Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

SymmetricalComponents

DuetoC.L.Fortescue (1918):asetofn
unbalancedphasors inannphase
systemcanberesolvedintonbalanced
phasors byalineartransformation

Lesson8
SymmetricalComponents

8SymmetricalComponents

NotesonPowerSystemAnalysis

Thensetsarecalledsymmetrical
components
Oneofthensetsisasinglephasesetand
theothersarenphasebalancedsets
Heren=3whichgivesthefollowingcase:
1

8SymmetricalComponents

NotesonPowerSystemAnalysis

Symmetricalcomponentdefinition
Zero Sequence

ThreephasevoltagesVa,Vb,andVc
(notnecessarilybalanced,withphase
sequenceabc)canberesolvedinto
threesetsofsequencecomponents:

NotesonPowerSystemAnalysis

Va

Positive Sequence

Vb
Vc

V0

a2

V1

a2

V2

a
c
b

NotesonPowerSystemAnalysis

Negative Sequence

8SymmetricalComponents

NotesonPowerSystemAnalysis

1
1
1

A=

1
a2
a

1
a
a2

Va

where
a=1/120 =(1+j3)/2
a2 =1/240 =1/120
a3 =1/360 =1/0
8SymmetricalComponents

Vb

Va

ZerosequenceVa0=Vb0=Vc0
PositivesequenceVa1,Vb1,Vc1 balanced
withphasesequenceabc
NegativesequenceVa2,Vb2,Vc2balanced
withphasesequencecba
8SymmetricalComponents

Vc

Vb
Vc

Vp =

Vp =AVs
5

8SymmetricalComponents

Vs=

V0
V1
V2

Vs =A1 Vp

NotesonPowerSystemAnalysis

Va =V0 +V1 +V2


Vb =V0 +a2V1 +aV2
Vc =V0 +aV1 +a2V2

1 1 1
A1= (1/3) 1 a a2
1 a2 a
Weusedvoltagesforexample,butthe
resultappliestocurrentoranyother
phasor quantity

Vp =AVs

V0 =(Va +Vb +Vc)/3


V1 =(Va +aVb +a2Vc)/3
V2 =(Va +a2Vb +aVc)/3

Vs =A1 Vp

Thesearethephaseasymmetrical(or
sequence)components.Theotherphases
followsincethesequencesarebalanced.

Ip =AIsIs =A1 Ip
8SymmetricalComponents

NotesonPowerSystemAnalysis

8SymmetricalComponents

Sequencenetworks
AbalancedYconnectedloadhas
threeimpedancesZy connectedlineto
neutral
andoneimpedanceZn connectedneutral
toground
a
Zy
b
Zy
c
Zn
g
8SymmetricalComponents

a
b
c

NotesonPowerSystemAnalysis

Zy

NotesonPowerSystemAnalysis

Sequencenetworks
Zy+Zn

Zn

Zn

Ia

Vbg =

Zn

Zy+Zn

Zn

Ib

Vcg

Zn

Zn

Zy+Zn

Ic

Vag

orinmorecompactnotationVp =Zp Ip
8SymmetricalComponents

NotesonPowerSystemAnalysis

Vp =Zp Ip

Zy
Zy

n
Zn

Zs =

Vp =AVs =Zp Ip =ZpAIs


AVs =ZpAIs
Vs =(A1ZpA)Is
Zs =A1ZpA
NotesonPowerSystemAnalysis

10

Zy+3Zn

Zy

Zy

V0 =(Zy +3Zn)I0 =Z0I0


V1 =Zy I1=Z1I1
V2 =Zy I2=Z2I2

Vs =Zs Iswhere

8SymmetricalComponents

11

8SymmetricalComponents

NotesonPowerSystemAnalysis

12

a
V0
g

I0

Zy
3Zn

Zero
sequence
network

a
V1
n

I1

Zy

Positive
sequence
network

I2
a
V2
n

Zy

a
V0
g

NotesonPowerSystemAnalysis

13

Remarks

NotesonPowerSystemAnalysis

15

NotesonPowerSystemAnalysis

I1

a
V1
n

I2

Z/3

Z/3

a
V2
n

Positive
sequence
network

Negative
sequence
network

8SymmetricalComponents

NotesonPowerSystemAnalysis

14

Generalcaseunsymmetrical
impedances
Zp =

Zs=A1ZpA

8SymmetricalComponents

Zaa

Zab

Zca

Zab

Zbb

Zbc

Zca

Zbc

Zcc

Z0
Z10
Z20

Z01
Z1
Z21

Z02
Z12
Z2

NotesonPowerSystemAnalysis

16

Specialcasesymmetricalimpedances

Z0 =(Zaa+Zbb+Zcc+2Zab+2Zbc+2Zca)/3
Z1 =Z2 =(Zaa+Zbb +ZccZabZbcZca)/3
Z01 =Z20 =
(Zaa+a2Zbb+aZccaZabZbca2Zca)/3
Z02 =Z10 =
(Zaa+aZbb+a2Zcca2ZabZbcaZca)/3
Z12 =(Zaa+a2Zbb+aZcc+2aZab+2Zbc+2a2Zca)/3
Z21 =(Zaa+aZbb+a2Zcc+2a2Zab+2Zbc+2aZca)/3
8SymmetricalComponents

Sequencenetworksforconnectedload
impedances.
NotethattheseareequivalentYcircuits.

Positivesequenceimpedanceisequalto
negativesequenceimpedancefor
symmetricalimpedanceloadsandlines
Rotatingmachinescanhavedifferent
positiveandnegativesequenceimpedances
Zerosequenceimpedanceisusually
differentthantheothertwosequence
impedances
Zerosequencecurrentcancirculateina
deltabutthelinecurrent(attheterminals
ofthedelta)iszerointhatsequence
8SymmetricalComponents

Z/3

Zero
sequence
network

Negative
sequence
network

SequencenetworksforYconnected
loadimpedances
8SymmetricalComponents

I0

Zp =

Zs =
17

8SymmetricalComponents

Zaa
Zab
Zab

Zab
Zaa
Zab

Zab
Zab
Zaa

Z0
0
0

0
Z1
0

0
0
Z2

NotesonPowerSystemAnalysis

18

Powerinsequencenetworks

Z0 =Zaa +2Zab
Z1 =Z2 =Zaa Zab
Z01=Z20=Z02=Z10=Z12=Z21=0
Vp =Zp Ip
Vs =Zs Is

Sp =Vag Ia* +Vbg Ib* +Vcg Ic*


Sp =[Vag Vbg Vcg][Ia* Ib* Ic*]T
Sp =VpT Ip*

Thisappliestoimpedanceloadsandto
seriesimpedances(thevoltageisthe
dropacrosstheseriesimpedances)
8SymmetricalComponents

NotesonPowerSystemAnalysis

19

=(AVs)T (AIs)*
=VsT ATA* Is*
8SymmetricalComponents

NotesonPowerSystemAnalysis

20

Powerinsequencenetworks

Sp =3(V0 I0* +V1 I1* +V2 I2*)=3Ss

Sp =VpT Ip*=VsT ATA*Is*

Inwords,thesumofthepowercalculated
inthethreesequencenetworksmustbe
multipliedby3toobtainthetotalpower.

1
ATA* =

1 1 1

1 a2

1 a a2 = 0 3 0

a2

1 a2 a

3 0 0

0 0 3

Sp =3VsT Is*
8SymmetricalComponents

NotesonPowerSystemAnalysis

21

Thisisanartifactoftheconstantsinthe
transformation.SomeauthorsdivideAby
3toproduceapowerinvariant
transformation.Mostoftheindustryuses
theformthatwedo.
8SymmetricalComponents

NotesonPowerSystemAnalysis

22

N
Sequencenetworksforpowerapparatus

N
V2

I2

Zn

Negative

Z2
Ygenerator

G
3Zn

N
NotesonPowerSystemAnalysis

Positive

Z1

Slidesthatfollowshowsequence
networksforgenerators,loads,and
transformers
Payattentiontozerosequence
networks,asallthreephasecurrents
areequalinmagnitudeandphase
angle
8SymmetricalComponents

V1

I1

23

8SymmetricalComponents

I0

Z0

NotesonPowerSystemAnalysis

V0

Zero
24

V1 I
1

Positive

Zerosequencenetworksforloads

G
N

V2 I
2

UngroundedYload

V0

Negative

I0

G
V0
8SymmetricalComponents

I0

Zero

NotesonPowerSystemAnalysis

25

V0

H1

X1

n
ZN

8SymmetricalComponents

Zn

8SymmetricalComponents

NotesonPowerSystemAnalysis

Zeq+3(ZN+Zn)
A
a
Va0
VA0 I0

H1

g
Zerosequence
network(perunit)

NotesonPowerSystemAnalysis

H1

X1

c
n
Zn

8SymmetricalComponents

A
VA0

27

X1

n
ZN

8SymmetricalComponents

Zn

Zeq

a
Va1

VA1 I1
n

Positivesequence
network(perunit)
Negativesequence
issamenetwork

NotesonPowerSystemAnalysis

28

Ytransformer

Zeq+3Zn
I0

H1

X1

Zeq
A
a
Va1
VA1 I1

Va0

g
Zerosequence
network(perunit)

NotesonPowerSystemAnalysis

26

YYtransformer

Ytransformer
A

connectedload
ungrounded

YYtransformer
A

Yconnectedload
groundedthroughZn

3Zn

29

n
Zn
8SymmetricalComponents

Positivesequence
network(perunit)
Deltasideleadswye
sideby30degrees

NotesonPowerSystemAnalysis

30

Threewinding(threephase)
transformersYY

Ytransformer
A

H1

X1

a
b
c

n
Zn
8SymmetricalComponents

HandXingroundedYandTindelta

Zeq

A
VA2 I2

Zerosequence

a
Va2

31

Threewindingtransformerdata:
Windings Z
BaseMVA
HX
5.39%
150
HT
6.44%
56.6
XT
4.00%
56.6
ConvertallZ'stothesystembaseof100MVA:
Zhx =5.39%(100/150)=3.59%
ZhT =6.44%(100/56.6)=11.38%
ZxT =4.00%(100/56.6)=7.07%
8SymmetricalComponents

NotesonPowerSystemAnalysis

33

ZH

ZX

X H

ZT

T
8SymmetricalComponents

ZX

ZH
T

NotesonPowerSystemAnalysis

32

8SymmetricalComponents

NotesonPowerSystemAnalysis

34

UnbalancedShortCircuits
Procedure:

Balancedthreephaselines:
Z0 >Z1 =Z2
Balancedthreephasetransformers
(usually):
Z1 =Z2= Z0
Rotatingmachines:Z1 Z2> Z0
NotesonPowerSystemAnalysis

ZT

Calculatetheequivalentcircuitparameters:
Solving:
ZHX =ZH +ZX
ZHT =ZH +ZT
ZXT =ZX +ZT
Gives:
ZH =(ZHX +ZHT ZXT)/2=3.95%
ZX =(ZHX +ZXT ZHT)/2=0.359%
ZT =(ZHT +ZXT ZHX)/2=7.43%

Typicalrelativesizesofsequence
impedancevalues

8SymmetricalComponents

Neutral

Ground

n
Negativesequence
network(perunit)
Deltasidelagswye
sideby30degrees

NotesonPowerSystemAnalysis

Positiveandnegative

Setupallthreesequencenetworks
Interconnectnetworksatpointofthe
faulttosimulateashortcircuit
CalculatethesequenceIandV
TransformtoABCcurrentsandvoltages

35

8SymmetricalComponents

NotesonPowerSystemAnalysis

36

You might also like