ELECTRICAL SPECIFICATION

ENVIRONMENTAL DESIGN DATA

Occidental Mukhaizna LLC


A subsidiary of Occidental Petroleum Corporation

ELECTRICAL SPECIFICATION ENVIRONMENTAL DESIGN DATA


The meteorological conditions are severe; the climate is mainly extremely hot and humid.
The summer is from April to October with June and July being the hottest period.
Ambient temperature
Shade temperature

Black bulb temperature

maximum

550C

minimum

50C

82 C

250C

maximum

Maximum daily variation in temperature

The maximum shade temperature occurs for short periods only.


Outdoor electrical equipment (switchgear, transformer, motors etc.) shall be designed for
550C ambient temperature.
All indoor electrical equipment shall be designed for 400C maximum ambient temperature to
cater for loss of air conditioning supply.
Soil Temperature
Maximum Ground Temperature (summer):
330C @ 1000 mm depth
350C @ 800 mm depth
0

38 C @ 650 mm depth
400C @ 500 mm depth
Minimum Ground Temperature (winter):
200C @ 1000 mm depth
Soil Thermal Resistivity
Average soil thermal resistivity :

300 cm 0C/W

Relative Humidity
Maximum relative humidity

98%

Minimum relative humidity

30%

REFERENCE MUK-FAC-122 Rev B Mar 2011

Approved by: Engineering Manager

1 of 2

ELECTRICAL SPECIFICATION
ENVIRONMENTAL DESIGN DATA

Occidental Mukhaizna LLC


A subsidiary of Occidental Petroleum Corporation

Barometric Pressure
Average barometric pressure

98.6 kPa

Barometric pressure range

95.9 to 98.9 kPa

157 m

Site elevation
Site elevation above sea level
Rainfall
This is infrequent, but when rainfall occurs, it is often combined with hail and sandstorms.
Design rainfall in one hour

25 mm

Design rainfall average

nil

Sandstorms
These are both frequent and severe; they can continue for days. The atmosphere is heavily
laden with dust particles as small as 2 microns.
Wind
Prevailing wind directions:
December/February

NNW

March/May

June/August

SSE to SW

Sept/ November

SSE to SSW

3-second gusts

34 m/s

Maximum hourly average

12 m/s

1.2 kW/m2

Design Wind Speeds:

Solar Radiation
Design (max) Solar radiation

REFERENCE MUK-FAC-122 Rev B Mar 2011

Approved by: Engineering Manager

2 of 2