF

KHF

KHF

Trunking rating (in A at 35 C)


Type of circuit breaker Compact
Icc max. in kA ms.

1000
28
28
70
28
28
70
28
28

1200

1450

2200/2500 3000/3400 4000/4500

38
38
150
38
38
38
38
38
38

48
48
150
48
48
48
48
48
48

38
38
38
38
150
150
38
38
38
38
38
38
38
38
38
38
38

38
38
38
38
150
150
38
38
38
38
38
38
38
38
38
38
38

Masterpact

174

NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NS1250N
NS1250H
NS1600N
NS1600H
NS1600bN
NS1600bH
NS2000N
NS2000H
NS2500N
NS2500H
NS3200N
NS3200H
NT08H1
NT10H1
NT12H1
NT16H1
NT08L1
NT10L1
NW08N1
NW10N1
NW12N1
NW16N1
NW20N1
NW08H1
NW10H1
NW12H1
NW16H1
NW20H1
NW25H1
NW32H1
NW40H1
NW40bH1
NW50H1
NW63H1
NW08H2
NW10H2
NW12H2
NW16H2
NW20H2
NW25H2
NW32H2
NW40H2
NW40bH2
NW50H2
NW63H2
NW25H3
NW32H3
NW40H3
NW08L1
NW10L1
NW12L1
NW16L1
NW20L1

28
28
28
28
80
80
28
28
28
28
28
28
28
28
28
28
28

28
28
28
28
28
28

28

28
28
28
28
28

38
38
38
38
38
38

38

38
38
38
38
38

38
38
38
38
38
38

38

38
38
38
38
38

70
85
70
85
70
85
70
85

KHF

KHF

70
85
70
85
70
85
70
85

42

42
42

42

65
65
65
65
65
92
92
92

65
65
65
65
100
100
100

92
92
92
92
92
92
92
92
92
92
92

100
100
100
100
117
117
117
117
117
117

150
150

150

65
65
100
100
100

100
100
147
147
147
147
147

Schneider Electric

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 660 V / 690 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

Schneider Electric

NS100N
NS100H
NS100L
NS160N
NS160H
NS160L
NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
NS630bN
NS630bH
NS630bL
NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NT06H1
NT08H1
NT10H1
NT12H1
NT06L1
NT08L1
NT10L1
NW08N1
NW10N1
NW12N1
NW08H1
NW10H1
NW12H1
NW08H2
NW10H2
NW12H2
NW08L1
NW10L1
NW12L1

KSA-10

KSA-16

KSA-25

KSA-40

KSA-50

KSA-63

KSA-80

100
8
10
20
8
10
20
8
10
15

160
8
10
75
8
10
75
8
10
20
10
17
14

250

400

500

630

800

10
20
35
26
26
75
26
26
75

10
20
35
30
32
75
30
32
75

26
26
26
26
25
25
25
26
26
26
26
26
26
26
26
26
26
26
26

32
32
32
32
25
25
25
32
32
32
32
32
32
32
32
32
32
32
32

20
20
35
30
38
75
30
38
75
30
38
35
38
38
38
38
25
25
25
38
38
38
38
38
38
38
38
38
38
38
38

8
10
75
8
10
20
10
20
28

14

14

10
20
35
10
20
35
24
24
75

24
24
24
24
25
25
25
24
24
24
24
24
24
24
24
24
24
24
24

175

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 660 V / 690 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

176

NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
NS630bN
NS630bH
NS630bL
NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NT06H1
NT08H1
NT10H1
NT06L1
NT08L1
NT10L1
NW08N1
NW10N1
NW08H1
NW10H1
NW08H2
NW10H2
NW08L1
NW10L1

KVA-20

KVA-31

KVA-40

KVA-50

KVA-63

KVA-80

200
8
10
20
10
20
20

315

400

500

630

800

10
20
75
10
20
35

10
20
75
10
20
35
24
24

10
20
75
10
20
35
26
26

10
20
75
10
20
35
30
30
65
30
30
75
30
30
35
36
36
36
25
25
25
36
36
36
36
36
36
36
36

23
23
23

24
24
24

26
26
26

65
30
35
75
30
35
35
40
40
25
25
25
40
40
40
40
40
40
40
40

Schneider Electric

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 660 V / 690 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

Schneider Electric

NS250N
NS250H
NS250L
NS400N
NS400H
NS400L
NS630N
NS630H
NS630L
NS630bN
NS630bH
NS630bL
NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NT06H1
NT08H1
NT10H1
NT06L1
NT08L1
NT10L1
NW08N1
NW10N1
NW08H1
NW10H1
NW08H2
NW10H2
NW08L1
NW10L1

KVC-20

KVC-31

KVC-40

KVC-63

KVC-80

200
8
10
20
10
20
20

315

400

630

800

10
20
75
10
20
35

10
20
75
10
20
35
19
19
27

10
20
75
10
20
35
30
30
75
30
36
75

25

27

25

25

36
36
36
25
25
25
36
36
36
36
36
36
36
36

30
35
75
30
35
35
40
40
40
25
25
25
40
40
40
40
40
40
40
40

177

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 660 V / 690 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

178

NS1000N
NS1000H
NS1000L
NS1250N
NS1250H
NS1600N
NS1600H
NT10H1
NT12H1
NT16H1
NT10L1
NW10N1
NW12N1
NW16N1
NW20N1
NW10H1
NW12H1
NW16H1
NW20H1
NW25H1
NW32H1
NW40H1
NW40bH1
NW50H1
NW10H2
NW12H2
NW16H2
NW20H2
NW25H2
NW32H2
NW40H2
NW40bH2
NW50H2
NW25H3
NW32H3
NW40H3
NW10L1
NW12L1
NW16L1
NW20L1

KTA-10

KTA-12

KTA-16

KTA-20

KTA-25

KTA-30

KTA-40

1000
30
40
35
30
40
30
40
40
40
40
25
40
40
40
40
40
40
40

1200
30
42
35
30
42
30
42
42
42
42
25
42
42
42
42
50
50
50

1600

2000

2500

3000

4000

42
42
42
25
42
42
42
42
60
60
60
60

42
42
42
25
42
42
42
42
65
65
65
65

40
40
40

50
50
50

60
60
60
60
60

60

40
40

50
50

65
65
65
65

72
72
72
72
72

72

100
100

42

65
65
65
65
65
80

65
65
65
65
65
86

80
80
80
80
80
80

86
86
86
86
86
86

80
80
80

86
86
86

65
65
90
90

85
85
90
90
90
90

100
100

Schneider Electric

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 660 V / 690 V


Type of Canalis busbar trunking
Trunking rating (in A at 35 C)
Type of circuit breaker Compact
Icc max. in kA ms.

Masterpact

Schneider Electric

NS1000N
NS1000H
NS1000L
NS1250N
NS1250H
NS1600N
NS1600H
NT10H1
NT12H1
NT16H1
NT10L1
NW10N1
NW12N1
NW16N1
NW20N1
NW10H1
NW12H1
NW16H1
NW20H1
NW25H1
NW32H1
NW40H1
NW40bH1
NW50H1
NW63H1
NW10H2
NW12H2
NW16H2
NW20H2
NW25H2
NW32H2
NW40H2
NW40bH2
NW50H2
NW63H2
NW25H3
NW32H3
NW40H3
NW10L1
NW12L1
NW16L1
NW20L1

KTC-10

KTC-13

KTC-16

KTC-20

KTC-25

KTC-30

KTC-40

KTC-50

1000
30
40
35
30
40
30
40
40
40
40
25
40
40
40

1350
30
42
35
30
42
40
42

1600

2000

2500

3000

4000

5000

25
42
42
42

42

50
50
50

25
42
42
42
42
65
65
65
65
65

42

40
40
40

25
42
42
42
42
60
60
60
60
60

65
65
65
65
82

65
65
65
65
82

65
65
90
90

95
95

90
90
90
90
90

95
95

40
40
40

50
50
50

60
60
60
60
60

60

40
40

50
50
50
50

65
65
65
65

73
73
73
73
73

73

100
100

82
82
82
82
82

82
82
82
82
82

82
82
82

82
82
82

100
100

100
100

90
90

179

Coordination tables between


Merlin Gerin with the circuit
breaker and Telemecanique
Canalis electrical busbar trunking

Complementary
technical information

Voltage: 660 V / 690 V


Type of Canalis busbar trunking

KHF

KHF

KHF

KHF

Trunking rating (in A at 35 C)


Type of circuit breaker Compact
Icc max. in kA ms.

1000
28
28
75
28
28
35
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
28
25
25
28
28
28
28
28
28
28
28
28
28
28

1200

1450

2200/2500 3000/3400 4000/4500

30
38
35
30
38
30
38
30
38

30
48
35
30
48
30
48
48
48
48
48

Masterpact

180

NS800N
NS800H
NS800L
NS1000N
NS1000H
NS1000L
NS1250N
NS1250H
NS1600N
NS1600H
NS1600bN
NS1600bH
NS2000N
NS2000H
NS2500N
NS2500H
NS3200N
NS3200H
NT08H1
NT10H1
NT12H1
NT16H1
NT08L1
NT10L1
NW08N1
NW10N1
NW12N1
NW16N1
NW20N1
NW08H1
NW10H1
NW12H1
NW16H1
NW20H1
NW25H1
NW32H1
NW40H1
NW40bH1
NW50H1
NW63H1
NW08H2
NW10H2
NW12H2
NW16H2
NW20H2
NW25H2
NW32H2
NW40H2
NW50bH2
NW50H2
NW63H2
NW25H3
NW32H3
NW40H3
NW08L1
NW10L1
NW12L1
NW16L1
NW20L1

28
28
28
28
28
28

28

28
28
28
28
28

38
38
38
38
25
25

38
38
38
38
25
25

38
38
38
38
38
38

38
38
38
38
38
38

38
38
38
38
38
38

38

38
38
38
38
38

38
38
38
38
38
38

38

38
38
38
38
38

30
42
60
40
60
40
60
40
60
40

KHF

KHF

60
40

38

65
65
65
65
65
92
92
92

65
65
65
65
100
100
100

85
85
85
85
85
92
92
92
92
92
92

85
85
85
85
100
100
100
100
100
100

100
100

100

65
65
100
100
100

85
85
100
100
100
100
100

Schneider Electric

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Circuit breaker selection taking
coordination into account
The use of current-limiting circuit breakers makes it possible to implement
coordination techniques. This improves circuit breaker performance in terms of
breaking capacity and continuity of service.
Coordination techniques are described and recognised by the following standards:
b product standards IEC 60947-1 and 60947-2
b installation standards IEC 60364, NF C15-100, etc.

Cascading
The use of a current-limiting circuit breaker upstream to reinforce the breaking
capacity of a downstream circuit breaker.

Principle
E40702

Cascading

CB1

CB2
Isc = 65 kA

CB2 breaking capacity

Application for Compact NS range


E40703

Cascading

CB1 = NS400H

Reinforced
break. cap.
70 kA

CB2 = NS160N
(Breaking
cap. = 35 kA)

Schneider Electric

181

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Discrimination
In the event of an electrical fault on one outgoing circuit, discrimination is the ability
of the electrical installation to maintain the continuity of electrical power supplied to
the other circuits not concerned by the fault.
As a general rule, cascading and discrimination techniques are applied
independently.
Schneider has developed an exclusive system to conciliate cascading and
discrimination.
This system ensures discrimination up to the reinforced breaking capacity of the
association of circuit breakers CB1 and CB2.

Principle
E40702

Cascading and reinforced discrimination

CB1

CB2
Isc = 65 kA

CB2 breaking capacity

Discrimination ensured up to the reinforced breaking capacity of CB2

Application for Compact NS range


E40704

Cascading and reinforced discrimination

CB1 = NS400H

Break. cap.
renforced
70 kA
CB2 = NS160N
Isc = 65 kA

182

Schneider Electric

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Cascading, reinforced discrimination and reinforced protection of busbar
trunking systems (BTS)
This technique is the direct application of cascading and discrimination techniques
to the protection of busbar trunking systems.
For various upstream circuit breakers and upstream busbar trunking systems, the
tables below give directly:
b the level of short-circuit protection of the busbar trunking
b the downstream circuit breaker and associated busbar trunking
b the cascading breaking capacity of the downstream circuit breaker
b the level of reinforced discrimination of the upstream and downstream circuit
breakers
b the level of reinforced protection of the downstream busbar trunking.
Application to a Canalis distributed distribution system:
b reinforcement of the breaking capacity of the NS 160N (CB2) up to 70 kA
b discrimination between CB1 and CB2 ensured up to 70 kA
b protection of Canalis KSA 16 busbar trunking up to 70 kA.

E40705

Alimentation

CB1 = NS400H

KSA40 (400 A)

CB2 = NS160N

KSA16 (160 A)

70 kA

Example of a table corresponding to the above diagram.

Rated current of the upstream busbar trunking: 315 and 400 A

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS400H

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
45

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
70

NS400L
STR23SE/STR53UE
STR23SE/STR53UE
KSA//KVA
KVA/ /KVC
KVC
KSA
315 and
and400
400AA
315
70
150

NS100N
TMD/STR22SE
KSA
100 A

NS160N

KSA
160 A

NS100N
TMD/STR22SE
KSA
100 A

KSA
160 A

NS100N
NS100H
TMD/STR22SE
TMD/STR22SE
KSA
KSA
100 A
A
100

KSA
KSA
160 AA
160

45

70

70

70
150

70
150

45

70

70

70
150

70
150

45

70

70

70
25

70
70

Discrimination limit between


upstream and downstream
circuit breakers (kA)
45
Reinforced breaking capacity of the
downstream circuit breaker (kA)
45
Reinforced protection of the
downstream busbar trunking (kA) 45

Schneider Electric

NS400H

NS400N

NS160N

NS160N

NS160H

183

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination

E39614

Voltage: 380/415 V
source

upstream
circuit breaker

level of protection
of the upstream
busbar trunking

reinforced cascading
and discrimination
between the 2 circuit
breakers

upstream
busbar trunking

downstream
circuit breaker

reinforced protection
of the downstream
busbar trunking

downstream
busbar trunking

Rated current of the upstream busbar trunking: 1600 A


Upstream circuit breaker
Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS1600N

NS1600N

Micrologic 5.0
KTA-16 / KTC-16
1600 A
50

Micrologic 5.0
KTA-16 / KTC-16
1600 A
50

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
50
Reinforced breaking capacity of the
downstream circuit breaker (kA)
50
Reinforced protection of the
downstream busbar trunking (kA) 50

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

KSA
250 A

NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
500 - 630 A

NS100N
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

50

50

45

40

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

NS1600H

NS1600H

Micrologic 5.0
KTA-16 / KTC-16
1600 A
70

Micrologic 5.0
KTA-16 / KTC-16
1600 A
70

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
70
Reinforced breaking capacity of the
downstream circuit breaker (kA)
70
Reinforced protection of the
downstream busbar trunking (kA) 70

184

NS250N

NS250N
KSA
250 A

NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
500 - 630 A

NS100N
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

70

70

45

40

70

70

70

70

70

70

70

70

70

70

70

70

70

70

50

50

50

Schneider Electric

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 1200 to 1350 A

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS1250N

NS1250N

Micrologic 5.0
KTA-12 / KTC-13
1200 and 1350 A
50

Micrologic 5.0
KTA-12 / KTC-13
1200 and 1350 A
50

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
50
Reinforced breaking capacity of the
downstream circuit breaker (kA)
50
Reinforced protection of the
downstream busbar trunking (kA) 50

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS250N
KSA
250 A

NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
500 - 630 A

NS100N
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

50

50

45

40

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

NS1250H

NS1250H

Micrologic 5.0
KTA-12 / KTC-13
1200 and 1350 A
70

Micrologic 5.0
KTA-12 / KTC-13
1250 and 1350 A
70

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
70
Reinforced breaking capacity of the
downstream circuit breaker (kA)
70
Reinforced protection of the
downstream busbar trunking (kA) 70

NS250N
KSA
250 A

NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
500 - 630 A

NS100N
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

70

70

45

40

70

70

70

70

70

70

70

70

70

70

70

70

70

70

50

50

50

Rated current of the upstream busbar trunking: 1000 A


Upstream circuit breaker
Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS1000N

NS1000N

Micrologic 5.0
KTA-10 / KTC-10
1000 A
50

Micrologic 5.0
KTA-10 / KTC-10
1000 A
50

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
50
circuit breakers (kA)
Reinforced breaking capacity of the
downstream circuit breaker (kA)
50
Reinforced protection of the
downstream busbar trunking (kA) 50

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

KSA
250 A

NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
500 - 630 A

NS100N
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

50

50

45

40

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

NS1000H

NS1000H

Micrologic 5.0
KTA-10 / KTC-10
1000 A
55

Micrologic 5.0
KTA-10 / KTC-10
1000 A
55

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
70
Reinforced breaking capacity of the
downstream circuit breaker (kA)
70
Reinforced protection of the
downstream busbar trunking (kA) 55

Schneider Electric

NS250N

NS250N
KSA
250 A

NS400N
NS630N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
500 - 630 A

NS100N
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

70

70

45

40

70

70

70

70

70

70

70

70

70

70

55

55

55

55

50

50

50

185

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 1000 A

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS1000L

NS100L

Micrologic 5.0
KTA-10 / KTC-10
1000 A
150

Micrologic 5.0
KTA-10 / KTC-10
1000 A
150

NS100N/H
NS160N/H
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
150
Reinforced breaking capacity of the
downstream circuit breaker (kA)
150
Reinforced protection of the
downstream busbar trunking (kA) 50

NS250N/H
KSA
250 A

NS400N/H
NS630N/H
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A
500 - 630 A

NS100N/H
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

150

150

150

150

150

150

150

150

150

150

150

150

150

150

70

150

150

150

50

50

50

Rated current of the upstream busbar trunking: 800 A


Upstream circuit breaker
Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS800N

NS800N

Micrologic 5.0
KVA-80 / KVC-80
800 A
50

Micrologic 5.0
KVA-80 / KVC-80
800 A
50

NS100N

Associated trip unit


Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

Associated trip unit


Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS100N

TMD / STR22SE

KSA
250 A

STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A

40 A
KN
40 A

63 A
KN
63 A

100 A
KN
100 A

50

50

35

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

NS800H

Micrologic 5.0
KVA-80 / KVC-80
800 A
60

Micrologic 5.0
KVA-80 / KVC-80
800 A
60

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

NS250N
KSA
250 A

NS400N
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A

NS100N
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

70

70

35

70

70

70

70

70

70

70

70

70

60

60

60

50

50

50

NS800L

NS800L

Micrologic 5.0
KVA-80 / KVC-80
800 A
150

Micrologic 5.0
KVA-80 / KVC-80
800 A
150

NS100N/H
NS160N/H
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
150
Reinforced breaking capacity of the
downstream circuit breaker (kA)
150
Reinforced protection of the
downstream busbar trunking (kA) 50

186

NS400N

NS800H

Discrimination limit between


upstream and downstream
circuit breakers (kA)
70
Reinforced breaking capacity of the
downstream circuit breaker (kA)
70
Reinforced protection of the
downstream busbar trunking (kA) 60

Upstream circuit breaker

NS250N

TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
50
Reinforced breaking capacity of the
downstream circuit breaker (kA)
50
Reinforced protection of the
downstream busbar trunking (kA) 50

Upstream circuit breaker

NS160N

NS250N/H
KSA
250 A

NS400N/H
STR23SE / STR53UE
KSA / KVA / KVC
315 - 400 A

NS100N/H
40 A
KN
40 A

TMD / STR22SE
63 A
100 A
KN
KN
63 A
100 A

150

150

150

150

150

150

150

150

150

150

150

150

70

150

150

50

50

50

Schneider Electric

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 500 and 630 A

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS630bN

NS630bH

NS630bL

Micrologic 5.0
KSA / KVA / KVC
630 A
20

Micrologic 5.0
KSA / KVA / KVC
630 A
29

Micrologic 5.0
KSA / KVA / KVC
630 A
150

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
50
Reinforced breaking capacity of the
downstream circuit breaker (kA)
50
Reinforced protection of the
downstream busbar trunking (kA)
50

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

Associated trip unit


Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

Associated trip unit


Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

KSA
250 A

NS100N/H NS160N/H
TMD / STR22SE
KSA
KSA
100 A
160 A

50

70

50

50

50

50

NS250N/H
KSA
250 A

70

70

150

150

150

70

70

70

150

150

150

60

70

70

50

70

150

NS630bH

NS630bL

Micrologic 5.0
KSA / KVA / KVC
630 A
29

Micrologic 5.0
KSA / KVA / KVC
630 A
150

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N/H TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

50

50

70

70

70

150

150

150

50

50

70

70

70

150

150

150

50

50

50

50

50

50

50

50

NS630N

NS630H

NS630L

STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
45

STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
70

STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
150

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

NS250N
KSA
250 A

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

45

45

70

45

45

45

45

NS250N
KSA
250 A

NS100H
NS160H
TMD / STR22SE
KSA
KSA
100 A
160 A

NS250H
KSA
250 A

70

70

150

150

150

70

70

70

150

150

150

70

70

70

70

70

70

NS630N

NS630H

NS630L

STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
45

STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
70

STR23SE/STR53UE
KSA / KVA / KVC
500 and 630 A
150

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
45
Reinforced breaking capacity of the
downstream circuit breaker (kA)
45
Reinforced protection of the
downstream busbar trunking (kA)
45

Schneider Electric

50

NS250N

Micrologic 5.0
KSA / KVA / KVC
630 A
29

Discrimination limit between


upstream and downstream
circuit breakers (kA)
45
Reinforced breaking capacity of the
downstream circuit breaker (kA)
45
Reinforced protection of the
downstream busbar trunking (kA)
45

Upstream circuit breaker

KSA
250 A

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

NS630bN

Discrimination limit between


upstream and downstream
circuit breakers (kA)
50
Reinforced breaking capacity of the
downstream circuit breaker (kA)
50
Reinforced protection of the
downstream busbar trunking (kA)
50

Upstream circuit breaker

NS250N

45

45

70

70

70

150

150

150

45

45

70

70

70

150

150

150

45

45

50

50

50

50

50

50

187

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 315 and 400 A

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS400N

NS400H

NS400L

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
45

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
70

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
150

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

NS100N
NS160N
TMD / STR22SE
KSA
KSA
100 A
160 A

NS100H
NS160H
TMD / STR22SE
KSA
KSA
100 A
160 A

45

70

70

150

150

45

70

70

150

150

45

70

70

70

70

Discrimination limit between


upstream and downstream
circuit breakers (kA)
45
Reinforced breaking capacity of the
downstream circuit breaker (kA)
45
Reinforced protection of the
downstream busbar trunking (kA)
45

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS400N

NS400H

NS400L

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
45

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
70

STR23SE/STR53UE
KSA / KVA / KVC
315 and 400 A
150

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
45
Reinforced breaking capacity of the
downstream circuit breaker (kA)
45
Reinforced protection of the
downstream busbar trunking (kA)
45

45

45

70

70

70

150

150

150

45

45

70

70

70

150

150

150

45

45

50

50

50

50

50

50

Rated current of the upstream busbar trunking: 200 and 250 A


Upstream circuit breaker
Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS250N

NS250H

NS250L

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
150

NS100N
TMD / STR22SE
KSA-10
100 A

NS100N
TMD / STR22SE
KSA-10
100 A

NS100H
TMD / STR22SE
KSA-10
100 A

36

36

70

150

70

70

Discrimination limit between


upstream and downstream
circuit breakers (kA)
36
Reinforced breaking capacity of the
downstream circuit breaker (kA)
36
Reinforced protection of the
downstream busbar trunking (kA)
36

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

NS250N

NS250H

NS250L

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
150

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

NS100N TMD / STR22SE


40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
36
Reinforced breaking capacity of the
downstream circuit breaker (kA)
36
Reinforced protection of the
downstream busbar trunking (kA)
36

188

36

36

36

36

36

36

36

36

36

36

70

70

70

150

150

150

36

36

50

50

50

50

50

50

Schneider Electric

Complementary
technical information

Coordination tables between Merlin Gerin


with the circuit breaker and Telemecanique
Canalis electrical busbar trunking
Cascading and reinforced discrimination
Rated current of the upstream busbar trunking: 200 and 250 A
(cont.)

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit (calibre A)
Downstream busbar trunking

NS250N

NS250H

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70

C60N
16/20
KLE
16 - 20 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
25
Reinforced breaking capacity of the
downstream circuit breaker (kA)
25
Reinforced protection of the
downstream busbar trunking (kA)
25

Upstream circuit breaker


Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

C60N
25/40
KBA / KBB
25 - 40 A

NC100L
25/40
KBA / KBB
25 - 40 A

C60H
16/20
KLE
16 -20 A

C60H
25/40
KBA / KBB
25 - 40 A

NC100L
25/40
KBA / KBB
25 - 40 A

NC100LH
25/40
KBA / KBB
25 - 40 A

25

36

40

40

50

70

25

36

40

40

50

70

25

36

40

40

50

50

NS250N

NS250H

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
36

TMD / STR22SE
KSA / KVA / KVC
200 and 250 A
70

C60N
40 A
KN
40 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
25
Reinforced breaking capacity of the
downstream circuit breaker (kA)
25
Reinforced protection of the
downstream busbar trunking (kA)
25

C60N
63 A
KN
63 A

NC100L
40 A
KN
40 A

NC100L
63 A
KN
63 A

C60H
40 A
KN
40 A

C60H
63 A
KN
63 A

NC100L
40 A
KN
40 A

NC100L
63 A
KN
63 A

NC100LH
40 A
KN
40 A

NC100LH
63 A
KN
63 A

25

36

36

40

30

50

50

70

70

25

36

36

40

30

50

50

70

70

25

36

36

40

30

50

50

50

50

Rated current of the upstream busbar trunking: 160 A


Upstream circuit breaker
Associated trip unit
Upstream busbar trunking
Level of protection of the
upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit (calibre A)
Downstream busbar trunking

NS160N

NS160H

TMD / STR22SE
KSA
160 A
36

TMD / STR22SE
KSA
160 A
70

C60N
16/20
KLE
16 - 20 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
25
Reinforced breaking capacity of the
downstream circuit breaker (kA)
25
Reinforced protection of the
downstream busbar trunking (kA)
25

C60N
25/40
KBA / KBB
25 - 40 A

NC100L
25/40
KBA / KBB
25 - 40A

C60H
16/20
KLE
16 - 20 A

C60H
25/40
KBA / KBB
25 - 40 A

NC100L
25/40
KBA / KBB
25 - 40 A

NC100LH
25/40
KBA / KBB
25 - 40 A

25

36

40

40

50

70

25

36

40

40

50

70

25

36

40

40

50

50

Upstream circuit breaker

NS160N

NS160H

Associated trip unit


Upstream busbar trunking

TMD / STR22SE
KSA
160 A
36

TMD / STR22SE
KSA
160 A
70

Level of protection of the


upstream busbar trunking (kA)
Downstream circuit breaker
Associated trip unit
Downstream busbar trunking

C60N
40 A
KN
40 A

Discrimination limit between


upstream and downstream
circuit breakers (kA)
25
Reinforced breaking capacity of the
downstream circuit breaker (kA)
25
Reinforced protection of the
downstream busbar trunking (kA)
25

Schneider Electric

C60N
63 A
KN
63 A

NC100L
40 A
KN
40 A

NC100L
63 A
KN
63 A

C60H
40 A
KN
40 A

C60H
63 A
KN
63 A

NC100L
40 A
KN
40 A

NC100L
63 A
KN
63 A

NC100LH
40 A
KN
40 A

NC100LH
63 A
KN
63 A

25

36

36

40

40

50

50

70

70

25

36

36

40

40

50

50

70

70

25

36

36

40

40

50

50

50

50

189

266

Compact NS

Schneider Electric

Compact

Catalogue numbers

Presentation
Functions and characteristics
Installation recommendations
Dimensions, volumes
Connection
Electrical diagrams
Additional characteristics

1
11
143
165
205
221
251

NSA80H-MA
NSC100N
NS100/160/250N/H 1P/2P
NS100/160/250N complete fixed/FC device
NS100/160/250H complete fixed/FC device
NS100/160/250L complete fixed/FC device
NS100/160/250N/H/L fixed/FC device based
on separate components
Installation and connection
Accessories
NS400/630 complete fixed/FC device
NS400/630 fixed/FC device based on separate
components
Installation and connection
Accessories
NB50/100
NB250N
NB400N/NB600N
NSA125/160 complete fixed/FC device
Accessories
NS125E
NS100/400
NS630b to NS1600 fixed manually operated
NS630b to NS1600 fixed electrically operated
Accessories for NS630b to NS1600 fixed devices
NS630b to NS1600 manually operated
withdrawable devices
NS630b to NS1600 electrically operated
withdrawable devices
Accessories for NS630b to NS1600
withdrawable devices
Common accessories for NS630b to NS1600
withdrawable devices
NS1600b to NS3200 fixed, front-connected,
manually operated device
Accessories for NS1600b to NS3200

267

Compact NS

268
270
272
274
276
277
278
279
280
285
287
288
290
294
298
298
300
301
302
304
309
311
312
314
315
316
318
320
321

Schneider Electric

Catalogue numbers

NSA125/160: complete fixed/FC


device
NSA160N/E and NSA125/160NA

E21016

Compact NSA160N with built-in trip unit


Compact NSA160N (36 kA at 380/415 V)
Rating
3P 3d
TM16D
28239
TM25D
28238
TM32D
28237
TM40D
28236
TM50D
28235
TM63D
28234
TM80D
28233
TM100D
28232
TM125D
28231
TM160D
28230

4P 4d
28259
28258
28257
28256
28255
28254
28253
28252
28251
28250

E21016

Compact NSA160E with built-in trip unit


Compact NSA160E (16 kA at 380/415 V)
Rating
3P 3d
TM16D
28209
TM25D
28208
TM32D
28207
TM40D
28206
TM50D
28205
TM63D
28204
TM80D
28203
TM100D
28202
TM125D
28201
TM160D
28200

4P 4d
28229
28228
28227
28226
28225
28224
28223
28222
28221
28220

Compact NSA125/160NA switch


Rating
Compact NSA125NA
Compact NSA160NA

550E5060.fm/78

3P
28263
28261

4P
28264
28262

Schneider Electric

Catalogue numbers

Accessories
NSA160N/E and NSA125/160NA

Vigi module 0.03/3A


E20793

Bottom connectors
R

Top connectors

3P
4P
3P
4P

28000
28001
28002
28003

3P
4P

28034
28035

Connection accessories

E18607

Long terminal shields (1 pair)

Electrical auxiliaries
Auxiliary contacts (changeover)
E18608

OF or SD
OF or SD low level

29450
29452

Voltage releases
E21394

AC 50/60 Hz

DC

Voltage (V)
48
110/130
220/240
380/415
440/480
Voltage (V)
24
48
125
250

MX
28070
28071
28072
28073
28074
MX
28075
28076
28077
28078

MN
28080
28081
28082
28083
28084
MN
28085
28086
28087
28088

Rotary handles

E31293

Door-mounted rotary control


Extended black handle
Red handle on yellow front

28059
28058

DIN rail and riser for Multi 9 devices

28041

ON
I

trippe

5...8

reset

O
OFF

Miscellaneous

Schneider Electric

550E5060.fm/79

Catalogue numbers

Source changeover
Compact NS100 to NS630 and
Compact C801 to C1251

Manual source changeover


Mechanical interlocking
NS100...250
NS400...630

29354
32614

For rotary handled circuit-breakers

NS100...250
NS400...630
C801...1251

29369
32621
46946

E18780

E21288

For toggle controlled circuit-breakers

Key lock interlocking


E23851

For rotary handled or remote controlled circuit breakers


2 locks, 1 key
Ronis 1351.500
Profalux KS5 B24 D4Z

41950
42878

Remote controlled source changeover


Plate + IVE
E33419

Source "normal"/source "replacement" (identical voltages) 24 to 250 V DC

48 to 415 V AC 50/60 Hz
480 V 60 Hz

NS100...250/NS100...250
Plate + IVE (1)
Plate
IVE
Auxiliary switches 2 OF + 2 SDE
Spare wiring system (device/IVE)
Back sockets option add:
Only long RC
Plug in base option add:
Plug in kit
NS400...630/NS100...630
Plate + IVE (1)
Plate
IVE
Auxiliary switches 2 OF + 2 SDE
Spare wiring system (device/IVE)
Back sockets option add:
Only long RC
Plug in base option add:
Plug in kit
Adaptator kit for NS100...250

29351
29349
29356
4 x 29450
29365
(2)
(2)

29350
29349
29352
4 x 29450
29365
(2)
(2)

32611
32609
29356
4 x 29450
29365
(2)
(2)
1 x 32618

32610
32609
29352
4 x 29450
29365
(2)
(2)
1 x 32618

C801...1251/C801...1251
Plate + IVE (1)
Plate
IVE
Auxiliary switches 3 OF + 1 SD
Contact SDE for Compact with T remote control
Motormech. For ats spare wiring (device/IVE)
Back sockets option

46955
46949
46956
2 x 44901
2 x 46962
46873
(2)

46954
46949
46957
2 x 44901
2 x 46962
46873
(2)

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz
480 V 60 Hz
29471
29364
29377
29473
29364
29380
29475
29364
29381

Control unit option


E33420

110/127 V AC 50/60 Hz
GERIN
MERLIN
multi

0 . OFF

P25M

GERIN
MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M
660V
AC3-IEC292-1

Test

Test

ACP + control unit BA (1)


Plate ACP
Control unit BA
ACP + control unit UA (1)
29448
Plate ACP
29447
Control unit UA 29446
ACP + control unit UA150 (1) (communication option)
Plate ACP
Control unit UA150

29470
29363
29376
29472
29363
29378
29474
29363
29379

Wiring cable between BA/UA and ACP/IVE


29368
29368
(1) the supply voltages BA/UA control unit, ACP plate, IVE and the remote control must be identical whatever the source
changeover type.
(2) see products pages.

Connection accessories

E23851

Downstream coupling accessories


Source "normal"/source "replacement"
NS100...250/NS100...250
250 A
NS400...630/NS400...630

550E5065.fm/114

630 A

3P
4P
3P
4P

29358
29359
32619
32620

Schneider Electric

Catalogue numbers

Source changeover (cont.)


Compact NS100 to NS630 and
Compact C801 to C1251 (cont.)

Typical composition of remote controlled source changeover


Remote controlled source changeover
E33422

1 normal device N (1)


+ 1 replacement device R (2)
+ 2 remote controls (3)
+ 1 plate with interlocking (4) with IVE (5) and its wiring (8)
+ 2 plug-in kits (if plug-in version)
+ 1 adaptor kit for NS100...250 plug-in (if NS400...630 with NS100...250)
+ auxilary switches (6)
2 x (1 OF + 1 SDE) for Compact NS100...630
2 x (3 OF + 1 SD) for Compact C801...1251
+ 1 downstream coupling accessory (7) for Compact NS100...630 (option)
+ long RC (if back connection)

IVE voltages and remote controls are identical.

E33423

Associated control unit


GERIN
MERLIN
multi

0 . OFF

P25M

GERIN
MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M
660V
AC3-IEC292-1

Test

Test

1 source changeover without associated control unit


+ 1 ACP (9) with BA control unit (10)
Or + 1 ACP (9) with UA control unit (11)
Or + 1 ACP (9) with UA150 control unit (11)

IVE voltages + remote control + ACP + BA or UA are identical.

Schneider Electric

550E5065.fm/115

550E5065.fm/116

Schneider Electric

Catalogue numbers

NS125E
Complete fixed/FC device and
accessories

Complete device
E21284

Compact NS125E with standard thermal-magnetic trip unit TM-D

push
to
trip

Im
5

Ir Im

.9

.95

1.5
.98
.63

Ir
.85
.8
.7

10
xIr

1
xIn

Compact NS125E (16 kA at 380/415 V)


Rating
3P 3d
TM16D
34636
TM25D
34635
TM40D
34634
TM63D
34633
TM80D
34632
TM100D
34631
TM125D
34630

4P 3d
34646
34645
34644
34643
34642
34641
34640

4P 4d
34656
34655
34654
34653
34652
34651
34650

4P 3d
34686
34685
34684
34683
34682
34681
34680

4P 4d
34696
34695
34694
34693
34692
34691
34690

E21279

Vigicompact NS125E MH with trip unit TM-D

push
to
trip

Vigicompact NS125E (16 kA at 380/415 V)


Rating
3P 3d
TM16D
34676
TM25D
34675
TM40D
34674
TM63D
34673
TM80D
34672
TM100D
34671
TM125D
34670

Installation and connection


E16992

RC device = FC device + RC kit


Short RC kit
3P
4P
Comprising:
Mixed RC kit
3P
4P
Comprising:

Kit 3P
Kit 4P

Kit 3P
Kit 4P

6 short RCs
8 short RCs

4 short RCs
2 long RCs
4 short RCs
4 long RCs

3x
4x

29237
29238
29235
29235

2x
1x
2x
2x

29239
29240
29235
29236
29235
29236

Accessories
Connection accessories

E18579

Rear connections
2 short
2 long

29235
29236

E18589

E18572

Bare cable connectors


Snap-on, for cable
1.5 to 95 mm2

Set of 3
Set of 4

29242
29243

Clips for bare-cable connector


Distribution connectors for six
1.5 to 35 mm2 cables with
interphase barriers

Set of 10
Set of 3
Set of 4

29241
29248
29249

Right-angle terminal extensions Set of 3


Set of 4

29261
29262

Straight terminal extensions

Set of 3
Set of 4

29263
29264

3P
4P
Supplied with 2 (or 3) interphase barriers

31563
31564

E18601

E18600

Terminal extensions

E186599

Spreaders

550E5080.fm/160

Schneider Electric

NS125E (cont.)
Accessories

Catalogue numbers

Connection accessories (cont.)


Crimp lugs
E18602

For cable 120 mm2

Set of 3
Set of 4
For cable 150 mm2
Set of 3
Set of 4
For cable 185 mm2
Set of 3
Set of 4
Supplied with 2 (or 3) interphase barriers

29252
29256
29253
29257
29254
29258

Short (1 pair)

3P
4P

29321
29322

Long (1 pair)

3P
4P

29323
29324

Interphase barriers

Set of 6

29329

E18606

E18618

Terminal shields

Electrical auxiliaries - test kits


Auxiliary contacts (changeovers)
E18608

OF or SD or SDE or SDV
SDE adapter for trip unit TM

29450
29451

Voltage releases
Voltage (V)
48
110/130
208/277
380/480
525/600
DC
Voltage (V)
12
24
30
48
60
125
250
MN 220/240 V AC with time delay
Composed of:
MN 250 V DC
Delay unit 220/240 V 50/60 Hz

E18609

AC 50/60 Hz

MX
29385
29386
29387
29388
29389
MX
29382
29390
29391
29392
29383
29393
29394

MN
29405
29406
29407
29408
29409
MN
29402
29410
29411
29412
29403
29413
29414
29422
29414
29427

Rotary handles

E18611

Direct rotary handle


ON
I

O
OFF

Standard black handle


Red handle on yellow front
MCC conversion accessory
CNOMO conversion accessory

29337
29339
29341
29342

Standard extended rotary handle


Red handle on yellow front

29338
29340

Locking devices
Key locks

29344
41940
42888
29345
29346

Extended rotary handle


E18612

ON
I

O
OFF

ON
I

OFF

E18620

Accessories
ON
I

pr

of

al

ux

O
OFF

Indication auxiliary

Ronis 1351.500
Profalux KS5 B24 D4Z
1 early-break contact
2 early-make contacts

Locks
Toggle locking device for 3 padlocks
Removable
Fixed

Schneider Electric

29370
29371

550E5080.fm/161

NS100/400 with "tarif jaune"


connection

Catalogue numbers

Complete fixed/FC device without accessories


Compact NS with trip unit STRAB
E22078

Compact NS

push
to
trip

STR
90 %Ir
105

.9
.95
.98
.63

alarm

5
6

3
8
2
1.5

10
xIr

xIn

22 DE

50/60H

Im
4

Ir
.85
.8
.7

Ir Im

test

NS100N STRAB
NS160N STRAB
NS250N STRAB
NS400N STRAB

Rating
100
160
240
400

Comprising:
NS100N + STRAB100
NS160N + STRAB160
NS250N + STRAB240
NS400N + STRAB400

4P
34562
34563
34564
34565
Basic frame
29008
30408
31408
32408

Trip unit
34550
34551
34554
34557

Vigicompact NS with trip unit STRAB


E22087

Vigicompact NS

push
to
trip

NS100N STRAB
NS160N STRAB
NS250N STRAB
NS400N STRAB

Rating
100
160
240
400

Comprising:
NS100N + STRAB100 + MH
NS160N + STRAB160 + MH
NS250N + STRAB240 + MH
NS400N + STRAB400 + MB

550E5080.fm/162

4P
34572
34573
34574
34575
Basic frame
29008
30408
31408
32408

Trip unit
34550
34551
34554
34557

Vigi module MH/MB


29211
29211
31536
32456

Schneider Electric

Catalogue numbers

NS100/400 "tarif jaune"


connection (cont.)

Complet fixed/FC device without accessories

E22086

Compact NS with normal trip unit

push
to
trip

STR

.9

.85

.98
.63
1

1.5

test

Ir Im

8
2

.982

22 DE

alarm
3

.9

3
.95 .95

.8
.7

.63

z
50/60H

90 %Ir
105 Im

Im
4

Ir

Ir
.85
.8
.7

1.5

10
xIr

Ir Im

10
xIr

xIn

xIn

Compact NS100N
Rating
TM40D
TM63D
TM80D
TM100D
Compact NS160N
Rating
TM80D
TM100D
TM125D
TM160D
Compact NS250N
Rating
TM125D
TM160D
TM200D
TM250D
Compact NS400N
STR23SE

4P 3d
29643
29642
29641
29640

4P 4d
29653
29652
29651
29650

4P 3d+N/Z

29661
29660

4P 3d
30643
30642
30641
30640

4P 4d
30653
30652
30651
30650

4P 3d+N/Z
30663
30662
30661
30660

4P 3d
31643
31642
31641
31640

4P 4d
31653
31652
31651
31650

4P 3d+N/Z
31663
31662
31661
31660

4P 3d
32694

4P 4d
32694

4P 3d+N/Z
32694

4P 3d
29943
29942
29941
29940

4P 4d
29953
29952
29951
29950

4P 3d+N/Z

29961
29960

4P 3d
30943
30942
30941
30940

4P 4d
30953
30952
30951
30950

4P 3d+N/Z
30963
30962
30961
30960

4P 3d
31943
31942
31941
31940

4P 4d
31953
31952
31951
31950

4P 3d+N/Z
31963
31962
31961
31960

4P 3d
32734

4P 4d
32734

4P 3d+N/Z
32734

E22087

Vigicompact NS with normal trip unit

push
to
trip

Compact NS100N
Rating
TM40D
TM63D
TM80D
TM100D
Compact NS160N
Rating
TM80D
TM100D
TM125D
TM160D
Compact NS250N
Rating
TM125D
TM160D
TM200D
TM250D
Compact NS400N
STR23SE

Schneider Electric

550E5080.fm/163

Catalogue numbers

NS100/400 "tarif jaune"


connection (cont.)

E51002

E51001

Interpact INV100 to INV630 standard version


Interpact INV100
Interpact INV160
Interpact INV200
Interpact INV250

For Compact NS100


For Compact NS160
For Compact NS250
For Compact NS250

4P
31161
31165
31163
31167

Interpact INV320
Interpact INV400

For Compact NS400


For Compact NS400

4P
31169
31171

E51003

Spare viewport
For INV100 to 250
For INV320/400

31089
31090

E51005

E51004

Combination with Compact NS devices

550E5080.fm/164

INV100 to 250 - NS250 combination assembly


INV320/400 - NS250 combination assembly
Front alignment base for INV320/400 - NS250 combination assembly
INV320/400 - NS400 combination assembly

31066
31067
31064
31068

Flexible connection assembly, vertical INV100 to 250 to horizontal NS250


Flexible connection assembly, vertical INV320/400 to horizontal NS250
Flexible connection assembly, vertical INV100 to 250 to vertical NS250, side-by-side
Flexible connection assembly, vertical INV320/400 to vertical NS400, side-by-side
Flexible connection assembly, vertical INV320/400 to vertical NS250, side-by-side

31069
31092
31071
31072
31093

Schneider Electric

Catalogue numbers

NS100/400 "tarif jaune"


connection (cont.)

Installation and connection with or without the visible break function


Conventional installation
Combination assembly
Upstream and downstream connection
INV100 to 250 4 snap-on bare cable
NS100/160/250
connectors for cables:

INV320/400 - NS100/160/250

INV320/400 - NS400

1.5 to 95 mm2 ; y 160 A


10 to 185 mm2 ; y 250 A

10 clips for bare cable connector


4 right-angle terminal extensions
2 long terminal shields
4 bare cable connectors :
For 1 cable, 35 mm2
to 300 mm2
For 2 cables, 35 mm2
to 240 mm2
4 right-angle terminal extensions
2 long terminal shields
4 snap-on bare cable
1.5 to 95 mm2 ; y 160 A
connectors for cables:
10 to 185 mm2 ; y 250 A
10 clips for bare cable connector
4 right-angle terminal extensions
2 long terminal shields
4 bare cable connectors :
For 1 cable, 35 mm2
to 300 mm2
For 2 cables, 35 mm2
to 240 mm2
4 right-angle terminal extensions
2 long terminal shields

2x
2x
1x
2x
1x
1x

29243
29260
29241
29262
29324
32480

1x

32482

1x
1x
1x
1x
1x
1x
1x
2x

32485
32565
29243
29260
29241
29262
29324
32480

2x

32482

2x
1x

32485
32565

2x
2x
1x
1x

29243
29260
29322
32480

1x

32482

1x
1x
1x
1x
2x

32563
29243
29260
29322
32480

2x

32482

1x

32563

Installation in cabinet or enclosure


Combination assembly (mounting in duct)
Flexible connection assembly (mounting in cubicle)
Upstream and downstream connection
INV100 to 250 4 snap-on bare cable
NS100/160/250
connectors for cables:
INV320/400 - NS100/160/250

2 short terminal shields


4 bare cable connectors :

2 short terminal shields


4 snap-on bare cable
connectors for cables:
INV320/400 - NS400

2 short terminal shields


4 bare cable connectors :

2 short terminal shields

Schneider Electric

1.5 to 95 mm2 ; y 160 A


10 to 185 mm2 ; y 250 A
For 1 cable, 35 mm2
to 300 mm2
For 2 cables, 35 mm2
to 240 mm2
1.5 to 95 mm2 ; y 160 A
10 to 185 mm2 ; y 250 A
For 1 cable, 35 mm2
to 300 mm2
For 2 cables, 35 mm2
to 240 mm2

550E5080.fm/165

550E5080.fm/166

Schneider Electric

Catalogue numbers

NS630b to NS1600 fixed


manually operated
Complete device

Front-connected circuit breaker with Micrologic 2.0 control unit


E59545

Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

3P
33460
33466
33472
33478
33482

4P
33463
33469
33475
33480
33484

3P
33461
33467
33473
33479
33483

4P
33464
33470
33476
33481
33485

3P
33462
33468
33474

4P
33465
33471
33477

3P
33546
33552
33558
33564
33568

4P
33549
33555
33561
33566
33570

3P
33547
33553
33559
33565
33569

4P
33550
33556
33562
33567
33571

Icu = 150 kA at 220/415 V


NS630b
NS800
NS1000

3P
33548
33554
33560

4P
33551
33557
33563

NS630b
NS800
NS1000
NS1250
NS1600

3P
33486
33487
33488
33489
33490

4P
33491
33492
33493
33494
33495

Compact NS type H
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type L
Icu = 150 kA at 220/415 V
NS630b
NS800
NS1000

Front-connected circuit breaker with Micrologic 5.0 control unit


E59545

Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type H
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type L

E59546

Front-connected switch-disconnector

Nota : select in addition the connection accessories, device accessories and auxiliaries, control-unit accessories and communications option, as required.

550E5100.fm/2

Schneider Electric

Catalogue numbers

NS630b to NS1600 fixed


manually operated (cont.)
Complete device (cont.)

Front-connected circuit breaker with Micrologic 2.0 A control unit


E47313

Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

3P
33223
33233
33243
33253
33263

4P
33227
33237
33247
33257
33267

3P
33228
33238
33248
33258
33268

4P
33229
33239
33249
33259
33269

3P
33497
33498
33499

4P
33500
33501
33502

Compact NS type H
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type L
Icu = 150 kA at 220/415 V
NS630b
NS800
NS1000

Front-connected circuit breaker with Micrologic 5.0 A control unit


E47313

Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

3P
33323
33333
33343
33353
33363

4P
33327
33337
33347
33357
33367

3P
33328
33338
33348
33358
33368

4P
33329
33339
33349
33359
33369

Compact NS type H
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type L
Icu = 150 kA at 220/415 V
3P
4P
NS630b
33516
33519
NS800
33517
33520
NS1000
33518
33521
Nota : select in addition the connection accessories, device accessories and auxiliaries, control-unit accessories and communications option, as required.

Schneider Electric

550E5100.fm/3

Catalogue numbers

NS630b to NS1600 fixed


manually operated (cont.)
Device based on separate
components

Basic circuit breaker


E59547

Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

3P
33220
33230
33240
33250
33260

4P
33224
33234
33244
33254
33264

3P
33221
33231
33241
33251
33261

4P
33225
33235
33245
33255
33265

3P
33222
33232
33242

4P
33226
33236
33246

Without ammeter
33504
33511

With ammeter
(option A)
33505
33512
33513
33514

3P
33420
33422
33424
33426
33428

4P
33421
33423
33425
33427
33429

Top
Bottom
Top
Bottom
Top
Bottom

3P
33598
33599
33600
33601
33602
33603

4P
33608
33609
33610
33611
33612
33613

Top
Bottom
Top
Bottom

3P
33604
33605
33606
33607

4P
33614
33615
33616
33617

Compact NS type H
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type L
Icu = 150 kA at 220/415 V
NS630b
NS800
NS1000

+ Micrologic control units

Basic protection
Selective protection
Selective + earth-fault protection
Selective + earth-leakage protection

2.0
5.0
6.0
7.0

Basic switch-disconnector
E59548

Compact NS type NA
NS630b
NS800
NS1000
NS1250
NS1600

Connections for circuit breakers and switch-disconnectors


E59549

Front connection
630/1000 A
1250 A
630/1000 A type L
1600 A

Rear connection
Vertical
Horizontal

Note: to order a complete device, order:


b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector
b connections
b accessories (for the device, the connection, the control unit) and communication option as required.

550E5100.fm/4

Schneider Electric

Catalogue numbers

NS630b to NS1600 fixed


electrically operated
Device based on separate
components

Basic circuit breaker


E59550

Compact NS type N

U?
I
O
push

push

ON

OFF

ed
discharg

O OFF

Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

3P
33270
33280
33290
33300
33310

4P
33274
33284
33294
33304
33314

3P
33271
33281
33291
33301
33311

4P
33275
33285
33295
33305
33315

3P
33272
33282
33292

4P
33276
33286
33296

Without ammeter

With ammeter
(option A)
33505
33512
33513
33514

Compact NS type H
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
Note: the characteristics of the motor
mechanism module for electrical operation are
specified separately by selecting a part number
from the table at the bottom of this page.

Compact NS type L
Icu = 150 kA at 220/415V
NS630b
NS800
NS1000

+ Micrologic control units

Basic protection
Selective protection
Selective + earth-fault protection
Selective + earth-leakage protection

2.0
5.0
6.0
7.0

33504
33511

Basic switch-disconnector
E59551

Compact NS type NA

U?
I
O
push

push

ON

OFF

ed
discharg

O OFF

3P
4P
NS630b
33440
33441
NS800
33442
33443
NS1000
33444
33445
NS1250
33446
33447
NS1600
33448
33449
Note: the characteristics of the motor mechanism module for electrical operation are specified
separately by selecting a part number from the table at the bottom of this page.

Connections for circuit breakers and switch-disconnectors


E59549

Front connection
630/1000 A
1250 A
630/1000 A type L
1600 A

Top
Bottom
Top
Bottom
Top
Bottom

3P
33598
33599
33600
33601
33602
33603

4P
33608
33609
33610
33611
33612
33613

Top
Bottom
Top
Bottom

33604
33605
33606
33607

33614
33615
33616
33617

Rear connection
Vertical
Horizontal

Motor mechanism module


AC 50/60 Hz

DC

Standard
Communicating
Standard
48 V
33691
33698
24-30 V
33690
100-130 V
33687
33694
48-60 V
33691
220-240 V
33688
33695
100-130 V
33692
380-415 V
33689
33696
200-250 V
33693
Note: to order a complete device, order:
b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector
b connections
b accessories (for the device, the connection, the control unit) and communication option as required.
Schneider Electric

Communicating
33697
33698
33699
33700

550E5100.fm/5

Catalogue numbers

NS630b to NS1600 manually


operated withdrawable devices
Device based on separate
components

Basic circuit breaker


E47311

Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

3P
33320
33330
33340
33350
33360

4P
33324
33334
33344
33354
33364

3P
33321
33331
33341
33351
33361

4P
33325
33335
33345
33355
33365

3P
33322
33332
33342

4P
33326
33336
33346

Without ammeter
33504
33511

With ammeter
(option A)
33525
33532
33533
33534

3P
33430
33432
33434
33436
33438

4P
33431
33433
33435
33437
33439

3P
33722
33723

4P
33725
33726

3P

4P

33727
33728

33733
33734

33729
33730
33731
33732

33735
33736
33737
33738

Compact NS type H
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type L
Icu = 150 kA at 220/415 V
NS630b
NS800
NS1000

+ Micrologic control units

Basic protection
Selective protection
Selective + earth-fault protection
Selective + earth-leakage protection

2.0
5.0
6.0
7.0

Basic switch-disconnector
E59685

Compact NS type NA
NS630b
NS800
NS1000
NS1250
NS1600

Basic chassis and connections


E59652

Chassis
630/1250 A
1600 A
630/1000 A type L

E59585

E59584

+ connection
Front connection
Top
Bottom

Rear connection
Vertical
Horizontal

Top
Bottom
Top
Bottom

Note: to order a complete device, order:


b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector
b chassis and connections
b accessories (for the device, the connection, the control unit) and communication option as required.

550E5100.fm/6

Schneider Electric

Catalogue numbers

NS630b to NS1600 electrically


operated withdrawable devices
Device based on separate
components

Basic circuit breaker


E47312

Compact NS type N

U?
I
push

O
push

ON

Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

3P
33370
33380
33390
33400
33410

4P
33374
33384
33394
33404
33414

3P
33371
33381
33391
33401
33411

4P
33375
33385
33395
33405
33415

OFF

Compact NS type H

d
discharge

O OFF

Note: the characteristics of the motor


mechanism module for electrical operation are
specified separately by selecting a part number
from the table at the bottom of this page.

Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600

Compact NS type L
Icu = 150 kA at 220/415 V

3P

4P

NS630b
NS800
NS1000

33372
33382
33392

33376
33386
33396

Without ammeter

With ammeter
(option A)
33525
33532
33533
33534

+ Micrologic control units

Basic protection
Selective protection
Selective + earth-fault protection
Selective + earth-leakage protection

2.0
5.0
6.0
7.0

33504
33511

Basic switch-disconnector
E59686

Compact NS type NA

U?
I
O
push

push

ON

OFF

ed
discharg

O OFF

3P
4P
NS630b
33450
33451
NS800
33452
33453
NS1000
33454
33455
NS1250
33456
33457
NS1600
33458
33459
Note: the characteristics of the motor mechanism module for electrical operation are specified
separately by selecting a part number from the table at the bottom of this page.

Chassis and connections


E59652

Chassis
630/1250 A
1600 A
630/1000 A type L

3P
33722
33723

4P
33725
33726

3P

4P

33727
33728

33733
33734

33729
33730
33731
33732

33735
33736
33737
33738

E59585

E59584

+ connection
Front connection
Top
Bottom
Rear connection
Vertical
Horizontal

Top
Bottom
Top
Bottom

Motor mechanism module


AC 50/60 Hz

DC

Standard
Communicating
Standard
48 V
33831
33838
24-30 V
33830
100-130 V
33827
33834
48-60 V
33831
220-240 V
33828
33835
100-130 V
33832
380-415 V
33829
33836
200-250 V
33833
Note: to order a complete device, order:
b a basic circuit breaker and a Micrologic control unit, or a basic switch disconnector,
b chassis and connections
b accessories (for the device, the connection, the control unit) and communication option as required.

Schneider Electric

Communicating
33837
33838
33839
33840

550E5100.fm/7

Catalogue numbers

Accessories for NS630b to NS1600


fixed devices

Connection accessories
Front connection

Rear connection

E59558

Bare-cable connectors + 1 connector shield for 4 cables (240 mm2)


3P (3 parts)
4P (4 parts)

33640
33641

3P
4P

33628
33629

3P (3 parts)
4P (4 parts)

33642
33643

3P (3 parts)
4P (4 parts)

33644
33645

E59578

1 long connection shield

E59559

Vertical-connection adapters

E59560

Cable lug adapters

Interphase barriers
E79151

3P/4P top (3 parts)


33646
3P/4P bottom (3 parts) 33646

3P/4P top (3 parts)


33648
3P/4P bottom (3 parts) 33648

Arc chute screen


E74437

3P
4P

33596
33597

Brackets for mounting on a horizontal surface


3P/4P (2 parts)

33647

3P
4P

33622
33623

Spreaders
E598561

3P
4P

33622
33623

Cable lug kits


E47820

240 mm2
300 mm2

3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)

33013
33014
33015
33016

Electrical auxiliaries
Indication contacts
(1)
6 A - 240 V
29450
(1)
Low level
29452
Up to 3 OF, 1 SD and 1 SDE can be connected (the SDE contact is standard for electrically operated devices).

E59574

OF, SD, SDE

Instantaneous voltage releases


E59575

MX
12 V DC
24-30 V AC/DC
48-60 V AC/DC
100-130 V AC/DC
200-250 V AC/DC
240-277 V AC
380-480 V AC

33658
33659
33660
33661
33662
33663
33664

MN

33668
33669
33670
33671

Delay unit for MN


R (non-adjustable)

Rr (adjustable)

33684
33685

33680
33681
33682

33673

33683

Installation accessories
33717

Escutcheon for:
- device with toggle (large cutout)
- device with rotary handle
- electrically operated device

33718

E59582

E59576

Escutcheon (small cut-out) for manually operated device with toggle

Blanking plate
E59588

33858

(1) See Compact NS.

550E5100.fm/8

Schneider Electric

Catalogue numbers

Accessories for NS630b to NS1600


withdrawable devices

Connection accessories

E59559

Vertical-connection adapters for front-connected chassis


3P (3 parts)
4P (4 parts)

33642
33643

3P (3 parts)
4P (4 parts)

33644
33645

3P/4P (3 parts)

33768

E59560

Cable lug adapters for front-connected chassis

E59579

Interphase barriers for rear-connected chassis

E598561

Spreaders for front-connected and rear-connected chassis


3P (3 parts)
4P (4 parts)

33622
33623

3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)

33013
33014
33015
33016

3P
4P

33763
33764

3P
4P

33765
33766

Cable lug kits


E47820

240 mm2
300 mm2

Chassis accessories

E59589

Auxiliary terminal shield (CB)

E59649

Safety shutters (VO)

Electrical auxiliaries
SD trip indication contact for manually operated devices
6 A - 240 V
Low level

33800
33803

SDE fault indication contact for manually operated devices


6 A - 240 V
Low level

33799
33802

6 A - 240 V
Low level
Up to 3 OF contacts per device

33801
33804

6 A - 240 V
Low level
Up to 3 CE, 1 CT, 2 CD per device

33170
33171

E59655

OF ON/OFF indication contacts

E59656

CE, CD, CT carriage switches

Instantaneous voltage releases


E59657

MX
12 V DC
24-30 V AC/DC
48-60 V AC/DC
100-130 V AC/DC
200-250 V AC/DC
240-277 V AC
380-480 V AC

33809
33810
33811
33812
33813
33814
33815

MN

33819
33820
33821
33822
33824

Delay unit for MN


R (non-adjustable)

Rr (adjustable)

33684
33685

33680
33681
33682
33683

Auxiliary terminals for chassis alone


3 wire terminal (30 parts)
6 wire terminal (10 parts)
Jumpers (10 parts)

Schneider Electric

47071
47072
47900

550E5100.fm/9

Catalogue numbers

Accessories for NS630b to NS1600


withdrawable devices (cont.)

Chassis locking
Keylocking in disconnected position
E59650

Profalux

Ronis

1 lock
1 lock + 1 lock with same key profile
2 locks (with different key profiles)
1 lock
1 lock + 1 lock with same key profile
2 locks (with different key profiles)

33773
33774
33775
33776
33777
33778

Option for locking in connected, disconnected and test positions


Keylock kit (without keylocks)
Profalux
Ronis
Castell
Kirk

33779
33769
33770
33771
33772

Right side of chassis (VPECD)


Left side of chassis (VPECG)

33786
33787

(1)

E59651

Door interlock

Racking interlock (VPOC)


E59653

33788

Mismatch protection (VDC)


E59654

33767

Installation accessories
Escutcheon
E46668

33857

Transparent cover for escutcheon


E59587

33859

Blanking plate
E59588

33858

(1) No charge.

550E5100.fm/10

Schneider Electric

Catalogue numbers

Accessories for NS630b to NS1600


fixed and withdrawable devices

Locking for manually operated devices


Removable toggle locking system
44936

E59562

Locking by 3 padlocks

Fixed toggle locking system


32631

E68390

Locking by 3 padlocks

Rotary handle for manually operated devices


Devices with direct rotary handles
E59563

Handle

Keylock kit (without keylocks)

33863
33864
33866
Ronis
33870
33872
33868

For 2 devices with extended rotary handles

33890

I on

trippe

Conversion accessory
Locking by keylocks

reset

0 OFF

Black
Red/yellow front
CNOMO
OFF position
OFF and ON positions

Profalux
33869
33871
33868

E70744

Mechanical interlocking

Devices with extended rotary handles


E59564

Handle
I on

d
trippe

Black
Red/yellow front
Telescopic (for chassis-mounted devices)

33878
33879
33880

reset

0 OFF

ON

tripped

reset

OFF

Control accessories
E59573

2 advanced indication contacts (6 A - 240 V)


Early break
Early make

33882
33883

Locking and accessories for electrically operated devices


Pushbutton locking
33897

E59577

By transparent cover + padlocks

Locking in OFF position


E59580

By Profalux keylocks
By Ronis keylocks
Keylock kit (without keylocks)

1 lock
1 lock + 1 lock with same key profile
1 lock
1 lock + 1 lock with same key profile
For Profalux keylocks
For Ronis keylocks
For Kirk keylocks
For Castell keylocks

33902
33904
33903
33905
33898
33899
47517
47518

Operation counter CDM


E59581

33895
9
0039

Schneider Electric

550E5100.fm/11

Catalogue numbers

Accessories for NS630b to NS1600


fixed and withdrawable devices

Communications options
E59553

For fixed devices


Modbus COM
Eco Modbus COM module
Digipact COM

Manually operated
33702
33703
33705

Electrically operated
33708
33709
33711

Manually operated
33842
33714
33845

Electrically operated
33848
33713
33851

33852
33855

33852
33855

For moving part


Modbus COM
Eco Modbus COM module
Digipact COM

+ chassis
Modbus
Digipact

Accessories for Micrologic control units


Long-time rating plug (enhanced accuracy by limiting the setting range)
alarm

E59658

long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr
(s)

2
1
.5

8 12
16
20
24
Ir
@6

Standard
Low setting
High setting

0.4 to 1 x Ir
0.4 to 0.8 x Ir
0.8 to 1 x Ir

33542
33543
33544

Without long-time protection

OFF

33545

External sensors
33576

E59659

External sensor for neutral + earth-fault protection (TCE)


CT rating: 400/1600 A

33573

E59660

Rectangular sensor for earth-leakage protection


280 mm x 115 mm

E59659

Source ground return (SGR) earth fault protection


External sensor (SGR)
MDGF summing module

33579
48891

E59661

External power supply module


24-30 V DC
48-60 V DC
125 V DC
110 V AC
220 V DC
380 V DC

54440
54441
54442
54443
54444
54445

Test equipment
Mini test kit
E59921

33594

Portable test kit


E59554

33595

Spare parts
46996

E23865

Toggle extension

550E5100.fm/12

Schneider Electric

Catalogue numbers

Accessories for NS630b to NS1600


fixed and withdrawable devices
(cont.)

Mechanical interlocking for source changeover


Interlocking using connecting rods for Compact electrically operated devices
E72941

Complete assembly with 2 adaptation fixtures + rods


2 Compact fixed devices
2 Compact withdrawable devices

33910
33913

FFO
hsup

NO h
sup

FFO

O
d e gr

ahcs

id

FFO
hsup

NO h
sup

FFO

O
d e gr

ahcs

id

Interlocking using cables for Compact electrically operated devices


E72942

Complete assembly with 2 adaptation fixtures + cables


2 Compact fixed devices
2 Compact withdrawable devices
1 Compact fixed + 1 Compact withdrawable device

33911
33914
33915

FFO
hsup

NO h
sup

FFO

O
d e gr

ahcs

id

FFO
hsup

NO h
sup

FFO

O
d e gr

ahcs

id

Schneider Electric

550E5100.fm/13

Catalogue numbers

NS1600b to NS3200 fixed, frontconnected, manually operated


device

Circuit breaker
Compact NS type N
E59555

Icu = 85/70 kA to 220/415 V


NS1600b
NS2000
NS2500
NS3200

3P
34000
34006
34012
34018

4P
34003
34009
34015
34021

3P
34001
34007
34013
34019

4P
34004
34010
34016
34022

Without ammeter
33504
33511

With ammeter
(option A)
33505
33512
33513
33514

3P
34024
34027
34030
34033

4P
34025
34028
34031
34034

Compact NS type H

OFF
OFF

Icu = 125/85 kA to 220/415 V


NS1600b
NS2000
NS2500
NS3200

+ Micrologic control units

Basic protection
Selective protection
Selective + earth-fault protection
Selective + earth-leakage protection

2.0
5.0
6.0
7.0

Switch-disconnector
E59556

Compact NS type NA
NS1600b
NS2000
NS2500
NS3200
OFF
OFF

Optional vertical connection adaptor


1600/2500 A

3P (3 parts)
4P (4 parts)

33975
33976

Note: standard for 3200 A.

Electrical auxiliaries
Indication contacts
E59574

OF, SD, SDE

6 A - 240 V
Low level
Up to 3 OF, 1 SD and 1 SDE can be connected.

29450
29452

(1)
(1)

Instantaneous voltage releases


E59575

MX
12 V DC
24-30 V AC/DC
48-60 V AC/DC
100-130 V AC/DC
200-250 V AC/DC
240-277 V AC
380-480 V AC

33658
33659
33660
33661
33662
33663
33664

MN

33668
33669
33670
33671
33673

Delay unit for MN


R (non-adjustable)

Rr (adjustable)

33684
33685

33680
33681
33682
33683

Locking
Removable toggle locking system
33996

E59562

Locking by 3 padlocks

Fixed toggle locking system


32631

E68390

Locking by 3 padlocks

(1) See Compact NS.

550E5100.fm/14

Schneider Electric

Catalogue numbers

Accessories for NS1600b to


NS3200

Communications option
Modbus COM
E59557

33986
Eco Modbus COM module
33988
Digipact COM
OFF

33987

OFF

Accessories for Micrologic control units


Long-time rating plug (enhanced accuracy by limiting the setting range)
alarm
long

E59658

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr

(s) 4

2
1
.5

8 12
16
20
24
Ir
@6

Standard
Low setting
High setting

0.4 to 1 x Ir
0.4 to 0.8 x Ir
0.8 to 1 x Ir

33542
33543
33544

Without long-time protection

OFF

33545

External sensors
34036

E59659

External sensor for neutral + earth-fault protection (TCE)


CT rating: 1000/4000 A

33574

E59660

Rectangular sensor for earth-leakage protection


470 mm x 160 mm

E59659

Source ground return (SGR) earth fault protection


External sensor (SGR)
MDGF summing module

33579
48891

E59661

External power supply module


24-30 V DC
48-60 V DC
125 V DC
110 V AC
220 V DC
380 V DC

54440
54441
54442
54443
54444
54445

Test equipment
Mini test kit
E59921

33594

Portable test kit


E59554

33595

Spare parts
NS3200 toggle extension for replacement

33997

Installation accessories
Escutcheon
E88640

33929

Interphase barriers (3 parts)


E88639

33998

Schneider Electric

550E5100.fm/15

Catalogue numbers

Communication bus accessories


and display modules

Display modules
DMB300
Max. 4 breakers

50894

Color display module

Max. 16 breakers

50895

E67954

Monochrome display module

E67955

DMC300

Spare parts
DMC300PCM: DMC300 memory card

50959

RS 485 Modbus pre-wired system


RS 485 Modbus junction block
50963

E67958

CJB306: 6 SubD 9 pins connectors junction block

RS 485 Modbus connector


50964

CDM303: display module pre-wired cable, 3 m length

50960

E67959

CSD309: 9 pins SubD with screw terminals

E79015

E67960

RS 485 Modbus cables

CCP303: Masterpact or Compact pre-wired cable (4 RS 485 wires + 2 power wires) 3 m length 50961
CCS303: Masterpact or Compact pre-wired cable (Modbus slave) 3 m length
50962

50965

E67961

CCR301: RS485 roll cable (2 RS 485 wires + 2 power wires) 60 m length

Digipact Bus pre-wired system


Data concentrator DC150
110-240 V AC, 50/60 Hz and 115-125 V DC

50823

E79014

Auxiliary supply voltage

Junction block
50778

E67956

Junction block for internal Bus

Cables
E67957

Cable for internal bus

20-meter roll (0.75 mm2)


100-meter roll (0.75 mm2)

50779
50780

Converter
RS 485/RS 232 (ACE909) 12 V DC power supply included
RS 485/RS 232
RS 485/Ethernet
RS 485/Ethernet (SMS compatible)
RS 485/Ethernet (Micrologic Transparent Ready available 2003)
(1) See catalogue Telemecanique.
(2) See catalogue PowerLogic System.

550E5100.fm/16

59648
TSX SCA72
174 CEV 300-10
EGX 200/400
33507

(1)
(1)
(2)

Schneider Electric

89 boulevard Franklin Roosevelt


F - 92500 Rueil Malmaison (France)
Tel : +33 (0)1 41 29 85 00
http://www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.

This document has been printed


on ecological paper.
Design: Schneider Electric - Ameg.
Photos: Schneider Electric.
Printed:

BTP550E