3AH Vacuum Circuit-Breakers

Description

3AH Vacuum
Circuit-Breakers

Technical specifications
Vacuum circuit-breaker operating time

Closing time

Opening time

H4
3A

< 75 1)

< 80 1)

1)

1)

H4
3A

H3

< 75 1) 2) < 80 1)
< 65

1)

< 65

1)

< 80 1)
< 65 1)

1st shunt release

ms

< 65

2nd and 3rd releases

ms

< 50

< 45

< 50

< 45

< 45

Opening time

Instantaneous release

ms

< 17

Arcing time

ms

< 15

< 15

< 15

< 15

< 15 3)

Break time

< 65

3A

H5
3A

ms

83

d
an
H3
3A

3A

H1

an

3A

H2

Va
c
eq uum
ui c
pm ir
en cuit
t -b

O
pe
at rat
r in
se ated g ti
co v me
nd olt s
ar ag
y e
cir of
cu
it

re
a

ke

Operating times

1st shunt release

ms

< 80

< 80

< 80

< 80

< 80

2nd and 3rd releases

ms

< 65

< 60

< 65

< 60

< 60

Dead time

ms

300

300

300

300

300

CLOSE/OPEN time

1st shunt release

ms

< 80

< 90

< 75

< 90

< 90

2nd and 3rd releases

ms

< 65

< 70

< 60

< 70

< 70

Closing solenoid

ms

45

45

45

45

45

1st shunt release

ms

40

40

40

40

40

2nd and 3rd releases

ms

20

20

20

20

20

1st shunt release

ms

> 15

> 15

> 15

> 15

> 15

2nd and 3rd releases

ms

> 10

> 10

> 10

> 10

> 10

< 15

< 15

< 10

< 15

Minimum command duration

Pulse time for breaker tripping signal


Spring-charging time for electrical operation

Synchronous operation error between the poles

ms

< 15

Rating plate
Example (full size)
Note
For further information
concerning determination
of spare parts, subsequent delivery, etc. the
following 4 details are
required:
Type designation
Serial No.
Design code
Year of manufacture

T ype 3AH1055-2
No. S 3AH/00005663
Ur
7.2 kV, 50/60 Hz
Isc
31.5 kA
Up
60 kV

Design code
1E
Year of manufacture 1999
I r 1250 A
tk
3 s
m
110 kg

Rated operating sequence: O- 0.3s -CO-3min-CO

MADE IN GERMANY

1) Shorter operating times on request


2) With stored-energy mechanism
3) Arcing time < 33 ms at rated frequency of 16 2/3 Hz
Siemens HG 11.12 June 19991/3