Currentcarryingcapacitychart

Single
phase
Cross
Current
Section
rating@
mm2
35degC
inair
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

22
30
39
50
69
94
125
160
195
245
300
350
405
460
555
640

VoltageDropChart

Three
phase
Current
rating@
35degC
inair

Cross Single
Three
Section PhaseAC phaseAC
mm2 system
system

16
23
32
41
56
75
98
120
150
190
230
270
305
350
410
470

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300

mV/A/m mV/A/m
27.9
24.1
17.1
14.8
10.7
9.3
7.2
6.2
4.3
3.7
2.8
2.4
1.8
1.5
1.3
1.1
0.96
0.85
0.7
0.6
0.55
0.45
0.45
0.35
0.35
0.31
0.3
0.26
0.25
0.22
0.22
0.19

DeviatedConditions
CABLESLAIDDIRECTINGROUND

a)CorrectionfactorsforvariationinGroundTemperature

GroundTemp(Deg)
RatingFactor

15
1.04

20
1

25
0.96

30
0.93

35
0.89

40
0.85

45
0.81

b)CorrectionfactorsforvariationinThermalresistivityofsoil

Thermalresistivityofsoil(DegCcm
RatingFactor

100
1

120
0.94

150
0.84

200
0.75

250
0.68

300
0.62

c)Cablecorrectionfactorsforgroupingofcables
Number
ofcables
ingroup
2
3
4
6

Multicorecablesinhorizontal
formation
Touching S=15cm S=30cm
0.79
0.82
0.86
0.69
0.72
0.76
0.62
0.66
0.72
0.54
0.59
0.65

Multicorecablesintrefoil
touchingformation
(Threecablespercircuit)
Touching S=15cm S=30cm
0.78
0.82
0.85
0.68
0.71
0.76
0.61
0.65
0.71
0.53
0.57
0.64

CABLELAIDONRACKSINAIR
a)CorrectionfactorsforvariationinAmbientTemperature

Ground
Temp(Deg)

RatingFact

20
1.07

25
1.04

30
1

35
0.96

40
0.91

45
0.86

50
0.83

b)Cablecorrectionfactorsforgroupingofcables
Number
ofcables
ingroup

2
3
4
6

Multicorecablesintouching

1
1
0.84
0.8
0.76

Numberofracks
2
3
1
1
0.8
0.78
0.76
0.74
0.71
0.7

6
1
0.76
0.72
0.68

Multicorecablesintrefoiltouching
formationspacingbetweencircuitequalto
twicethediameterofcable
Numberofracks
1
2
3
6
1
1
1
1
0.98
0.95
0.94
0.93
0.96
0.93
0.92
0.9