Canalis KTA 800-4000A - 2011 - EN
Canalis KTA 800-4000A - 2011 - EN
Canalis KTA 800-4000A - 2011 - EN
Canalis KTA
800 - 4000 A
Busbar trunking systems
Aluminium
Catalogue
2011
YFJYVIIVGIT
6FKQHLGHU(OHF ULF
)55(9$
Contents
DEBU021EN_Contents.indd
Index
Introduction
3
19
37
Catalogue numbers
and dimensions
65
Design guide
135
173
Recommandations
233
version: 1.1
version: 1.1
DEBU021EN_Contents.indd
Index
Cat. no.
03000
03561
04000
Designations
CANALIS SUPPORT
Pages
79
Cat. no.
Designations
Pages
87816
80
87817
80
04694
87818
80
04703
78
04704
78
87821
80
04711
79
87822
80
04712
79
87823
80
04713
79
87824
80
04714
79
87825
80
04715
78
87826
78
80
04716
04725
78
87827
80
04726
78
04735
78
87828
80
04736
78
04737
78
04738
78
04851
79
04852
79
04853
KH0
KH010SD85
KH016CB
130
130
KH018CB
130
04854
130
KH018CB86NS
131
04861
79
04863
79
KH025SB131
130
04871
CANALIS COVER
79
KH025SB132
130
KH025SB141
130
KH025SB142
130
KH025SD14
126
KH025SD15
126
KH025SD541
125
KH025SD542
125
KH025SD551
125
KH025SD552
125
KH025SD85
KH025SE341
129
KH025SE351
129
KH025ZA05
129
KH026CB
130
130
KH028CB86NS
131
KH036CB
08000
08903
112
08905
112
08907
112
13000
13940
30000
33596
78
33597
78
40000
47335
78
47336
78
80000
130
130
KH038CB86NS
131
KH040SD85
KH040SD9502
KH040SE341
129
KH040ZA05
129
KH046CB
87800
81
87801
81
87811
80
87812
80
87813
80
87814
80
KH040ZA06
130
87815
80
130
DEBU021EN_Index.indd
KH040SE351
version: 1.1
129
129
Index
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KH048CB86NS
131
KSB160SM513
104
130
KSB250DC4
105
KH056CB
130
KH058CB86NS
131
KH063SB131
130
KH063SB132
130
KH063SB141
130
KH063SB142
130
KH063SD14
126
KH063SD15
126
KH063SD541
125
KH063SD542
125
KH063SD551
125
KH063SD552
125
KH063SD85
KH063SD9502
KH063SE341
129
129
KH063ZA03
129
KH063ZA05
129
KH063ZA06
129
KH063ZA10
129
KH086SB131
130
KH086SB132
130
KH086SB141
130
KH086SB142
130
KH086SB5311
131
KH086SB5312
131
KH086SB5411
131
KH086SB5412
131
KH063SE351
KSB
KSB25SD4
109
KSB25SD5
109
KSB32SG4
111
KSB50SF4
107
KSB50SF5
107
KSB50SN4
109
KSB50SN5
109
KSB63SD4
109
KSB63SD5
109
KSB63SM48
103
KSB63SM58
103
KSB80SG4
111
KSB100SE4
108, 110
KSB100SE5
108, 110
KSB100SF4
107
KSB100SF5
107
KSB100SM412
103
KSB100SM512
103
KSB160DC4
105
KSB160DC5
105
KSB160SE4
108, 110
KSB160SE5
108, 110
KSB160SF4
108
KSB160SF5
108
KSB160SG4
111
KSB160SM413
104
106
KSB250DC5
105
106
KSB250SE4
108, 110
KSB250SE5
108, 110
KSB400DC4
105
106
KSB400DC5
105
106
KSB400SE4
108, 110
KSB400SE5
108, 110
KSB400ZC1
112
KTA0800CP31
77
KTA0800CP32
77
KTA0800CP33
77
KTA0800CP34
77
KTA0800CP41
77
KTA0800CP42
77
KTA0800CP43
77
KTA0800CP44
77
KTA0800CP51
77
KTA0800CP52
77
KTA0800CP53
77
KTA0800CP54
77
KTA0800CP71
77
KTA0800CP72
77
KTA0800CP73
77
KTA0800CP74
77
KTA0800DB310
71
KTA0800DB410
67
KTA0800DB510
67
KTA0800DB710
67
KTA0800EB320
69
KTA0800EB340
69
KTA0800EB420
69
KTA0800EB440
69
KTA0800EB520
69
KTA0800EB540
69
KTA0800EB720
69
KTA0800EB740
69
KTA0800ED320
68
KTA0800ED340
68
KTA0800ED420
68
KTA0800ED440
68
KTA0800ED520
68
KTA0800ED540
68
KTA0800ED720
68
KTA0800ED740
68
KTA0800EH320
70
KTA0800EH340
70
KTA0800EH420
70
KTA0800EH440
70
KTA0800EH520
70
KTA0800EH540
70
KTA0800EH720
70
KTA0800EH740
70
KTA0800EL31
90
KTA0800EL32
90
KTA0800EL33
91
KTA0800
version: 1.1
DEBU021EN_Index.indd
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA0800EL34
91
KTA0800ET71A
68
KTA0800EL35
92
KTA0800ET720
68
KTA0800EL41
90
KTA0800ET72B
68
KTA0800EL42
90
KTA0800ET72C
68
KTA0800EL43
91
KTA0800ET73D
68
KTA0800EL44
91
KTA0800ET740
68
KTA0800EL45
92
KTA0800LC3A
74
KTA0800EL51
90
KTA0800LC3B
74
KTA0800EL52
90
KTA0800LC4A
74
KTA0800EL53
91
KTA0800LC4B
74
KTA0800EL54
91
KTA0800LC5A
74
KTA0800EL55
92
KTA0800LC5B
74
KTA0800EL71
90
KTA0800LC7A
74
KTA0800EL72
90
KTA0800LC7B
74
KTA0800EL73
91
KTA0800LP3A1
73
KTA0800EL74
91
KTA0800LP3A2
73
KTA0800EL75
92
KTA0800LP3B1
73
KTA0800ER31
82
KTA0800LP3B2
73
KTA0800ER32
82
KTA0800LP3C1
73
KTA0800ER33
83
KTA0800LP3C1
73
KTA0800ER34
83
KTA0800LP3C2
73
KTA0800ER35
84
KTA0800LP4A1
73
KTA0800ER36
84
KTA0800LP4A2
73
KTA0800ER37
85
KTA0800LP4B1
73
KTA0800ER41
82
KTA0800LP4B2
73
KTA0800ER42
82
KTA0800LP4C1
73
KTA0800ER43
83
KTA0800LP4C2
73
KTA0800ER44
83
KTA0800LP5A1
73
KTA0800ER45
84
KTA0800LP5A2
73
KTA0800ER46
84
KTA0800LP5B1
73
KTA0800ER47
85
KTA0800LP5B2
73
KTA0800ER51
82
KTA0800LP5C1
73
KTA0800ER52
82
KTA0800LP5C2
73
KTA0800ER53
83
KTA0800LP7A1
73
KTA0800ER54
83
KTA0800LP7A2
73
KTA0800ER55
84
KTA0800LP7B1
73
KTA0800ER56
84
KTA0800LP7B2
73
KTA0800ER57
85
KTA0800LP7C1
73
KTA0800ER71
82
KTA0800LP7C2
73
KTA0800ER72
82
KTA0800TC3
75
KTA0800ER73
83
KTA0800TC4
75
KTA0800ER74
83
KTA0800TC5
75
KTA0800ER75
84
KTA0800TC7
75
KTA0800ER76
84
KTA0800TN410
71
KTA0800ER77
85
KTA0800TP410
71
KTA0800ET31A
68
KTA0800YA3
72
KTA0800ET320
68
KTA0800YA4
72
KTA0800ET32B
68
KTA0800ZC31
76
KTA0800ET32C
68
KTA0800ZC32
76
KTA0800ET33D
68
KTA0800ZC41
76
KTA0800ET340
68
KTA0800ZC42
76
KTA0800ET41A
68
KTA0800ZC51
76
KTA0800ET420
68
KTA0800ZC52
76
KTA0800ET42B
68
KTA0800ZC71
76
KTA0800ET42C
68
KTA0800ZC72
76
KTA0800ET43D
68
KTA0800ZP3
76
KTA0800ET440
68
KTA0800ZP4
76
KTA0800ET51A
68
KTA0800ZP5
76
KTA0800ET520
68
KTA0800ZP7
76
KTA0800ET52B
68
KTA0800ET52C
68
KTA0800ET53D
68
KTA0800ET540
68
KTA1000CP31
77
KTA1000CP32
77
DEBU021EN_Index.indd
KTA1000
version: 1.1
Index
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA1000CP33
77
KTA1000ER32
82
KTA1000CP34
77
KTA1000ER33
83
KTA1000CP41
77
KTA1000ER34
83
KTA1000CP42
77
KTA1000ER35
84
KTA1000CP43
77
KTA1000ER36
84
KTA1000CP44
77
KTA1000ER37
85
KTA1000CP51
77
KTA1000ER41
82
KTA1000CP52
77
KTA1000ER42
82
KTA1000CP53
77
KTA1000ER43
83
KTA1000CP54
77
KTA1000ER44
83
KTA1000CP71
77
KTA1000ER45
84
KTA1000CP72
77
KTA1000ER46
84
KTA1000CP73
77
KTA1000ER47
85
KTA1000CP74
77
KTA1000ER51
82
KTA1000DB310
71
KTA1000ER52
82
KTA1000DB410
71
KTA1000ER53
83
KTA1000DB510
71
KTA1000ER54
83
KTA1000DB710
71
KTA1000ER55
84
KTA1000EB320
69
KTA1000ER56
84
KTA1000EB340
69
KTA1000ER57
85
KTA1000EB420
69
KTA1000ER71
82
KTA1000EB440
69
KTA1000ER72
82
KTA1000EB520
69
KTA1000ER73
83
KTA1000EB540
69
KTA1000ER74
83
KTA1000EB720
69
KTA1000ER75
84
KTA1000EB740
69
KTA1000ER76
84
KTA1000ED320
68
KTA1000ER77
85
KTA1000ED340
68
KTA1000ET31A
68
KTA1000ED420
68
KTA1000ET320
68
KTA1000ED440
68
KTA1000ET32B
68
KTA1000ED520
68
KTA1000ET32C
68
KTA1000ED540
68
KTA1000ET33D
68
KTA1000ED720
68
KTA1000ET340
68
KTA1000ED740
68
KTA1000ET41A
68
KTA1000EH320
70
KTA1000ET420
68
KTA1000EH340
70
KTA1000ET42B
68
KTA1000EH420
70
KTA1000ET42C
68
KTA1000EH440
70
KTA1000ET43D
68
KTA1000EH520
70
KTA1000ET440
68
KTA1000EH540
70
KTA1000ET51A
68
KTA1000EH720
70
KTA1000ET520
68
KTA1000EH740
70
KTA1000ET52B
68
KTA1000EL31
90
KTA1000ET52C
68
KTA1000EL32
90
KTA1000ET53D
68
KTA1000EL33
91
KTA1000ET540
68
KTA1000EL34
91
KTA1000ET71A
68
KTA1000EL35
92
KTA1000ET720
68
KTA1000EL41
90
KTA1000ET72B
68
KTA1000EL42
90
KTA1000ET72C
68
KTA1000EL43
91
KTA1000ET73D
68
KTA1000EL44
91
KTA1000ET740
68
KTA1000EL45
92
KTA1000LC3A
74
KTA1000EL51
90
KTA1000LC3B
74
KTA1000EL52
90
KTA1000LC4A
74
KTA1000EL53
91
KTA1000LC4B
74
KTA1000EL54
91
KTA1000LC5A
74
KTA1000EL55
92
KTA1000LC5B
74
KTA1000EL71
90
KTA1000LC7A
74
KTA1000EL72
90
KTA1000LC7B
74
KTA1000EL73
91
KTA1000LP3A1
73
KTA1000EL74
91
KTA1000LP3A2
73
KTA1000EL75
92
KTA1000LP3B1
73
KTA1000ER31
82
KTA1000LP3B2
73
version: 1.1
DEBU021EN_Index.indd
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA1000LP3C1
73
KTA1250CP71
77
KTA1000LP3C1
73
KTA1250CP72
77
KTA1000LP3C2
73
KTA1250CP73
77
KTA1000LP4A1
73
KTA1250CP74
77
KTA1000LP4A2
73
KTA1250DB310
71
KTA1000LP4B1
73
KTA1250DB410
71
KTA1000LP4B2
73
KTA1250DB510
71
KTA1000LP4C1
73
KTA1250DB710
71
KTA1000LP4C2
73
KTA1250EB320
69
KTA1000LP5A1
73
KTA1250EB340
69
KTA1000LP5A2
73
KTA1250EB420
69
KTA1000LP5B1
73
KTA1250EB440
69
KTA1000LP5B2
73
KTA1250EB520
69
KTA1000LP5C1
73
KTA1250EB540
69
KTA1000LP5C2
73
KTA1250EB720
69
KTA1000LP7A1
73
KTA1250EB740
69
KTA1000LP7A2
73
KTA1250ED320
68
KTA1000LP7B1
73
KTA1250ED340
68
KTA1000LP7B2
73
KTA1250ED420
68
KTA1000LP7C1
73
KTA1250ED440
68
KTA1000LP7C2
73
KTA1250ED520
68
KTA1000PL31
118
KTA1250ED540
68
KTA1000PL41
118
KTA1250ED720
68
KTA1000PL51
118
KTA1250ED740
68
KTA1000PL71
118
KTA1250EH320
70
KTA1000SL31
115
KTA1250EH340
70
KTA1000SL41
115
KTA1250EH420
70
KTA1000SL51
115
KTA1250EH440
70
KTA1000SL71
115
KTA1250EH520
70
KTA1000TC3
75
KTA1250EH540
70
KTA1000TC4
75
KTA1250EH720
70
KTA1000TC5
75
KTA1250EH740
70
KTA1000TC7
75
KTA1250EL31
90
KTA1000TN410
71
KTA1250EL32
90
KTA1000TP410
71
KTA1250EL33
91
KTA1000YA3
72
KTA1250EL34
91
KTA1000YA4
72
KTA1250EL35
92
KTA1000ZC31
76
KTA1250EL41
90
KTA1000ZC32
76
KTA1250EL42
90
KTA1000ZC41
76
KTA1250EL43
91
KTA1000ZC42
76
KTA1250EL44
91
KTA1000ZC51
76
KTA1250EL45
92
KTA1000ZC52
76
KTA1250EL51
90
KTA1000ZC71
76
KTA1250EL52
90
KTA1000ZC72
76
KTA1250EL53
91
KTA1000ZP3
76
KTA1250EL54
91
KTA1000ZP4
76
KTA1250EL55
92
KTA1000ZP5
76
KTA1250EL71
90
KTA1000ZP7
76
KTA1250EL72
90
KTA1250EL73
91
KTA1250EL74
91
KTA1250EL75
92
KTA1250ER31
82
KTA1250ER32
82
KTA1250ER33
83
KTA1250ER34
83
KTA1250ER35
84
KTA1250ER36
84
KTA1250ER37
85
KTA1250ER41
82
KTA1250ER42
82
KTA1250ER43
83
KTA1250ER44
83
KTA1250
KTA1250CP31
77
KTA1250CP32
77
KTA1250CP33
77
KTA1250CP34
77
KTA1250CP41
77
KTA1250CP42
77
KTA1250CP43
77
KTA1250CP44
77
KTA1250CP51
77
KTA1250CP52
77
KTA1250CP53
77
KTA1250CP54
77
DEBU021EN_Index.indd
version: 1.1
Index
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA1250ER45
84
KTA1250LP5A2
73
KTA1250ER46
84
KTA1250LP5B1
73
KTA1250ER47
85
KTA1250LP5B2
73
KTA1250ER51
82
KTA1250LP5C1
73
KTA1250ER52
82
KTA1250LP5C2
73
KTA1250ER53
83
KTA1250LP7A1
73
KTA1250ER54
83
KTA1250LP7A2
73
KTA1250ER55
84
KTA1250LP7B1
73
KTA1250ER56
84
KTA1250LP7B2
73
KTA1250ER57
85
KTA1250LP7C1
73
KTA1250ER71
82
KTA1250LP7C2
73
KTA1250ER72
82
KTA1250PL31
118
KTA1250ER73
83
KTA1250PL41
118
KTA1250ER74
83
KTA1250PL51
118
KTA1250ER75
84
KTA1250PL71
118
KTA1250ER76
84
KTA1250SL31
115
KTA1250ER77
85
KTA1250SL41
115
KTA1250ET31A
68
KTA1250SL51
115
KTA1250ET320
68
KTA1250SL71
115
KTA1250ET32B
68
KTA1250TC3
75
KTA1250ET32C
68
KTA1250TC4
75
KTA1250ET33D
68
KTA1250TC5
75
KTA1250ET340
68
KTA1250TC7
75
KTA1250ET41A
68
KTA1250TN410
71
KTA1250ET420
68
KTA1250TP410
71
KTA1250ET42B
68
KTA1250YA3
72
KTA1250ET42C
68
KTA1250YA4
72
KTA1250ET43D
68
KTA1250ZC31
76
KTA1250ET440
68
KTA1250ZC32
76
KTA1250ET51A
68
KTA1250ZC41
76
KTA1250ET520
68
KTA1250ZC42
76
KTA1250ET52B
68
KTA1250ZC51
76
KTA1250ET52C
68
KTA1250ZC52
76
KTA1250ET53D
68
KTA1250ZC71
76
KTA1250ET540
68
KTA1250ZC72
76
KTA1250ET71A
68
KTA1250ZP3
76
KTA1250ET720
68
KTA1250ZP4
76
KTA1250ET72B
68
KTA1250ZP5
76
KTA1250ET72C
68
KTA1250ZP7
76
KTA1250ET73D
68
KTA1250ET740
68
KTA1250LC3A
74
KTA1250LC3B
74
KTA1600CP31
77
KTA1250LC4A
74
KTA1600CP32
77
KTA1250LC4B
74
KTA1600CP33
77
KTA1250LC5A
74
KTA1600CP34
77
KTA1250LC5B
74
KTA1600CP41
77
KTA1250LC7A
74
KTA1600CP42
77
KTA1250LC7B
74
KTA1600CP43
77
KTA1250LP3A1
73
KTA1600CP44
77
KTA1250LP3A2
73
KTA1600CP51
77
KTA1250LP3B1
73
KTA1600CP52
77
KTA1250LP3B2
73
KTA1600CP53
77
KTA1250LP3C1
73
KTA1600CP54
77
KTA1250LP3C1
73
KTA1600CP71
77
KTA1250LP3C2
73
KTA1600CP72
77
KTA1250LP4A1
73
KTA1600CP73
77
KTA1250LP4A2
73
KTA1600CP74
77
KTA1250LP4B1
73
KTA1600DB310
71
KTA1250LP4B2
73
KTA1600DB410
71
KTA1250LP4C1
73
KTA1600DB510
71
KTA1250LP4C2
73
KTA1600DB710
71
KTA1250LP5A1
73
KTA1600EB320
69
KTA1600EB340
69
KTA1600
version: 1.1
DEBU021EN_Index.indd
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA1600EB420
69
KTA1600ER71
82
KTA1600EB440
69
KTA1600ER72
82
KTA1600EB520
69
KTA1600ER73
83
KTA1600EB540
69
KTA1600ER74
83
KTA1600EB720
69
KTA1600ER75
84
KTA1600EB740
69
KTA1600ER76
84
KTA1600ED320
68
KTA1600ER77
85
KTA1600ED340
68
KTA1600ET31A
68
KTA1600ED420
68
KTA1600ET320
68
KTA1600ED440
68
KTA1600ET32B
68
KTA1600ED520
68
KTA1600ET32C
68
KTA1600ED540
68
KTA1600ET33D
68
KTA1600ED720
68
KTA1600ET340
68
KTA1600ED740
68
KTA1600ET41A
68
KTA1600EH320
70
KTA1600ET420
68
KTA1600EH340
70
KTA1600ET42B
68
KTA1600EH420
70
KTA1600ET42C
68
KTA1600EH440
70
KTA1600ET43D
68
KTA1600EH520
70
KTA1600ET440
68
KTA1600EH540
70
KTA1600ET51A
68
KTA1600EH720
70
KTA1600ET520
68
KTA1600EH740
70
KTA1600ET52B
68
KTA1600EL31
90
KTA1600ET52C
68
KTA1600EL32
90
KTA1600ET53D
68
KTA1600EL33
91
KTA1600ET540
68
KTA1600EL34
91
KTA1600ET71A
68
KTA1600EL35
92
KTA1600ET720
68
KTA1600EL41
91
KTA1600ET72B
68
KTA1600EL42
91
KTA1600ET72C
68
KTA1600EL43
92
KTA1600ET73D
68
KTA1600EL44
92
KTA1600ET740
68
KTA1600EL45
93
KTA1600LC3A
74
KTA1600EL51
91
KTA1600LC3B
74
KTA1600EL52
91
KTA1600LC4A
74
KTA1600EL53
92
KTA1600LC4B
74
KTA1600EL54
92
KTA1600LC5A
74
KTA1600EL55
93
KTA1600LC5B
74
KTA1600EL71
91
KTA1600LC7A
74
KTA1600EL72
91
KTA1600LC7B
74
KTA1600EL73
92
KTA1600LP3A1
73
KTA1600EL74
92
KTA1600LP3A2
73
KTA1600EL75
93
KTA1600LP3B1
73
KTA1600ER31
82
KTA1600LP3B2
73
KTA1600ER32
82
KTA1600LP3C1
73
KTA1600ER33
83
KTA1600LP3C1
73
KTA1600ER34
83
KTA1600LP3C2
73
KTA1600ER35
84
KTA1600LP4A1
73
KTA1600ER36
84
KTA1600LP4A2
73
KTA1600ER37
85
KTA1600LP4B1
73
KTA1600ER41
82
KTA1600LP4B2
73
KTA1600ER42
82
KTA1600LP4C1
73
KTA1600ER43
83
KTA1600LP4C2
73
KTA1600ER44
83
KTA1600LP5A1
73
KTA1600ER45
84
KTA1600LP5A2
73
KTA1600ER46
84
KTA1600LP5B1
73
KTA1600ER47
85
KTA1600LP5B2
73
KTA1600ER51
82
KTA1600LP5C1
73
KTA1600ER52
82
KTA1600LP5C2
73
KTA1600ER53
83
KTA1600LP7A1
73
KTA1600ER54
83
KTA1600LP7A2
73
KTA1600ER55
84
KTA1600LP7B1
73
KTA1600ER56
84
KTA1600LP7B2
73
KTA1600ER57
85
KTA1600LP7C1
73
DEBU021EN_Index.indd
version: 1.1
Index
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA1600LP7C2
73
KTA2000ED520
68
KTA1600PL31
118
KTA2000ED540
68
KTA1600PL41
118
KTA2000ED720
68
KTA1600PL51
118
KTA2000ED740
68
KTA1600PL71
118
KTA2000EH320
70
KTA1600SL31
115
KTA2000EH340
70
KTA1600SL41
115
KTA2000EH420
70
KTA1600SL51
115
KTA2000EH440
70
KTA1600SL71
115
KTA2000EH520
70
KTA1600TC3
75
KTA2000EH540
70
KTA1600TC4
75
KTA2000EH720
70
KTA1600TC5
75
KTA2000EH740
70
KTA1600TC7
75
KTA2000EL31
90
KTA1600TN410
71
KTA2000EL32
90
KTA1600TP410
71
KTA2000EL33
91
KTA1600YA3
72
KTA2000EL34
91
KTA1600YA4
72
KTA2000EL35
92
KTA1600ZC31
76
KTA2000EL41
90
KTA1600ZC32
76
KTA2000EL42
90
KTA1600ZC41
76
KTA2000EL43
91
KTA1600ZC42
76
KTA2000EL44
91
KTA1600ZC51
76
KTA2000EL45
92
KTA1600ZC52
76
KTA2000EL51
90
KTA1600ZC71
76
KTA2000EL52
90
KTA1600ZC72
76
KTA2000EL53
91
KTA1600ZP3
76
KTA2000EL54
91
KTA1600ZP4
76
KTA2000EL55
92
KTA1600ZP5
76
KTA2000EL71
90
KTA1600ZP7
76
KTA2000EL72
90
KTA2000EL73
91
KTA2000EL74
91
KTA2000EL75
92
KTA2000ER31
82
KTA2000ER32
82
KTA2000ER33
83
KTA2000ER34
83
KTA2000ER35
84
KTA2000ER36
84
KTA2000ER37
85
KTA2000ER41
82
KTA2000ER42
82
KTA2000ER43
83
KTA2000ER44
83
KTA2000ER45
84
KTA2000ER46
84
KTA2000ER47
85
KTA2000ER51
82
KTA2000ER52
82
KTA2000ER53
83
KTA2000ER54
83
KTA2000ER55
84
KTA2000ER56
84
KTA2000ER57
85
KTA2000ER71
82
KTA2000ER72
82
KTA2000ER73
83
KTA2000ER74
83
KTA2000ER75
84
KTA2000ER76
84
KTA2000ER77
85
KTA2000ET31A
68
KTA2000ET320
68
KTA2000ET32B
68
KTA2000
KTA2000CP31
77
KTA2000CP32
77
KTA2000CP33
77
KTA2000CP34
77
KTA2000CP41
77
KTA2000CP42
77
KTA2000CP43
77
KTA2000CP44
77
KTA2000CP51
77
KTA2000CP52
77
KTA2000CP53
77
KTA2000CP54
77
KTA2000CP71
77
KTA2000CP72
77
KTA2000CP73
77
KTA2000CP74
77
KTA2000DB310
71
KTA2000DB410
71
KTA2000DB510
71
KTA2000DB710
71
KTA2000EB320
69
KTA2000EB340
69
KTA2000EB420
69
KTA2000EB440
69
KTA2000EB520
69
KTA2000EB540
69
KTA2000EB720
69
KTA2000EB740
69
KTA2000ED320
68
KTA2000ED340
68
KTA2000ED420
68
KTA2000ED440
68
10
version: 1.1
DEBU021EN_Index.indd
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA2000ET32C
68
KTA2000TP410
71
KTA2000ET33D
68
KTA2000YA3
72
KTA2000ET340
68
KTA2000YA4
72
KTA2000ET41A
68
KTA2000ZC31
76
KTA2000ET420
68
KTA2000ZC32
76
KTA2000ET42B
68
KTA2000ZC41
76
KTA2000ET42C
68
KTA2000ZC42
76
KTA2000ET43D
68
KTA2000ZC51
76
KTA2000ET440
68
KTA2000ZC52
76
KTA2000ET51A
68
KTA2000ZC71
76
KTA2000ET520
68
KTA2000ZC72
76
KTA2000ET52B
68
KTA2000ZP3
76
KTA2000ET52C
68
KTA2000ZP4
76
KTA2000ET53D
68
KTA2000ZP5
76
KTA2000ET540
68
KTA2000ZP7
76
KTA2000ET71A
68
KTA2000ET720
68
KTA2000ET72B
68
KTA2000ET72C
68
KTA2500CP31
77
KTA2000ET73D
68
KTA2500CP32
77
KTA2000ET740
68
KTA2500CP33
77
KTA2000LC3A
74
KTA2500CP34
77
KTA2000LC3B
74
KTA2500CP41
77
KTA2000LC4A
74
KTA2500CP42
77
KTA2000LC4B
74
KTA2500CP43
77
KTA2000LC5A
74
KTA2500CP44
77
KTA2000LC5B
74
KTA2500CP51
77
KTA2000LC7A
74
KTA2500CP52
77
KTA2000LC7B
74
KTA2500CP53
77
KTA2000LP3A1
73
KTA2500CP54
77
KTA2000LP3A2
73
KTA2500CP61
77
KTA2000LP3B1
73
KTA2500CP62
77
KTA2000LP3B2
73
KTA2500CP63
77
KTA2000LP3C1
73
KTA2500CP64
77
KTA2000LP3C1
73
KTA2500CP71
77
KTA2000LP3C2
73
KTA2500CP72
77
KTA2000LP4A1
73
KTA2500CP73
77
KTA2000LP4A2
73
KTA2500CP74
77
KTA2000LP4B1
73
KTA2500DB310
71
KTA2000LP4B2
73
KTA2500DB410
71
KTA2000LP4C1
73
KTA2500DB510
71
KTA2000LP4C2
73
KTA2500DB610
71
KTA2000LP5A1
73
KTA2500DB710
71
KTA2000LP5A2
73
KTA2500EB320
69
KTA2000LP5B1
73
KTA2500EB340
69
KTA2000LP5B2
73
KTA2500EB420
69
KTA2000LP5C1
73
KTA2500EB440
69
KTA2000LP5C2
73
KTA2500EB520
69
KTA2000LP7A1
73
KTA2500EB540
69
KTA2000LP7A2
73
KTA2500EB620
69
KTA2000LP7B1
73
KTA2500EB640
69
KTA2000LP7B2
73
KTA2500EB720
69
KTA2000LP7C1
73
KTA2500EB740
69
KTA2000LP7C2
73
KTA2500ED320
68
KTA2000SL31
115
KTA2500ED340
68
KTA2000SL41
115
KTA2500ED420
68
KTA2000SL51
115
KTA2500ED440
68
KTA2000SL71
115
KTA2500ED520
68
KTA2000TC3
75
KTA2500ED540
68
KTA2000TC4
75
KTA2500ED620
68
KTA2000TC5
75
KTA2500ED640
68
KTA2000TC7
75
KTA2500ED720
68
KTA2000TN410
71
KTA2500ED740
68
KTA2500EH320
70
DEBU021EN_Index.indd
KTA2500
version: 1.1
11
Index
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA2500EH340
70
KTA2500ER72
82
KTA2500EH420
70
KTA2500ER73
83
KTA2500EH440
70
KTA2500ER74
83
KTA2500EH520
70
KTA2500ER75
84
KTA2500EH540
70
KTA2500ER76
84
KTA2500EH620
70
KTA2500ER77
85
KTA2500EH640
70
KTA2500ET31A
68
KTA2500EH720
70
KTA2500ET320
68
KTA2500EH740
70
KTA2500ET32B
68
KTA2500EL31
90
KTA2500ET32C
68
KTA2500EL32
90
KTA2500ET33D
68
KTA2500EL33
91
KTA2500ET340
68
KTA2500EL34
91
KTA2500ET41A
68
KTA2500EL35
92
KTA2500ET420
68
KTA2500EL41
90
KTA2500ET42B
68
KTA2500EL42
90
KTA2500ET42C
68
KTA2500EL43
91
KTA2500ET43D
68
KTA2500EL44
91
KTA2500ET440
68
KTA2500EL45
92
KTA2500ET51A
68
KTA2500EL51
90
KTA2500ET520
68
KTA2500EL52
90
KTA2500ET52B
68
KTA2500EL53
91
KTA2500ET52C
68
KTA2500EL54
91
KTA2500ET53D
68
KTA2500EL55
92
KTA2500ET540
68
KTA2500EL61
90
KTA2500ET61A
68
KTA2500EL62
90
KTA2500ET620
68
KTA2500EL63
91
KTA2500ET62B
68
KTA2500EL65
91
KTA2500ET62C
68
KTA2500EL66
92
KTA2500ET63D
68
KTA2500EL71
90
KTA2500ET640
68
KTA2500EL72
90
KTA2500ET71A
68
KTA2500EL73
91
KTA2500ET720
68
KTA2500EL74
91
KTA2500ET72B
68
KTA2500EL75
92
KTA2500ET72C
68
KTA2500ER31
82
KTA2500ET73D
68
KTA2500ER32
82
KTA2500ET740
68
KTA2500ER33
83
KTA2500LC3A
74
KTA2500ER34
83
KTA2500LC3B
74
KTA2500ER35
84
KTA2500LC4A
74
KTA2500ER36
84
KTA2500LC4B
74
KTA2500ER37
85
KTA2500LC5A
74
KTA2500ER41
82
KTA2500LC5B
74
KTA2500ER42
82
KTA2500LC6A
74
KTA2500ER43
83
KTA2500LC6B
74
KTA2500ER44
83
KTA2500LC7A
74
KTA2500ER45
84
KTA2500LC7B
74
KTA2500ER46
84
KTA2500LP3A1
73
KTA2500ER47
85
KTA2500LP3A2
73
KTA2500ER51
82
KTA2500LP3B1
73
KTA2500ER52
82
KTA2500LP3B2
73
KTA2500ER53
83
KTA2500LP3C1
73
KTA2500ER54
83
KTA2500LP3C1
73
KTA2500ER55
84
KTA2500LP3C2
73
KTA2500ER56
84
KTA2500LP4A1
73
KTA2500ER57
85
KTA2500LP4A2
73
KTA2500ER61
82
KTA2500LP4B1
73
KTA2500ER62
82
KTA2500LP4B2
73
KTA2500ER63
83
KTA2500LP4C1
73
KTA2500ER64
83
KTA2500LP4C2
73
KTA2500ER65
84
KTA2500LP5A1
73
KTA2500ER66
84
KTA2500LP5A2
73
KTA2500ER67
85
KTA2500LP5B1
73
KTA2500ER71
82
KTA2500LP5B2
73
12
version: 1.1
DEBU021EN_Index.indd
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA2500LP5C1
73
KTA3200CP64
77
KTA2500LP5C2
73
KTA3200CP71
77
KTA2500LP6A1
73
KTA3200CP72
77
KTA2500LP6A2
73
KTA3200CP73
77
KTA2500LP6B1
73
KTA3200CP74
77
KTA2500LP6B2
73
KTA3200DB310
71
KTA2500LP6C1
73
KTA3200DB410
71
KTA2500LP6C2
73
KTA3200DB510
71
KTA2500LP7A1
73
KTA3200DB610
71
KTA2500LP7A2
73
KTA3200DB710
71
KTA2500LP7B1
73
KTA3200EB320
69
KTA2500LP7B2
73
KTA3200EB340
69
KTA2500LP7C1
73
KTA3200EB420
69
KTA2500LP7C2
73
KTA3200EB440
69
KTA2500RL61
116
KTA3200EB520
69
KTA2500RL62
116
KTA3200EB540
69
KTA2500RL71
116
KTA3200EB620
69
KTA2500RL72
116
KTA3200EB640
69
KTA2500SL31
115
KTA3200EB720
69
KTA2500SL41
115
KTA3200EB740
69
KTA2500SL51
115
KTA3200ED320
68
KTA2500SL71
115
KTA3200ED340
68
KTA2500TC3
75
KTA3200ED420
68
KTA2500TC4
75
KTA3200ED440
68
KTA2500TC5
75
KTA3200ED520
68
KTA2500TC6
75
KTA3200ED540
68
KTA2500TC7
75
KTA3200ED620
68
KTA2500TN410
73
KTA3200ED640
68
KTA2500TP410
73
KTA3200ED720
68
KTA2500YA3
72
KTA3200ED740
68
KTA2500YA4
72
KTA3200EH320
70
KTA2500ZC31
76
KTA3200EH340
70
KTA2500ZC32
76
KTA3200EH420
70
KTA2500ZC41
76
KTA3200EH440
70
KTA2500ZC42
76
KTA3200EH520
70
KTA2500ZC51
76
KTA3200EH540
70
KTA2500ZC52
76
KTA3200EH620
70
KTA2500ZC61
76
KTA3200EH640
70
KTA2500ZC62
76
KTA3200EH720
70
KTA2500ZC71
76
KTA3200EH740
70
KTA2500ZC72
76
KTA3200EL31
91
KTA2500ZP3
76
KTA3200EL32
91
KTA2500ZP4
76
KTA3200EL33
92
KTA2500ZP5
76
KTA3200EL34
92
KTA2500ZP6
76
KTA3200EL35
93
KTA2500ZP7
76
KTA3200EL41
91
KTA3200EL42
91
KTA3200EL43
92
KTA3200EL44
92
KTA3200EL45
93
KTA3200EL51
91
KTA3200EL52
91
KTA3200EL53
92
KTA3200EL54
92
KTA3200EL55
93
KTA3200EL61
91
KTA3200EL62
91
KTA3200EL63
92
KTA3200EL65
92
KTA3200EL66
93
KTA3200EL71
91
KTA3200EL72
91
KTA3200EL73
92
KTA3200
KTA3200CP31
77
KTA3200CP32
77
KTA3200CP33
77
KTA3200CP34
77
KTA3200CP41
77
KTA3200CP42
77
KTA3200CP43
77
KTA3200CP44
77
KTA3200CP51
77
KTA3200CP52
77
KTA3200CP53
77
KTA3200CP54
77
KTA3200CP61
77
KTA3200CP62
77
KTA3200CP63
77
DEBU021EN_Index.indd
version: 1.1
13
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA3200EL74
92
KTA3200ET72B
68
KTA3200EL75
93
KTA3200ET72C
68
KTA3200ER31
82
KTA3200ET73D
68
KTA3200ER32
82
KTA3200ET740
68
KTA3200ER33
83
KTA3200LC3A
74
KTA3200ER34
83
KTA3200LC3B
74
KTA3200ER35
84
KTA3200LC4A
74
KTA3200ER36
84
KTA3200LC4B
74
KTA3200ER37
85
KTA3200LC5A
74
KTA3200ER41
82
KTA3200LC5B
74
KTA3200ER42
82
KTA3200LC6A
74
KTA3200ER43
83
KTA3200LC6B
74
KTA3200ER44
83
KTA3200LC7A
74
KTA3200ER45
84
KTA3200LC7B
74
KTA3200ER46
84
KTA3200LP3A1
73
KTA3200ER47
85
KTA3200LP3A2
73
KTA3200ER51
82
KTA3200LP3B1
73
KTA3200ER52
82
KTA3200LP3B2
73
KTA3200ER53
83
KTA3200LP3C1
73
KTA3200ER54
83
KTA3200LP3C1
73
KTA3200ER55
84
KTA3200LP3C2
73
KTA3200ER56
84
KTA3200LP4A1
73
KTA3200ER57
85
KTA3200LP4A2
73
KTA3200ER61
82
KTA3200LP4B1
73
KTA3200ER62
82
KTA3200LP4B2
73
KTA3200ER63
83
KTA3200LP4C1
73
KTA3200ER64
83
KTA3200LP4C2
73
KTA3200ER65
84
KTA3200LP5A1
73
KTA3200ER66
84
KTA3200LP5A2
73
KTA3200ER67
85
KTA3200LP5B1
73
KTA3200ER71
82
KTA3200LP5B2
73
KTA3200ER72
82
KTA3200LP5C1
73
KTA3200ER73
83
KTA3200LP5C2
73
KTA3200ER74
83
KTA3200LP6A1
73
KTA3200ER75
84
KTA3200LP6A2
73
KTA3200ER76
84
KTA3200LP6B1
73
KTA3200ER77
85
KTA3200LP6B2
73
KTA3200ET31A
68
KTA3200LP6C1
73
KTA3200ET320
68
KTA3200LP6C2
73
KTA3200ET32B
68
KTA3200LP7A1
73
KTA3200ET32C
68
KTA3200LP7A2
73
KTA3200ET33D
68
KTA3200LP7B1
73
KTA3200ET340
68
KTA3200LP7B2
73
KTA3200ET41A
68
KTA3200LP7C1
73
KTA3200ET420
68
KTA3200LP7C2
73
KTA3200ET42B
68
KTA3200SL31
117
KTA3200ET42C
68
KTA3200SL41
117
KTA3200ET43D
68
KTA3200SL51
117
KTA3200ET440
68
KTA3200SL71
117
KTA3200ET51A
68
KTA3200TC3
75
KTA3200ET520
68
KTA3200TC4
75
KTA3200ET52B
68
KTA3200TC5
75
KTA3200ET52C
68
KTA3200TC6
75
KTA3200ET53D
68
KTA3200TC5
75
KTA3200ET540
68
KTA3200TN410
71
KTA3200ET61A
68
KTA3200TP410
71
KTA3200ET620
68
KTA3200YA3
71
KTA3200ET62B
68
KTA3200YA4
71
KTA3200ET62C
68
KTA3200ZC31
76
KTA3200ET63D
68
KTA3200ZC32
76
KTA3200ET640
68
KTA3200ZC41
76
KTA3200ET71A
68
KTA3200ZC42
76
KTA3200ET720
68
KTA3200ZC51
76
14
version: 1.1
DEBU021EN_Index.indd
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA3200ZC52
76
KTA4000EL43
92
KTA3200ZC61
76
KTA4000EL44
92
KTA3200ZC62
76
KTA4000EL45
93
KTA3200ZC71
76
KTA4000EL51
91
KTA3200ZC72
76
KTA4000EL52
91
KTA3200ZP3
76
KTA4000EL53
92
KTA3200ZP4
76
KTA4000EL54
92
KTA3200ZP5
76
KTA4000EL55
93
KTA3200ZP6
76
KTA4000EL71
91
KTA3200ZP7
76
KTA4000EL72
91
KTA4000EL73
92
KTA4000EL74
92
KTA4000EL75
93
KTA4000ER31
82
KTA4000ER32
82
KTA4000ER33
83
KTA4000ER34
83
KTA4000ER35
84
KTA4000ER36
84
KTA4000ER37
85
KTA4000ER41
82
KTA4000ER42
82
KTA4000ER43
83
KTA4000ER44
83
KTA4000ER45
84
KTA4000ER46
84
KTA4000ER47
85
KTA4000ER51
82
KTA4000ER52
82
KTA4000ER53
83
KTA4000ER54
83
KTA4000ER55
84
KTA4000ER56
84
KTA4000ER57
85
KTA4000ER71
82
KTA4000ER72
82
KTA4000ER73
83
KTA4000ER74
83
KTA4000ER75
84
KTA4000ER76
84
KTA4000ER77
85
KTA4000ET31A
68
KTA4000ET320
68
KTA4000ET32B
68
KTA4000ET32C
68
KTA4000ET33D
68
KTA4000ET340
68
KTA4000ET41A
68
KTA4000ET420
68
KTA4000ET42B
68
KTA4000ET42C
68
KTA4000ET43D
68
KTA4000ET440
68
KTA4000ET51A
68
KTA4000ET520
68
KTA4000ET52B
68
KTA4000ET52C
68
KTA4000ET53D
68
KTA4000ET540
68
KTA4000ET71A
68
KTA4000ET720
68
KTA4000ET72B
68
KTA4000ET72C
68
KTA4000
KTA4000CP31
77
KTA4000CP32
77
KTA4000CP33
77
KTA4000CP34
77
KTA4000CP41
77
KTA4000CP42
77
KTA4000CP43
77
KTA4000CP44
77
KTA4000CP51
77
KTA4000CP52
77
KTA4000CP53
77
KTA4000CP54
77
KTA4000CP71
77
KTA4000CP72
77
KTA4000CP73
77
KTA4000CP74
77
KTA4000DB310
71
KTA4000DB410
71
KTA4000DB510
71
KTA4000DB710
71
KTA4000EB320
69
KTA4000EB340
69
KTA4000EB420
69
KTA4000EB440
69
KTA4000EB520
69
KTA4000EB540
69
KTA4000EB720
69
KTA4000EB740
69
KTA4000ED320
68
KTA4000ED340
68
KTA4000ED420
68
KTA4000ED440
68
KTA4000ED520
68
KTA4000ED540
68
KTA4000ED720
68
KTA4000ED740
68
KTA4000EH320
70
KTA4000EH340
70
KTA4000EH420
70
KTA4000EH440
70
KTA4000EH520
70
KTA4000EH540
70
KTA4000EH720
70
KTA4000EH740
70
KTA4000EL31
91
KTA4000EL32
91
KTA4000EL33
92
KTA4000EL34
92
KTA4000EL35
93
KTA4000EL41
91
KTA4000EL42
91
DEBU021EN_Index.indd
version: 1.1
15
Cat. no.
Designations
Pages
Cat. no.
Designations
Pages
KTA4000ET73D
68
KTB0000YC1
96
KTA4000ET740
68
KTB0000YC2
96
KTA4000LC3A
74
KTB0000YC3
96
KTA4000LC3B
74
KTB0000YC4
96
KTA4000LC4A
74
KTB0000YC5
96
KTA4000LC4B
74
KTB0000YE1
KT L PLATE 160
93
KTA4000LC5A
74
KTB0000YE2
KT L PLATE 200
93
KTA4000LC5B
74
KTB0000YF1
KT INSULATING SHEATH
97
KTA4000LC7A
74
KTB0000YS1
99
KTA4000LC7B
74
KTB0000YS2
KT CLAMP 100
99
KTA4000LP3A1
73
KTB0000YS3
KT CLAMP 120
99
KTA4000LP3A2
73
KTB0000YT1
97
KTA4000LP3B1
73
KTB0000ZA1
100
KTA4000LP3B2
73
KTB0000ZA3
KT FIXING GRIP
100
KTA4000LP3C1
73
KTB074CF6
102
KTA4000LP3C1
73
KTB0074FA
72
KTA4000LP3C2
73
KTB0074TT01
81
KTA4000LP4A1
73
KTB0074ZA4
101
KTA4000LP4A2
73
KTB0104CF6
102
KTA4000LP4B1
73
KTB0104FA
72
KTA4000LP4B2
73
KTB0104TT01
81
KTA4000LP4C1
73
KTB0124CF6
102
KTA4000LP4C2
73
KTB0124FA
72
KTA4000LP5A1
73
KTB0124TT01
81
KTA4000LP5A2
73
KTB0164CF6
102
KTA4000LP5B1
73
KTB0164FA
72
KTA4000LP5B2
73
KTB0164PE1
78, 80, 81
KTA4000LP5C1
73
KTB0164TT01
81
KTA4000LP5C2
73
KTB0164ZA5
101
KTA4000LP7A1
73
KTB0204CF6
102
KTA4000LP7A2
73
KTB0204FA
72
KTA4000LP7B1
73
KTB0204TT01
81
KTA4000LP7B2
73
KTB0204ZA5
101
KTA4000LP7C1
73
KTB0230BC01
89
KTA4000LP7C2
73
KTB0230CR1
86
KTA4000TC3
75
KTB0230CR2
87
KTA4000TC4
75
KTB0230CR3
87
KTA4000TC5
75
KTB0230CR6
95
KTA4000TC7
75
KTB0230CR7
88
KTA4000TN410
71
KTB0230CR8
88
KTA4000TP410
71
KTB0230CS0
89
KTA4000YA3
72
KTB0244CF6
102
KTA4000YA4
72
KTB0244FA
72
KTA4000ZC31
76
KTB0244PE1
78, 80, 81
KTA4000ZC32
76
KTB0244TT01
81
KTA4000ZC41
76
KTB0244ZA5
101
KTA4000ZC42
76
KTB0324CF6
102
KTA4000ZC51
76
KTB0324FA
72
KTA4000ZC52
76
KTB0324TT01
81
KTA4000ZC71
76
KTB0324ZA5
101
KTA4000ZC72
76
KTB0350BC01
89
KTA4000ZP3
76
KTB0350CR1
86
KTA4000ZP4
76
KTB0350CR2
87
KTA4000ZP5
76
KTB0350CR3
87
KTA4000ZP7
76
KTB0350CR6
95
KTB0350CR7
88
KTB0350CR8
88
KTB0350CS0
89
KTB350HT01
121
KTB350HT02
121
KTB0404CF6
102
KTB0404FA
72
KTB0404PE1
78, 80, 81
KTB
KTB0000CR4
94
KTB0000CR5
94
KTB0000YB1
98
KTB0000YB2
98
KTB0000YB3
98
KTB0000YB4
98
16
version: 1.1
DEBU021EN_Index.indd
Cat. no.
Designations
Pages
KTB0404TT01
81
KTB0404ZA4
100
KTB0404ZA5
101
KTB0510BC01
89
KTB0510CR1
86
KTB0510CR2
87
KTB0510CR3
87
KTB0510CR6
95
KTB0510CR7
88
KTB0510CR8
88
KTB0510CS0
89
KTB510HT01
121
KTB510HT02
121
KTB510HT03
121
KTB0630CB3
113
KTB0630CB4
113
KTB0630CB5
113
KTB0630HF3
114
KTB0630HF4
114
KTB0630HF5
114
KTB1000CB3
113
KTB1000CB4
113
KTB1000CB5
113
KTB1000HF3
114
KTB1000HF4
114
KTB1000HF5
114
KTB1250CB3
113
KTB1250CB4
113
KTB1250CB5
113
DEBU021EN_Index.indd
Cat. no.
Designations
version: 1.1
Pages
17
18
version: 1.1
DEBU021EN_Index.indd
Introduction
PD202382-m_r
PD202088-104_r
b more flexibility
b ease of connection with the "plug and play" transformer and switchboard
connections
b more assistance. Our teams will assist you throughout your project.
K9AE01010.indd
version: 1.1
19
Distribution systems
Schneider Electric offers different distribution systems to fit your operating needs.
D205848
Centralised distribution
b
v
v
v
v
v
b
v
v
v
Our solutions:
b Prisma Plus and Okken switchboards.
DD205849
Decentralised distribution
b
v
v
v
v
v
v
v
b
v
v
v
v
Our solutions:
b Prisma Plus switchboards
b Canalis busbar trunking.
DD205850
Combined distribution
Where the advantages of both centralised and decentralised distribution are
required.
b Commercial and service buildings:
v offices
v stores
v hospitals
v exhibition halls, etc.
b Infrastructures:
v airports
v telecommunications
v internet data centres
v tunnels, etc.
b Industrial facilities:
v pharmaceuticals
v food processing, etc.
Our solutions:
b Prisma Plus and Okken switchboards
b Canalis busbar trunking.
20
version: 1.1
K9AE01020.indd
PD202427_r
Total coordination of the Schneider Electric system provides maximum safety of life
and property, continuity of service, upgradeability and ease of installation.
Total coordination is made easy by the tables in the "Selection Guide". They help
you chose the right combination of circuit breakers and busbar trunking.
Product characteristics are checked by calculations and tests carried out in our
laboratories.
A competitive installation.
DD205658
DD202383_r
K9AE01020.indd
version: 1.1
21
The busbar trunking has a low combustible load. Its construction uses very little
consumable material and is halogen free.
In the event of a fire, the busbar trunking does not emit any gas or toxic smoke.
DD205675
The busbar trunking helps prevent the propagation of a fire through partition walls
and floors.
Halogen-sensitive applications
b Public buildings (infrastructures, hospitals, schools, etc.).
b Buildings with evacuation difficulties (high-rises, ships, etc.) and service-activity
buildings.
b Sensitive processes (production of electronic components, etc.).
DD205674
Health
When PVCs burn, they produce large amounts of smoke that can be a serious
safety hazard.
b Reduced visibility:
v risk of panic
v complicates rescue work
b Smoke toxicity:
v hydrogen chloride gas (highly toxic)
v carbon monoxide (danger of asphyxiation).
22
version: 1.1
K9AE01030.indd
DD205673
Environment
Example:
1 kg of PVC generates 1 kg of waste.
Conservation of natural
resources
The depletion of raw materials (copper, plastics, etc.) is one of our ongoing
concerns.
For this reason, we have optimised the used of all materials used to make our
busbar trunking.
b Reduction of dangerous or polluting materials. We design our products to meet
future European directives.
b Reduction in the weight of insulating materials.
b Reduction in the use of plastics for improved fire performance: less energy
released during combustion, thereby limiting propagation and facilitating extinction
(lower calorific value).
The cost of an electrical installation includes the initial investment for the
equipment and its installation, the cost of maintenance and the cost of energy
losses during operation.
The concept of decentralised distribution is a way to merge all the circuits in one
and thus to reduce to the maximum the low cross-section lengths and the weight of
insulating materials.
DD206048
Example:
34 m of Canalis KS 250 A trunking equipped with fourteen 4-pole 25 A feeders.
kg
kg
K9AE01030.indd
version: 1.1
23
PD202384_r
24
version: 1.1
K9AE01040.indd
K9AE01040.indd
version: 1.1
25
A compact solution
b The compact size of Canalis KT means it takes up very little space in the
building:
v used as a rising main, it takes up only a minimum of space,
v used for horizontal distribution, it fits easily into the buildings structure (false
floors, false ceilings, service shafts, etc).
b Changes in direction have been designed to optimise the space taken up,
contrary to an equivalent installation using cables which requires large bending
radii.
DD202860
b Tap-off units, complete with protective devices, are fitted along the entire length
of the busbar trunking thus reducing the floor area taken up by the electrical
distribution switchboards.
b The design study is easy to perform as it does not require a detailed layout of
each load. Equipment choice is pre-determined and optimised.
b Installing the busbar trunking requires 2 or 3 people only, for a time equivalent
to that for installing cableways. The time normally needed for laying cables is
therefore saved.
b Connection to the MV/LV substation is made using a quick fitting joint block. The
tap-off units can be prepared in the workshop thus reducing on-site time. Their
connection to the busbar trunking is done in a single plugging-on operation.
b Installing busbar trunking lengths can be done as and when building work
progresses, thus optimising on-site work and allowing possible unexpected events
to be anticipated in advance.
PD202385_r
26
version: 1.1
K9AE02010.indd
Complete safety
b Busbar trunking temperature rise and short-circuit withstand are known and
independent of the installation. Coordination of the Schneider Electric system
results in complete control of the electrical network.
b Installation standards UTE C 15-105 chapter B.6.2 and IEC 60 364 chapter
5.523.6 stipulate that above 4 parallel cables, it is preferable to use busbar
trunking. Paralleling many cables leads to uneven distribution of currents and the
risk of abnormal temperature rise.
PD202386_r
b The busbar trunking and tap-off units are designed to guarantee the safety of
personnel and equipment:
v plug-on connections to silver-plated copper bars,
v bolted connections with tightening torque guaranteed by torque nuts,
v foolproof system to avoid the risk of assembly errors,
v IP55 certified splash and dust protection,
v sprinkler resistance test in compliance with Volkswagen specifications (valid
only for top-mounted units).
v access to live parts have IPxxD protection (1 mm wire diameter).
Its metal enclosure and high protection degree protect the busbar trunking from all
external aggressions (corrosion, rodents, etc).
b Seismic certification to IEC 60980, Richter scale >7 and MSK 64 severity 9.
Operating continuity
When working on the electrical installation, the busbar trunking provides immediate
readability of the electrical circuit thus allowing the appropriate zone to be quickly
identified.
Tap-off units can be plugged-on and off without the need for a shutdown; service
continuity is thus irreproachable.
The quality of the electrical contacts guarantees maintenance free operating
continuity.
PD202229-68_r
K9AE02010.indd
version: 1.1
27
Key points
PD202391_r
b Fire barrier.
b Halogen free.
b Small size.
PD202389_r
PD202388_r
b Operating continuity.
Key points
b Halogen free.
PD202387_r
PD202390_r
b Sprinklers.
28
version: 1.1
K9AE02020.indd
Key points
b Operating continuity.
PD395077-68_r
b Able to be evolved.
b Low voltage drops.
PD202393_r
PD202392_r
b Network readability.
Key points
109405_r
b Operating continuity.
b High tap-off density.
b Able to be evolved.
PD202395_r
PD202394_r
K9AE02020.indd
version: 1.1
29
Tertiary
Name
PD202244_r
Offices
Medium current
High
current
KDP
KN
KT
KBA
KBB
Axa
b
b
b
b
Trade Center
Tour du RDC
Turning Torso
Vodafone
PD202245_r
Sweden
Spain
Spain
Tunisia
Sweden
b
b
New Zealand
Colt
Digiplex
Portugal
France
Sweden
IBM
Spain, Italy
MCI-Worldcom
Tunisia
Hyatt
Mc Donalds
France
PD202247_r
Hospitals
Children Clinic
Brussels University Hospital
Spain
Sweden
Belgium
Derby Hospital
United Kingdom
Oran Hospital
b
b
France
Stockholm Hospital
Sweden
Michalon Hospital
Manussia Hospital
Alcampo
PD202248_r
Algeria
St Joseph Hospital
France
b
Auchan
b
b
B&Q
Carrefour
Coop
Fnac
Ikea
Mark & Spencer
b
b
ToysR Us
version: 1.1
France
Egypt
30
Luxembourg
Germany
b
b
Germany
France
Commerz Bank
Telefnica
Lexel
France
Allianz
Chamber of Commerce
KS
Country
Spain
World
United Kingdom
World
Italy
Spain, France
K9AE02030.indd
Industry
Name
PD202249_r
Car industry
Medium current
High
current
KDP
KT
BMW
Citron
KBA
KBB
KN
KS
Daewo
Italy
b
Iveco
Peugeot
Dacia
Country
Romania
Spain, Italy
Nissan
Spain
Renault
Seat
Spain
Valo
Volkswagen
Other industries
Aerospace industry
Airbus
Coca-Cola
Danone
Italy
World
Food-processing industry
b
Pasquier
France
France
Greenhouse
Netherlands
Ceramic industry
Esmalglas ceramic
Legrand
Rolex
Intel
ST Micro-electronique
Spain
Electricity
France, Turkey
Watch-making
b
Switzerland
Microelectronics
b
Irelande
b
France
China
China
Netherlands
Sweden
Spain
Industrial technology
Bosch
Telephony
Phillips
Nokia
Louis Vuitton
Delta
Textile industry
K9AE02030.indd
version: 1.1
Israel
31
Infrastructure
Name
PD202250_r
Airports
Paris Airport
Medium current
High
current
KDP
KBA
KBB
KN
KS
KT
Cairo Airport
b
Hong-Kong Airport
Landvetter Airport
Arlanda
Satelite Barajas
PD202251_r
Marine
PD202252_r
Undergrounds
United Kingdom
China
Sweden
b
b
Sweden
Spain
Chantier de lAtlantique
France
Meyerwerft
Germany
Guanghzou Underground
Madrid Underground
China
London Underground
United Kingdom
b
b
Singapore Underground
Spain
Singapore
Egypt
Other infrastructures
Alexandria Library
Centre international dexposition
de Suzhou
32
France
Egypt
Heathrow Airport
Country
b
b
China
CERN
Switzerland
Stade de France
France
version: 1.1
K9AE02030.indd
Technical files
The technical files have been compiled from completed contracts and provide
answers to questions concerning the installation of Canalis busbar trunking in
specific business sectors.
In data centers
Reference:
ART 37222
DESBS001EN
In exhibition centres
Reference:
ART 65946
KD0C00CTAFEEN
In shopping centres
Reference:
Available in your sales office.
In electronics factories
Reference:
ART 65944
KD0C00CTAFEEN
In tiles factories
Reference:
DEBU005EN
In car plants
Reference:
Available in your sales office.
In livestock buildings
Reference:
DESWED105010EN
In greenhouses
Reference:
ART 808260
DESWED105013EN
In logistic centres
Reference:
ART 807993
DESWED105011EN
In cruise ships
Reference:
DESWED105014EN
In garages
Reference:
DESWED103004EN
K9AE02040.indd
version: 1.1
33
Work-out your
solution together
PD202396_r
Our teams are available to provide customers with technical assistance throughout
the installation of their projects.
b
v
v
v
v
b
v
v
v
DD210862
Project
launch
Technical
support
CanBrass
drawing
After-sales
service
Autocad
drawing
On-site
instruction
and
installation
Production
Project
management
34
version: 1.1
K9AE02040.indd
PD202374
Design guide.
PD202375
PD202376
K9AE02040.indd
version: 1.1
35
Graphical costing
PD202377
PD202378
The software gives an optimum breakdown of the project and provides a bill of
materials: catalogue number, quantity, price.
The software can also generate 2D or 3D drawings with dimensions.
Quote
PD202379
36
version: 1.1
K9AE02040.indd
Contents
Index
Introduction
3
19
Presentation
38
38
44
47
Description
48
General
48
Run sections
50
51
52
Connection sections
53
Connection accessories
58
60
Tap-off units
61
62
63
64
Lighting distribution 38
Power distribution
40
For horizontal transport and distribution
For distribution to different levels
DEBU021EN_Presentation.indd
version: 1.1
44
46
65
135
173
233
37
Presentation
Canalis KTA
Canalis KDP
PD202216_r
Range
Run components
Degree of protection
Number of circuits
Rating
Tap-off intervals
Standard lengths
Finish
Maximum distance between fixing points
IP55
1
20 A
1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm
24 and 192 meters
0,70 meter
PD202225_r
Rating
Option
38
10 and 16 A
version: 1.1
K9AE11000.indd
Canalis KBB
PD202219_r
PD202217_r
Canalis KBA
IP55
1 or 2
25 and 40 A
500 and 1000 mm
2 and 3 meters
Galvanised steel
5 meters
PD202225_r
PD202225_r
IP55
1
25 and 40 A
500 - 1000 and 1500 mm
2 and 3 meters
Galvanised steel
3 meters
10 and 16 A
10 and 16 A
K9AE11000.indd
version: 1.1
39
Presentation
Canalis KTA
Canalis KN
PD202221_r
Range
Run components
Degree of protection
Polarity
Rating
Tap-off intervals
Standard lengths
Finish
Maximum distance between fixing points
IP55
3L + N + PE
40, 63, 100 and 160 A
500 - 1000 or 3000 mm
3 meters
White RAL 9001
3 meters
PD202227_r
Tap-off units
Rating
Option
40
Plug-in
Bolt-on
16 to 63 A
version: 1.1
K9AE11000.indd
PD202222_r
Canalis KS
IP55
3L + N + PE
100, 160, 250, 400, 500, 630, 800 and 1000 A
500 mm
Defined by the floor pitch
White RAL 9001
Defined by the floor pitch
PD202228_r
PD202228_r
IP55
3L + N + PE
100, 160, 250, 400, 500, 630, 800 and 1000 A
1000 mm on each face
3 and 5 meters
White RAL 9001
3 meters
25 to 400 A
25 to 400 A
K9AE11000.indd
version: 1.1
41
Presentation
Power distribution
Canalis KTA
Canalis KT
PD202088-74_r
Range
Run components
Degree of protection
Polarity
Rating
Tap-off intervals
Standard lengths
Finish
Maximum distance between fixing points
IP55
3L + PE ; 3L + N +PE ; 3L + N + oversized PE
800, 1000, 1250, 1600, 2000, 2500, 3200 and 4000 A
500 - 1000 mm
2 and 4 meters
White RAL 9001
3 meters
PD202229_r
Tap-off units
Rating
Option
42
Plug-in
Bolt-on
25 to 400 A
400 to 1250 A
-
version: 1.1
K9AE11000.indd
K9AE11000.indd
version: 1.1
43
Presentation
Canalis KTA
Run sections
Tap-off units
PD202328_r
PD202312_r
PD202313_r
Change-of-direction sections
PD202314_r
b
b
v
v
b
v
44
version: 1.1
K9AE11500.indd
Interface connections
PD202300_r
PD202318_r
PD202431_r
PD202317_r
K9AE11500.indd
version: 1.1
45
Presentation
PD202319_r
PD202320_r
PD202321_r
Tap-off units
PD202322_r
46
version: 1.1
K9AE11500.indd
Presentation
Rating (A)
Type of protection
Modular switchgear
Fuses
PD202138_r
PD202150_r
PD202148_r
63 A, 8 x 18 mm modules
PD202323_r
250 to 400
PD202324_r
PD202150_r
100 A, 12 x 18 mm modules
160
PD202147_r
25 to 100
PD202149_r
PD202325_r
PD202325_r
DB402027
PD240004_r
PD202326_r
PD240005_r
PD202327_r
For Compact NSX400 and NSX630 400 to 630 A for DIN fuses(1)
circuit breakers
(1) Tap-off units for NS1250 and fuses (from 400 to 1000 A) in IP31 only.
K9AE11500.indd
version: 1.1
47
Description
General
Canalis KTA
The Canalis KT busbar trunking is intended for high power distribution and
transport in industrial, commercial and tertiary buildings.
Assembly of prefabricated sections that adapt to all run configurations.
Run sections
DD205853
DD202434
b
b
b
b
b
b
DD202435-m
3L + PE
3L + N + PE
DD202436-m
-1/2
L1 L2 L3 N PE
DD205854
3L + N + PER
The KT busbar trunking is of compact design and can be installed edgewise, flat or
vertically.
This design, allows the busbar trunking to be installed through a floor slab or fire
barrier wall.
As standard, the Canalis KT busbar trunking acts as a fire barrier in accordance
with IEC 60439-2.
The compact technology allows Canalis KT busbar trunking to withstand high
short-circuit currents and is suitable for most electricity distribution applications.
The RAL 9001 pre-lacquered galvanized steel casing provides protection and
mechanical fixing of the conductors.
Further, it is used as the PE protective conductor (in accordance with NFC 15100
and IEC 60364).
In its reinforced version 3L + N + PER, the busbar trunking is fitted with an
additional internal copper conductor with a cross-section equal to half that of the
phase conductor.
A reinforced version can be supplied on demand. This version has lateral
reinforcement (see page "Characteristics").
The Canalis KT busbar trunking is suitable for applications containing harmonics by
taking into account the appropriate derating factor. See "Harmonic currents" in the
Design guide.
Tap-off contact
DD205855
The KS plug-on tap-off units are connected to the busbar trunking whilst live (offload) via spring jaw connections.
Contact zone coating:
b silver-plated copper at jaw contact points
b aluminium / silver-plated copper bimetallic saddle welded to the live conductors.
The electrical contact pads of the sections are made from
bonded bimetallic aluminium/copper.
48
version: 1.1
K9AE12000.indd
Joint block
DD205856
DD205857
Phase order
DD205858
The standard phase order for the busbar trunking is denoted N321.
-1/2
L1 L2 L3 N PE
-1/2
L1 L2 L3 N PE
DD205859
However, this order can be changed to N123. A label showing the phase order
"N123" is supplied with each element to indicate the change.
-1/2
L1 L2 L3 N PE
-1/2
L1 L2 L3 N PE
K9AE12000.indd
version: 1.1
49
Description
Run sections
Canalis KTA
Straight sections
Transport sections - Type ET
DD202390
DD205860
DD205861
50
version: 1.1
K9AE12000.indd
It controls and absorbs the expansion of Canalis runs and must be used on runs
over 30 metres and each time the busbar trunking passes through a building
expansion joint.
Refer to the installation guide.
Available in a 1 metre length, it can be fitted vertically or horizontally.
At its centre it has flexible conductor joints and a sliding case able to absorb the
relative movements of each part of the section.
DD205863
DD202439
Used when the phase order of the switchboard is different to that of the
transformer.
Available in a 1 metre length and is the same physical size as a transport section.
b The TN version transposes the neutral.
DD205862
DD210811A
DD205864
If the run has a feed unit (supplied without a joint block) at each end, an additional
joint block must be ordered.
Each joint block is supplied with the necessary covers, nuts and bolts.
The end cover protects and insulates the conductor ends and is fitted to the last
section.
DD202441
DD202440
Type SL for:
b Compact NS1000 to 1600 A type NA fixed isolators:
v unhingeable door
v 3-point closing (possibility of locking with key lock, not supplied)
b Interpact INV isolator, 2000 to 2500 A:
v unhingeable door
v 3-point closing (possibility of locking with key lock, not supplied)
b Masterpact NW3200 A type HA fixed isolator supplied with:
v transparent protection cover
v adaptation kit for Ronis lock + 1 Ronis lock
v complete Harting plug, not cabled.
Type PL for:
b Compact NS1000 to 1600 A type N fixed circuit-breakers:
v unhingeable door
v 3-point closing (possibility of locking with key lock, not supplied).
For circuit-breakers greater than 1600 A, consult the sales office.
K9AE12000.indd
version: 1.1
51
Description
Canalis KTA
Simple changes of direction
Elbows - Types LP and LC
DD205865
DD202432
DD205866
DD205867
Changes of direction
Zeds - Types ZP, ZC and CP
DD205869
3-branch made-to-measure:
b flat or edgewise, to move the run axis upwards, downwards, to the right or to the
left without having to bend the busbar trunking:
v type ZP, flat Zed
DD205870
DD205871
52
version: 1.1
K9AE12000.indd
Connection sections
DD202314
DD202306
Direct connection to Trihal transformers and Prisma Plus & Okken switchboards.
Supplied factory or panelbuilder assembled and tested to IEC 60439-1 and 2.
Quick and simple connection of the busbar trunking to the interface.
Reduced size.
Joint block integrated into the interface.
A sealing kit (rating dependent) must be ordered.
DD202310
Okken switchboard.
DD202503
K9AE12000.indd
version: 1.1
53
Description
Connection sections
Canalis KTA
Universal connections to switchboards and oil immersed transformers
DD210777
DD205872
DD202502
Types ER N1/N2
Types ER N3/N4
Types ER N5/N6
Type ER N7
Connection:
b either directly to the busbar
b or by flexible bars and connection plates
b or by braids
b or by cables.
b ER feed units are supplied without a joint block.
b If the run has a feed unit at each end, an additional joint block must be ordered.
54
version: 1.1
K9AE12000.indd
DD210866
DD210864
b Type CS
Height adaptable flexible protective cover adaptable for ER N1 to N6 feed units
with a between centres distance of 115 mm.
DD205873
DD205624
DD210865
DD202321
DD202325
v Type BC
Protective cover for direct cable connection to ER N1 to N6 feed units with a
between centres distance of 115 mm.
K9AE12000.indd
version: 1.1
55
Description
Connection sections
Canalis KTA
Universal connections to dry type transformers
DD202447
For dry type transformers with the neutral between the phases.
They allow optimum connection to the busbar trunking.
DD205874
Type EL N1/N2.
DD205877
Type EL N3/N4.
DD205876
DD205875
Type EL N5.
They are of similar design to straight transport sections and can be installed
edgewise or flat.
If installed flat, a set of angle brackets can be ordered.
The following must be specified at the time of order:
b phase order
b distance between phases (a 20 mm lateral adjustment can be made use of on
site).
The link between the transformer terminals and the connection section is either by
flexible bar connection plates or by braids.
56
version: 1.1
K9AE12000.indd
DD202342
b Type CR4
Protective cover for EL N1 to N4 feed units.
Edgewise assembly.
DD202343
b Type CR5
Protective cover for EL N1 to N4 feed units.
Flat assembly.
DD202346
b Type CR6
Protective cover for EL N5 feed unit.
Edgewise assembly.
K9AE12000.indd
version: 1.1
57
Description
Connection accessories
Canalis KTA
Accessories for direct connection to the switchboard
DD202363
Make-up of kit:
b 8 x 2 mm thick copper spacers
b 16 off M12 x 60 mm bolts, class 8.8
b 16 contact washers
b 16 torque nuts
b 8 steel spacer plates.
Order a set per feed unit whatever the rating.
DD202403
b YC5, insulated 1000 mm long flexible bar, stripped at one end and with 4 oblong
holes.
The length of the holes at the switchboard side are to be adapted on-site.
DD205878
DD202411
Clamps
YS1 clamps enable high short-circuit current levels to be withstood; only for bars
with a 115 mm spacing.
Insulation
See page 59.
58
version: 1.1
K9AE12000.indd
The feed unit conductors are connected to the transformer bars via connection
plates or braids:
b connection plates, YC types, are flexible bars made up of 5 copper sheets of
1 x 100 mm (500 mm cross-section).
b braids, YT type, are copper braids with a 600 mm cross-section.
The number of connection plates needed is proportional to the busbar trunking
rating.
Connection plates
DD202412
The YC3 is an uninsulated bar with an expansion kink; it is 400 mm long and has
4 holes at one end.
They can be fitted to the transformer side:
b either using bar clamps (no drilling),
b or drilled and bolted (to be carried out on site).
DD205880
YS2 and YS3 bar clamps enable connection without the need to drill the connection
plates.
They allow height adjustment.
b Type YS2, bar clamps for 100 mm transformer connection terminals.
b Type YS3, bar clamps for 120 mm transformer connection terminals.
Make-up of kit: 1 set of 8 parts.
DD202414
b The YC4 is an uninsulated bar with an expansion kink; it is 400 mm long and has
4 oblong holes at each end (ready to use).
Braids
DD202415
Type YT, 400 mm long insulated braid with 4 holes at each end.
The connection plates and braids are fixed to the feed unit using the YB4 nut and
bolt kit, made up of:
b 16 off M12 x 80 mm bolts, class 8.8
b 16 contact washers
b 16 torque nuts
b 8 steel spacer plates.
DD230229
Insulation
DD230230
K9AE12000.indd
version: 1.1
59
Description
Canalis KTA
Horizontal supports
273202DD
The ZA types allow the busbar trunking to be fixed and adjusted along its length, as
well as absorbing its movements.
DD202485
b Type ZA1, to support edgewise busbar trunking only, consists of a steel angle
bracket and 2 x 2 metre threaded M10 rods.
The maximum distance between supports is:
v 3 metres for edgewise busbar trunking
v 2 metres for flat busbar trunking.
See installation precautions.
DD202368
DD202486
DD202369
Fixing bracket
DD202484
The ZA3 keeps the busbar trunking in place on its support, without blocking it, in
order to allow expansion movements.
Vertical supports
DD202496
DD202374
To a wall.
60
To a wall bracket.
version: 1.1
To the floor.
K9AE12000.indd
Tap-off units
DD210275
The tap-off units are used to instantly connect loads or secondary runs, and comply
with installation standards and regulations (IEC 60364), whatever the earthing
system (TT, TNS, TNC or IT).
When off-load, they can be plugged-on and off and be operated whilst live.
Plugging-on and plugging-off automatically opens and closes the tap-off point.
DD210276
No live part is accessible with the door open. The protection degree is IPXXB
(finger protection).
They are IP55 by construction (no accessory is required).
Fuse and modular switchgear tap-off units (AC20) are isolated as soon as the tapoff unit door is opened.
Tap-off unit disconnection by opening or closing the cover should be carried
out only if the downstreamload is de-energised.
For circuit breaker tap-off units, there are safety mechanisms to prevent:
b the tap-off unit being plugged-on and plugged-off with the tap-off unit door closed
b the door being closed if the tap-off unit has not been locked onto the busbar
trunking
b access to the electrical equipment and connection terminals when live
b the door being opened in the "ON" position for tap-off units fitted with a Compact
NS or NSX or NG circuit breaker.
DD210466
DD202012
K9AE13000.indd
version: 1.1
61
Description
Canalis KTA
DD210454
Most 18 mm Multi 9 modular devices can be fitted into these tap-off units.
They have a window on the front face for switchgear control and visualisation.
A transparent shutter ensures the window can be sealed.
Two tap-off ratings are available:
b 63 A nominal current for 8 modules
b 100 A nominal current for 12 modules (accepts C120 circuit breakers).
These tap-off units are fitted with a DIN rail and upstream connections for 18 mm
wide modular devices.
The switchgear is operated via a rotary handle which prevents door opening when
the circuit breaker is in the "ON" position.
Nominal current: 160 A for a 13-module capacity (accepts NG125 or NG160 fitted
with a Vigi unit).
These tap-off units are fitted with mounting plates and upstream connections
for fixed, front-connected 100 to 400 A Compact NSX circuit breakers (N, H or L
version) with a rotary handle.
The 400 A tap-off units can only be fitted onto straight lengths with a rating greater
than 400 A.
For plug-on circuit breakers, Vigi units, etc, please consult your Schneider Electric
contact.
62
version: 1.1
K9AE13000.indd
These tap-off units provide the tap-offs with fuse protection (fuses not supplied).
DD210472
DD202012
K9AE13000.indd
version: 1.1
63
Description
Canalis KTA
Safety and operation
The electrical connection is made by plugging-on the tap-off unit into dedicated tapoff point whilst the busbar trunking is de-energised (plugging-off the unit must also
be done with the busbar trunking de-energised).
The connection is mechanically tightened using a one-use torque bolt (10 daN.m).
A mechanical foolproof system avoids the risk of incorrect assembly.
The door can only be opened once the load has been isolated (rotary handle).
The bolt can only be tightened or untightened with the door open.
No live part is accessible with the door open, protection degree IP2X.
b Colour:
v white (RAL 9001) body
b Material: galvanized sheet steel.
b Other characteristics:
v the cables exit laterally through 2 aluminium plates (to be drilled by the
installation contractor)
v cabling space can be increased by using the cable box supplied with the tap-off
unit
v the door is fixed using 6 captive M6 screws and can be completely removed to
facilitate cabling.
DD202451
These tap-off units are used to supply loads or secondary runs (e.g. medium power
distribution using Canalis KS).
They are fitted to specific EB type straight lengths.
They comply with installation standards and regulations, whatever the earthing
system (TT, IT, TNS or TNC):
b tap-off units fitted with a mounting plate for Compact NS and NSX 400/1250 A,
3 or 4 P:
v fixed device
v front connections
v extended rotary handle.
DD202497
3 models:
b Compact NSX400/630 A, connection capacity:
v IP54
v 3 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm)
v 150 mm for the PE
b Compact NS800/1000 A, connection capacity:
v IP54
v 4 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm)
v 200 mm2 for the PE (cable clamp)
b Compact NS1250 A, connection capacity:
v IP31
v 4 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm)
v 200 mm2 for the PE (cable clamp).
64
version: 1.1
K9AE13000.indd
Contents
Index
Introduction
Presentation and description
3
19
37
Catalogue-number coding
67
Run components
68
71
73
76
78
80
Sealing kits
81
82
86
88
89
90
94
IP55
IP55
Connection accessories
73
76
96
100
Accessories
102
103
112
113
114
IP31 114
Design guide
Design and installation guide
Recommandations
DEBU021EN_Catalogue numbers.
indd
135
173
233
115
116
117
118
Special products
119
121
65
66
version: 1.1
K9AE20000.indd
Catalogue numbers
and dimensions
Catalogue-number coding
Canalis KTA
Catalogue-number composition
KT
Code
A
B
Code
AJ
BC
CB
CP
CR
CS
DB
EB
ED
EH
EL
ER
ET
FA
HF
HT
LC
LP
PL
SL/RL
TC
TN
TP
TT
YA
YB
YC
YE
YF
YS
YT
ZA
ZC
ZP
p p p p p p p p pp
PE protective
conductor(1)
Standard
Standard
Standard
Reinforced
Reinforced
Short circuit
level(1)
Standard (2)
Standard
Reinforced
Standard
Reinforced
Code
3
4
6 (3)
5
7
800
1000
1250
1600
2000
2500
3200
4000
70 x 6
100 x 6
120 x 6
160 x 6
200 x 6
2 x (120 x 6)
2 x (160 x 6)
2 x (200 x 6)
230
230
350
350
350
510
510
DD202180
DD205881
DD205882
K9AE20000.indd
230
version: 1.1
67
Catalogue numbers
and dimensions
Run components
IP55
Canalis KTA
Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b for the 800 A rating, add a "0" in the catalogue number : KTA0800
b add the dimensions of the selected component as a technical comment
Example: the catalogue number of an 800 A feeder length, 3L + N + PE,
2450 mm long, is:
KTA0800ET42C, L = 2450
Rating
Type
Fixed
Made to
measure
Length "L"
(mm)
Cat. no.
2000
4000
500 to 1500
1501 to 1999
2001 to 2500
3L + PE
3L + N + PE (2)
3L + N + PER (1)
2501 to 3000
KTAppppETppp
DD210795
KTAppppETppp
Cat. no.
2000
4000
DD210798
Type Length
"L" (mm)
Fixed
3L + PE
3L + N + PE (2)
3L + N + PER (1)
DD210800
KTAppppEDp20
KTAppppEDp20
DB402701
KTAppppEDp40
16
KTAppppEDp40
(1) See the "Trunking cross-section" table opposite.
68
version: 1.1
K9AE21010.indd
Cat. no.
2000
4000
DD205884
Type Length
"L" (mm)
Fixed
3L + PE
3L + N + PE (2)
3L + N + PER (1)
DD205883
DD210803
KTAppppEBp20
KTAppppEBp40
DD210802
KTAppppEBp40
Trunking cross-section
Rating (A)
Weight (kg/m)
800(1)
1000
1250
1600
2000
2500
3200
4000
3L + PE
12
14
16
19
22
25
31
38
3L + N + PE
13
16
18
22
26
30
37
45
3L + N + PER
15
19
21
26
31
36
46
56
DD210867
DD202180
Height H (mm)
Width W (mm)
K9AE21010.indd
version: 1.1
69
Run components
Catalogue numbers
and dimensions
IP55
Canalis KTA
Ordering
Complete the catalogue number by replacing the "pppp" with the rating.
Important: in the catalogue number, for a rating of 800 A, add a "0": KTA0800.
Example: a transport section 800 A, length 4 m.
Catalogue number for 3L+N+PE: KTA0800EH440.
Straight
lengths for KH plug-in
tap-off units
Type
Length
"L" (mm)
Fixed
3L + N + PE (2)
3L + N + PER (3)
2000
KTAppppEH320
KTAppppEH420 KTAppppEH520
4000
KTAppppEH340
KTAppppEH440 KTAppppEH540
DB402102
DB402025
KTAppppEHp20
KTAppppEHppp
DB402127
KTAppppEHp40
70
version: 1.1
K9AE21010.indd
Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b for the 800 A rating, add a "0" in the catalogue number : KTA0800
b add the dimensions of the selected component as a technical comment
Example: the catalogue number of a 1250 A neutral crossover length,
3L + N + PE, 1000 mm long, is:
KTA1250TN410
Rating
Type
Length "L"
(mm)
Cat. no.
3L + PE
3L + N + PE (2)
3L + N + PER(1)
Fixed
1000
KTAppppDB310 KTAppppDB410 KTAppppDB510
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppDB510 by
KTAppppDB710.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500DB4pp by KTA2500DB6pp and KTA3200DB4pp by KTA3200DB6pp.
KTAppppDBp10
DD210806
KTAppppDBp10
Type
Fixed
Length "L"
(mm)
Cat. no.
1000
KTAppppTN410
3L + N + PE
DD210808
KTAppppTNp10
KTAppppTNp10
(1) See the "Trunking cross-section" table opposite.
DD205886
Length "L"
(mm)
Cat. no.
Fixed
1000
KTAppppTP410
3L + N + PE
DD210810
KTAppppTPp10
KTAppppTPp10
(1) See the "Trunking cross-section" table opposite.
K9AE21020.indd
version: 1.1
71
Catalogue numbers
and dimensions
IP55
Canalis KTA
Additional jointing units
DD210811
Type
Cat. no.
Jointing unit
3L + PE
3L + N + PE
3L + N + PER
KTAppppYA3
KTAppppYA4
KTAppppYA4
DD210812
KTAppppYAp
DD210868
KTAppppYAp
End covers
DD205887
Type
End cover
Rating of the
trunking (A)
Height H of the
trunking (mm)
Cat. no.
800(1)
1000
1250
1600
2000
2500
3200
4000
74
104
124
164
204
244
324
404
KTB0074FA
KTB0104FA
KTB0124FA
KTB0164FA
KTB0204FA
KTB0244FA
KTB0324FA
KTB0404FA
KTB0ppppFA
DD210814
KTB0ppppFA
Trunking cross-section
Rating (A)
Weight (kg/m)
800(1)
1000
1250
1600
2000
2500
3200
4000
3L + PE
12
14
16
19
22
25
31
38
3L + N + PE
13
16
18
22
26
30
37
45
3L + N + PER
15
19
21
26
31
36
46
56
DD210867
DD202180
Height H (mm)
Width W (mm)
72
version: 1.1
K9AE21020.indd
Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b for the 800 A rating, add a "0" in the catalogue number : KTA0800
b add the dimensions of the selected component as a technical comment
Example: the catalogue number of a 2000 A flat elbow, N1, 3L + N + PE with
dimensions A = 300 mm and B = 650 mm is:
KTA2000LP4B1, A = 300, B = 650.
Rating
Flat elbows
DD205888
Type
Fixed
Position of
neutral
Cat. no.
3L + PE
N1
N2
Made to
measure
N1
N2
3L + N + PE (2)
3L + N + PER (1)
KTAppppLPppp
DD205889
KTAppppLPpp1
DD205892
KTAppppLPpp2
Type
Rating (A)
Type
Position of
neutral
Cat. no.
N1
DD205890
Made to
measure angle
3L + PE
3L + N + PE (2)
3L + N + PER(1)
N2
KTAppppLP3C2 KTAppppLP4C2 KTAppppLP5C2
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppLP5Cp by
KTAppppLP7Cp.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500LP4pp by KTA2500LP6pp and KTA3200LP4pp by KTA3200LP6pp.
DD205893
KTAppppLPpCp
DD205891
KTAppppLPpC1
K9AE22010.indd
Rating (A)
Dimensions (mm)
A
300
version: 1.1
B
300
W
91 to 179
73
Catalogue numbers
and dimensions
IP55
Canalis KTA
DD205894
Edgewise elbows
Type
Cat. no.
Fixed
3L + PE
3L + N + PE (2)
3L + N + PER (1)
KTAppppLC3A
KTAppppLC4A
KTAppppLC5A
Made to measure
KTAppppLC3B KTAppppLC4B KTAppppLC5B
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppLC5p by
KTAppppLC7p.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500LC4p by KTA2500LC6p and KTA3200LC4p by KTA3200LC6p.
DD205895
KTAppppLCpp
KTAppppLCpp
Rating (A)
Dimensions (mm)
A
275
290
300
320
340
360
400
440
Made to
276 to 774
275
measure(3)
1000
291 to 789
290
1250
301 to 799
300
1600
321 to 819
320
2000
341 to 839
340
2500
361 to 859
360
3200
401 to 899
400
4000
441 to 939
440
(2) For the 800 A rating, indicate "KTA0800".
(3) Only one llmb may be made to measure.
Fixed
B
275
290
300
320
340
360
400
440
275
276 to 774
290
291 to 789
300
301 to 799
320
321 to 819
340
341 to 839
360
361 to 859
400
401 to 899
440
441 to 939
800(2)
1000
1250
1600
2000
2500
3200
4000
800(2)
Trunking cross-section
Rating (A)
Weight (kg/m)
800(1)
1000
1250
1600
2000
2500
3200
4000
3L + PE
12
14
16
19
22
25
31
38
3L + N + PE
13
16
18
22
26
30
37
45
3L + N + PER
15
19
21
26
31
36
46
56
DD210867
DD202180
Height H (mm)
Width W (mm)
74
version: 1.1
K9AE22010.indd
Edgewise tee
DD205896
Type
Cat. no.
3L + PE
3L + N + PE (2)
3L + N + PER (1)
Fixed
KTAppppTC3
KTAppppTC4
KTAppppTC5
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppTC5 by KTAppppTC7.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace KTA2500TC4
by KTA2500TC6 and KTA3200TC4 by KTA3200TC6.
DD205897
KTAppppTCp
KTAppppTCp
Rating (A)
Dimensions (mm)
A
800(2)
275
1000
290
1250
300
1600
320
2000
340
2500
360
3200
400
4000
440
(2) For the 800 A rating, indicate "KTA0800".
B
275
290
300
320
340
360
400
440
Fixed
C
275
290
300
320
340
360
400
440
Trunking cross-section
Rating (A)
Weight (kg/m)
800(1)
1000
1250
1600
2000
2500
3200
4000
3L + PE
12
14
16
19
22
25
31
38
3L + N + PE
13
16
18
22
26
30
37
45
3L + N + PER
15
19
21
26
31
36
46
56
DD210867
DD202180
Height H (mm)
Width W (mm)
K9AE22010.indd
version: 1.1
75
Catalogue numbers
and dimensions
IP55
Canalis KTA
Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b for the 800 A rating, add a "0" in the catalogue number : KTA0800
b add the dimensions of the selected component as a technical comment
Example: the catalogue number of a 1600 A edgewise zed unit, N2, 3L + N + PE
with dimensions A = 300 mm, B = 450 mm, C = 300 mm is:
KTA1600ZC42, A = 300, B = 450, C = 300.
Rating
Type
Cat. no.
3L + PE
3L + N + PE (2)
3L + N + PER (1)
Made to measure
KTAppppZP3
KTAppppZP4
KTAppppZP5
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppZP5 by KTAppppZP7.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace KTA2500ZP4
by KTA2500ZP6 and KTA3200ZP4 by KTA3200ZP6.
DD205899
KTAppppZPp
KTAppppZPp
Dimensions (mm)
A
B
300
130 to 599
All
C
300
DD205900
Type
Position of
neutral
DD205902
KTAppppZCpp
DD205901
KTAppppZCp1
KTAppppZCp2
76
Dimensions
Rating (A)
Dimensions (mm)
800(2)
1000
1250
1600
2000
2500
3200
4000
A
275
290
300
320
340
360
400
440
B
90 to 549
90 to 579
90 to 599
90 to 639
90 to 679
90 to 719
90 to 799
90 to 879
version: 1.1
C
275
290
300
320
340
360
400
440
K9AE22020.indd
Type
Made to
measure
Position of
neutral
Cat. no.
3L + PE
3L + N + PE (2)
3L + N + PER (1)
N1
KTAppppCP31
KTAppppCP41
KTAppppCP51
N2
KTAppppCP32
KTAppppCP42
KTAppppCP52
N3
KTAppppCP33
KTAppppCP43
KTAppppCP53
N4
KTAppppCP34 KTAppppCP44 KTAppppCP54
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppCP5p by
KTAppppCP7p.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500CP4p by KTA2500CP6p and KTA3200CP4p by KTA3200CP6p.
KTAppppCPp1
DD202188
DD205904
KTAppppCPp1
and KTAppppCPp2
DD202367
DD205905
KTAppppCPp2
KTAppppCPp3
and KTAppppCPp4
DD205906
KTAppppCPp3
Dimensions
Rating (A)
KTAppppCPp4
A
300
300
300
300
300
300
300
300
800(2)
1000
1250
1600
2000
2500
3200
4000
Dimensions (mm)
B
195 to 574
210 to 589
220 to 599
240 to 619
260 to 639
280 to 659
320 to 699
360 to 739
C
275
290
300
320
340
360
400
440
Trunking cross-section
Rating (A)
Weight (kg/m)
3L + PE
3L + N + PE
3L + N + PER
800(1)
12
13
15
1000
14
16
19
1250
16
18
21
1600
19
22
26
2000
22
26
31
2500
25
30
36
4000
38
45
56
DD210867
DD202180
Height H (mm)
Width W (mm)
3200
31
37
46
K9AE22020.indd
version: 1.1
77
Catalogue numbers
and dimensions
Canalis KTA
DD202304
Type of
circuit
breaker
Canalis
polarity
NW08/16
Fixed or
drawout
NW20/25
NW32
Fixed or
drawout
Fixed or
drawout
NW40
Fixed or
drawout
Cat. no.
3L+PE
3L+N+PE
4P
04716
3L+N+PER
4P
04716+KTB0164PE1
3L+PE
3P
04725
3L+N+PE
4P
04726
3L+N+PER
4P
04726+KTB0244PE1
3L+PE
3P
04735
3L+N+PE
4P
04736
3L+N+PER
4P
04736+KTB0404PE1
3L+PE
3P
04737
3L+N+PE
4P
04738
b
3L+N+PER 4P
For the position in the switchboard, see the "Installation guide".
04715
04738+KTB0404PE1
NW20/32
Rear connection
Connection
Type of circuit
breaker
Number of vertical
modules(1)
Top direct
Fixed or drawout
27
Rear
Fixed
16
Drawout
17
Top direct
Fixed or drawout
28
Rear
Fixed
16
Drawout
17
Fixed or drawout
36
NW40
Rear
(1) 1 module = 50 mm.
DD202306
Canalis
polarity
NT06/12 Fixed or
drawout
NT16
DD202307
Fixed or
drawout
3L+PE
04703
3L+N+PE
4P
04704
3L+N+PER 4P
04704+KTB0164PE1
3L+PE
3P
04703
3L+N+PE
4P
04704
b
3L+N+PER 4P
For the position in the switchboard, see the "Installation guide".
Circuit Type of
breaker circuit
breaker
Canalis
polarity
NS630b/ Fixed or
1250
drawout
3L+PE
3L+N+PE
4P
04704
3L+N+PER 4P
04704+KTB0164PE1
Fixed or
drawout
Cat. no.
04703
3L+PE
3P
04703
3L+N+PE
4P
04704
b
3L+N+PER 4P
For the position in the switchboard, see the "Installation guide".
04704+KTB0164PE1
Connection
Type of circuit
breaker
Number of vertical
modules(1)
Top direct
Fixed
17
Drawout
18
Rear
Fixed or drawout
16
NT16
Rear
NS1600
(1) 1 module = 50 mm.
Fixed or drawout
16
NT06/12
NS630b/1250
78
04704+KTB0164PE1
Compact NS
NS1600
Rear connection
Cat. no.
version: 1.1
K9AE23000.indd
Masterpact NW
Circuit
breaker
NW08/32
DD202309
03561
NW40
Supports Terminal
Cover
extension
bar supports
Fixed or
drawout
Top direct
03561
3 x 04694
04871 + 04861
Rear
03561
2 x 04694
04871 + 04863
Fixed or
drawout
Top direct
03561
04871 + 04861
Rear
03561
04871 + 04863
Masterpact NT
04711
04712
04713
04714
Circuit
breaker
Type of
circuit
breaker
Canalis
polarity
NT06/12
Fixed or
drawout
3P
Top direct
03561
04712
04871 + 04852
Rear
03561
04713
04871 + 04853
Top direct
03561
04712
04871 + 04852
Rear
03561
04714
04871 + 04853
3P
Rear
03561
04713
04871 + 04854
4P
Rear
03561
04714
04871 + 04854
Type of
circuit
breaker
Canalis
polarity
Fixed
3P
Top direct
03561
04712
04871 + 04851
Rear
03561
04713
04871 + 04853
Top direct
03561
04712
04871 + 04851
Rear
03561
04714
04871 + 04853
Top direct
03561
04711
04871 + 04852
Rear
03561
04713
04871 + 04854
Top direct
03561
04712
04871 + 04852
Rear
03561
04714
04871 + 04854
3P
Rear
03561
04713
04871 + 04853
4P
Rear
03561
04714
04871 + 04853
3P
Rear
03561
04713
04871 + 04854
4P
Rear
03561
04714
04871 + 04854
4P
NT16
Fixed or
drawout
Compact NS
Circuit
breaker
NS630b/
1250
4P
Drawout
3P
4P
NS1600
Fixed
Drawout
Arc-chute covers
Circuit breaker
Masterpact NT
Compact NS
K9AE23000.indd
Canalis polarity
Cat. no.
Fixed
3P
47335
4P
47336
3P
33596
4P
33597
Fixed
version: 1.1
79
Catalogue numbers
and dimensions
Canalis KTA
Interfaces for Masterpact NW circuit breakers
DD202310
Fitting the interface does not change switchboard modularity as fixed by the devices.
Circuit
breaker
Type of
circuit
breaker
Canalis
polarity
NW08/16
Drawout
3L+PE
3L+N+PE
4P
b
b
DD202311
Drawout
3L+PE
3P
3L+N+PE
4P
3L+N+PER 4P
NW32
Drawout
3L+PE
3P
87823
87824
87824+KTB0244PE1
87814
87814+KTB0244PE1
4P
3L+N+PER 4P
87815
Drawout
3L+PE
3P
3L+N+PE
4P
3L+N+PER 4P
87825
87816
NW40
87822+KTB0164PE1
87813
b
3L+N+PE
87822
87812+KTB0164PE1
b
NW20/25
87811
87821
87812
3L+N+PER 4P
Cat. no.
87826
87816+KTB0404PE1
87826+KTB0404PE1
87827
87828
87817
87818
87818+KTB0404PE1
b
87828+KTB0404PE1
Fitting the interface does not change switchboard modularity as fixed by the devices.
Circuit
breaker
Type of
circuit
breaker
Canalis
polarity
NT08/16
Drawout
3L+PE
3L+N+PE
4P
3L+N+PER 4P
87811
87821
87812
87822
87812+KTB0164PE1
87822+KTB0164PE1
DD202313
Cat. no.
80
version: 1.1
K9AE23000.indd
Sealing kits
IP55
Interface supports
Circuit breaker
NW08/40
NT08/16
Connection
Cat. no.
Drawout
Top direct
87800
NW08/32(1)
Drawout
Rear
87801
NT08/16
(1) For rear connection of the interface to a Masterpact NW40 circuit breaker, the supports are
supplied with the interface.
Sealing kits for switchboard and Trihal transformer roofs with interface
DD202314
Type
Sealing kit
Rating of the
trunking (A)
Height H of the
trunking (mm)
Cat. no.
800
74
KTB0074TT01
1000
104
KTB0104TT01
1250
124
KTB0124TT01
1600
164
KTB0164TT01
2000
204
KTB0204TT01
2500
244
KTB0244TT01
3200
324
KTB0324TT01
4000
404
KTB0404TT01
KTB0ppppTT01
Reinforced protective earth (PER) for Prisma Plus and Okken interfaces
Height "H" (mm)
DD230215
Number of holes
Cat.no.
160
KTB0164PE1
240
KTB0244PE1
400
KTB0404PE1
DD230216
KTB0pppPE1
Thickness: 3 mm.
KTB0pppPE1
K9AE23000.indd
version: 1.1
81
Catalogue numbers
and dimensions
Canalis KTA
Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b in the catalogue number for the 800 A rating, add a 0: KTA0800
b add the dimensions of the selected unit as a technical comment.
Example: the catalogue number of a 1250 A made to measure end feed unit, N2,
3L + N + PE, 235 mm long and with between centres J, K and M = 170 mm, is:
KTA1250ER42, A = 235, J = 170, K = 170 and M = 170.
Rating
DD205907
Type
Position of
neutral
DD210832
KTAppppERp1, KTAppppERp2
3L + N + PE ou PER
KTAppppERp1
KTAppppERp2
3L + PE
DD230218
Table of dimensions
Rating (A)
800(3) to 1250
1600 to 2500
3200 to 4000
Neutral
Dimensions (mm)
N1
N2
N1
N2
N1
N2
A
235
235 to 734
235
235 to 734
235
235 to 734
J, K, M
115
80 to 250
115
80 to 250
115
80 to 250
Y
230
230
350
350
510
510
82
800
1000
1250
1600
2000
2500
3200
4000
DD205908
Rating (A)
Drilling for connection (mm)
Thickness of conductor = 6 mm.
version: 1.1
K9AE24010.indd
DD205909
Position of
neutral
Cat. no.
Made to measure N3
3L + PE
3L + N + PE (2)
3L + N + PER (1)
KTAppppER33
KTAppppER43
KTAppppER53
N4
KTAppppERp4(3), 3L + N + PE or PER
DD205910
DD205911
KTAppppERp3
KTAppppERp4
Neutral
Dimensions (mm)
A
B
800(4) to 1250 N3, N4
200 to 534
300
1600 to 2500 N3, N4
200 to 534
300
3200 to 4000 N3, N4
200 to 534
300
(4) For the 800 A rating, indicate "KTA0800".
J, K, M
80 to 250
80 to 250
80 to 250
Y
230
350
510
DD205912
Cut-out drawing for feed units placed directly on the device roof
Table of dimensions
Rating (A)
Dimensions (mm)
Y
U
800(1) to 1250 230
K/2 + J + 80
1600 to 2500
350
K/2 + J + 80
3200 to 4000
510
K/2 + J + 80
(1) For the 800 A rating, indicate "KTA0800".
V
K/2 + M + 80
K/2 + M + 80
K/2 + M + 80
Trunking cross-section
Rating (A)
Weight (kg/m)
800(1)
1000
1250
1600
2000
2500
3200
4000
3L + PE
12
14
16
19
22
25
31
38
3L + N + PE
13
16
18
22
26
30
37
45
3L + N + PER
15
19
21
26
31
36
46
56
DD210867
DD202180
Height H (mm)
Width W (mm)
K9AE24010.indd
version: 1.1
83
Catalogue numbers
and dimensions
Canalis KTA
Edgewise elbow feed units
DD205913
Type
Position of
neutral
Made to measure N5
N6
Cat. no.
3L + PE
3L + N + PE (2)
3L + N + PER (1)
KTAppppER35
KTAppppER45
KTAppppER55
KTAppppERp5(3), 3L + N + PE ou PER
DD205914
KTAppppERp5
KTAppppERp6(3), 3L + N + PE ou PER
KTAppppERp6
Table of dimensions
Rating Neutral
(A)
800(4)
1000
1250
1600
2000
2500
3200
4000
N5, N6
N5, N6
N5, N6
N5, N6
N5, N6
N5, N6
N5, N6
N5, N6
Dimensions (mm)
A
175 to 509
190 to 524
200 to 534
220 to 554
240 to 574
260 to 594
300 to 634
340 to 674
B
275
290
300
320
340
360
400
440
J, K, M
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250
Y
230
230
230
350
350
350
510
510
DD205915
Dimensions (mm)
Y
U
800(1) to 1250 230
K/2 + J + 80
1600 to 2500
350
K/2 + J + 80
3200 to 4000
510
K/2 + J + 80
(1) For the 800 A rating, indicate "KTA0800".
V
K/2 + M + 80
K/2 + M + 80
K/2 + M + 80
800
1000
1250
1600
2000
2500
3200
4000
84
DD205916
version: 1.1
K9AE24010.indd
DD205917
Type
DD202316
3L + N + PE (2)
3L + N + PER (1)
Made to measure
KTAppppER37 KTAppppER47 KTAppppER57
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppER57 by
KTAppppER77.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500ER4p by KTA2500ER6p and KTA3200ER4p by KTA3200ER6p.
KTAppppERp7
DB402690
3L + PE
Dimensions (mm)
A
800(2) to 1250 235 to 734
1600 to 2500 235 to 734
3200 to 4000 235 to 734
P-Q
160 to 600
160 to 600
160 to 600
S - R ou R - S
160 to 600
160 to 600
160 to 600
Q, R, S minimum
80
80
80
Y
230
350
510
DD205918
Cut-out drawing for straight feed units connected directly to the device
Dimensions (mm)
Y
U
V
800(1) to 1250 230
if S > R, V = S + 80
1600 to 2500
350
U = P + 80
if R > S, V = R + 80
3200 to 4000
510
(1) For the 800 A rating, indicate "KTA0800".
Trunking cross-section
Rating (A)
Weight (kg/m)
3L + PE
3L + N + PE
3L + N + PER
800(1)
12
13
15
1000
14
16
19
1250
16
18
21
1600
19
22
26
2000
22
26
31
2500
25
30
36
4000
38
45
56
DD210867
DD202180
Height H (mm)
Width W (mm)
3200
31
37
46
K9AE24010.indd
version: 1.1
85
Catalogue numbers
and dimensions
Canalis KTA
Ordering
To order a protective cover onto which a feed connector is fitted, the parameters D,
G and Z, which depend on the feed connector, must be given.
Example: the catalogue number of a rigid vertical protective cover with dimension
Y = 350 mm intended for a feed unit with different between centre dimensions D, G
and Z (in mm) is:
KTB0350CR2, D = 330, G = 450 and Z = 500.
DD205919
Important : when ordering a horizontal cover, make sure you indicate dimensions "D, G and Z"
with the catalogue number.
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Cat. no.
KTB0230CR1
KTB0350CR1
KTB0510CR1
Weight (kg)
12.00
12.00
12.00
KTBppppCR1
DD205920
KTBppppCR1
Dimensions (mm)
Y
230
350
510
D
220 to 475
220 to 475
220 to 475
G
220 to 475
220 to 475
220 to 475
Z
310 to 800
430 to 800
590 to 800
86
Dimensions (mm)
Y
230
350
510
D
340 to 1000
340 to 1000
340 to 1000
version: 1.1
G
340 to 1000
340 to 1000
340 to 1000
Z
310 to 800
430 to 800
590 to 800
K9AE24010.indd
Cat. no.
KTB0230CR2
KTB0350CR2
KTB0510CR2
Weight (kg)
40.00
40.00
40.00
DD202322
KTBppppCR2
KTBppppCR2
Dimensions D and G are determined by the between centres dimensions (J, K and M) of the
end feed connector bars to be protected.
D = K/2 + J + 100
G = K/2 + M + 100
For the 3L + PE version, consider M = J to calculate the D and G quotations.
Table of dimensions for ER N1 to N6 straight feed units
Rating (A)
DD202323
800 to 1250
1600 to 2500
3200 to 4000
Dimensions (mm)
Y
230
350
510
D
220 to 475
220 to 475
220 to 475
G
220 to 475
220 to 475
220 to 475
Z
400 to 800
400 to 800
400 to 800
Cat. no.
KTB0230CR3
KTB0350CR3
KTB0510CR3
Weight (kg)
17.00
17.00
17.00
KTBppppCR3
DD202324
KTBppppCR3
Dimensions D and G are determined by the between centres dimensions of the end feed
connector bars to be protected.
Table of dimensions for ER N1 to N6 straight feed units
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
D = K/2 + J + 100
G = K/2 + M + 100
Dimensions (mm)
Y
230
350
510
D
220 to 475
220 to 475
220 to 475
G
220 to 475
220 to 475
220 to 475
Z
100 to 400
100 to 400
100 to 400
Dimensions (mm)
Y
230
350
510
D
220 to 475
220 to 475
220 to 475
G
220 to 475
220 to 475
220 to 475
Z
100 to 400
100 to 400
100 to 400
K9AE24010.indd
version: 1.1
87
Catalogue numbers
and dimensions
Canalis KTA
Ordering
There is no need to add technical comments to the catalogue number ordered.
Height adjustable cover for the fitting of a feed unit with between centre dimensions of
150 or 170 mm depending on the rating.
Never use with HV porcelaine bushings.
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Between centres
"J, K and M" (mm)
150
170
170
Dimensions "Y"
(mm)
230
350
510
Cat. no.
Weight (kg)
KTB0230CR7
KTB0350CR7
KTB0510CR7
30.00
36.00
42.00
DD206050
KTBppppCR5
KTBppppCR5
Table of dimensions
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Dimensions (mm)
Y
230
350
510
Z
565
825
905
X
450
650
650
A
830
890
960
B
750
810
880
E
330
350
460
F
125
265
185
G
365
485
645
Height adjustable cover for the fitting of a feed unit with between centre dimensions of
150 or 170 mm depending on the rating.
Never use with HV porcelaine bushings.
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
Between centres
"J, K and M" (mm)
150
170
170
Dimensions "Y"
(mm)
230
350
510
Cat. no.
Weight (kg)
KTB0230CR8
KTB0350CR8
KTB0510CR8
30.00
36.00
42.00
DD206051
KTBppppCR8
KTBppppCR8
Table of dimensions
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
88
Dimensions (mm)
Y
230
350
510
Z
600
600
600
A
830
890
960
B
750
810
880
version: 1.1
C
345
460
625
E
330
350
460
K9AE24010.indd
DD202318
DD202319
Rating (A)
Dimensions "Y" (mm)
Cat. no.
800 to 1250
230
KTB0230CS0
1600 to 2500
350
KTB0350CS0
3200 to 4000
510
KTB0510CS0
It is recommended to use insulating sheaths KTB0000YF1 with connection braids
KTB0000YT1.
KTBppppCS0
Weight (kg)
15.00
17.00
19.00
Table of dimensions
Rating (A)
800 to 1250
1600 to 2500
3200 to 4000
KTBppppCS0
Dimensions (mm)
Y
230
350
510
C
200 to 650
200 to 650
200 to 650
DD205922
Cable boxes
DD205923
Rating (A)
Dimensions "Y" (mm)
Cat. no.
Weight (kg)
800 to 1250
230
KTB0230BC01
15.00
1600 to 2500
350
KTB0350BC01
17.00
3200 to 4000
510
KTB0510BC01
19.00
Cable boxes are only to be used on ER N1 to N6 straight feed units with standard between
centre distances = 115 mm.
KTBppppBC01
DD205924
KTBppppBC01
Cable entry.
Aluminium plate to be drilled.
Table of dimensions
Rating (A)
Dimensions (mm)
Y
800 to 1250
230
1600 to 2500
350
3200 to 4000
510
See table page 85 for connection pad dimensions.
K9AE24010.indd
version: 1.1
89
Catalogue numbers
and dimensions
Canalis KTA
Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b in the catalogue number for the 800 A rating, add a "0": KTA0800
b add the dimensions of the selected unit as a technical comment.
Example: the catalogue number of a 3200 A end feed unit, N2, 3L + N + PER, with
a between centre distance E = 550 mm, length N = 310 mm and phase order
T = 3N21 is:
KTA3200EL72, E = 550 mm, N = 310 mm and T = 3.
Rating
DD202329
Position of
neutral
Cat. no.
Made to measure N1
3L + PE
3L + N + PE (2)
3L + N + PER (1)
KTAppppEL31
KTAppppEL41
KTAppppEL51
N2
KTAppppEL32 KTAppppEL42 KTAppppEL52
For an installation with flat mounted busbar trunking, add angle brackets between the
transformer and the feed unit, see page 93.
For fixing supports, see KTBppppZA4 page 100.
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppEL5p by
KTAppppEL7p.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500EL4p by KTA2500EL6p and KTA3200EL4p by KTA3200EL6p.
DD210330n
KTAppppELp1, KTAppppELp2
DD202331
KTAppppELp1
KTAppppELp2
Neutral
Dimensions (mm)
E
390 to 700
470 to 700
N
195 to E - 195
235 to E - 235
X
160
200
-1/2
-1/2
L1 L2 L3 N PE
-1/2
L1 L2 L3 N PE
DD205926
Views according to F
-1/2
-1/2
KTAppppELp2
L1 L2 L3 N PE
L1 L2 L3 N PE
KTAppppELp1
-1/2
L1 L2 L3 N PE
DD205925
KTAppppELp2
L1 L2 L3 N PE
Top views
KTAppppELp1
90
version: 1.1
K9AE24020.indd
Type
Position of
neutral
Cat. no.
Made to measure N3
3L + PE
3L + N + PE (2)
3L + N + PER (1)
KTAppppEL33
KTAppppEL43
KTAppppEL53
N4
KTAppppEL34 KTAppppEL44 KTAppppEL54
For an installation with flat mounted busbar trunking, add angle brackets between the
transformer and the feed unit, see page 93.
For fixing supports, see KTBppppZA4 page 100.
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppEL5p by
KTAppppEL7p.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500EL4p by KTA2500EL6p and KTA3200EL4p by KTA3200EL6p.
DD210335n
KTAppppELp3, KTAppppELp4
DD202334
KTAppppELp3
Neutral
Dimensions (mm)
E
390 to 700
470 to 700
N
195 to E - 195
235 to E - 235
F
0 to 200
0 to 200
X
160
200
-1/2
L1 L2 L3 N PE
-1/2
-1/2
-1/2
L1 L2 L3 N PE
DD205928
KTAppppELp4
L1 L2 L3 N PE
L1 L2 L3 N PE
KTAppppELp3
-1/2
-1/2
KTAppppELp4
L1 L2 L3 N PE
DD205927
Top views
KTAppppELp3
L1 L2 L3 N PE
Views according to F
Trunking cross-section
K9AE24020.indd
version: 1.1
91
Catalogue numbers
and dimensions
IP55
Canalis KTA
N5 feed units for dry-type transformers
DD202337
Type
Position of
neutral
Cat. no.
3L + PE
3L + N + PE (2)
3L + N + PER (1)
Made to measure N5
KTAppppEL35 KTAppppEL45 KTAppppEL55
For an installation with flat mounted busbar trunking, add angle brackets between the
transformer and the feed unit, see page 93.
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppEL5p by
KTAppppEL7p.
(2) To order the 3L+N+PE 2500 A and 3200 A version with reinforced Icc, replace
KTA2500EL4p by KTA2500EL6p and KTA3200EL4p by KTA3200EL6p.
DB402688
KTAppppELp5
DD210873n
DB402689
Table of dimensions
Rating
(A)
Neutral
Y
800 to 1250 N1, N2 230
1600 to 2500 N1, N2 350
3200 to 4000 N1, N2 510
Dimensions (mm)
E
390 to 700
470 to 700
470 to 700
N
195 to E - 195
235 to E - 235
235 to E - 235
X
160
200
200
92
version: 1.1
K9AE24020.indd
DD202340
Rating (A)
Cat. no.
160
KTB0000YE1
200
KTB0000YE2
DD210341n
KTB0000YE1, KTB0000YE2
KTB0000YE1, KTB0000YE2
Trunking cross-section
Rating (A)
Weight (kg/m)
800(1)
1000
1250
1600
2000
2500
3200
4000
3L + PE
12
14
16
19
22
25
31
38
3L + N + PE
13
16
18
22
26
30
37
45
3L + N + PER
15
19
21
26
31
36
46
56
DD210867
DD202180
Height H (mm)
Width W (mm)
K9AE24020.indd
version: 1.1
93
Catalogue numbers
and dimensions
IP55
Canalis KTA
Ordering
There is no need to add technical comments to the catalogue number ordered.
DD202342
Adjustable vertical protective covers for EL, N1 to N4 feed units, edgewise mounting
Type
Vertical cover
Position of neutral
Cat. no.
Weight (kg)
KTB0000CR4
24.00
Position of neutral
Cat. no.
Weight (kg)
KTB0000CR5
32.00
DD202344
KTB0000CR4
KTB0000CR4
Table of dimensions
Rating (A)
Dimensions (mm)
Z
Minimum
800 to 1250 200
1600 to 2500 200
3200 to 4000 200
Maximum
350
350
350
Adjustable horizontal protective covers for EL, N1 to N4 feed units, flat mounting
DD202343
Type
Horizontal cover
DD202345
KTB0000CR5
KTB0000CR5
Table of dimensions
Rating (A)
Dimensions (mm)
Z
Minimum
800 to 1250 330
1600 to 2500 330
3200 to 4000 330
94
Maximum
480
480
480
version: 1.1
K9AE24020.indd
DD202346
Cat. no.
Weight (kg)
N5
230
KTB0230CR6
38.00
350
KTB0350CR6
40.00
510
KTB0510CR6
47.00
DD202347
KTBppppCR6
KTBppppCR6
Table of dimensions
Rating (A)
Dimensions (mm)
Y
Z
Minimum
380
500
660
Maximum
530
650
810
DD205929
K9AE24020.indd
version: 1.1
95
Catalogue numbers
and dimensions
Connection accessories
Canalis KTA
DD202348
Connection plates
Type
Options
Cat. no.
Weight (kg)
KTB0000YC1
2.70
KTB0000YC2
2.70
KTB0000YC3
2.30
KTB0000YC4
2.30
KTB0000YC5
4.50
KTB0000YC1
KTB0000YC3
KTB0000YC4
DD202353
DD202352
KTB0000YC2
DD202351
DD202350
Insulated
1
(1) Each connector plate is made up 5 x 1 mm thick sheets.
DD202354
KTB0000YC5
1000
1600
1000
2000
1500
2500
1500
3200
2000
4000
2500
Busbar trunking
rating (A)
DD205933
DD205932
1000
1250
DD205931
Cross-section (mm2)
DD205930
Number
1000
Connector plates
96
2000 to 2500
3200
4000
1000 to 1600
version: 1.1
K9AE24030.indd
DD205934
Connection braids
Description
Connection braid
Cat. no.
Weight (kg)
KTB0000YT1
2.80
DD202356
KTB0000YT1
KTB0000YT1
Determining the number of braids required
Busbar trunking rating (A)
1200
1600
1200
2000
1200
2500
1800
3200
1800
4000
2400
Braids
Busbar trunking
rating (A)
DD205938
1250
DD205937
1000
DD205936
Cross-section (mm2)
DD205935
Number
1000
1250 to 2000
2500 to 3200
4000
Insulating sheaths
DD205939
Cat. no.
Weight (kg)
KTB0000YF1
1.00
DD202479
KTB0000YF1
KTB0000YF1
K9AE24030.indd
version: 1.1
97
Connection accessories
Catalogue numbers
and dimensions
Canalis KTA
DD202363
Spacers
Description
KTB0000YB1
8 x 3 mm galvanized steel
KTB0000YB2
spacers + 8 x 2 mm copper
spacers + 16 x M12 x 60 bolts +
washers and nuts
5.50
8 x 3 mm galvanized steel
plates + 16 x M12 x 60 bolts +
washers and nuts
KTB0000YB3
4.00
8 x 3 mm galvanized steel
plates + 16 x M12 X 80 bolts +
washers and nuts
KTB0000YB4
4.00
DD202366
DD230233
DD202365
Weight
(kg)
Copper spacer
KTB0000YB2
Cat. no.
DD202364
KTB0000YB3
KTB0000YB4
98
version: 1.1
K9AE24030.indd
DD202359
Bar supports
Description
Bar support, 115 mm between centres
for bar of 5 or 10 mm
Cat. no.
Weight (kg)
KTB0000YS1
2.40
DD202360
KTB0000YS1
KTB0000YS1
DD202361
Bar clamps
Description
1 bar clamps
Weight (kg)
100
KTB0000YS2
6.40
120
KTB0000YS3
6.40
DD202362
KTB0000YS2
KTB0000YSp
K9AE24030.indd
version: 1.1
99
Catalogue numbers
and dimensions
Canalis KTA
DD202372
Horizontal supports
Description
Rating
(A)
Busbar trunking
height (mm)
Cat. no.
Weight
(kg)
KTB0000ZA1
2.80
74
KTB0074ZA4
3.20
104 to 404
KTB0404ZA4
3.80
DD202370
KTB0000ZA1
KTB0000ZA1
Table of dimensions
DD202371
DD202368
KTBppppZA4
Height
H(mm)
74
104 to 404
Dimensions (mm)
A
74
86
B
160
186
C
110
136
Hooks
2 fixing grip are needed for each fixing point.
Description
1 fixing grip
Order indivisible quantity: 8.
Cat. no.
Weight
(kg)
KTB0000ZA3
0.60
KTB000ZA3
KTB0000ZA3
100
DD202373
DD202369
KTBppppZA4
version: 1.1
K9AE25000.indd
DD202374
Vertical supports
Description
Fixings
Rating
(A)
Cat. no.
Weight
(kg)
800 to 1600
74 to 164
KTB0164ZA5
5.75
2000
204
KTB0204ZA5
10.02
2500
244
KTB0244ZA5
10.62
3200
324
KTB0324ZA5
11.82
404
KTB0404ZA5
12.58
4000
For further details, see page 190.
DD202375
KTB0164ZA5
KTBppppZA5
Table of dimensions
Rating Dimensions (mm)
(A)
L
M
N
2000
202 205 152 to 202
2500
240 245 172 to 222
3000
322 325 212 to 262
4000
402 325 252 to 302
Trunking cross-section
Rating (A)
800
1000
1250
1600
2000
DD210867
K9AE25000.indd
2500
3200
4000
DD202180
Height H (mm)
Width W (mm)
version: 1.1
101
Accessories
Catalogue numbers
and dimensions
Fire-barrier kit
Canalis KTA
DB401570
Fire-barrier
Type
Fire-barrier kit
Busbar trunking
rating (A)
800
1000
1250
1600
2000
2500
3200
4000
Busbar trunking
height "H" (mm)
74
104
124
164
204
244
324
404
Fire barrier
length
650
650
650
650
650
650
650
650
Cat. no.
KTB074CF6
KTB104CF6
KTB124CF6
KTB164CF6
KTB204CF6
KTB244CF6
KTB324CF6
KTB404CF6
DB401571
The filler material around the busbar trunking must meet the requirements currently
in force to guarantee that the wall and ceiling fire-resistance class (for example DIN
1045 and DIN 1053-1) is maintained.
Filler material not supplied.
The fire barrier kit can also be made up on site by the installer according to
Schneider Electric's drawings and specifications.
For further information, consult your sales office.
102
version: 1.1
K9AE25000.indd
System earthing
arrangement
KSB63SMp8,
KSB100SMp12
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. circuit breaker
protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
DD205034
Tap-off polarity
DD205033
DD210454
Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.
Rating
(A)
Number of 18 mm
modules(3)
Connection
63
On devices
16
16
ISO 50 max.
100
12
On devices
35
35
ISO 63 max.
Cat. no.
Weight
(kg)
KSB63SM48
KSB63SM58
2.40
KSB100SM412
KSB100SM512 5.00
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Supplied with blanking plates:1x5 divisible (8 modules) or 2x5 divisible (12 modules).
(4) Maximum diameter for a multipolar cable.
DD202008
DD210455n
KSB63SMp8, KSB100SMp12
X = 432.5 (KSB63SMp8)
X = 545.5 (KSB100SMp12)
Cable exit
Centre line of tap-off outlets
(5) Protruding
Dimensions Rating (A)
A
B
C
D
E
F
K9AE26010_bis.indd
63
357
158
167
309
108
202
100
444
183
202
397
133
220
version: 1.1
103
Catalogue numbers
and dimensions
Canalis KTA
Tap-off units for NG modular devices, not equipped
System earthing
arrangement
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. circuit breaker
protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
DD210452
Tap-off polarity
DD210452
DD202154
The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.
KSB160SMp13
Rating
(A)
Type of
circuit-breaker
160
NG125 ou NG160
Rotary handle
28060
Connection
Terminals
Max. size
(mm2)
Flexible
Rigid
50
70
ISO 25 max.
KSB160SM413
Cat. no.
Weight
(kg)
KSB160SM513 8.50
DD202008
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
DD202155
KSB160SMp13
X = 625.5
Cable exit
Centre line of tap-off outlets
(4) Protruding
104
version: 1.1
K9AE26010_bis.indd
System earthing
arrangement
KSBpppDCp
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. circuit breaker
protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
DD210452
Tap-off polarity
DD210451
DD210461
The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.
Cat. no.
Cat. no.
Weight
(kg)
50
70
ISO 25 max.
KSB160DC4
KSB160DC5
9.00
250
NSX250
Curve N, H or L
Rotary handle
29338
Terminals
70
150
ISO 32 max.
KSB250DC4
KSB250DC5
12.50
400
NSX400
Curve N, H or L
Rotary handle
32598
Terminals
150
240
ISO 40 max.
KSB400DC4
KSB400DC5
18.00
Rating
(A)
Type of
circuit breaker
160
Connection
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
DD210462
DD202008
KSB160DCp
DD202008
X = 625.5
DD210463
KSB250DCp
X = 726.5
DD202008
DD210464
KSB400DCp
X = 976.5
4
Cable exit
Centre line of tap-off outlets
(4) Protruding
K9AE26010_bis.indd
version: 1.1
105
Catalogue numbers
and dimensions
Canalis KTA
System earthing
arrangement
KSBpppDCpTRE
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. circuit breaker
protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
Connection
DD210452
Tap-off outlets
DD210452
DD210465
The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.
Cat. no.
Weight
(kg)
Rating
(A)
Type of circuit
breaker
250
NSX250
Curve N, H or L
Rotary handle
29338
Terminals
70
150
ISO 32 max.
400
NSX400
Curve N, H or L
Rotary handle
32598
Terminals
150
240
ISO 40 max.
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.
DD202085
DD202008
KSB250DCpTRE
DD202008
X = 726.5
DD202086
KSB400DCpTRE
X = 976.5
Cable exit
Centre line of tap-off outlets
(4) Protruding
106
version: 1.1
K9AE26010_bis.indd
System earthing
arrangement
KSBpppSFp
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. fuse protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
Connection
DD210471
Tap-off polarity
DD210470
DD210466
Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.
Cat. no.
Weight
(kg)
KSB50SF5
2.40
Rating
(A)
For fuses
(not supplied)
50
NF 14 x 51
Type gG : 50 A max.
Type aM : 50 A max.
100
NF 22 x 58
Terminals
50
50
ISO 63 max. KSB100SF4
KSB100SF5
5.00
Type gG : 100 A max.
Type aM : 100 A max.
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.
Terminals
25
25
ISO 50 max.
KSB50SF4
DD210467n
DD202008
KSB50SFp, KSB100SFp
X = 432.5 (KSB50SFp)
X = 545.5 (KSB100SFp)
Cable exit
Centre line of tap-off outlets
(4) Protruding
Dimensions Rating (A)
A
B
C
D
E
F
K9AE26010_bis.indd
50
356
153
167
309
103
202
100
444
178
202
397
128
220
version: 1.1
107
Catalogue numbers
and dimensions
Canalis KTA
Tap-off unit with isolator for blade-type fuses
Disconnection by opening the tap-off unit cover
System earthing
arrangement
DD210472
KSB400SEp
KSB160SEp
KSB250SEp
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. fuse protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
DD210470
Tap-off polarity
DD210471
DD202012
Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised. It is possible to install an OF contact triggered by cover
opening (see the "Accessories" section, page 112).
Cat. no.
Cat. no.
Size 00
Terminals
Type gG : 100 A max.
Type aM : 100 A max.
50
50
KSB100SE4(5)
KSB100SE5(5) 5.00
Size 00
Terminals
Type gG : 160 A max.
Type aM : 160 A max.
35
50
KSB160SE4
KSB160SE5
11.00
Size 0
Terminals
Type gG : 160 A max.
Type aM : 160 A max.
35
50
KSB160SF4
KSB160SF5
11.00
250
Size 1
Terminals
Type gG : 250 A max.
Type aM : 250 A max.
150
150
KSB250SE4
KSB250SE5
20.00
400
Size 2
Terminals
240
240 ISO 40(4) max. KSB400SE4
KSB400SE5
29.20
Type gG : 400 A max.
Type aM : 400 A max.
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100A dimensions, see Tap-off units with insulators for cylindrical fuses, page 107 cat.
no. KSB100SFp.
Rating
(A)
100
160
Connection
Weight
(kg)
(1)
DD210473n
DD202008
KSB160SEp, KSB250SEp
Dimensions Rating (A)
A
B
C
D
E
F
G
H
(2)
(1)
6
X = 577.5 (KSB160SEp)
X = 777 (KSB250SEp)
160
450
257
300
395
207
32
32
182
250
600
308
400
548
258
32
32
192
DD210474n
DD202008
KSB400SEp
X = 855
108
version: 1.1
K9AE26010_bis.indd
System earthing
arrangement
KSBppSpp
Rating
(A)
For fuses
(not supplied)
25
Diazed E27
50
Noezd E18
63
Diazed E33
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. fuse protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
DD210471
Tap-off polarity
DD210470
DD210466
Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.
Cat. no.
Cat. no.
Weight
(kg)
Terminals
25
25
ISO 50 max
KSB25SD4
KSB25SD5
2.40
Terminals
25
25
ISO 50 max.
KSB50SN4
KSB50SN5
2.40
Terminals
25
25
ISO 63 max.
KSB63SD4
KSB63SD5
2.40
Connection
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.
DD202008
DD205037
KSBppSpp
Cable exit
Centre line of tap-off outlets
(4) Protruding
Dimensions Rating (A)
A
B
C
D
E
F
K9AE26010_bis.indd
25 and 50
356
153
167
309
103
202
63
444
178
202
397
198
220
version: 1.1
109
Catalogue numbers
and dimensions
Canalis KTA
Tap-off unit with isolator for blade-type fuses
Disconnection by opening the tap-off unit cover
System earthing
arrangement
DD210472
KSB400SEp
KSB160SEp
KSB250SEp
Busbar trunking
TT-TNS-TNC-IT(1) TNC
Tap-off unit
TT-TNS-TNS-IT(1) TNC
3L + N + PE(2)
3L + PEN
Tap-off diagram
(e.g. fuse protection)
L1 L2 L3 N PE
L1 L2 L3 N PE
DD210470
Tap-off polarity
DD210471
DD202012
Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised. It is possible to install an OF contact triggered by cover
opening (see the "Accessories" section, page 112).
Cat. no.
Cat. no.
Size 00
Terminals
Type gG : 100 A max.
Type aM : 100 A max.
50
50
KSB100SE4(5)
KSB100SE5(5) 5.00
160
Size 00
Terminals
Type gG : 160 A max.
Type aM : 160 A max.
35
50
KSB160SE4
KSB160SE5
11.00
250
Size 1
Terminals
Type gG : 250 A max.
Type aM : 250 A max.
150
150
KSB250SE4
KSB250SE5
20.00
400
Size 2
Terminals
240
240 ISO 40(4) max. KSB400SE4
KSB400SE5
29.20
Type gG : 400 A max.
Type aM : 400 A max.
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100 A dimensions, see "Tap-off units with insulators for cylindrical fuses", page 107,
catalogue number KSB100SFp.
Rating
(A)
100
Connection
Weight
(kg)
(1)
DD210473n
DD202008
KSB160SEp, KSB250SEp
Dimensions Rating (A)
A
B
C
D
E
F
G
H
(2)
(1)
6
X = 577.5 (KSB160SEp)
X = 777 (KSB250SEp)
160
450
257
300
395
207
32
32
182
250
600
308
400
548
258
32
32
192
DD210474n
DD202008
KSB400SEp
X = 855
110
version: 1.1
K9AE26010_bis.indd
System earthing
arrangement
DD202014
KSB160SG4
Busbar trunking
TT-TNS-TNC-IT(1)
Tap-off unit
TT-TNS-TNS-IT(1)
Tap-off polarity
3L + N + PE(2)
Tap-off diagram
(e.g. fuse protection)
L1 L2 L3 N PE
DD210470
DD202013
Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.
Cat. no.
Weight
(kg)
Terminals
25
25
KSB32SG4
2.40
BS88 A1 or A3
Terminals
35
50
5.00
BS88 B1 or B2
Terminals
35
50
Rating
(A)
For fuses
(not supplied)
32
BS88 A1
80
160
Connection
KSB160SG4
11.00
(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Maximum diameter for a multipolar cable.
(4) Maximum diameter for a unipolar cable.
KSBppSG4
DD202267n
DD202008
KSB32SG4, KSB80SG4
Dimensions Rating (A)
A
B
C
D
E
F
32
356
153
167
309
103
202
80
444
178
202
397
128
220
X = 432.5 (KSB32SG4)
X = 545.5 (KSB80SG4)
DD202015n
DD202008
KSB160SG4
X = 577.5
Cable exit
Centre line of tap-off outlets
(5) Protruding
K9AE26010_bis.indd
version: 1.1
111
Catalogue numbers
and dimensions
Canalis KTA
Accessories for all tap-off units for modular devices
Designation
Description
Cat. no.
Weight
(kg)
13940
0.08
Adhesive label(1)
08905
08903
Cover contact
KSB100Sp to KSB400Sp
(break before opening)
112
version: 1.1
Order in
multiples of
Cat. no.
Weight
(kg)
KSB400ZC1 0.03
K9AE26010_bis.indd
Tap-off diagram
(e.g. circuit breaker
protection)
L1 L2 L3 PE
L1 L2 L3 N PE
L1 L2 L3 N PE
DD210452
3L + N + PE
3L + N + PER
DD210451
3L + PE
DD230225
Tap-off polarity
Cat. no.
Weight
(kg)
Rating
(A)
Type of circuit
breaker(2)
400 to
630
150
KTB0630CB3
KTB0630CB4
KTB0630CB5
35.00
800 to
1000
200
KTB1000CB3
KTB1000CB4
KTB1000CB5
45.00
1250(4)
NS1250
Rotary handle
33878
240
KTB1250CB3
KTB1250CB4
KTB1250CB5
50.00
4 x 300
PE
DD202451
DD205939
DD202497
KTB0630CBp
Table of dimensions
Dim.
A
B
C
D
E
400 to
630
860
350
300
547
315
800 to
1000
1130
550
330
710
510
DD230206
KTB1000CBp
Rating (A)
DD205940
From 1250 A
DD210880
KTB1250CBp
Cable exit
Center line of tap-off outlets
Axis of Canalis KT
Connection box to be fitted above or below
K9AE26020bis.indd
version: 1.1
113
Catalogue numbers
and dimensions
IP31
Canalis KTA
Tap-off diagram
(e.g. circuit breaker
protection)
L1 L2 L3 PE
L1 L2 L3 N PE
L1 L2 L3 N PE
DD230228
3L + N + PE
3L + N + PER
DD230226
3L + PE
DD230227
Tap-off polarity
Cat. no.
Weight
(kg)
Rating
(A)
630(3)
T3
3 x 300
150
KTB0630HF3
KTB0630HF4
KTB0630HF5
54.00
1000(3)
T4
4 x 300
200
KTB1000HF3
KTB1000HF4
KTB1000HF5
96.00
PE
DD230200
DD230223
KTBppppHFp
DD230203
KTB0630HFp
Table of dimensions
Dim.
DD210880
KTB1000HFp
A
B
C
D
E
Rating (A)
630
1108
480
300
786.5
315
1000
1438
690
330
1010
510
Cable exit
Center line of tap-off outlets
Axis of Canalis KT
Connection box to be fitted above or below
114
version: 1.1
K9AE26020bis.indd
Type of
isolator
(supplied)
Cat. no.
3L + PE
3L + N + PE
3L + N + PER(1)
Weight
(kg)
1000
NS1000 NA
KTA1000SL31
KTA1000SL41
KTA1000SL51
135.00
1250
NS1250 NA
KTA1250SL31
KTA1250SL41
KTA1250SL51
140.00
1600
NS1600 NA
KTA1600SL31
KTA1600SL41
KTA1600SL51
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppSL51 by
KTAppppSL71.
150.00
KTAppppSLp1
DD202381
DD202378
KTAppppSLp1
Type of
isolator
(supplied)
Cat. no.
3L + PE
3L + N + PE
3L + N + PER(1)
Weight
(kg)
INV2000
KTA2000SL31
KTA2000SL41
KTA2000SL51
170.00
2500
INV2500
KTA2500SL31
KTA2500SL41
KTA2500SL51
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppSL51 by
KTAppppSL71.
180.00
2000
DD202378
KTAppppSLp1
DD202381
KTAppppSLp1
Trunking cross-section
Rating (A)
800
1000
1250
1600
2000
DD210867
K9AE26030_bis.indd
2500
3200
4000
DD202180
Height H (mm)
Width W (mm)
version: 1.1
115
Catalogue numbers
and dimensions
new
Canalis KTA
DB402026
Rating
(A)
Type of switch
(supplied)
Cat. no.
3L + N + PE
3L + N + PER
Weight
(kg)
2500
KTA2500RL61
KTA2500RL71
14.00
2500
KTA2500RL62
KTA2500RL72
18.00
DB401409
KTA2500RL61, KTA2500RL71
DB401410
The enclosure withstands internal arcing for a short circuit current of 110 kA during
0.1 s.
DD202381
KTA2500RL62, KTA2500RL72
116
version: 1.1
K9AE26030_bis.indd
Type of
isolator
(supplied)
Cat. no.
3L + PE
3L + N + PE
3L + N + PER(1)
3000(2)
NW3200 HA
KTA3200SL31 KTA3200SL41 KTA3200SL51
(1) To order the 3L+N+PER version with reinforced Icc, replace KTAppppSL51 by
KTAppppSL71.
(2) The use of this coupling isolator requires derating the busway run to 3000 A.
Weight
(kg)
320.00
DD205942
KTA3200SLp1
KTA3200SLp1
244
K9AE26030_bis.indd
version: 1.1
117
Catalogue numbers
and dimensions
Canalis KTA
Protection of the run using Compact NS circuit breakers
DD202377
Type of
isolator (2)
(supplied)
Cat. no.
3L + PE
3L + N + PE
3L + N + PER(3)
Weight
(kg)
1000
NS1000 N
KTA1000PL31
KTA1000PL41
KTA1000PL51
135.00
1250
NS1250 N
KTA1250PL31
KTA1250PL41
KTA1250PL51
140.00
1600
NS1600 N
KTA1600PL31
KTA1600PL41
KTA1600PL51
150.00
DD202378
KTAppppPLp1
DD202381
KTAppppPLp1
Trunking cross-section
Rating (A)
800
1000
1250
1600
2000
DD210867
118
2500
3200
4000
DD202180
Height H (mm)
Width W (mm)
version: 1.1
K9AE26030_bis.indd
Special products
For further information about the use and the dimensions, consult your sales office.
DD205943
DD210884
Reduction sections
DD210883
HB
74
104
124
164
204
244
324
404
74
104
124
164
204
244
324
404
DD230234
Available.
DD205944
K9AE27000_bis.indd
version: 1.1
119
Catalogue numbers
and dimensions
Special products
Canalis KTA
DD210885
DD210881
On demand
b
b
b
b
120
version: 1.1
K9AE27000_bis.indd
Canalis KH substitution
byCanalis KT
new
KTB0pppHT0p
DB402128
DB401490
Ratings (A)
Table of dimensions
KTB0350HT01
KTB0350HT02
KTB0510HT01
KTB0510HT02
KTB0510HT03
A
850
850
890
890
890
B
331.5
331.5
310
310
310
C
518.5
518.5
580
580
580
D
300
300
300
300
300
DB402827
DB402826
E
300
300
300
300
300
F
600
600
600
600
600
G
258
258
329
329
329
H
208
208
306
306
306
I
466
466
635
635
635
KHF14
1000
166
KTA1000
1000
104
230
KHF16
1200
166
KTA1250
1250
124
230
KHF18
1450
166
KTA1600
1600
164
350
KHF26
2200
238
KTA2500
2500
244
350
KHF28
2500
238
KTA2500
2500
244
350
KHF36
3000
310
KTA3200
3200
324
510
KHF38
3500
310
KTA4000
4000
404
510
KHF46
4000
382
KTA4000
4000
404
510
KHF48
4500
382
404
510
KTB0510HT02
KHF56
5000
454
404
510
KTB0510HT03
KHF58
5500
454
KTA1600
KTB0350HT02
KTB0510HT01
(1) See the KTC catalogue for details of the product range.
KHF14
KHF26
KHF36
KHF46
KHF16
KHF28
KHF38
KHF48
KHF18
KTA1000 KTA1250
KTB0350HT01
KTA2500
KHF Polarity
KTA3200
KHF56
KHF58
KTA4000
KTA5000
KTA Polarity
3L+PE
3L+PE
3L+1/2N+PE
3L+N+PE
3L+N+PE
3L+N+PE
3L+N+PER (2)
3L+N+PER
K9AE27000_bis.indd
version: 1.1
121
Catalogue numbers
and dimensions
new
Canalis KTA
Canalis KH substitution
byCanalis KT
Preserved KH tap-off units
and substitution table
Polarity
Rating
Catalogue number
Status
Substitued by
3L+PE
160
250
400
630
160
250
400
630
160
250
400
630
KH016SD13
KH025SD13
KH040SD13
KH063SD13
KH016SD14
KH025SD14
KH040SD14
KH063SD14
KH016SD15
KH025SD15
KH040SD15
KH063SD15
KH063SD1530758
KH016SD24
KH025SD24
KH040SD24
KH063SD24
KH020SD33
KH031SD33
KH050SD33
KH005SD34
KH010SD34
KH020SD34
KH025SE341
KH031SD34
KH040SE341
KH050SD34
KH063SE341
KH005SD35
KH010SD35
KH020SD35
KH025SE351
KH031SD35
KH040SE351
KH050SD35
KH063SE351
KH020SD44
KH031SD44
KH050SD44
KH016SD541
KH025SD541
KH040SD541
KH063SD541
KH016SD551
KH025SD551
KH040SD551
KH063SD551
KH016SD542
KH025SD542
KH040SD542
KH063SD542
KH016SD552
KH025SD552
KH040SD552
KH063SD552
KH063SD841
KH010SD85
KH025SD85
KH040SD85
KH063SD85
KH063SD8502
KH040SD9502
KH063SD9502
KH0SD108919802
KH0SD108919803
KH0SD108920002
KH0SD108922201
KH0SD108922202
KH0SD107080401
KH0SD107076901
KH0SD107080402
KH0SD107076902
KH0SD1530710
Removed
Removed
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Preserved
Preserved
Preserved
Removed
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
KH025SD15
KH025SD15
KH063SD15
KH063SD15
KH025SD14
KH063SD14
KH025SD15
KH063SD15
KH063SD15
No
No
No
No
KH025SE351
KH040SE351
KH063SE351
KH025SE341
KH025SE341
KH025SE341
KH040SE341
KH063SE341
KH025SE351
KH025SE351
KH025SE351
KH040SE351
KH063SE351
No
No
No
KH025SD541
KH063SD541
KH025SD541
KH063SD551
KH025SD542
KH063SD541
KH025SD542
KH063SD551
No
KH063SD85
No
No
No
No
No
No
No
No
No
No
3L+N+PE
3L+PEN
3L+NP+PE
3L+PE
3L+N+PE
3L+PEN
3L+NP+PE
Circuit breaker manuel
3L+N+PE
3L+PEN
3L+N+PE
3L+PEN
Muller Isolator
3L+N+PE
3L+PEN
3L+PEN
Dumeco switch
Other
3L+N+PE
3L+PEN
-
122
160
250
400
630
200
315
500
50
100
200
250
315
400
500
630
50
100
200
250
315
400
500
630
200
315
500
160
250
400
630
160
250
400
630
160
250
400
630
160
250
400
630
630
100
250
400
630
400
630
-
100
60
100
60
400
version: 1.1
K9AE27000_bis.indd
new
Bolted tap-off units
Protection
Isolator and fuse carriers
Polarity
Rating
Catalogue number
Status
Substitued by
3L+PE
160
KH016SB131
KH016SB132
KH025SB131
KH025SB132
KH040SB131
KH040SB132
KH063SB131
KH063SB132
KH086SB131
KH086SB132
KH0SB331132
KH016SB141
KH016SB142
KH025SB141
KH025SB142
KH040SB141
KH040SB142
KH063SB141
KH063SB142
KH086SB141
KH086SB142
KH016SB151
KH016SB152
KH025SB151
KH025SB152
KH040SB151
KH040SB152
KH063SB151
KH063SB152
KH086SB151
KH086SB152
KH016SB241
KH016SB242
KH025SB241
KH025SB242
KH040SB241
KH040SB242
KH063SB241
KH063SB242
KH086SB241
KH086SB242
KH086SB331
KH086SB332
KH025SB331
KH025SB332
KH040SB331
KH040SB332
KH063SB331
KH063SB332
KH086SB351
KH086SB352
KH025SB341
KH025SB342
KH025SB441
KH025SB442
KH040SB341
KH040SB342
KH040SB441
KH040SB442
KH063SB341
KH063SB342
KH063SB441
KH063SB442
KH086SB341
KH086SB342
Removed
Removed
Preserved
Preserved
Removed
Removed
Preserved
Preserved
Preserved
Preserved
Removed
Removed
Removed
Preserved
Preserved
Removed
Removed
Preserved
Preserved
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
KH025SB131
KH025SB132
KH063SB131
KH063SB132
KH086SB132
KH025SB141
KH025SB142
KH063SB141
KH063SB142
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
250
400
630
1000
3L+N+PE
160
250
400
630
1000
3L+PEN
160
250
400
630
1000
3L+NP+PE
160
250
400
630
1000
3L+PE
1000
3P+PE
250
400
630
3P+PEN
1000
3L+N+PE
250
400
630
1000
K9AE27000_bis.indd
version: 1.1
123
Catalogue numbers
and dimensions
new
Canalis KTA
Canalis KH substitution
byCanalis KT
Preserved KH tap-off units
and substitution table
Polarity
Rating
Catalogue number
Status
Substitued by
3L+PEN
250
KH025SB351
KH025SB352
KH040SB351
KH040SB352
KH063SB351
KH063SB352
KH086SB5311
KH086SB5312
KH025SB5411
KH025SB5412
KH040SB5411
KH040SB5412
KH063SB5411
KH063SB5412
KH086SB5411
KH086SB5412
KH025SB5511
KH025SB5512
KH040SB5511
KH040SB5512
KH063SB5511
KH063SB5512
KH086SB5511
KH086SB5512
KH025SB5521
KH040SB5521
KH063SB5521
KH025SB5421
KH025SB5422
KH040SB5421
KH040SB5422
KH063SB5421
KH063SB5422
KH025SB5522
KH040SB5522
KH063SB5522
KH040DD411
KH0SB1393108
KH0SB1393132
KH0SA345794
KH0SB1041086
KH0SA1088568
KH0SA1088123
Removed
Removed
Removed
Removed
Removed
Removed
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
No
No
No
No
No
No
KH086SB5411
KH086SB5412
KH086SB5411
KH086SB5412
KH086SB5411
KH086SB5412
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
400
630
Circuit breaker manuel
3L+PE
1000
3L+N+PE
250
400
630
1000
3L+PEN
250
400
630
1000
3L+N+PE
250
400
630
250
400
630
3L+PEN
3L+PEN
250
400
630
1000
Others
1000
1500
2000
124
version: 1.1
K9AE27000_bis.indd
new
Tap-off units for Compact NSX, fixed, front-connected circuit breakers, not equipped
DB402027
The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.
TT-TNS-TNC-IT TNC
Tap-off unit
TT-TNS-TNS-IT
TNC
3L + N + PE
3L + PEN
Tap-off polarity
KH0ppSD5pp
Rating Type of
(A)
circuit
breaker
DD210452
Tap-off diagram
(e.g. fuse protection)
Cable
Cable
capacity clamp on
(mm2)
(mm)
L1 L2 L3 N PE
DB401484
System earthing
arrangement (1)
L1 L2 L3 N PE
Cat. no.
Weight
(kg)
250
30...70
KH025SD541
KH025SD551
32.00
630
2 x 30...70
KH063SD541
KH063SD551
45.00
Plug-in tap-off units for motor mechanisme control 220 V 50 Hz (not supplied)
Busbar
trunking
TT-TNS-TNC-IT TNC
Tap-off unit
TT-TNS-TNS-IT
TNC
3L + N + PE
3L + PEN
Tap-off polarity
DD210452
Tap-off diagram
(e.g. fuse protection)
Cat. no.
Weight
(kg)
NSX250 N/H/L
control 31541
KH025SD542
KH025SD552
32.00
630
NSX630 N/H/L
control 32841
KH063SD542
KH063SD552
45.00
KH063SDppp
DD402104
DD402103
L1 L2 L3 N PE
250
KH025SDppp
DB401483
L1 L2 L3 N PE
DB401484
System earthing
arrangement (1)
DB401483
x = 520
x = 646
K9AE27000_bis.indd
version: 1.1
125
Canalis KH substitution
byCanalis KT
Catalogue numbers
and dimensions
new
Canalis KTA
System earthing
arrangement (1)
Busbar
trunking
TT-TNS-TNC-IT TNC
Tap-off unit
TT-TNS-TNS-IT
TNC
3L + N + PE
3L + PEN
Tap-off polarity
KH0ppSD1p
Rating
(A)
DD210470
Tap-off diagram
(e.g. fuse protection)
L1 L2 L3 N PE
DD210471
DB402028
Tap-off disconnection by opening or closing the cover should be carried out only
if the downstreamload is de-energised.
L1 L2 L3 N PE
Fuse Cable
Cable
size capacity clamp on
(mm2)
(mm)
Cat. no.
Weight
(kg)
250
1 x 95
1 x 30-70
KH025SD14
KH025SD15
37.00
630
2 x 185
2 x 30-70
KH063SD14
KH063SD15
56.00
DD402108
KH063SDpp
DD402107
KH025SDpp
DD202008
DD202008
x = 790
126
x = 920
version: 1.1
K9AE27000_bis.indd
new
Busbar
trunking
Tap-off unit
DB402115
Tap-off polarity
DD210471
Ith (A)
Fuse
size
With MULLER disconnector
With MULLER disconnector
00
1
Cable
capacity
(mm2)
1 x 50
1 x 95
2
1 x 185
400
With MULLER disconnector
3
2 x 185
630
With MULLER disconnector
(1) These units can be fitted either on Canalis KTA or KHF.
KH010SD85
TNC
3L + PEN
Tap-off diagram
(e.g. fuse protection)
100
250
TNC
L1 L2 L3 N PE
Cat. no.
Weight
(kg)
KH010SD85
KH025SD85
12.50
37.00
KH040SD85
KH063SD85
39.00
46.00
DB402116
KH010SD85
DB402118
DB402117
KH040SD85
K9AE27000_bis.indd
version: 1.1
127
Canalis KH substitution
byCanalis KT
Catalogue numbers
and dimensions
new
Canalis KTA
DD401398
Busbar
trunking
Tap-off unit
Tap-off polarity
TNC
TNC
3L + PEN
DD210471
Tap-off diagram
(e.g. fuse protection)
Ith (A)
Fuse
size
400
Cable
capacity
(mm2)
1 x 185
630
2 x 185
L1 L2 L3 N PE
Cat. no.
Weight
(kg)
KH040SD9502
39.00
KH063SD9502
46.00
KH040SD9502
DB401399
KH040SD9502
DB401401
DD401400
KH063SD9502
KH063SD9502
version: 1.1
K9AE27000_bis.indd
new
Tap-off unit installed under voltage, unloaded, for KTA2500, KTA3200, KTA4000.
Functionalities
TT-TNS-TNC-IT
TNC
Tap-off unit
TT-TNS-TNS-IT
TNC
3L + N + PE
3L+ PEN
Tap-off polarity
Rating (A)
DB401476
KH0ppSE3p1
DD210470
Tap-off diagram
Ith (A)
L1 L2 L3 N PE
Fuse size
(DIN 43653)
Cat. no.
DB401472
L1 L2 L3 N PE
250
250
KH025SE341
KH025SE351
400
350
KH040SE341
KH040SE351
630
500
KH063SE341
KH063SE351
DB401480
KH025SEp1
KH040SEp1
KH063SEp1
569
569
665
700
760
765
590
590
620
165
165
165
255
255
285
550
550
650
Optional accessories
DB401475
Accessories
Cat. no.
KH063ZA03
KH025ZA05
KH040ZA05
KH063ZA05
KH040ZA06
KH063ZA06
Cable gland (185 - 240 mm2) for cable boxes KH0ppZA05 and KH0ppZA06
KH063ZA10
DB401473
DB401474
Extension handle.
K9AE27000_bis.indd
version: 1.1
129
Canalis KH substitution
byCanalis KT
Catalogue numbers
and dimensions
new
System earthing
arrangement (1)
Busbar
trunking
IT-TT-TNS
TT-TNS-TNC-IT (3)
Tap-off
unit
IT-TT-TNS
TT-TNS-TNS-IT (3)
3L + PE
3L + N + PE
Tap-off polarity
Rating
(A)
DB401487
Weight
(kg)
250
1 x 150
1 x 30-70
KH025SB13p
46.00
KH025SB14p
48.00
630
2 x 300
2 x 30-70
KH063SB13p
71.00
KH063SB14p
75.00
1000
4 x 185
KH086SB13p
86.00
KH086SB14p
90.00
(1) To be installed only on Canalis KHF junction, do not use on Canalis KT.
(3) Also suitable for tap-off unit 3L + PE (N not distributed).
(4) The reference number ends with 1 if the tap-off unit is mounted on the identification label
side. The reference number ends with 2 if the tap-off unit is mounted on the opposite side to the
label.
KH0ppSBppp
y
l
n
o
1
e
l
2
b
0
a 2
l
i
a til
v
A un
L1 L2 L3 N PE
Fuse Cable
Cable
size capacity clamp on
2
(mm )
(mm)
DB402113
L1 L2 L3 PE
DB401486
KH0ppSB1pp
DD230227
Tap-off diagram
(e.g. fuse protection)
DD230226
DB401455
The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.
160/250
Rating (A)
540
500
630
265
e
-
400/630
640
600
750
290
1000
650
485
300
120
Note: this equipment sould be ordered at the same time as the SB tap-off unit.
Type of busbar trunking SB tap-off unit (except 1000 A) SB tap-off unit 1000 A only
KHF 14/16
KH016CB
KH016CB311571
KHF 18
KH018CB
KH018CB311571
KHF 26/28
KH026CB
KH026CB311571
KHF 36/38
KH036CB
KH036CB311571
KHF 46/48
KH046CB
KH046CB311571
KHF 56/58
KH056CB
KH056CB311571
(2) The neutral must be not distributed (3L + PE) for the IT system.
130
version: 1.1
K9AE27000_bis.indd
new
Canalis KHF only
Busbar
trunking
IT-TT-TNS
TT-TNS-TNC-IT
Tap-off unit
IT-TT-TNS
TT-TNS-TNS-IT
3L + PE
3L + N + PE
Tap-off polarity
DD230225
y
l
n
o
1
e
l
2
b
0
a 2
l
i
a til
v
A un
Tap-off diagram
(e.g. fuse protection)
L1 L2 L3 PE
DD210452
DB401485
L1 L2 L3 N PE
DB40487
DB401487
DB401486
KH086SB5p1p
In front
In
front of
of yellow
yellow label.
label.
Rated
Control Type of
current In
circuit
(2)
35 C
breakers
1000 A
Manual
Opposite of
Opposite
of yellow
yellow label.
label.
N, H, L
MG
NS630b,
NS800,
NS1000 (2)
Side
Weight
(kg)
In front of
yellow label
KH086SB5311
Opposite of
yellow label
KH086SB5411 88.00
(1) To be installed only on Canalis KHF junction, do not use on Canalis KT.
(2) The circuit breaker more than 1000 A, with the same dimension, cannot be used on these tapoff units.
(3) The reference number ends with 1 if the tap-off unit is mounted on the identification label side.
The reference number ends with 2 if the tap-off unit is mounted on the opposite side to the label.
y
l
n
o
1
e
l
2
b
0
a
l
i
2
a til
v
A un
K9AE27000_bis.indd
Note: this equipment should be ordered at the same time as the SB tap-off unit.
Type of busbar
trunking
Cat. no.
Mounting position
KHF 14/16/18
KH018CB86NS
KHF 26/28
KH028CB86NS
KHF 36/38
KH038CB86NS
KHF 46/48
KH048CB86NS
KHF 56/58
KH058CB86NS
or
version: 1.1
131
Catalogue numbers
and dimensions
new
DB401535
Canalis KTA
Canalis KH substitution
byCanalis KT
132
version: 1.1
K9AE27000_bis.indd
DB401534
new
K9AE27000_bis.indd
version: 1.1
133
Catalogue numbers
and dimensions
new
DB401497
Canalis KTA
Canalis KH substitution
byCanalis KT
134
version: 1.1
K9AE27000_bis.indd
Contents
Design guide
Index
Introduction
Presentation and description
Catalogue numbers and dimensions
3
19
37
65
Characteristics
136
Other characteristics
139
140
142
144
Coordination
146
149
151
Selection guide
152
Degree of protection
154
Harmonic currents
156
Direct current
158
Frequencies
160
161
Fire resistance
164
Seismic resistance
166
168
173
233
400 Hz 160
Transparent Ready units 161
DEBU021EN_Design guide.indd
version: 1.1
135
Characteristics
Design guide
Canalis KTA 3L + PE
Canalis KTA
Characteristics of run sections
Symbol Unit
General characteristics
2000
2500
3200
4000
IEC/EN 60439-2
Protection degree
IP
55
Any installation (indoors only) is possible for the busbar truncking: edgewise, flat
or vertical. See test condition, page 155.
Shock resistance
IK
08
800
1000
1250
1600
Ui
2000
2500
3200
4000
Ue
Operating frequency
Hz
Icw
kA
31
50
50
65
110
Ipk
kA
64
110
110
143
242
113
86
90
248
189
I2t
A2s 106
961
2500
2500
4225
198
4900
6400
7396
8100
1000
1000
Ratings 2000 and 2500 A are equipped in standard version with side reinforcements.
Conductor characteristics
Phase conductors
R20
mW/m
0.079
0.057
0.046
0.035
0.028
0.023
0.017
0.014
R1
mW/m
0.096
0.069
0.056
0.042
0.034
0.028
0.021
0.017
X1
mW/m
0.018
0.016
0.015
0.013
0.011
0.008
0.007
0.007
Z1
mW/m
0.097
0.071
0.058
0.044
0.035
0.029
0.022
0.018
mW/m
0.203
0.178
0.164
0.143
0.126
0.113
0.093
0.080
Casing
(Equivalent copper cross-section)
mm
120
130
140
155
165
180
190
200
PE = casing
At 20 C
Average resistance
R0 ph/PE
mW/m
0.809
0.676
0.587
0.490
0.420
0.370
0.303
0.256
Average reactance
X0 ph/PE
mW/m
0.762
0.586
0.478
0.364
0.286
0.231
0.170
0.131
Average impedance
Z0 ph/PE
mW/m
1.111
0.895
0.757
0.610
0.508
0.436
0.347
0.288
Rb0 ph/ph
mW/m
0.160
0.115
0.097
0.073
0.059
0.051
0.038
0.031
Ph/PE
Rb0 ph/PE
mW/m
0.531
0.440
0.353
0.281
0.231
0.197
0.154
0.125
Rb1 ph/ph
mW/m
0.193
0.140
0.120
0.091
0.075
0.066
0.049
0.039
Rb1 ph/PE
mW/m
0.641
0.535
0.438
0.348
0.292
0.252
0.197
0.160
Xb ph/ph
mW/m
0.040
0.029
0.024
0.019
0.015
0.013
0.010
0.008
Xb ph/PE
mW/m
0.426
0.329
0.275
0.212
0.170
0.141
0.106
0.084
Other characteristics
Voltage drop
Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
For a cosine j of
V/100 m/A
0.0083
0.0060
0.0049
0.0037
0.0029
0.0024
0.0018
0.0015
0.9
V/100 m/A
0.0081
0.0060
0.0050
0.0038
0.0030
0.0025
0.0019
0.0016
0.8
V/100 m/A
0.0076
0.0056
0.0047
0.0036
0.0029
0.0024
0.0018
0.0015
0.7
V/100 m/A
0.0069
0.0052
0.0043
0.0034
0.0027
0.0022
0.0017
0.0015
kg/m
12
14
16
19
22
25
31
38
kWh/m
2.1
2.9
3.2
3.9
5.7
6.2
8.9
11.2
0.4
0.5
0.75
0.9
1.3
1.6
2.1
3.0
Average weight
3L + PE
136
version: 1.1
K9AE39000.indd
Canalis KTA 3L + N + PE
General characteristics
IP
Shock resistance
Nominal rated current at an ambient temperature of 35 C
Rated insulation voltage
Rated operating voltage
Operating frequency
IK
Inc
Ui
Ue
f
A
V
V
Hz
Icw
Ipk
I2t
kA
kA
A2s 106
2000
2500
3200
4000
IEC/EN 60439-2
55
Any installation (indoors only) is possible for the busbar truncking: edgewise, flat
or vertical. See test condition, page 155.
08
800
1000
1250
1600
2000
2500
3200
4000
1000
1000
c 50/60 (for 60 to 400 Hz AC or for DC, consult us)
31
64
961
50
110
2500
50
110
2500
65
143
4225
70
154
4900
80
176
6400
86
189
7396
90
198
8100
Icw
Ipk
I2t
kA
kA
A2S.106
113
248
12769
113
248
12769
R20
R1
X1
Z1
mW/m
mW/m
mW/m
mW/m
0.079
0.096
0.018
0.097
0.057
0.069
0.016
0.071
0.046
0.056
0.015
0.058
0.035
0.042
0.013
0.044
0.028
0.034
0.011
0.035
0.023
0.028
0.008
0.029
0.017
0.021
0.007
0.022
0.014
0.017
0.007
0.018
mW/m
mm
0.203
120
0.178
130
0.164
140
0.143
155
0.126
165
0.113
180
0.093
190
0.080
200
R0 ph/N
X0 ph/N
Z0 ph/N
R0 ph/PE
X0 ph/PE
Z0 ph/PE
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
0.345
0.143
0.373
0.809
0.762
1.111
0.248
0.103
0.269
0.676
0.586
0.895
0.209
0.087
0.226
0.587
0.478
0.757
0.159
0.067
0.172
0.490
0.364
0.610
0.128
0.054
0.139
0.420
0.286
0.508
0.111
0.046
0.120
0.370
0.231
0.436
0.083
0.035
0.090
0.303
0.170
0.347
0.066
0.028
0.072
0.256
0.131
0.288
Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph
Rb1 ph/N
Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
0.160
0.161
0.531
0.193
0.194
0.641
0.040
0.064
0.426
0.115
0.115
0.440
0.140
0.140
0.535
0.029
0.047
0.329
0.097
0.097
0.353
0.120
0.120
0.438
0.024
0.040
0.275
0.073
0.074
0.281
0.091
0.092
0.348
0.019
0.030
0.212
0.059
0.059
0.231
0.075
0.075
0.292
0.015
0.024
0.170
0.051
0.052
0.197
0.066
0.066
0.252
0.013
0.021
0.141
0.038
0.039
0.154
0.049
0.049
0.197
0.010
0.016
0.106
0.031
0.031
0.125
0.039
0.039
0.160
0.008
0.013
0.084
Conductor characteristics
Phase conductors
PE = casing
Average resistance at an ambient temperature of 20 C
Casing
(Equivalent copper cross-section)
Fault loop
Ph/N
Average resistance
characteristics at 20 C Average reactance
Average impedance
Ph/PE
Average resistance
at 20 C Average reactance
Average impedance
Impedance
method
At 20 C
Average resistance
Ph/Ph
Ph/N
Ph/PE
Ph/Ph
Ph/N
Ph/PE
Ph/Ph
Ph/N
Ph/PE
Other characteristics
Voltage drop
For a cosine j of
Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
1
V/100 m/A
0.0083 0.0060 0.0049 0.0037 0.0029 0.0024 0.0018 0.0015
0.9
V/100 m/A
0.0081 0.0060 0.0050 0.0038 0.0030 0.0025 0.0019 0.0016
0.8
V/100 m/A
0.0076 0.0056 0.0047 0.0036 0.0029 0.0024 0.0018 0.0015
0.7
V/100 m/A
0.0069 0.0052 0.0043 0.0034 0.0027 0.0022 0.0017 0.0015
Average weight
3L + N + PE
kg/m
13
16
18
22
26
30
37
45
kWh/m
2.5
3.6
4.1
5.9
7.3
8.0
11.5
14.4
0.4
0.5
0.75
0.9
1.3
1.6
2.1
3.0
K9AE39000.indd
version: 1.1
137
Characteristics
Design guide
Symbol Unit
2000
2500
3200
4000
IEC/EN 60439-2
55
Any installation (indoors only) is possible for the busbar truncking: edgewise, flat
or vertical. See test condition, page 155.
08
800
1000
1250
1600
2000
2500
3200
4000
1000
1000
IP
Shock resistance
Nominal rated current at an ambient temperature of 35 C
Rated insulation voltage
Rated operating voltage
Operating frequency
IK
Inc
Ui
Ue
f
A
V
V
Hz
Icw
Ipk
I2t
kA
kA
A2s 106
31
64
961
50
110
2500
50
110
2500
65
143
4225
70
154
4900
80
176
6400
86
189
7396
90
198
8100
Icw
Ipk
I2t
kA
kA
A2S.106
35
73
1225
65
143
4225
65
143
4225
85
187
7225
110
242
12100
113
248
12769
113
248
12769
120
264
14400
Ratings 2000 and 2500 A are equipped in standard version with side reinforcements.
Conductor characteristics
Phase conductors
R20
R1
X1
Z1
mW/m
mW/m
mW/m
mW/m
0.079
0.096
0.018
0.097
0.057
0.069
0.016
0.071
0.046
0.056
0.015
0.058
0.035
0.042
0.013
0.044
0.028
0.034
0.011
0.035
0.023
0.028
0.008
0.029
0.017
0.021
0.007
0.022
0.014
0.017
0.007
0.018
mW/m
mm
0.050
210
0.039
300
0.034
360
0.026
480
0.022
600
0.019
720
0.014
960
0.012
1200
R0 ph/N
X0 ph/N
Z0 ph/N
mW/m
mW/m
mW/m
0.345
0.143
0.373
0.248
0.103
0.269
0.209
0.087
0.226
0.159
0.067
0.172
0.128
0.054
0.139
0.111
0.046
0.120
0.083
0.035
0.090
0.066
0.028
0.072
R0 ph/PE
X0 ph/PE
Z0 ph/PE
Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph
Rb1 ph/N
Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
0.247
0.111
0.270
0.160
0.161
0.135
0.193
0.194
0.162
0.040
0.064
0.047
0.186
0.087
0.205
0.115
0.115
0.099
0.140
0.140
0.120
0.029
0.047
0.037
0.160
0.077
0.177
0.097
0.097
0.084
0.120
0.120
0.102
0.024
0.040
0.032
0.125
0.062
0.139
0.073
0.074
0.064
0.091
0.092
0.078
0.019
0.030
0.026
0.102
0.017
0.104
0.059
0.059
0.052
0.075
0.075
0.065
0.015
0.024
0.022
0.087
0.045
0.098
0.051
0.052
0.044
0.066
0.066
0.055
0.013
0.021
0.019
0.067
0.035
0.075
0.038
0.039
0.032
0.049
0.049
0.041
0.010
0.016
0.014
0.054
0.029
0.061
0.031
0.031
0.027
0.039
0.039
0.035
0.008
0.013
0.012
Average resistance
Average reactance
Average impedance
Ph/PE
at 20 C
Impedance
method
Average resistance
Average reactance
Average impedance
At 20 C Average resistance Ph/Ph
Ph/N
Ph/PE
At Inc and Average resistance Ph/Ph
at 35 C
Ph/N
Ph/PE
At Inc and Average reactance Ph/Ph
at 35 C
Ph/N
and at
Ph/PE
50 Hz
Other characteristics
Voltage drop
For a cosine j of
Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
1
V/100 m/A
0.0083 0.0060 0.0049 0.0037 0.0029 0.0024 0.0018 0.0015
0.9
V/100 m/A
0.0081 0.0060 0.0050 0.0038 0.0030 0.0025 0.0019 0.0016
0.8
V/100 m/A
0.0076 0.0056 0.0047 0.0036 0.0029 0.0024 0.0018 0.0015
0.7
V/100 m/A
0.0069 0.0052 0.0043 0.0034 0.0027 0.0022 0.0017 0.0015
Average weight
3L + N + PER
138
kg/m
15
19
21
26
31
36
46
56
kWh/m
2.5
3.6
4.1
5.9
7.3
8.0
11.5
14.4
0.4
0.5
0.75
0.9
1.3
1.6
2.1
3.0
version: 1.1
K9AE39000.indd
Other characteristics
Other characteristics
2000
2500
3200
4000
Choice of products when harmonics are present (see "harmonic currents" for more details).
Rated current according to THD3 (3rd order distortion) THD < 15 %
800
1000
1250
1600
2000
2500
3200
4000
1000
1250
1600
2000
2500
3200
4000
THD > 33 %
1250
1600
2000
2500
3200
4000
Canalis busbar trunking is sized to operate at an ambient air which does not exceed +40 C and its average over a period of 24 h does not exceed +35 C. Above
this value, the busbar trunking must be derated.
Where k1 = ambient temperature derating coefficient.
Ambiant temperature 24 hours average
C
35
40
45
50
55
k1
k1=1
k1=0.97
k1=0.93
k1=0.90
k1=0.86
See "Busbar trunking installed outside under an aluminium roof" on page 141.
k1
Tests performed in accordance with the requirements of NF EN 1363-1 and those specific to EN 1366-3.
Performance criteria
Fire integrity
Thermal
insulation
120 mn
30 mn
120 mn
120 mn
Symbol Unit
Protection degree
IP
Shock resistance
IK
Ui
Ue
Operating frequency
Hz
K9AE39000.indd
55
08
400 or 500 depending on protection device
50/60
version: 1.1
139
Design guide
Design order:
Protection degree
Canalis KT busbar trunking is IP55 and IPxxD by construction.
This protection degree protects the busbar trunking against:
b dust
b penetration by a 1mm diameter wire
b water projections from all directions.
It can be installed in almost all premises; for more details see the "Determining the
protection degree" pages.
Wherever the busbar trunking must pass outside the building, an aluminium
roof can be supplied; consult your Schneider Electric distributor for information
concerning this option.
Corrosive atmosphere
The busbar trunking has been qualified for industrial atmospheres.
For sulphurous atmospheres such as sulphur dioxide (SO2) and hydrogen sulphide
(H2S), there is a suitable Canalis KT solution; consult your Schneider Electric
distributor for more information on this option.
Example: paper mills, water treatment works, etc.
140
version: 1.1
K9AE31000.indd
DD210982
DD210066
Ib
Ib
Ib
Ib
Ib
Ib
Ib
Ib
Ib
Ib
Ib
In
Ib
Calculation of the total current (Ib) absorbed by a run is equal to the sum of the
currents absorbed by all of the loads.
The loads do not all operate at the same time and, as they are not continuously at
full load, a stacking or simultaneity factor Ks has to be taken into account:
Ib = Ib load x Ks
Stacking factor Ks depending on the number of loads according to
IEC 60439- 1
Number of loads
Ks coefficient
Lighting, heating
Application
Distribution
(mechanic workshop)
2...3
0.9
4...5
0.8
6...9
0.7
10...40
0.6
40 and over
0.5
Caution: for industrial installations, remember to take into account future increases in the
number of machines. A 20 % reserve is recommended.
Type of
installation
Busbar trunking
installed inside
All
0.97
0.93
0.90
0.86
Busbar trunking
installed outside under
an aluminium roof
KTA800
Busbar trunking
installed in a fire duct
K9AE31000.indd
0.97
0.95
0.92
0.90
0.86
KTA1000 0.97
0.95
0.92
0.90
0.86
KTA1250 0.89
0.86
0.83
0.80
0.77
KTA1600 0.85
0.83
0.81
0.78
0.75
KTA2000 0.81
0.79
0.77
0.75
0.73
KTA2500 0.78
0.76
0.74
0.72
0.70
KTA3200 0.78
0.75
0.73
0.72
0.70
KTA4000 0.74
0.73
0.69
0.66
0.62
version: 1.1
141
Design guide
Canalis KTA
5 - Choosing the busbar trunking rating according to the nominal current ln
Nominal current
In (A)
Busbar trunking
0 to 800
KTA0800
801 to 1000
KTA1000
1001 to 1250
KTA1250
1251 to 1600
KTA1600
1601 to 2000
KTA2000
2001 to 2500
KTA2500
2501 to 3200
KTA3200
3201 to 4000
KTA4000
Other use
3%
5%
6%
8%
The allowable voltage drop is that which is compatible with correct load operation
(refer to manufacturers guides).
b Read voltage drop in V/100 m/A
for the busbar trunking chosen in accordance
with temperature rise.
b Determine the voltage drop for the worst case loads, i.e. those furthest from the
source and for the highest current.
If the voltage drop exceeds allowable limits, choose the next rating up.
Re-check the voltage drop for the new rating.
Voltage drop, in volts per 100 metres and per amp for 3-phase 50 Hz current with
load spread over the run. For loads concentrated at the end of a run (transport),
the voltage drops are double those shown in the table below:
Delta U
for evenly distributed loads (V/100m/A)
KTA08
KTA10
Cosine j = 1
0.0072
KTA12
KTA16
KTA20
Cosine j = 0.9
0.0073
0.0050
Cosine j = 0.8
0.0069
Cosine j = 0.7
0.0064
KTA25
KTA32
0.00227 0.0017
KTA40
0.0014
142
version: 1.1
K9AE31000.indd
8 - Checking the rating and choice of circuit breaker with respect to short-circuit withstand current
Short-circuit current withstand is shown in the table below.
This value must be greater than the prospective short-circuit current, at all points of
the installation.
b Calculate the short-circuit current value at the worst case points.
b Check the chosen rating allows the busbar trunking to cope with this short-circuit
current.
If this is not the case, there are 2 possible solutions:
b choose a higher rating busbar trunking and re-check
b provide a peak current limiting protection system upstream of the busbar
trunking.
Standard version 3L + N + PE or 3L + PE
Unit
Allowable
Icw kArms/1s 31
rated shorttime withstand
current (t =1s)
50
50
65
70
80
86
90
Allowable
rated peak
current
Ipk
64
110
110
143
154
176
189
198
A2s.106
961
2500
2500
4225
4900
6400
7396
8100
Allowable
Icw kArms/1s 35
rated shorttime withstand
current (t=1s)
65
65
85
110
113
113
120
Allowable
rated peak
current
248
248
264
Maximum
I2t
thermal stress
Ipk
Maximum
I2t
thermal stress
73
143
143
187
242
A2s.106
1225
4225
4225
7225
K9AE31000.indd
version: 1.1
143
Design guide
Canalis KTA
9 - Choosing source and feeder circuit breakers according to the number and rating of the supply
transformers
DD210981
The choice of a circuit breaker to protect a circuit depends mainly on the following
2 criteria:
b the nominal current of the source or the loads, which determines the appropriate
rating of the device
b the maximum short-circuit current at the point in question, which determines the
minimum breaking capacity of the device.
DD210983n
Example:
3 incoming 1250 kVA transformers 20 kV/410 V (In = 1760 A).
Feeders: including one 2000 A feeder, one 1600 A feeder and one 1000 A feeder.
What circuit breakers should be fitted at the incomer and for the feeders?
b Incomer circuit breakers:
either the Drawout Masterpact NW20N1 or the Drawout NS2000N circuit breakers
can be chosen. The choice will depend on the options required.
b Feeder circuit breakers:
the NW20H2 for the 2000 A feeder, the NW16H2 for the 1600 A feeder and the
NW10H2 for the 1000 A feeder are to be chosen.
These circuit breakers have the advantage of providing discrimination (full
discrimination) with the NW12H1 or NS1250N circuit breakers.
144
version: 1.1
K9AE31000.indd
Calculation assumption:
b the upstream network short-circuit power is not defined
b the transformers are 20 kV/410 V
b between each transformer and corresponding circuit breaker there is 5 metres of
KT busbar trunking
b between a source circuit breaker and a feeder circuit breaker there is 1 metre of
bars
b the equipment is installed into a switchboard with an ambient temperature of
40 C.
Transformer
P (kVA) In (A)
Usc
(%)
Isc
(kA)
400 A
630 A
1 transformer
50
70
NSX100N TM-D/STR22SE
NSX100N
100
141
NSX160N TM-D/STR22SE
NSX100N NSX160N
160
225
NSX250N TM-D/STR22SE
250
352
NSX400N STR23SE/53UE
400
563
14
14
NSX630N STR23SE/53UE
14
630
887
22
22
22
800
1127
19
19
19
1000
1408
23
23
23
1250
1760
29
29
NW20N1 Micrologic
29
1600
2253
38
38
NW25H1 Micrologic
38
2000
2816
47
47
NW32H1 Micrologic
47
2500
3521
59
59
NW40H1 Micrologic
59
2 transformers
50
70
NSX100N TM-D/STR22SE
NSX100N NSX160N
100
141
NSX160N TM-D/STR22SE
160
225
NSX250N TM-D/STR22SE
11
250
352
NSX400N STR23SE/53UE
18
400
563
14
14
NSX630N STR23SE/53UE
28
630
887
22
22
44
800
1127
19
19
38
1000
1408
23
23
47
1250
1760
29
29
NW20N1 Micrologic
59
1600
2253
38
38
NW25H1 Micrologic
75
2000
2816
47
47
NW32H1 Micrologic
94
2500
3521
59
59
NW40H1 Micrologic
117
3 transformers
50
70
NSX100N TM-D/STR22SE
100
141
NSX160N TM-D/STR22SE
11
160
225
11
NSX250N TM-D/STR22SE
17
250
352
18
NSX400N STR23SE/53UE
26
400
563
14
28
NSX630N STR23SE/53UE
42
630
887
22
44
67
800
1127
19
38
56
1000
1408
23
47
70
1250
1760
29
59
88
1600
2253
38
75
113
2000
2816
47
94
K9AE31000.indd
version: 1.1
145
Design guide
Coordination
DD210888
Fuse
b
v
v
v
v
b
b
Inc = Ib x k1 x k2
Ib : current rating
Inc : allowable busbar trunking current
k1 : temperature derating coefficient
k2 : derating coefficient linked to the type of switchgear:
- fuse k2 = 1.1
- circuit breaker k2 = 1.
Iz = Ib x k1.
In = I standardised fuse or circuit breaker.
Example:
For a current rating Ib = 1900 A in an ambient temperature of 35 C:
b fuse protection:
Inc = Ib x k1 x k2 = 1900 x 1 x 1.1 = 2090 A
The correct choice of busbar trunking is the KTA25 (Inc = 2500 A)
b circuit breaker protection:
Inc = Ib x k1 x k2 = 1900 x 1 x 1 = 1900 A
The correct choice of busbar trunking is the KTA20 (Inc = 2000 A),
A difference of 20 % in the measurement of operating currents results in an overrating of the busbar trunking of 10 % if it is protected by fuses.
DD210887
Circuit breaker
Explanations
b Calibration of thermal asymptotes:
v the distribution fuse is calibrated to operate for overloads of between 1.25 and
1.6 times its nominal current (In fuse)
v the circuit breaker is calibrated to operate for overloads of between 1.05 and
1.3times (1.2 for circuit breakers with electronic protection) its setting current (Ir
which is a function of circuit breaker In).
b Maximum operating current:
v the maximum limit for this current is set by installation standards (IEC 364,
NFC15-100, etc) at 1.45 times the allowable current of the busbar trunking.
In
146
version: 1.1
K9AE31000.indd
Circuit breakers fitted with electronic trip units have the following setting ranges:
b thermal protection Ir adjustable from 0.4 In to In
b short-circuit protection adjustable from 2 Ir to 10 Ir
DD210603
Example:
A 250 A circuit breaker (NS250N fitted with an STR22SE) can easily have the
following settings:
b thermal protection from 100 to 250 A
b short-circuit protection from 200 to 2500 A.
K9AE31000.indd
Avdantages
This provides great flexibility for:
b modifications (flexibility), extensions (installation changes): the protective
devices easily adapt to the load to be protected and to the earthing system
(protection of personnel and equipment)
b maintenance, the use of this type of device considerably reduces the stocks of
maintenance components.
version: 1.1
147
Design guide
Coordination
The busbar trunking must meet all of the rules detailed in IEC 60439.1 and
IEC 60439.2.
The sizing of busbar trunking for short-circuits is determined by the following
characteristics:
b the allowable rated peak current Ipk (k).
This characteristic represents the busbar trunkings instantaneous electrodynamic
withstand limits. The peak current value is often the most restrictive instantaneous
characteristic for the protective device
b the maximum short-time withstand rms current Icw (kArms/s).
This characteristic represents the allowable temperature rise limit of the conductors
during a given time period (0.1 to 1s)
b the thermal stress in A2s.
This characteristic represents the instantaneous thermal stress withstand of the
busbar trunking. In general, if the short-circuit generates fault conditions compatible
with the first two characteristics, this constraint is "automatically satisfied".
The circuit breaker must satisfy the requirements of product construction standards
(IEC 60947-2, etc) and installation standards (IEC 60364 or those in force in the
country concerned), i.e. have a breaking capacity Icu(1) greater than the prospective
short-circuit current Isc at the point where it is installed.
(1) Installation standard IEC 60364 and construction standards specify the breaking capacity of
a circuit breaker as being:
- the ultimate breaking capacity, Icu, if it is not coordinated with an upstream protective device,
- the reinforced breaking capacity (cascading) if there is coordination with the upstream
protective device.
DD210986
When the busbar trunking is directly protected, the circuit breaker must be chosen
as follows:
b Icu of the circuit breaker u prospective Isc at point A
b I peak of the busbar trunking u prospective asymmetrical or limited Isc at point A
b busbar trunking thermal withstand Icw u thermal stress through the busbar
trunking.
DD206049
When the busbar trunking is protected downstream of a cable, the circuit breaker
must be chosen as follows:
b Icu of the circuit breaker u prospective Isc at point A
b I peak of the busbar trunking u prospective asymmetrical or limited Isc at point B
b busbar trunking thermal withstand Icw u thermal stress through the busbar
trunking.
148
version: 1.1
K9AE31000.indd
DD210989
It must be checked that the busbar trunking can handle the peak fault current to
which it may be subjected and the thermal withstand during any time delay.
The allowable peak current (I peak) of the busbar trunking must be greater than the
peak current value of the prospective asymmetrical short-circuit current (Isc asym)
at A.
The asymmetrical short-circuit current value is obtained by multiplying the
symmetrical short-circuit current value (Isc) by a standardised asymmetrical
coefficient (k).
It is the first value of the 1st transient asymmetrical peak of the short-circuit which is
taken into account.
Standardised table for calculating asymmetrical short-circuit values
Isc: prospective symmetrical shortcircuit value
kA (rms value)
Asymmetrical coefficient
k
4,5 y I y 6
1.5
6 < I y 10
1.7
10 < I y 20
2.0
20 < I y 50
2.1
50 < I
2.2
Example:
For a circuit with a prospective short-circuit current of 50 kA rms, the 1st peak
reaches 105 k (50 kA x 2.1), see figure opposite.
DD210990
The short-time withstand value (Icw) of the busbar trunking must be greater than
the current flowing through the installation during the duration of the short-circuit
(Isc) (duration T - total breaking time - including any time delay).
K9AE31000.indd
version: 1.1
149
Design guide
This is mainly applicable to the protection of busbar trunking using moulded case
circuit breakers (y 1600 A).
This type of circuit breaker is used for energy discrimination and is therefore often
associated with Canalis KTA.
DD210991
Here, it has to be checked that the busbar trunking can cope with the peak current
(Ipk) limited by the protective device and the corresponding thermal stress (As):
b the peak current (I peak), once limited by the circuit breaker, must be less than
the allowable peak current value of the busbar trunking
b the thermal stress, once limited by the circuit breaker, must be less than the
allowable thermal stress of the busbar trunking.
DD210992
150
version: 1.1
K9AE31000.indd
Even if this combination is less frequent than for KS busbar trunking, some KT
ratings can benefit from the association with a limiter circuit breaker.
DD210993nA
K9AE31000.indd
version: 1.1
151
Design guide
Selection guide
Canalis KTA
The selection guide below will, according to the prospective short-circuit current of
the installation, allow you to determine the type of circuit breaker needed to fully
protect the busbar trunking.
Example: for an installation with a prospective Isc of 55 kA, the circuit breaker
needed to protect a KTA12 A busbar trunking is a NW10L1 or NW12L1 (the rating
depends on the circuits nominal current).
31 kA
50 kA
70 kA
90 kA
150 kA
NS800N/H
NSX630N
NSX630H
NS800L
NSX630L
NS1000N/H
NT08L1
NS800LB
NW08H1/H2
NT10L1
NW10H1/H2
42 kA
50 kA
60 kA
150 kA
NT1.H1
NS800N/H
NW10L1
NS1000L
NW1.N1
NS1000N/H
NW12L1
NT10L1
NS1200N/H
NT.H2
NW1.H1/H2
42 kA
50 kA
55 kA
150 kA
NT1.H1
NS1000N/H
NW10L1
NS1000L
NW1.N1
NS1200N/H
NW12L1
NT10L1
NS1600N/H
NT.H2
NW1.H1/H2
42 kA
50 kA
60 kA
90 kA
NT12H1
NS1200N
NS1200H
NW12L1
NT16H1
NS1600N
NS1600H
NW16L1
NW12N1
NT12H2
NW12H1/H2
NW20L1
NW16N1
NT16H2
NW16H1/H2
NW20N1
NW2.H1/H2
42 kA
50 kA
65 kA
72 kA
110 kA
NT16H1
NS1600N
NW16H1
NW16H2
NW16L1
NW16N1
NT16H2
NW2.H1
NW2.H2
NW20L1
NW20N1
NW25H3
42 kA
65 kA
80 kA
150 kA
NW20N1
NW2.H1
NW40bH1
NW16L1
NW32H1
NW2.H2
NW20L1
NW40H1
NW32H2
NW40.H2
NW..H3
65 kA
86 kA
150 kA
NW25H1
NW40bH1
NW20L1
NW32H1
NW2.H2
NW40H1
NW32H2
NW40.H2
NW..H3
65 kA
90 kA
NW32H1
NW40bH1
NW40H1
NW50H1
NW32H2
NW40.H2
NW50H2
NW32H3
NW40H3
152
version: 1.1
K9AE31000.indd
25 kA
28 kA
30 kA
40 kA
NS1000L
NS1600bN
NS1000N
NS1000H
NS1200N
NS1200H
NS1600N
NS1600H
NT10L1
NT1.H1/H2
NW..N1
NW1.H1/H2
NW10L1
NW12L1
25 kA
30 kA
38 kA
42 kA
50 kA
NS1000L
NS1000N
NS1600bN
NS1000H
NW1.H1
NT10L1
NS1200N
NS2000N
NS1200H
NW1.H2
NS1600N
NS2500N
NS1600H
NW10L1
NS3200N
NT1.H.
NW12L1
NW..N1
42 kA
60 kA
65 kA
NT12H.
NS1600bN
NW..L1
NT16H.
NS2000N
NW12N1
NW12H1/H2
NW16N1
NW16H1/H2
NW20N1
NW20H1/H2
NW25H3
42 kA
65 kA
72 kA
100 kA
NT16H1/H2
NS1600bN
NW16H2
NW16L1
NW16N1
NS2000N
NW20H2
NW20L1
NW20N1
NS2500N
NW25H2/H3
NW16H1
NW20H1
NW25H1
42 kA
65 kA
80 kA
100 kA
NW20N1
NS2000N
NW40bH1
NW16L1
NS2500N
NW25H2/H3
NW20L1
NS3200N
NW32H2/H3
NW20H1
NW40H2/H3
NW25H1
NW40bH2
NW32H1
NW40H1
65 kA
85 kA
NS2500N
NW40bH1
NS3200N
NW2.H2/H3
NW25H1
NW32H2/H3
NW32H1
NW40H2
NW40H1
NW40bH2
65 kA
85 kA
90 kA
NS3200N
NW32H2
NW40bH1
NW32H1
NW40H2
NW50H1
NW40H1
NW40bH2
NW50H2
NW32H3
NW40H3
K9AE31000.indd
version: 1.1
153
Design guide
Degree of protection
Canalis KTA
Standard IEC 60364-5-51 categorises a large number of external influences to
which electrical installations can be subjected, for instance the presence of water,
solid objects, shocks, vibrations and corrosive substances.
The importance of these influences depends on the installation conditions. For
example, the presence of water can vary from a few drops to total immersion.
Degree of protection IP
Standard IEC 60529 (February 2001) indicates the degree of protection provided
by electrical equipment enclosures against accidental direct contact with live parts
and against the ingress of solid foreign objects or water.
This standard does not apply to protection against the risk of explosion or
conditions such as humidity, corrosive gases, fungi or vermin.
The IP code comprises 2 characteristic numerals and may include an additional
letter when the actual protection of persons against direct contact with live parts is
better than that indicated by the first numeral.
The first numeral characterises the protection of the equipment against penetration
of solid objects and the protection of people.
The second numeral characterises the protection of the equipment against
penetration of water with harmful effects.
Additional letter
Degree of protection IK
Standard IEC 62-262 defines a coding system (IK code) indicating the degree of
protection provided by electrical equipment enclosures against external mechanical
impact.
Installation standard IEC 60-364 provides a cross-reference between the various
degrees of protection and the environmental conditions classification, relating to
the selection of equipment according to external factors.
IK codepp
154
version: 1.1
K9AE32000.indd
The new Canalis KTA busbar trunking products are designed to provide IP55D and
IK08 protection.
Dust tight.
Additional letter
DD210015
DD210016
DD210017
DD210018
DD210019
Dust protected
(no harmful deposits).
B
C
D
DD210007
DD210008
DD210009
DD210010
Non-protected.
DD210011
DD210012
Non-protected.
DD210014
Non-protected.
DD210006
DD210013
DD210533
Non-protected
01
0.20
02
Energy
(J)
7.50
0.15
10
0.20
03
17.50
0.35
04
25
0.50
35
0.70
05
06
0.50
07
20
40
08
1.70
30
09
20
10
40
20
10
K9AE32000.indd
Height
(cm)
version: 1.1
155
Design guide
Harmonic currents
Canalis KTA
Origin of harmonic currents
DD210679
Harmonic order
The order is the ratio
between the harmonic
frequency fn and the
fundamental frequency
(generally the power
frequency, 50 or 60 Hz):
n = fn/f1
By definition, the
fundamental f1 is order 1
(H1).
Third-order harmonics (H3)
have a frequency of 150 Hz
(when f1 = 50 Hz).
PD202029_r
PD202028_r
Workshops
Offices
156
version: 1.1
K9AE33000.indd
i h1
i h1
i h1
i h1
i h1
i h3
i h3
i h3
i h3
i h3
i h3
DD210680
i h1
DD210681
i h3
i h3
i h3
i h3
i h3
i h3
Busbar-trunking selection
THD y 15 %
Rating (A)
800
630
500
KTA
800
1000
800
630
KTA
1000
1200
1000
800
KTA
1250
1600
1250
1000
KTA
1600
2000
1600
1250
KTA
2000
2500
2000
1600
KTA
2500
3200
2500
2000
KTA
3200
4000
3200
2500
KTA
4000
Example. For a total rms current of 2356 A (estimation based on power drawn by loads,
including harmonics), the operational current is 2500 A.
THD is estimated at 30 %. The appropriate trunking is KTA 3200 A.
See the Cahier Technique publications on the Schneider Electric web site:
www.schneider-electric.com
K9AE33000.indd
version: 1.1
157
DD210683
i h1
i h1
i h3
i h1
i h1
i h3
i h3
i h1
i h3
Fundamental frequency:
ih1 (50 Hz) and
33 % H3
i h1
i h3
i h3
DD210680
Design guide
Direct current
Canalis KTA
Determining the DC current value
Thermal effect
Rule
The total power dissipated as heat must remain constant in the duct:
Pac = Pdc
Where:
b the power dissipated as heat: Pac = 3 x R x Iac where:
v R= resistance of a conductor
v Iac = conductor rms current
b the dissipated power for 4 conductors: Pdc = 4 x R x Idc where:
v Idc = direct current.
Selection table
DD210893
b 1 source
Case of 2 conductors in parallel for the + and 2 conductor in parallel for the (only
1 circuit in the busbar trunking):
DD210894
b 2 sources
Case of 1 conductor for the + and 1 conductor for the (2 circuits possible in the
same busbar trunking):
158
1 source
2 sources
800
1386
693
1000
1732
866
1250
2165
1083
1600
2771
1385
2000
3464
1732
2500
4330
2165
3200
5542
2771
4000
6928
3464
version: 1.1
K9AE34010.indd
Protection
With DC, there is no zero crossing point of the voltage and current to facilitate arc
extinction in the protective device.
The arcing time is longer and the energy that has to be absorbed is higher than for
AC.
The voltage of the DC arc must rise to the source voltage very quickly in order to
"put out" the short-circuit current.
"Shortened" electrical equation: U network = R x Isc + Uarc where:
b Isc = U network - Uarc / R
b Isc = 0 when Uarc = U network.
A quick rise in arcing voltage can be achieved by using series fuses, one fuse on
the + and one fuse on the of each circuit.
For some current rating and fuse characteristics, the placing of two fuses in series
on each polarity may be specified (highly inductive circuit).
In some cases, two fuses must be placed in parallel for each polarity.
K9AE34010.indd
version: 1.1
159
Design guide
Frequencies
400 Hz
Canalis KTA
KT busbar trunking derating at 400Hz
Values at 35 C.
Application of a derating coefficient at 400 Hz combined with that for temperature
derating.
Busbar trunking derating
KTA08 KTA10 KTA12 KTA16 KTA20 KTA25 KTA32 KTA40
Voltage drop
In (A)
688
851
1014
1327
1635
2024
2394
3162
Coefficient K at
400 Hz
0.86
0.85
0.84
0.83
0.82
0.81
0.80
0.79
3-phase voltage drop, in millivolts per metre and per amp 400 Hz with load spread
over the run.
For a concentration of load at the end of a run (transport), the voltage drops are
double those shown in the table below.
U evenly spread (mV. A. m)
KTA08 KTA10 KTA12 KTA16 KTA20 KTA25 KTA32 KTA40
Conductor characteristics
Cos = 1.0
0.079
0.068
0.057
0.044
0.038
0.033
0.025
0.020
Cos = 0.9
0.12
0.109
0.096
0.079
0.067
0.054
0.045
0.039
Cos = 0.8
0.13
0.121
0.108
0.089
0.076
0.060
0.051
0.045
Conductor impedance
KTA08 KTA10 KTA12 KTA16 KTA20 KTA25 KTA32 KTA40
Average ohmic
resistance of phase
and neutral
conductors at In(1)
Rb1ph (m/m)
160
0.092
0.079
0.066
0.051
0.044
0.039
0.029
0.023
Average resistance
0.14
0.128
0.120
0.104
at In and rated
(1)
F(Hz)
Xph (m/m)
(1) In line with the CENELEC RO.64.013 document.
0.088
0.064
0.059
0.056
version: 1.1
K9AE34020.indd
DD205669_r
This information can be accessed from any PC connected to your Ethernet network
via a simple Web browser (e.g. Internet Explorer). No other software is required.
DD205671
DD205668_r
DD205666
In all non-residential buildings, the need for sub-metering exists and is growing
underthe combined effects of:
b national and supra-national energy regulations
b the need to reduce overheads and production costs
b the allocation of energy expenditures to cost centres
b the outsourcing of operations tasks to specialists.
Operators must therefore have access to reliable pre-processed information in
order to:
b identify areas for potential savings
b model building energy flows and anticipate evolving needs
b optimise energy supply and consumption.
K9AE34030.indd
version: 1.1
161
Design guide
Canalis offers measurement and metering units that can be mounted on both
Canalis KS and KT trunking ranges, available in two ratings (250 A and 400 A).
They are equipped with mounting plates designed to receive a PowerLogic
PM810 Power Meter, a Compact NS circuit breaker and the associated current
transformers.
These units are connected to Transparent Ready solutions using a Modbus
communication network.
DD205947
162
version: 1.1
K9AE34030.indd
When the power-monitoring unit is installed in a tap-off unit, it is often too high for
easy reading of the measurements.
DD205949
DD202287n
Then the Canalis solution is to install a KBA line 25ED4303T parallel to the main
line and dedicated to carry the information (as a Modbus network) from the
powermonitoring tap-off unit to the Ethernet TCP/IP network (see "The Transparent
Ready Concept") and the connections are:
K9AE34030.indd
version: 1.1
163
Design guide
Fire resistance
Canalis KTA
As required by standards, Canalis KT busbar trunking complies with:
1 - material resistance to abnormal temperatures,
2 - flame propagation resistance,
3 - fire barrier function when going through a partition wall,
4 - conservation of all circuits for 1h30 in an insulating sheath.
Definition of tests
164
version: 1.1
K9AE35000.indd
K9AE35000.indd
version: 1.1
165
Seismic resistance
Design guide
Canalis KTA
DD405612
Acceleration (g)
10
15
20
25
30
Frequency (Hz)
GOST horizontal
GOST vertical
166
version: 1.1
K9AE35000.indd
DB402682
Safety limit: 250 mm round the busbar trunking (amplitude noted during testing).
DB402683
K9AE35000.indd
version: 1.1
167
Design guide
Canalis KTA
All the operations described below are given for indication only. Under no
circumstances can they be used to substitute the installation companys own
procedures and engage Schneider Electrics responsibility.
Scope
Prerequisites
b If need be, the old equipment has been removed from the premises.
b The new equipment has been manoeuvred into the premises where it is to be
installed by the installation contractor.
b The equipment has been installed by the installation contractor in accordance
with manufacturers recommendations.
b The equipments installation diagram, connection diagram and assembly results
sheet are available for the commissioning engineer.
The works manager is responsible for worksite safety and must ensure the
installation is de-energised and made safe in accordance with safety rules before
any inspection or measurement is performed.
After the installation contractor has positioned, assembled and connected the
busbar trunking in accordance with the supplied installation, assembly and
connection diagrams, and using the recommended tools and handling equipment,
the following characteristics must:
b be noted,
b be checked for compliance with respect to the details shown on the drawing.
Brand
Equipment type:
Serial number:
Reference:
Date of manufacture:
Transformer power:
The equipment has been chosen according to its electrical environment (rating and
protection adapted to operating conditions).
The following points do not require checking.
Points concerning reception, storage and handling
No signs of:
b shock (which may deteriorate internal insulation: conductor insulation on straight
lengths or at the tap-off points or joint blocks)
b humidity or oxidation (equipment stored outside should have been covered with
a plastic sheet, sheltered from humidity, dirt and dust)
b firms label defining the products characteristics.
168
version: 1.1
K9AE36000.indd
DD206098
Check the number of connection parts and their cross-sections for each conductor
(see "Installation guide").
Check insulation distances between 2 conductors and between conductors and
metal panels.
DD210764
DD205951
Check the tightening torque of bolts not fitted with torque nuts. For bolts fitted with
torque nuts, check the head has broken-off.
Check the bolt length exceeding the nut ; some bolts may have been removed and
then put back, but left untightened.
Mark each tightened nut using indelible varnish. As well as a means of selfinspection to ensure correct tightening torque, it also allows any untightening to be
identified.
Class 8-8 nuts and bolts (M8 on LV switchboard side, see "Commissioning Guide
for Schneider Electric LV Switchboards").
Bolt
Tightening torque
HM16
16 mdaN
HM14
12 mdaN
HM12
7 mdaN
HM10
5 mdaN
The results of all these checks must be noted on the results sheet by the
installation contractor.
PB104861
version: 1.1
169
Design guide
Canalis KTA
Checking the earth network and locks
Earth network
PB104862
Locks
To protect personnel by not allowing access to live parts through the use of locks.
Only concerns key operated safety locks.
170
version: 1.1
K9AE36000.indd
This test is performed once the busbar trunking has been energised. The
progressive start-up of loads will highlight any undesirable phenomena due to the
increased average load.
Real life operating test
Once the high power busbar trunking has been energised, the other busbar
trunking must be gradually put into service starting with those furthest from the
load, then each load itself, those with high pull-in currents, then the lighting,
contactors, heating, motors, etc.
There must not be excessive vibration, and no sparkovers should be observed.
The test simply consists of checking correct busbar trunking operation according
to:
b the average number of machines in operation
b the load variation of each individual load
b the simultaneous operation of machines (superimposing of peaks).
If everything is in order, the busbar trunking is declared "in-service".
Testing is completed.
K9AE36000.indd
version: 1.1
171
172
version: 1.1
K9AE36000.indd
Contents
Index
Introduction
Presentation and description
Catalogue numbers and dimensions
Design guide
3
19
37
65
135
Layout advice
174
Horizontal distribution
184
Rising mains
190
198
Connection to LV switchboards
200
202
203
205
207
Connection to LV switchboards
208
214
216
219
224
Recommandations
233
Selection guide
By Canalis interface
By Canalis interface
By Canalis interface
By Canalis interface
By Canalis interface
DEBU021EN_Installation guide.indd
version: 1.1
200
202
203
205
207
208
210
214
216
219
224
226
231
173
Installation guide
Layout advice
Run optimisation
Canalis KTA
CanBrass software
PD202428_r
Advice
Before defining your busbar trunking run, it is recommended you pay particular
attention to the various parameters which could be detrimental to the installation.
DD210900
DD210895
DD210903
DD210902
174
DD210896
DD210897
version: 1.1
K9AE41000.indd
DD210898
DD210899
DD210903
DD210904
DD210905
Also make sure that as the work progresses other tradesmen do not carry out
installations that could hinder your initial layout.
K9AE41000.indd
version: 1.1
175
Installation guide
Layout advice
Run optimisation
Canalis KTA
Examples of link optimisation
DD210910
Example 1
Reducing the number of changes of direction by modifying the switchboard or
transformer layout.
DD210911
Example 2
Use of 2 standard elbows in place of a made to measure zed by increasing
dimension "L".
DD210912
Neutral position
DD205952
When choosing the layout of the electrical installation, it is important care is taken
when positioning the neutral between the transformer and the switchboard.
If the neutral position is different to that planned, it is recommended the transformer
is moved, if possible, to align the neutral with respect to the switchboards neutral.
When it is not possible to move the transformer, it is recommended the phase order
in the switchboard is inversed.
If this cannot be done, use the phase and neutral transposition section.
KTAppppTNp10
KTAppppTPp10
176
version: 1.1
K9AE41000.indd
DD205953
DD210933
K9AE41000.indd
Rating (A)
800
1000
1250
1600
2000
2500
3200
4000
Height H (mm)
74
104
124
164
204
244
324
404
version: 1.1
177
Installation guide
Layout advice
3000
178
version: 1.1
K9AE41000.indd
The position of the joint block with respect to the transformer axes and switchboard
edges (defined in the "Installation guide").
Edgewise installation
DD210928
DD210927
Flat installation
Rating (A)
800
1000
1250
1600
2000
2500
3200
4000
Height H (mm)
74
104
124
164
204
244
324
404
Edgewise installation
DD210925
(1) Provide 2 times the height if the joint block must be fitted from the top.
Direction of fitting joint blocks.
DD210926
Flat installation
K9AE41000.indd
version: 1.1
179
Installation guide
Layout advice
DD210906
DD205956
Undecided section
DD210907
3: Made to measure
straight section.
4: Standard elbow.
DD210909
In order to provide for the place needed for an adjustable or undecided section,
install the elbows and the sections attached to the elbows in each angle (support
each assembly using 2 supports on each straight section).
And then complete the layout with standard and made to measure straight
sections.
180
version: 1.1
K9AE41000.indd
DD210913
The nominal length "L" of a straight section is measured from the axis of the
joint block to the other axis of the joint block, in millimetres (the joint block axis is
located 20 mm from the end of the bars).
Dimension L of the standard or made to measure section = x - 40 mm.
(1) For the different busbar trunking heights, see page 179.
(2) See "Run sections" in "Catalogue numbers and Dimensions".
x : measured dimension.
Flat elbows
Change-of-directions
DD210918
DD205957
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
K9AE41000.indd
version: 1.1
181
Installation guide
Layout advice
Edgewise elbows
DD210919
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
DD205959
Flat Zed
DD210922
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
The nominal length of the intermediary branch(es) is measured from the axis of
one branch to the axis of another.
B = B1 - B2
(1) See "Changes of direction" in "Catalogue numbers and Dimensions".
182
version: 1.1
K9AE41000.indd
DD205960
Edgewise Zed
DD210923
The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
The nominal length of the intermediary branch(es) is measured from the axis of
one branch to the axis of another.
B = B1 - B2
(1) See "Changes of direction" in "Catalogue numbers and Dimensions".
DD205961
Tools
Tape
measure
Spirit level
Lead line
Stick
Ruler
DD205962
Their use
K9AE41000.indd
version: 1.1
183
Installation guide
Horizontal distribution
Positioning the tap-off units
Canalis KTA
PD202398_r
DD210936
v 1 x 400 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit,
DD210939
DD210995
DD210996
v 1 x 400 A fuse tap-off unit, 1 x 250 A fuse tap-off unit and 1 x160 A fuse tap-off
unit:
DD210937
Cable exit.
184
version: 1.1
K9AE41000.indd
Tap-off units
DD210997
When the tap-off units have to be distributed along the length of the busbar
trunking, use 2 metre sections and alternate the tap-off point positions.
For an installation with tap-off units, provide for a between centres distance that
takes into account the minimum dimension of 100 mm and the dimensions A and B
of the tap-off units.
DD205963
Type
Circuit
breaker
tap-off units
Fuse tap-off
units
KSB160DCp
160
150
KSB250DCp
240
160
KSB400DCp
240
160
KTB0630CBp
175
175
KTB1000CBp
275
275
KSB160SEp
150
150
KSB250SEp
250
160
KSB400SEp
440
160
DD205964
Provide for a minimum distance of 1000 mm between the busbar trunking and the
ceiling to allow for the opening of tap-off unit doors.
Type
Rating (A)
K9AE41000.indd
Dimensions
(mm)
A
B
Cat. no.
Dimensions
(mm)
X
E(1)
Circuit
breaker
tap-off units
KSB160DCp
625.5
246
KSB250DCp
726.5
300
KSB400DCp
976,5
350
Fuse tap-off
units
KSB160SEp
577,5
207
KSB250SEp
777
258
KSB400SEp
(1) With the handle.
855
316
DD210942
Cat. no.
Dimensions (mm)
A
B
1000
159
529
1250
149
539
1600
129
559
2000
109
579
2500
89
599
3200
98
662
version: 1.1
185
Installation guide
Horizontal distribution
If the busbar trunking length is greater than 30 metres, provide for expansion
sections and appropriate blocking means. The ends and, in some cases, the
centre of part runs must be blocked in order to direct the extensions towards the
expansion sections.
DD210998
Layout of expansion sections and blocking means for the following busbar
trunking lengths:
b 0 to 30 metres:
DD210999
b 31 to 60 metres:
DD211000
b 61 to 90 metres:
DD211001
91 to 120 metres:
186
version: 1.1
K9AE41000.indd
DD211002
Layout of expansion sections and blocking means for the following busbar trunking
lengths:
b 0 to 30 metres:
DD211003
b 31 to 60 metres:
DD211004
b 61 to 120 metres:
DD2111005
Transformer/switchboard links
K9AE41000.indd
version: 1.1
187
Installation guide
Horizontal distribution
DD205965
For correct system operation, the expansion of the part run in question must be
directed towards the expansion section.
This implies:
b the busbar trunking must be free from all longitudinal movement on its supports
b the expansion section must be blocked on the opposite side to that by which it is
pushed.
1
2
Free fixings.
Blocked fixings.
Direction of expansion.
Flat assembly
DD211008
DD211007
Edgewise assembly
DD211010
DD211009
188
Flat assembly
version: 1.1
K9AE41000.indd
Here, the expansion section allows the busbar trunking to absorb the forces due to
the relative movement between the 2 buildings.
Building A
Building B
DD205966
1 Blocked fixings.
Flat assembly
DD211009
DD211010
Edgewise assembly
K9AE41000.indd
version: 1.1
189
Installation guide
Rising mains
General
Canalis KTA
PD202319_r
190
version: 1.1
K9AE45000.indd
DD205967
The busbar trunking must be positioned with the neutral on the right.
DD205968
The run sections are fitted with 3 tap-off points. Spaced at 500 mm intervals, they
provide a high density of tap-offs per floor.
Flat passage through
partition wall
K9AE45000.indd
DD210933
DD210932
Rating (A)
800
1000
1250
1600
2000
2500
3200
4000
Height H (mm)
74
104
124
164
204
244
324
404
version: 1.1
191
Installation guide
Rising mains
Cable exit
DD210964
R = 12 x of cable
For an installation with tap-off units, provide for a between centres distance that
takes into account the minimum dimension of 100 mm and the dimensions A and B
of the tap-off units.
Cable exit.
DD205970
Type
Circuit
breaker
tap-off units
Fuse tap-off
units
Cat. no
Dimensions
(mm)
A
B
KSB160DCp
160
150
KSB250DCp
240
160
KSB400DCp
240
160
KTB0630CBp
175
175
KTB1000CBp
275
275
KSB160SEp
150
150
KSB250SEp
250
160
KSB400SEp
440
160
DD205971
192
version: 1.1
K9AE45000.indd
Positioning of supports
DD205972
DD210967
Wall support
800 to 1600 A.
2000 to 4000 A.
DD210966
X u 400.
2000 to 4000 A.
800 to 1600 A.
DD210965
Floor support
800 to 1600 A.
K9AE45000.indd
2000 to 4000 A.
version: 1.1
193
Rising mains
Installation guide
200
DB401852
DB401853
Vertical mounting
400
200
200
400
200
L
650
650
650
650
650
650
650
650
200
DB402665
600
DB402664
500
500
Rating
KTA0800
KTA1000
KTA1250
KTA1600
KTA2000
KTA2500
KTA3200
KTA4000
20
Distances to comply
DB402678
DB402680
DB402679
DB402681
194
version: 1.1
K9AE45000.indd
K9AE45000.indd
DD205973
2 possibilities:
b installation with feed direct to the switchboard
b installation with feed via a cable box.
version: 1.1
195
Installation guide
Rising mains
196
DD205974
Canalis KTA
version: 1.1
K9AE45000.indd
K9AE45000.indd
version: 1.1
197
Installation guide
Panorama of
connection solutions
Canalis KTA
The Schneider Electric system
The comprehensive Schneider Electric system makes it simple to design a
complete transformer/Canalis KT/switchboard installation.
Using dedicated interfaces, the trunking connects directly to the dry-type
transformer and the switchboard for:
b tested and standardised connections
b fast and flexible installation
b shorter lead times.
Advantages
b No design work for the connections.
b Simplified layout design:
v pre-defined position of the jointing unit
v simplified routing (only three dimensions required)
v smaller size (no additional covers required).
b Transformer and switchboard supplied with connections already mounted.
b Short lead times and fewer catalogue numbers for connections.
b Adaptable on the worksite:
v transformer end: 15 mm adjustments along all three axes
v switchboard end: phases can be inverted.
b Continuity of service:
v transformer can be replaced in less than one hour
v transformer, trunking and switchboard designed to be used together.
b Safety:
v trunking fully tested in compliance with IEC 60439-1 and 2
v compliance with standards and installation rules
v excellent fire-withstand capability.
b Comfort:
v low level of electromagnetic radiation
v no noise.
Compatibility between Trihal transformers/Canalis KT/Prisma Plus or Okken switchboards
Trihal transformers
Rating
Naturally
ventilated
(AN) dry-type
transformers
Ie max.
2200 A
n4
H244
2816 A
3516 A
n5
n6
H324
H404
630 kVA
887 A
800 kVA
1126 A
2500 A
3200 A
32
H404
NW circuit
breakers
4000 A
40
H404
KTA1600 KTA1600 -
KTA1600,
KTA2000
KTA2000,
KTA2500
KTA2500
-
KTA1600,
KTA2000
KTA2000,
KTA2500
KTA2500
-
PD202432_r
KTA3200 KTA3200
KTA3200, KTA3200,
KTA4000 KTA4000
2500 kVA 3520 A
4400 A
n7
H404
KTA4000 KTA4000
(1) The compatibilities indicated correspond to the electrical connection possibilities; in all cases, coordination between circuit breaker and electrical busbar
trunking must be checked.
-
Connection to an LV
switchboard using a
dedicated interface,
see page 202.
198
version: 1.1
K9AE42000.indd
Connection to an
LV switchboard
using a dedicated
interface,
see page 202.
PD202301_r
Universal
connection to a
dry-type transformer,
see page 219.
Universal
connection
to an oil-filled
transformer,
see page 226.
PD202302_r
Universal
connection to an
LV switchboard,
see page 208.
K9AE42000.indd
version: 1.1
199
Installation guide
Connection to LV switchboards
Selection guide
Canalis KTA
This guide may be used to:
b select the connection best suited to your installation (incoming direction, trunking
installed flat or edgewise, different phase order)
b check the total height of the connection with respect to the ceiling, i.e.
dimension Z0 + Z2 (100 mm minimum clearance required between top of
connection and ceiling)
b optimise the connection by ensuring that (Z0 + Z1)switchboard = (Z0 + Z1)transformer to
avoid having to use elbows and zed units
b position the fixing devices used to support the trunking.
DD205975
PD202304_r
SB1
Z0
SB2
Direct connection
Without protective covers
SB3
DD205977
DD205976
Type of connection
minimum
74
82
138
maximum
472
Z2
Z1 + 140
Z1 + H
Z1 + H
Mounting in workshop
Z1
Edgewise installation
Flat installation
200
version: 1.1
K9AE42000.indd
Trunking cross-section
Rating (A)
800(1)
1000
1250
1600
2000
2500
3200
4000
DD210867
DD202180
Height H (mm)
Width W (mm)
DD205981
DD205980
SB6
DD205979
SB5
DD205978
SB4
473
130
465
H = 74 to 124 mm
195 - H/2
H = 164 to 244 mm
255 - H/2
H = 324 to 404 mm
355 - H/2
464
Z1 + H
Z1 + 140
Z1 + 140
H = 74 or 104 or 124 mm
H = 164 or 204 or 244 mm
H = 324 or 404 mm
Z1 + H/2 + 115
Z1 + H/2 + 175
Z1 + H/2 + 255
b
b
b
b
K9AE42000.indd
version: 1.1
201
Installation guide
By Canalis interface
Canalis KTA
PD202328_r
Switchboards can be equipped with connections for Canalis KT. Jointing with the
switchboard is via a standard run component (straight length, elbow, etc.) and a
jointing unit (identical to those used between line components). The trunking enters
the switchboard via the top (roof).
Switchboard connections are available from 800 to 4000 A.
Type of
switchboard
Prisma Plus
Okken
Type of connection
800 to 1600
Compact NS
Masterpact NT
800 to 3200
Masterpact NW
4000
Masterpact NW
Rear
800 to 4000
Masterpact NW
KTA1000
KTA1250
KTA1600
KTA2000
KTA2500
KTA3200
KTA4000
Rating
(A)
Height
(mm)
Sealing kit
1000
1250
1600
2000
2500
3200
4000
104
124
164
204
244
324
404
KTB0104TT01
KTB0124TT01
KTB0164TT01
KTB0204TT01
KTB0244TT01
KTB0324TT01
KTB0404TT01
NW
3200 A
4000 A
Interface 32 Interface 40
H404(3)
H404(3)
(1) The compatibilities indicated correspond to the electrical connection possibilities; in all
cases, coordination between circuit breaker and electrical busbar trunking must be checked.
(2) Coordination with a dry-type transformer, see the "Transformer" section, see page 216.
(3) Height of the jointing unit in millimetres.
Phase order
DD205982
202
version: 1.1
K9AE42000.indd
Connection to Okken
switchboards
By Canalis interface
Dimensions (mm)
A
B
NW08/16
175
325
156
NW20/25
175
325
156
NW32
175
325
156
175
325
156
DD206059
NW40
(1) To order, see "Catalogue numbers", page 80.
Reference
point
K9AE42000.indd
version: 1.1
203
Installation guide
Connection to Okken
switchboards
By Canalis interface
Canalis KTA
Rear connection (RC)
DD202311
Drawout, 3P/4P(1) ,
top position
Drawout, 3P/4P(1) ,
medium position
Drawout, 3P/4P(1) ,
bottom position
Dimensions (mm)
A
Depth (mm)
1000 1200 1400
317
NW08/16
825
363
NW20/25
825
363
317
NW32
825
363
317
NW40
953
NW08/16
825
363
156
363
942
942
NW20/25
825
363
NW32
825
363
942
NW40
363
881
1417
953
NW08/16
1225
363
NW20/25
1225
363
1417
1225
363
1417
DD206058
NW32
(1) To order, see "Catalogue numbers", page 80.
Depth: 1200 mm
Depth: 1400 mm
DD202384
Top views
Depth: 1000 mm
Reference
point
Bottom connection
204
For installations with connections through the bottom, please consult us.
version: 1.1
K9AE42000.indd
DD202306
Dimensions(1) (mm)
A
B
C
Fixed, 3P/4P(2)
NS800/1250
236
325
160
NT08/12
260
325
160
260
325
170
NS800/1250
or 08/NT12
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 78.
DD210765
Drawout, 3P/4P(2)
Reference
point
DD202304
Dimensions(1) (mm)
A
B
C
NW08/16
185
325
264
NW20/25
185
325
289
NW32
185
325
264
NW08/16
185
344
164
NW20/25
185
344
214
NW32
185
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 78.
344
214
DD210767
Drawout, 3P/4P(2)
Reference
point
K9AE42000.indd
version: 1.1
205
Installation guide
Canalis KTA
Rear connection (RC)
DD202307
Dimensions(1) (mm)
A
B
C
Fixed, 3P/4P(2)
NS800/1600
or NT08/16
NS800/1600
or NT08/16
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 78.
325
160
638
325
170
DD210769
Drawout, 3P/4P(2)
638
Reference
point
DD202305
815
325
264
NW20/25
757
325
414
NW32
774
325
414
NW40
790
325
439
NW08/16
815
317
414
NW20/25
815
342
414
NW32
815
317
439
NW40
790
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 78.
325
439
DD210771
Drawout, 3P/4P(2)
Reference
point
206
version: 1.1
K9AE42000.indd
DD205984
DD202314
The sealing kit must be ordered with the KT trunking. The size of the trunking
determines that of the sealing kit. For the different types of kit, see the "Catalogue
numbers and dimensions" pages.
The kit includes a drilling and cut-out drawing for the switchboard roof.
DD205983
KTB0ppppTT01
DD205985
Centre lines.
K9AE42000.indd
version: 1.1
207
Connection to LV switchboards
Installation guide
230
400
1600 to 2500
350
400
3200 to 4000
510
600
DD205986
1000 to 1250
DD205987
Busbars in switchboard
(recommended distance between
centres = 115 mm)
DD205988
DD205989
Phase order
KTAppppTNp10
KTAppppTPp10
208
version: 1.1
K9AE42000.indd
Cut-out drawing
1600 2500
350
3200 4000
510
DD205990
1000 1250
Centre lines.
K9AE42000.indd
version: 1.1
209
Installation guide
Connection to LV switchboards
By feed and connection plates
Canalis KTA
PD202331_r
Connection plates are flexible copper bars, insulated or not, and drilled at one or
both ends. They are supplied with bolts, washers and torque nuts for connection to
straight or elbow universal feed units.
To simplify the work, it is advised to universal feed units with a distance between
centres of 115 mm.
Enclosure depth depending on the rating of the trunking
Rating of trunking (A)
1000 to 1250
230
400
1600 to 2500
350
400
3200 to 4000
510
600
Vertical incomer
Horizontal incomer
DD205993
DD205992
DD205991
KTAppppERpp
210
version: 1.1
K9AE42000.indd
1000
1000
1600
1000
2000
1500
2500
1500
3200
2000
4000
2500
DD205994
DD210786
Connection
plates
Busbar trunking
rating (A)
Short-circuit withstand
DD210789
1250
DD210788
1000
DD210787
DD210764
1000 to 1600
2000 to 2500
3200
4000
DD202359
y 43 kA
43 kA y Icw y 50 kA
50 kA y Icw y 100 kA
150
Vertical incomer
DD205998
DD205997
Horizontal incomer
Phase order
DD205999
DD205995
DD205996
If the order of the phases in the trunking and the switchboard is different, it is
advised to invert the phases in the switchboard. If that is not possible, use the
phase and neutral crossover components.
For more information, see the "Description" section, section, page 51 and
"Catalogue numbers and dimensions" section, page 71.
KTAppppTNp10
KTAppppTPp10
K9AE42000.indd
version: 1.1
211
Installation guide
Connection to LV switchboards
By feed and connection plates
Canalis KTA
Dimensions of protective covers
Horizontal incomer
DD206000
Dimensions (mm)
Y
D
800 to 1250
230
220 to 475
220 to 475
310 to 800
1600 to 2500
350
220 to 475
220 to 475
430 to 800
3200 to 4000
510
220 to 475
220 to 475
590 to 800
KTBppppCR1
Cut-out drawing
DD206001
Centre lines.
212
version: 1.1
K9AE42000.indd
DD202322
Vertical incomer
230
220 to 475
220 to 475
400 to 800
1600 to 2500
350
220 to 475
220 to 475
400 to 800
3200 to 4000
510
220 to 475
220 to 475
400 to 800
KTBppppCR2
Cut-out drawing
DD206002
Centre lines.
DD202324
Dimensions (mm)
Y
D
230
220 to 475
1600 to 2500
350
220 to 475
220 to 475
400 to 800
KTBppppCR3
3200 to 4000
510
220 to 475
220 to 475
400 to 800
Cut-out drawing
220 to 475
400 to 800
DD206003
800 to 1250
Centre lines.
K9AE42000.indd
version: 1.1
213
Installation guide
Canalis KTA
This guide will allow you to:
b choose the connection best suited to your layout (incoming direction, flat or
edgewise busbar trunking, possibility of adjusting phase order)
b check the total height of the link with respect to the premises ceiling height,
dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link
and the ceiling)
b optimise your link whilst respecting the following rule:
(Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels
b position the sections for the busbar trunking supports.
Z2
Z1 + 140
Fixed
Z0
Z1 minimum
maximum
DD206007
TS4
DD206006
Universal connection
TS3
DD206005
PD202399_r
Type of connection
According to manufacturers
drawing
350
According to manu
drawing
280
350
280(1)
Z1 + H
Z1 + H
420(1)
Fixed
At time of order
At time of order
b
(1) To use standard connection plates L = 406 mm in accordance with our recommendations.
214
version: 1.1
K9AE43000.indd
Rating (A)
800(1)
1000
1250
1600
2000
2500
3200
4000
TS6
TS7
TS8
DD206011
DD206009
TS5
DD206010
DD210867
DD202180
Height H (mm)
Width W (mm)
DD2006008
ufacturers
Trunking cross-section
According to manufacturers
drawing
350
According to manufacturers
drawing
-
350(1)
280(1)
350(1)
Z1 + H
420(1)
500(1)
At time of order
At time of order
At time of order
b
b
K9AE43000.indd
version: 1.1
215
Installation guide
Canalis KTA
PD202434_r
The Trihal dry-type transformers are supplied with a specific interface tested to
receive the Canalis KT busbar trunking. Jointing with the switchboard is achieved
using a standard run section (straight, elbow section, etc) and a joint block identical
to that for connecting run elements.
The Canalis KT/dry type transformer interface, which is fitted to the transformer,
is designed to accept the transformers 25 % overload in the case of forced
ventilation.
The connections are tested and qualified in normal operating conditions with
respect to temperature rise (Dq) and short-circuits (Isc).
The busbar trunking is quickly connected to the dry-type transformer using a simple
joint block with torque nuts, guaranteeing tightening torque.
Table of compatibility between Canalis KT and the connection interface for
naturally ventilated (AN) dry-type transformers.
Dry-type transformer
Canalis KT
Rating l nominal(1)
(kVA) (A)
Cross-section
Type
Interface
Type Junction Rating (A)
630
887
H124
1250
140 x 104
KTA1000
800
1126
H164
1600
140 x 124
KTA1250
1000
1408
H204
2000
140 x 164
KTA1600
1250
1760
H244
2500
140 x 204
KTA2000
1600
2253
H324
3200
140 x 244
KTA2500
2000
2816
H404
4000
140 x 324
KTA3200
2500
3520
7
H404
5000
140 x 404
(1) I is given as an indication only and is calculated with U - 410 V.
KTA4000
Canalis KT
Rating l nominal(1)
(kVA) (A)
Cross-section
Type
Interface
Type Junction Rating (A)
630
1108
H124
1250
140 x 124
1250
800
1407
H164
1600
140 x 164
1600
1000
1760
H204
2000
140 x 204
2000
1250
2253
H244
2500
140 x 244
2500
1600
2816
H324
3200
140 x 324
3200
2000
3520
6
H404
4000
140 x 404
(1) I is given as an indication only and is calculated with U - 410 V.
4000
DD206012
DD210945
Phase order
KTAppppTNp10
KTAppppTPp10
216
version: 1.1
K9AE43000.indd
DD210946
Reference point
Dimensions
Dimensions X, Y and Z
Dimensions
(mm)
1600
2000
2500
147
150
170
147
150
170
153
100
100
108
93
124
144
149
X0
233
215
265
245
300
300
322.5
Interface type
Dimensions Y0 and Z0
Y0 = X + L
Z0 = C - M
Dimensions C and L are different according to country standards.
French standard
FT no.235627 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 410 V
Dimensions
(mm)
1600
2000
2500
1614
1744
1749
1929
2089
2209
2297
220
225
240
240
240
257
275
German standard
FT no.235763 rev. 0 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 400 V
Dimensions
(mm)
1600
2000
2500
1734
1744
1749
2019
1979
2199
2279
210
220
225
245
255
255
265
Spanish standard
FT no.235515 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 420 V
Dimensions
(mm)
1600
2000
1614
1744
1879
1929
1979
2194
220
225
215
245
250
245
Belgian standard
FT no.235820 rev. 0 - Primary voltage: 15 kV - Insulation voltage: 17.5 kV Secondary voltage: 400 V
Dimensions
(mm)
K9AE43000.indd
1600
2000
2500
1484
1564
1694
1844
2054
2149
2164
215
210
215
225
230
255
235
version: 1.1
217
Installation guide
Canalis KTA
DD206013
Sealing kit
The sealing kit must be ordered with the KT busbar trunking. The busbar trunking
size defines the sealing kit size. For the different types of kit, see Catalogue
numbers / Dimensions.
The kit includes a drilling and cut-out template for the dry-type transformer panels.
KTB0ppppTT01
It is recommended that the cutting-out of the transformer panels is done in the
workshop.
DD206014
Cut-out drawing
Junction axis.
218
version: 1.1
K9AE43000.indd
I nominal(1) (A)
KTA rating
at nominal
power(2) (A)
630
887
1000
800
1126
1250
1000
1408
1600
1250
1760
2000
1600
2253
2500
2000
2816
3200
2500
3520
4000
(1) I is given as an indication only and is calculated with U = 410 V and at transformer nominal
setting, without forced ventilation.
(2) The busbar trunking rating is defined for normal operating conditions.
DD206016
TS4 and TS6 universal connection, flat mounting (using angle brackets)
version: 1.1
219
Installation guide
DD206017
KTAppppELp5
DD206018
1600
1000
2000
1500
2500
1500
3200
2000
4000
2500
Connection
plates
Busbar trunking
rating
(A)
220
DD206023
1000
DD206022
1250
DD206021
1000
DD206020
DD206019
1000 to 1600
2000 to 2500
3200
4000
version: 1.1
K9AE43000.indd
Phase order
DD206024
DD206025
K9AE43000.indd
version: 1.1
221
Installation guide
230
200
350
1600 to 2500
350
200
350
3200 to 4000
510
200
350
DD202344n
KTB0000CR4
230
330
480
1600 to 2500
350
330
480
3200 to 4000
510
330
480
DD202345n
KTB0000CR5
222
version: 1.1
K9AE43000.indd
230
380
530
1600 to 2500
350
500
650
3200 to 4000
510
660
810
DD202347
KTBppppCR6
K9AE43000.indd
version: 1.1
223
Installation guide
Canalis KTA
This guide will allow you to:
b choose the connection best suited to your layout (incoming direction, flat or
edgewise busbar trunking, possibility of adjusting phase order)
b check the total height of the link with respect to the premises ceiling height,
dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link
and the ceiling)
b optimise your link whilst respecting the following rule:
(Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels
b position the sections for the busbar trunking supports.
TH3
DD206029
TH2
DD206028
Vertical incomer
TH1
DD206027
PD202429_r
Incomer type
According
minimum
738
1073
730
maximum
1072
1064
Z2
Z1 + H
Z1 + H
Z1 + 140
Z0
Z1
b
b
Flat layout
224
version: 1.1
K9AE44000.indd
Trunking cross-section
Rating (A)
800(1)
1000
1250
1600
2000
2500
3200
4000
g to manufacturers drawing
TH4
Direct connection
TH5
DD206030
DD206031
DD210867
DD202180
Height H (mm)
Width W (mm)
1065
Z1 = (Y/H)/2
Z1 = (Y/H)/2
Z1 + 140
H = 74 or 104 or 124 mm
H = 164 or 204 or244 mm
H = 324 or 404 mm
b
510
770
850
b
b
b
K9AE44000.indd
version: 1.1
225
Installation guide
l nominal(1)
(A)
500
704
800
140 x 74
630
887
1000
140 x 104
800
1126
1250
140 x 124
1000
1408
1600
140 x 164
1250
1760
2000
140 x 204
1600
2253
2500
140 x 244
2000
2816
3200
140 x 324
2500
3520
4000
(1) I is given as an indication only and is calculated with U - 410 V.
140 x 404
Note: if, for reasons of busbar trunking operating conditions or performance requirements, you
have to use a rating other than those defined in the above tables, consult us.
230
1600 to 2500
350
3000 to 4000
510
Vertical incomer
Horizontal incomer
DD202422
DD202421
1000 to 1250
226
version: 1.1
K9AE44000.indd
Phase order
DD202423n
DD206034
DD206032
DD206033
If the phase order of the busbar trunking is different to that of the switchboards
busbars, it is recommended a phase inversion is carried out in the switchboard. If
this cannot be done, use the phase and neutral transposition section.
For more information, see the "Description" section, page 51 and "Catalogue
numbers and dimensions" section, page 71.
KTAppppTNp10
KTAppppTPp10
K9AE44000.indd
version: 1.1
227
Installation guide
1600
1000
2000
1500
2500
1500
3200
2000
4000
2500
DD202426
Connection
plates
2000 to 2500
3200
4000
1000 to 1600
DD206035
Busbar trunking
rating
(A)
DD206040
1000
DD206039
1250
DD206038
1000
DD206037
DD210764
600
1250
1200
1600
1200
2000
1200
2500
1800
3200
1800
4000
2400
Braids
Busbar trunking
rating (A)
228
DD206044
DD206043
Cross-section (mm2)
1000
DD206042
DD206041
DD206036
Definition of braids
1000
1250 to 2000
2500 to 3200
4000
version: 1.1
K9AE44000.indd
Horizontal incomer
Dimensions (mm)
Y
D
800 to 1250
230
220 to 475
220 to 475
310 to 800
1600 to 2500
350
220 to 475
220 to 475
430 to 800
3200 to 4000
510
220 to 475
220 to 475
590 to 800
DD206045
KTBppppCR1
Dimensions (mm)
Y
Z
X
800 to 1250
230
565
450
830
750
330
125
365
1600 to 2500
350
825
650
890
810
350
265
485
3200 to 4000
510
905
650
960
880
460
185
645
DD206046
KTBppppCR7
Vertical incomer
230
220 to 475
220 to 475
400 to 800
1600 to 2500
350
220 to 475
220 to 475
400 to 800
3200 to 4000
510
220 to 475
220 to 475
400 to 800
DD202322
KTBppppCR2
K9AE44000.indd
version: 1.1
229
Installation guide
Dimensions (mm)
Y
Z
A
800 to 1250
230
600
830
750
345
330
1600 to 2500
350
600
890
810
460
350
3200 to 4000
510
600
960
880
625
460
DD206047
KTBppppCR8
230
200 to 650
1600 to 2500
350
200 to 650
3200 to 4000
510
200 to 650
DD202319
KTBppppCS0
230
version: 1.1
K9AE44000.indd
DD210955
1250
2500
DD202429
1600
DD202428
800
1000
2500
5000
DD202431
3150
DD202430
1600
2000
3150
K9AE44000.indd
Dimensions (mm)
DD202427
Power (kVA)
630
version: 1.1
231
Installation guide
Canalis KTA
Connection to porcelain bushings
DD210956
Connection terminals of the type defined below must be used. These are available
in the transformer manufacturers catalogues.
Cover
DD210957
The transformers can be supplied with or without a low voltage cover. This cover is
not used in our solutions.
232
version: 1.1
K9AE44000.indd
Contents
Recommandations
Index
Introduction
Presentation and description
Catalogue numbers and dimensions
Design guide
Design and installation guide
3
19
37
65
135
173
234
Maintenance
236
Recycling
237
Run sections
DEBU021EN_Recommandations.
indd
236
version: 1.1
233
Recommendations
Canalis KTA
This document contains practical information, lays out the general
recommendations (as a complement to the installation regulations) and specifies
the basic instructions that must be respected when handling and storing Schneider
Electric Canalis busbar trunking system.
The purchasers engineering, installation and operating staff must become
acquainted with this document and become familiar with the appearance and
characteristics of each of the Canalis busbar trunking systems components.
Appropriate planning and coordination between the different job functions is
indispensable for ensuring an efficient installation of the equipment.
Each Canalis busbar trunking system is carefully inspected and packaged at the
assembly plant.
The entire system is checked both structurally and electrically.
At the end of inspection, the busbar trunking system is prepared for shipping.
Each section is packed to guarantee easy handling before its installation.
The catalogue number is written on each shipping unit.
Warning
RISK OF ELECTRIC SHOCK, BURNS OR EXPLOSION
b Protect the equipment against all contact with water, salt, concrete and other
corrosive surroundings both before and during installation.
b Outdoor equipment is not resistant to bad weather until after it has been fully and
correctly installed.
b Do not sit or walk on the equipment.
If these instructions are not respected, the equipment may deteriorate leading to a
risk of serious or mortal injury.
Reception
Upon reception, check the information on the shipping note corresponds to the
equipment received to ensure all of the order has been received and shipped.
Complaints concerning missing components or other errors must be sent in
writing to Schneider Electric SAS within 30 days from the date the shipping item
was received. If no complaint has been received within 30 days from the date the
shipping item was received, Schneider Electric SAS will no longer be responsible
for repairs or replacements that may be required.
Upon reception, check the various units of the busbar trunking system immediately
to identify any damage that has occurred during transport.
If there is observed or suspected damage, file a claim immediately with the carrier
and inform the nearest Schneider Electric office.
Handling
Handle Canalis products with the greatest of care to avoid damaging the internal
components of the system and to avoid changing the external appearance of the
various parts, as well as the bar ends (connection terminals).
The busbar trunking must be constantly supported by independent means, in
such a way its weight is not resting on the top of the transformers or distribution
switchboards.
The distance between these support means must not exceed 3 metres.
Avoid exposing the busbar trunking to twisting, embossing or impacts, and all other
actions likely to causing damage.
Ensure the handling equipment available at the site of installation is suitable for
handling busbar trunking. In particular, check the lifting capacity of the crane or the
other lifting equipment to be used.
234
version: 1.1
K9AE51000.indd
K9AE51000.indd
version: 1.1
235
Recommendations
Maintenance
Run sections
Canalis KTA
Danger
Warning
Run sections
Tightening torque
16 mdaN
12 mdaN
7 mdaN
5 mdaN
236
version: 1.1
K9AE52000.indd
Recycling
After having performed all the necessary inspections and repairs mentioned above,
it may be desirable to carry out infrared temperature measurements on all the
electrical connections. This operation must be done once the busbar trunking has
been re-energised and reached a stabilized temperature.
Responsibility
Schneider Electric declines all responsibility for maintenance carried out in a
non-compliant way with respect to specifications or installation regulations, for
inappropriate storage conditions, for inappropriate product environments (chemical
and ambient conditions, atmospheric conditions, etc.), for the incorrect use of the
products, and for the non-respect of installation and/or connection procedures.
Busbar trunking contacts consist of sprung silver plated contact jaws to ensure
optimum contact quality. The contacts do not use plastic for their support or
transmission of force.
They are connected to the live conductors of the run at the tap-off point. Silverplated copper conductors are used at the place of contact.
These devices are maintenance-free.
Cable connection
Protection switchgear
For all devices fitted in Canalis tap-off units, the manufacturers recommendations
must be complied with.
Checking appearance
Canalis busbar trunking can be reused. Canalis busbar trunking is designed for a
long service life and can easily be dismantled, cleaned and reused.
DD205673_r
Example:
1 kg of PVC generates 1 kg of waste.
K9AE52000.indd
The depletion of raw materials (copper, plastics, etc.) is one of our ongoing
concerns.
For this reason, we have optimised the used of all materials used to make our
busbar trunking.
b Reduction of dangerous or polluting materials. We design our products to meet
future European directives.
b Reduction in the weight of insulating materials.
b Reduction in the use of plastics for improved fire performance: less energy
released during combustion, thereby limiting propagation and facilitating extinction
(lower calorific value).
version: 1.1
237
DEBU021EN
As standards, specifications and designs change from time to time, please ask for confirmation