Qubino ZW+ Safety Report
Qubino ZW+ Safety Report
IEC 60669-2-5
Test specification:
Standard .......................................... : IEC 60669-2-5:2013 (First Edition) used in conjunction with IEC
60669-1:1998 + A1:99 + A2:06 and IEC 60669-2-1:2002 + A1:08
Test procedure ................................. : CB Scheme
Non-standard test method ................ : N/A
Page 2 of 21
IEC60669_2_5A
Page 3 of 21
Test item particulars:
Type of electronic switch and its function
(examples given in Annex AA) ......................: Electronic switches, Electronic dimmer
Pattern number .............................................: 1; 1+1; 4
Contact opening (gap) and switch
normal gap / without contact gap (semiconductor switching
performance .................................................: device)
Degree of protection against access to
hazardous parts and against harmful effects
due to the ingress of solid foreign objects ......: IP2X
Degree of protection against harmful effects
due to the ingress of water ............................: IPX0
Method of actuating ......................................: External via RF-remote or button
Method of mounting ......................................: Method of installation ....................................: Special built-in purposes
Type of terminals ..........................................: screw-type
Flexible cable outlet ......................................: without
Rated current (A) / Rated load (VA or W) ......: See general product data
Minimum current (A) / Minimum load (VA or
W) ................................................................: See general product data
Kind of load controlled by the switch .............: incandescent lamp / motors
Type of switching mechanism .......................: Relays or semi-conductor device
Rated control voltage (V) ..............................: a.c. / d.c.
Rated control current (A) ...............................: a.c. / d.c.
Rated voltage (V) ..........................................: 110-230 VAC, 24-30 VDC
Rated frequency (Hz) ....................................: 50-60 Hz
Characteristic of fuses ..................................: N.A
Electronics RCS or TDS having ...................: N/A
Possible test case verdicts:
- test case does not apply to the test object ...: N/A
- test object does meet the requirement ........: P (Pass)
- test object does not meet the requirement ..: F (Fail)
Testing:
Date of receipt of test item ............................: 2015-12
Date (s) of performance of tests ....................: 2015-12
IEC60669_2_5A
Page 4 of 21
General product formation:
Flush 1 Relay :
Pattern no 1
Max load 2300 W
P/N: ZMNHAD1
Flush 2 Relay :
Pattern no. 1+1
Max. load 2 x 920 W
P/N: ZMNHBD1
Flush Shutter :
Pattern no. 4
Max. load 2 x 920 W
P/N: ZMNHCD1
Flush dimmer :
Pattern no. semi
Max. load 200 W
P/N: ZMNHDD1
IEC60669_2_5A
Page 5 of 21
IEC 60669-2-5
Clause
Requirement + Test
10
10.1
Result - Remark
Verdict
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Test carried out between accessible metal parts and earth, through a non-inductive
resistor of 2 k:
IEC60669_2_5A
Page 6 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
N/A
N/A
N/A
10.3
N/A
10.3.1
N/A
N/A
N/A
N/A
10.3.2
N/A
10.4
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
10.5
10.6
IEC60669_2_5A
Page 7 of 21
IEC 60669-2-5
Clause
Requirement + Test
10.7
10.101
10.102
Result - Remark
N/A
10.103
N/A
P
N/A
N/A
12
TERMINALS
12.1
General
Switches provided with screw-type terminals or
with screwless terminals .......................................: Screw-terminal
Verdict
IEC60669_2_5A
N/A
Page 8 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
12.2.1
Verdict
F
12.2.2
12.2.3
12.2.5
P
P
See appended table 12.2.5
12.2.7
Not
known
P
P
See appended table 12.2.6
IEC60669_2_5A
Page 9 of 21
IEC 60669-2-5
Clause
Requirement + Test
12.2.8
Result - Remark
Verdict
Torque test:
- rated current (A) .................................................: Max 10 A
- solid rigid copper conductor of the largest crosssectional area (mm) (table 2) ..............................: 0.75 2.5 mm
12.2.9
N/A
12.2.10
N/A
N/A
N/A
12.2.11
g measured >1.5 mm
Pillar terminals: distance g no less than the value
g required 1.5 mm
specified in figure 1: required (mm); measured
(mm) ....................................................................:
16
16.1
16.2
17
TEMPERATURE RISE
17.1
Not
tested
P
P
P
Page 10 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
101
ABNORMAL CONDITIONS
Electronic switches do not create hazard under
abnormal conditions
101.1.1.2
12.2.5
P
Only 101.1.1.2
number of conductors............................................: 1
Cross-sectional
area (mm2)
Diameter of
bushing hole per
table 4 (mm)
Mass (kg)
Remarks
0.75
6.5
260
0.4
2.5
9.5
280
0.7
supplementary information:
IEC60669_2_5A
Page 11 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
12.2.6
Verdict
Cross-sectional
area (mm2)
Number of
conductors
Type of conductors
(rigid solid / rigid
stranded)
Remarks
0.75
solid
40
2.5
solid
50
supplementary information:
16.2
item per
table 14
flashover /
breakdown
(Yes/No)
2000
No
2000
No
supplementary information:
IEC60669_2_5A
Page 12 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush 1 Relay
17
TABLE: temperature rise measurements; Flush 1 Relay
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
39
55
Enclosure
43
55
Ambient capacitor
44
60
supplementary information:
IEC60669_2_5A
Page 13 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush 2 Relay
17
TABLE: temperature rise measurements; Flush 2 Relay
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
33
55
Enclosure
45
55
Ambient capacitor
33
60
supplementary information:
IEC60669_2_5A
Page 14 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush shutter
17
TABLE: temperature rise measurements; Flush shutter
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
23
55
Enclosure
25
55
Ambient capacitor
33
60
supplementary information:
IEC60669_2_5A
Page 15 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush Dimmer
17
TABLE: temperature rise measurements; Flush Dimmer
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Max
intensity
Min
intensity
0.95 A
0.64 A
Terminals
21
35
55
Enclosure
35
68
55
Ambient capacitor
36
58
60
supplementary information: during min intensity the dimmer broke down and stopped working
IEC60669_2_5A
Page 16 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush 1 Relay
101.1.1.2 TABLE: temperature rise measurements during overload tests
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
118
110
Enclosure
189
110
N/A
IEC60669_2_5A
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Page 17 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush 2 Relay
101.1.1.2 TABLE: temperature rise measurements during overload tests
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
38
110
Enclosure
45
110
101.1.1.2
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
66
110
Enclosure
79
110
supplementary information: at 14 A the switch short-circuited between L-N, home fuse blows
IEC60669_2_5A
Page 18 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush shutter
101.1.1.2 TABLE: temperature rise measurements during overload tests
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
72
110
Enclosure
85
110
max. measured
temperature rise (K)
permissible
temperature rise
(K)
Terminals
95
110
Enclosure
169
110
IEC60669_2_5A
Page 19 of 21
IEC 60669-2-5
Clause
Requirement + Test
Result - Remark
Verdict
Flush dimmer
101.1.1.2 TABLE: temperature rise measurements during overload tests
max. measured
temperature rise (K)
permissible
temperature rise
(K)
1 hour 25.6 A
Terminals
110
Enclosure
110
IEC60669_2_5A
Page 20 of 21
IEC 60669-2-5
Clause 10.101
Photo 1
IEC60669_2_5A
Page 21 of 21
IEC 60669-2-5
Clause 101 Abnormal conditions
Photo 2 Flush 1 Relay