Current Ratings: Table 3.16 Single Conductor Al PVC Cables - Three Phase Ratings (A)
Current Ratings: Table 3.16 Single Conductor Al PVC Cables - Three Phase Ratings (A)
Current Ratings: Table 3.16 Single Conductor Al PVC Cables - Three Phase Ratings (A)
CURRENT RATINGS
Aluminium conductor
PVC insulation
Unarmoured
Sheathed or unsheathed
Table 3.16 Single Conductor Al PVC Cables Three Phase Ratings (A)
Conductor
Size
(mm2)
16
79
67
64
55
44
32
89
66
77
25
106
91
86
72
57
43
114
86
100
35
131
112
105
89
71
52
136
103
119
50
161
138
129
105
84
162
123
144
70
204
174
163
135
107
199
154
175
95
253
218
203
162
130
238
185
213
120
296
254
237
193
154
272
216
242
150
340
292
272
217
173
304
242
271
185
396
341
317
253
202
344
278
312
240
475
408
381
307
236
400
325
362
300
551
473
441
348
278
453
375
418
400
650
556
519
400
320
518
430
477
500
763
651
606
480
384
591
505
558
630
899
762
709
548
439
673
575
636
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C
Soil Temperature
15C
Soil Thermal Resistivity
1.2 K.m/W
Depth of Burial
0.5 m
Section 3, Page 86