Professional Documents
Culture Documents
Case - 2.3 Ef (Star TCC)
Case - 2.3 Ef (Star TCC)
kV=33)
.5
10
30
50
100
300
500
1K
3K
5K
1K
10K
1K
500
500
300
300
100
100
H08-RP - G
OC1
50
50
120MVA I/C
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.47
3x = 2.96 s, 5x = 2.01 s, 8x = 1.55 s
30
10
30
10
Seconds
H05-RP - G
OC1
5
33kV B/C
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.44
3x = 2.77 s, 5x = 1.88 s, 8x = 1.45 s
.5
.5
.3
.3
H14-RP - G
OC1
.1
.1
20MVA T/F
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.06
3x = 0.378 s, 5x = 0.257 s, 8x = 0.198 s
.05
.03
.05
.03
.01
.5
10
30
50
100
300
500
1K
3K
CASE:2.3 EF
Date:
SN:
Rev:
Fault:
Circuit:
21-01-2016
LARSENTRN2
Base
Ground
120MVAI/C,33kVB/C,20MVA
5K
.01
10K